You are on page 1of 1

DRAWING LIST PROJECT DECLARATION GENERAL NOTES NOTES FOR CLEAN AGENT SYSTEMS SPRINKLER DESIGN CRITERIA FIRE

PROJECT DECLARATION GENERAL NOTES NOTES FOR CLEAN AGENT SYSTEMS SPRINKLER DESIGN CRITERIA FIRE PROTECTION SYSTEM DESIGN CRITERIA NOTES:
1. ALL DIMENSIONS AND SIZES ARE IN MILLIMETERS AND LEVELS ARE IN METERS UNLESS
S/N SHEET NUMBER SHEET NAME SHEET SIZE SCALE
TYPE OF OCCUPANCY : MULTIPLE TYPE OCCUPANCY 1. THE PROTECTION SYSTEM HAS BEEN DESIGNED IN ACCORDANCE OTHERWISE NOTED. DO NOT SCALE THE DRAWINGS.
1. NO DIMENSIONS ARE TO BE SCALED FROM THIS DRAWING. 1. THE DESIGN, INSTALLATION AND TESTING OF CLEAN AGENT SYSTEMS SHALL
2. ANY DISCREPANCIES FOUND SHOULD BE REPORTED TO THE RESPONSIBLE ARCHITECT OR
1 1245-F-A0-0001 GENERAL NOTES, LEGENDS, ABBREVIATIONS, & DRAWINGS LIST A0 NTS BE DONE BY THE QCDD APROVED SPECIALIST CONTRACTOR IN ACCORDANCE
FIRE FIGHTING LAYOUT 2. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED. WITH THE AUTHORITY REGULATIONS AND NFPA 2001 STANDARDS. RESTAURANT MECH., PLANT, SAUNA & WITH THE FOLLOWING CODES & REGULATIONS: ENGINEER IMMEDIATELY.
AREA OF OPERATION PARKING CORRIDORS BED ROOMS VOID SPACES 3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR OR BUILDERS TO ASCERTAIN AND
2 1245-F-A0-0002 SITE DEVELOPMENT PLAN FIRE FIGHTING SYSTEM LAYOUT A0 AS SHOWN SITTING SERVICE RM. STEAM BATH
3. BUILDER TO CHECK ALL DIMENSIONS AT SITE PRIOR TO CONSTRUCTION, 2. ONLY CLEAN AGENTS SPECIFICALLY APPROVED BY THE QATAR CIVIL DEFENSE OH1 LH LH LH LH OH1 OH2 NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHER CONFIRM THAT ALL DIMENSIONS SHOWN IN THESE DRAWINGS SHALL COMPLY WITH THE
3 1245-F-A0-0003 SCHEMATIC RISER DIAGRAM FIRE FIGHTING SYSTEM LAYOUT A0 NTS HAZARD CLASSIFICATION
ASSEMBLY OR FABRICATION OF ALL WORKS. SHALL BE USED. NFPA 13 STANDARD FOR THE INSTALLATION OF AUTOMATIC SPRINKLER SITE DIMENSIONS AND LEVELS PRIOR TO PREPARING DRAWINGS AND EXECUTING THE
4 1245-F-A0-0004 BUILDING SECTION - A FIRE FIGHTING SYSTEM LAYOUT A0 1:150 DESIGN DENSITY (gpm/ft) 0.15 0.10 0.10 0.10 0.10 0.15 0.20
NFPA 14 STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM WORKS.
5 1245-F-A0-0005 BUILDING SECTION - B FIRE FIGHTING SYSTEM LAYOUT A0 1:150 4. ALL WORKS ARE TO BE CARRIED OUT TO Q.C.S. AND OTHER RELEVANT CODES 3. CLEAN AGENT STORAGE CONTAINERS SHALL NOT BE STORED WITHIN THE AREA PER SPRINKLER 1500 1500 1500 1500 1500 1500 1500 NFPA 16 STANDARD FOR INSTALLATION OF FOAM-WATER SPRINKLER AND FOAM-WATER
6 1245-F-A0-0006 TYPICAL INSTALLATION DETAILS FIRE FIGHTING SYSTEM LAYOUT A0 NTS OF CONSTRUCTIONS. PROTECTED ENCLOSURE. THEY SHALL BE EASILY ACCESSIBLE AND WITHIN COVERAGE (ft) 4. ALL WORKS ARE TO BE CARRIED OUT TO Q.C.S. AND OTHER RELEVANT CODES OF
SPRAY SYSTEM
2000mm FROM THE MAIN ENTRANCE OF THE PROTECTED ENCLOSURE. DESIGN AREA OF 130 225 225 225 225 130 130 CONSTRUCTIONS.
7 1245-F-A0-0007 FIRE PUMP ROOM "PLANS & PERSPECTIVE" FIRE FIGHTING A0 AS SHOWN SPRINKLER OPERATION (ft) NFPA 20 STANDARD FOR THE INSTALLATION OF STAIONARY PUMPS FOR FIRE PROTECTION
SYSTEM LAYOUT 5. THIS DRAWING IS TO BE READ FOR FIRE PROTECTION OF ALL SERVICES. NFPA 22 STANDARD FOR WATER TANKS FOR PRIVATE FIRE PROTECTION 5. THIS DRAWING SHOULD BE READ IN CONJUNCTION WITH THE OTHER RELEVANT
4. A MANUAL MECHANICAL MEANS OF DISCHARGING THE REQUIRED AGENT TYPE OF SPRINKLER UPRIGHT PENDENT PENDENT PENDENT UPRIGHT UPRIGHT PENDENT
8 1245-F-A0-0008 FIRE PUMP ROOM "SECTIONS" FIRE FIGHTING SYSTEM LAYOUT A0 AS SHOWN NFPA 72 NATIONAL FIRE ALARM CODE ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWING AND ALL
9 1245-F-A0-0009 GENERATOR & FUEL TANK ROOM FOAM WATER SPRINKLER A0 AS SHOWN
PROJECT DESCRIPTION 6. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL SERVICES. SHALL BE PROVIDED ON THE STORAGE CONTAINER. TYPE OF K-FACTOR 5.6(80) 5.6(80) 5.6(80) 5.6(80) 5.6(80) 5.6(80) 5.6(80) NFPA 96 STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF COMMERCIAL RELEVANT SECTIONS OF THE SPECIFICATIONS.
DELUGE SYSTEM LAYOUT TEMPERATURE RATING (C) 79C 68C 68C 68C 68C 68C 141C COOKING OPERATIONS 6. EXACT LOCATION & DETAIL OF ELECTRO-MECHANICAL OPENING SHALL BE COORDINATED
7. ALL PORTABLE TYPE FIRE EXTINGUISHERS SHALL BE LISTED AND COMPLY 5. CLEAN AGENT SYSTEMS SHALL BE OPERATED AUTOMATICALLY BY A QCD NFPA 101 STANDARD FOR LIFE SAFETY CODE
10 1245-F-A0-0010 BASEMENT-1 CABLE TRENCH AUTOMATIC FIRE EXTINGUISHING A0 AS SHOWN TYPE OF RESPONSE STANDARD QUICK RESP. QUICK RESP. QUICK RESP. QUICK RESP. QUICK RESP. QUICK RESP. WITH ELECTRO-MECHANICAL ENGINEER.
WITH THE REQUIREMENTS OF NFPA 10. APPROVED AUTOMATIC DETECTION SYSTEM. NFPA 2001 STANDARD ON CLEAN AGENT FIRE EXTINGUISHING SYSTEM
SYSTEM LAYOUT 7. DIMENSION AND LOCATION OF SERVICES COORDINATED WITH RESPECTIVE ARCHITECTURAL
HOSE STREAM 100 GPM NFPA 2010 STANDARD FOR FIXED AEROSOL FIRE EXTINGUISHING SYSTEM
11 1245-F-A0-0011 B1 & TYP.B2-B4 ELEC. RM. & B1 PLC/MCC RM. AUTOMATIC FIRE A0 AS SHOWN 8. THE FIRE PUMP SHALL BE UL LISTED, FM APPROVED TYPE, QCDD APPROVED 6. THE CONTROL PANEL SHALL BE LOCATED EXTERNAL TO THE PROTECTED AND SERVICES DRAWINGS PRIOR TO COMMENCEMENT OF ANY WORK. ANY DISCREPANCY
MINIMUM DURATION 60 MINUTES
EXTINGUISHING SYSTEM AND SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 20. ENCLOSURE AND LOCATED NEAR THE MAIN ENTRANCE TO THE PROTECTED FOUND SHOULD BE BROUGHT TO THE NOTICE OF THE CONCERNED ENGINEER.
12 1245-F-A0-0012 GROUND FLR. MV RM. & ELEC. RM. AUTOMATIC FIRE A0 AS SHOWN ENCLOSURE. THE CONTROL PANEL SHALL BE CONNECTED TO THE BUILDING 2. SPRINKLER IS DESIGNED TO THE FOLLOWING HAZARD CLASS SYSTEM.
EXTINGUISHING SYSTEM LAYOUT 9. ALL PIPES ABOVE GROUND SHALL BE GALVANIZED STEEL ERW SCHEDULE 40 MAIN FIRE ALARM SYSTEM THROUGH AN INTERFACE MODULE AND SHALL
CALCULATION OF EFFECTIVE FIRE WATER STORAGE CAPACITY
13 1245-F-A0-0013 1ST,TYP. 2ND-29TH,& RF ELEC. RM. AUTOMATIC FIRE A0 AS SHOWN TO ASTM A 53 GRADE. PROVIDE ALARM.
FIRE PUMP CAPACITY 1000 GPM @ 295 PSI TYPE OF OCCUPANCY
EXTINGUISHING SYSTEM LAYOUT MACHINE ROOM
14 1245-F-A0-0014 BASEMENT-1 TRANSFORMER ROOM CLEAN AGENT FIRE A0 AS SHOWN 10. ALL ISOLATING CONTROL VALVES SHALL BE UL LISTED, QCDD APPROVED 7. GAS DISCHARGED AND FAULT INDICATIONS ON THE MAIN PANEL. GAS 60,000 GALLONS
EXTINGUISHING SYSTEM LAYOUT INDICATING VALVES AND SHALL BE PROVIDED WITH SUPERVISORY SWITCHES DISCHARGE SHALL ONLY OCCUR AFTER A PREDETERMINED TIME DELAY TO BE STORAGE CAPACITY REQUIRED FOR 60MIN PUMP OPERATION HAZARD CLASS OF PROTECTION ORDINARY HAZARD GROUP-1
227,124.7 LITERS
15 1245-F-A0-0015 BASEMENT-1 LV ROOM CLEAN AGENT FIRE EXTINGUISHING A0 AS SHOWN CONNECTED TO THE BUILDING MAIN FIRE ALARM SYSTEM THROUGH AN APPROVED BY THE QCD. THE TIME DELAY SHALL BE INTERRUPTED BY THE
INTERFACE MODULE. OPERATION OF THE ABORT SWITCH AND SHALL RE-COMMENCE ON RELEASE 227.12 m
SYSTEM LAYOUT MIN. DESIGN DENSITY OF DISCHARGE 0.15 GPM / FT
OF THE ABORT SWITCH. THE MINIMUM DELAY SHALL BE 20 SECONDS. FIRE WATER STORAGE TANK AREA HEIGHT VOLUME
16 1245-F-A0-0016 BASEMENT-1 MAIN TELECOM ROOM CLEAN AGENT FIRE A0 AS SHOWN
11. ALL ABOVE GROUND PIPES 50mm AND LESS IN DIAMETER SHALL BE JOINED
EXTINGUISHING SYSTEM LAYOUT ASSUMED AREA OF OPERATION 1500 FT
WITH THREADED CONNECTIONS. 8. AT LEAST ONE MANUAL RELEASE PUSH BUTTON SHALL BE PROVIDED * CONCRETE FIRE WATER STORAGE TANK-1 WITH GRP LINING 45.00 m 3.90 m 175.5 m
17 1245-F-A0-0017 GRND. FLR. FCC & SECURITY CLEAN AGENT FIRE EXTINGUISHING A0 AS SHOWN EXTERNAL TO THE PROTECTED ENCLOSURE AND MOUNTED WITHIN 1.5M OF
SYSTEM LAYOUT 12. ALL ABOVE GROUND PIPES LARGER THAN 50mm IN DIAMETER SHALL BE JOINED THE MAIN ENTRANCE. SUBJECT TO THE SIZE AND CONFIGURATION OF THE * CONCRETE FIRE WATER STORAGE TANK-2 WITH GRP LINING 43.00 m 3.90 m 167.7 m MAX. AREA COVERAGE PER SPRINKLER 130 FT
18 1245-F-A1-0001 BASEMENT-4 FIRE FIGHTING SYSTEM LAYOUT A0 AS SHOWN WITH ROLL GROOVED TYPE COUPLINGS. PROTECTED ENCLOSURE, MORE THAN ONE MANUAL RELEASE PUSH BUTTON CLEARANCE PROVIDED AT THE BOTTOM OF THE VORTEX PLATE 0.15 m 3.90m-1.15m
19 1245-F-A1-0002 BASEMENT-3 FIRE FIGHTING SYSTEM LAYOUT A0 1:100 MAY BE REQUIRED. OPERATION OF THE MANUAL PUSH BUTTON SHALL CAUSE TYPE OF SPRINKLER QUICK RESPONSE 68C, NPT, RED
13. FLEXIBLE COUPLINGS SHALL BE USED IN ALL PIPE JOINTS AS PER NFPA INSTANT RELEASE OF THE CLEAN AGENT. CLEARANCE FROM THE SOFFIT OF SLAB TO WATER LEVEL 1.15 m EF HT=2.60m
20 1245-F-A1-0003 BASEMENT-2 FIRE FIGHTING SYSTEM LAYOUT A0 1:100
21 1245-F-A1-0004 BASEMENT-1 FIRE FIGHTING SYSTEM LAYOUT A0 1:100 STANDARDS.
THE EFFECTIVE HEIGHT OF WATER COLUMN INSIDE THE TANK EF HT=2.60m ORIFICE SIZE 1/2"
9. AN ABORT SWITCH THAT INTERRUPTS THE COUNTDOWN DELAY TIMER SHALL
22 1245-F-A1-0005 GROUND FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100
14. THE FIRE FIGHTING SYSTEM SHALL BE INSTALLED STRICTLY IN ACCORDANCE BE PROVIDED WITHIN THE PROTECTED ENCLOSURE AND MOUNTED WITHIN AREA HEIGHT VOLUME
23 1245-F-A1-0006 1ST FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 WITH THE REQUIREMENTS OF NFPA 10, NFPA 13, NFPA 14, NFPA 16, NFPA 20, 1.5M OF THE MAIN ENTRANCE. SUBJECT TO THE SIZE AND CONFIGURATION OF ORIFICE K-FACTOR 5.6 (gpm/psi)
24 1245-F-A1-0007 2ND FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 NFPA 22, NFPA 24, NFPA 25, NFPA 96, NFPA 2001, & NFPA 2010. THE PROTECTED ENCLOSURE, MORE THAN ONE ABORT SWITCH MAY BE THE EFFECTIVE VOLUME WATER STORAGE TANK-1 45.00 m 2.60 m 117.00 m
25 1245-F-A1-0008 TYP. 3RD-7TH & 9TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 REQUIRED. CONTINUOUS OPERATION OF THE ABORT SWITCH SHALL BE THE EFFECTIVE VOLUME WATER STORAGE TANK-2 43.00 m 2.60 m 111.80 m MIN. DURATION OF WATER SUPPLY 60 MINUTES
26 1245-F-A1-0009 8TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 15. THE SUCTION LINE OF THE PUMPS SHALL BE DETERMINED IN CONJUNCTION REQUIRED TO INTERRUPT THE COUNTDOWN TIMER. RELEASE OF THE ABORT
27 1245-F-A1-0010 10TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 WITH PUMPS SELECTION. SWITCH SHALL RESET THE COUNTDOWN TIMER TO GAS DISCHARGE. THE EFFECTIVE VOLUME OF WATER SHALL BE 228.80 m (60,442.58 gallons)
INSIDE HOSE FLOW 100 GPM
28 1245-F-A1-0011 11TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 60,442.58
16. THE PIPES SIZES SHALL BE BASED ON HYDRAULIC CALCULATION HOWEVER 10. "DO NOT ENTER - GAS DISCHARGED" ILLUMINATED SIGNS SHALL BE EXTERNAL 60.44 MINUTES =
29 1245-F-A1-0012 TYP. 12TH-18TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 AREA STATEMENT CONTRACTOR SHALL SUBMIT CALCULATION BASED ON ACTUAL PUMP TO THE PROTECTED ENCLOSURE AND MOUNTED ABOVE ALL ENTRANCES SO
DURATION OF USAGE
1000 3. FIRE HOSE REEL SHALL BE AS PER BELOW REQUIREMENT:
30 1245-F-A1-0013 19TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 CAPACITY AND ACTUAL SITE CONDITION IN ORDER TO IDENTIFY PRESSURE AS TO BE VISIBLE TO ANY PERSON ENTERING. THE LETTERING SHALL BE A
31 1245-F-A1-0014 20TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 LIMITS AS PER NFPA STANDARD. MINIMUM OF 50MM HIGH. IT SHALL BE VISIBLE AT ALL TIMES OF THE DAY. THE PUMP SCHEDULE
32 1245-F-A1-0015 TYP. 21ST-28TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 ILLUMINATION SHALL BE ACTIVATED BY A PRESSURE SWITCH FITTED TO THE TYPE OF OCCUPANCY MACHINE ROOM
33 1245-F-A1-0016 29TH FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 17. ALL OS&Y GATE VALVE SHALL BE INDICATING TYPE WITH A TAMPER SWITCH. DISCHARGE PIPING. "EVACUATE NOW - GAS DISCHARGE" ILLUMINATED SIGNS MOTOR CAPACITY
UNIT TOTAL
SHALL BE PROVIDED ABOVE THE EXITS OF THE PROTECTED ENCLOSURE. THE EQUIPMENT QTY EACH LOCATION HOSE REEL SYSTEM 100 GPM
34 1245-F-A1-0017 ROOF FLOOR FIREFIGHTING SYSTEM LAYOUT A0 1:100 No. HEAD PSIG
18. OS&Y GATE VALVE WITH TAMPER SWITCH, BUTTERFLY VALVE WITH LETTERING SHALL BE A MINIMUM OF 50MM HIGH. IT SHALL BE VISIBLE AT ALL AMPS. PHASE
35 1245-F-A1-0018 MACHINE ROOM LEVEL FIREFIGHTING SYSTEM LAYOUT A0 1:100 H.P. VOLTS HERTZ G.P.M
MOTORIZED DAMPER, FLOW SWITCH, ALARM CHECK VALVE ASSEMBLY TIMES OF THE DAY. ILLUMINATION SHALL BE ACTIVATED BY ON (FULL LOAD)
PRESSURE SWITCH, SPECIAL SYSTEM RELEASING PANELS, FIRE PUMP COMMENCEMENT OF THE DISCHARGE TIME DELAY.
FP-1 FIRE ELECTRIC PUMP (DUTY) 1 250 415 676 3 50 1000 295 BASEMENT-1
EQUIPMENT AND VALVES
CONTROLLERS (ELEC., DIESEL, JOCKEY) SHALL BE INTERFACED WITH BUILDING
MAIN FIRE ALARM SYSTEM THROUGH AN INTERFACE MODULE. 11. ALL ENCLOSURES PROTECTED BY CLEAN AGENTS SYSTEMS MUST BE SYMBOL DESCRIPTION ABBREVIATION
SUBJECTED TO AN ENCLOSURE INTEGRITY TEST. THE TEST MUST BE FP-2 FIRE DIESEL PUMP (STANDBY) 1 282 1000 295 BASEMENT-1
19. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR CARRYING OUT OF ALL CONDUCTED BY A QUALIFIED TESTER ACCEPTABLE TO THE QCD. THE TEST ALARM CHECK VALVE ACV
FIRE DETECTION AND PROTECTION, FIRE HOSE REEL/SPRINKLER WORK AS PER SHALL VERIFY THE ABILITY OF THE PROTECTED ENCLOSURE TO MAINTAIN THE FP-3 JOCKEY PUMP 1 30 415 81 3 50 50 335 BASEMENT-1 GATE VALVE GV
SPECIFICATION AND DRAWINGS IN ADDITION TO CIVIL DEFENSE REQUIREMENT. MINIMUM DESIGN CONCENTRATION FOR 10 MINUTES.THE ENCLOSURE TEST
CONTRACTOR SHALL INCLUDE IN THE PRICING ALL ITEMS WHICH ARE MUST BE WITNESSED BY THE QCD. THIS IS A PRE-CONDITION FOR ISSUE BE OS&Y VALVE WITH TAMPER SWITCH OS&Y
INDICATED ON THE ITEMS REQUIRED TO FULFILL THE REQUIREMENTS OF Q.C.S WITNESSED BY THE QCD. THIS IS A PRE-CONDITION FOR ISSUE OF THE
FUEL TANK SCHEDULE PER DIESEL ENGINE
BUTTERFLY VALVE WITH SUPERVISORY SWITCH BV
IN ADDITION TO CIVIL DEFENSE AUTHORITY BUT SPECIFICALLY NOT BUILDING'S FIRE SAFETY CERTIFICATE. EFFECTIVE --
MENTIONED IN THE DRAWING/SPECIFICATION. LOCATION TANK CAPACITY EFFECTIVE CAPACITY MINIMUM TANK SIZE NON RETURN VALVE / CHECK VALVE
DURATION -- NRV/CV
12. COMPLETE AREA OF THE ROOM TO BE PROTECTED WITH THE CLEAN AGENT
PRESSURE RELIEF VALVE RV
20. FIRE FIGHTING CONTRACTOR SHALL INCLUDE PRV WHEREVER PRESSURE SYSTEM INCLUDING ROOM SPACE, CEILING VOID, CABLE TRENCHES, AND ETC. BASEMENT-1 1 GAL / HP 2.46 m 2.35 m 18.44 Hrs.
EXCEEDS 12 BAR. WASTE CONE WAC

21. 1" PRV SHALL BE INSTALLED IN THE FIRE HOSE REEL WHEREVER THE CLEAN AGENT SYSTEM SEQUENCE OF OPERATION FIRE WATER TANK SCHEDULE FLOAT VALVE FLV
PRESSURE EXCEEDS 7 BAR. TEST AND DRAIN VALVE T&D
TYPE OF EFFECTIVE
LOCATION CONSTRUCTION NO. OF COMPARTMENT EFFECTIVE DURATION
22. ALL THE EQUIPMENT AND DEVICES USED FOR FIRE SAFETY-FIRE FIGHTING I-AUTOMATIC OPERATION: CAPACITY FLUSHING CONNECTION FLC
SYSTEM SHALL BE LISTED FOR SUCH PURPOSES AND APPROVED TYPE BY THE A. ACTIVATION OF ANY ONE OF THE DETECTOR IN EITHER CIRCUIT WITHIN THE REINFORCED 228.80 m
BASEMENT-1 2 Nos. 60.44 MINUTES CONCENTRIC REDUCER CR
QCDD. AFFECTED AREA SHALL; CONCRETE ( 60,442.58 gallons )
FOAM FIRE EXTINGUISHING SYSTEM FIRE PUMP SEQUENCE OF OPERATION AUTOMATIC AIR RELEASE VALVE AAV
23. THE CONTRACTOR TO REPLACE ONLY EQUIPMENTS THAT ARE NOT POSSIBLE 1. ILLUMINATE "ALARM" INDICATOR ON THE CONTROL PANEL AND
SEQUENCE OF OPERATION TO BRING BACK IN WORKING CONDITION. WHERE EVER, POSSIBLE THE DISPLAY CUSTOM MESSAGE FOR PROPER ZONE INDICATION.
FIRE PUMP ROOM REQUIREMENT 2-WAY 4" BREECHING INLET OR 4-WAY 6"
BREECHING INLET WITH CABINET BI2W / BI4W
1. FIRE PUMP SET CONSIST OF 3-PUMPS ( MAIN ELECTRICAL, DIESEL PUMP (SAME FLOW RATES ) EXISTING FIRE FIGHTING EQUIPMENTS SHALL BE REFURBISH AND USED. 2. ACTIVATE STROBE/HORN INSIDE (1ST STAGE ALARM). PG
PRESSURE GAUGE PG
AND A JOCKEY PUMP ) ENCLOSURE ENCLOSURE RATING
SEQUENCE OF OPERATION: 3. SEND PRE-ALARM SIGNAL TO MAIN FIRE ALARM PANEL. LOCATION DIMENSION
24. ALL SPRINKLER WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF CONSTRUCTION WALLS DOOR WINDOW WATER FLOW SWITCH WFS
ELECTRICALLY CONTROLLED FOAM DELUGE SYSTEM REQUIRES AN ELECTRIC SOLENOID VALVE COMPATIBLE
WITH SYSTEM RELEASING PANEL. AN EMERGENCY RELEASE VALVE IS PROVIDED FOR MANUAL OVERRIDE IN 2. ALL FIRE PUMP HAS IT'S OWN UL LISTED CONTROL PANEL COMPLETE WITH CONTROL WIRING, THE NFPA-13 AND ALL LOCAL AUTHORITIES AND AGENCIES HAVING REINFORCED
PRESSURE SWITCHES, POWER SUPPLY ETC... JURISDICTION. 1ST BASEMENT RECTANGULAR 2Hrs. 1.5Hrs. N.A. PG

FLOOR CONTROL VALVE ASSEMBLY FCVA


CASE OF MALFUNCTION OF THE RELEASING CONTROL PANEL. B. SUBSEQUENT OPERATION OF A "CROSS-ZONED" DETECTOR WITHIN THE CONCRETE
AFFECTED AREA SHALL; PG PG

1. WHEN THE RELEASING CONTROL PANEL DETECTS AN ALARM THRU SMOKE AND HEAT DETECTOR. 3. ALL FIRE PUMP SETS SHALL BE PREPARED TO WORK AUTOMATICALLY AND TO BE ACTUATED 25. IN ALL AREAS CONTRACTOR SHALL VERIFY AND INCLUDE FOR ANY ADDITIONAL 6" PRESSURE REDUCING VALVE PRVS
SUMMARY OF MATERIAL SPECIFICATION

DISCLAIMER: The CAD data is being supplied only to assist in production of the Sub-Consultant/Trade Contractor's work. It may contain some discrepancies and hence it should always be cross-checked with other relevant documents applying due diligence. Users are solely responsible for anything they produce using all or part of
PG PG

2. RELEASE CIRCUIT WILL ENERGIZE THE SOLENOID ACTUATOR IN THE DELUGE VALVE. BY PRESSURE SWITCH. SPRINKLER HEADS FOR CO-ORDINATION OF HEADS WITH FINAL INTERIOR 1. ILLUMINATE "PRE-DISCHARGE" INDICATOR ON THE CONTROL PANEL STATION (WITH BYPASS)
3. IT WILL ALLOWS THE VALVE TO OPEN AND WATER FLOW INTO THE SYSTEM PIPING TO FOAM DESIGNERS REQUIREMENTS. AND DISPLAY CUSTOM MESSAGE FOR PROPER ZONE INDICATION. OBLIQUE FLANGE TYPE LANDING VALVE LV-1
PROPORTIONER. 4. FIRE PUMP - PRESSURE SETTING SHALL BE ON PRE CALCULATED AND ACCURATE TO SUITE 2. ACTIVATE STROBE/HORN OUTSIDE (2ND STAGE ALARM).
THE SYSTEM REQUIREMENTS. 26. CONTRACTOR SHALL PERFORM & SUBMIT HYDRAULIC CALCULATIONS & SHOP OBLIQUE FLANGE TYPE LANDING VALVE LV-2
4. FOAM PROPORTIONER MIXED THE WATER AND THE SOLUTION TO CREATE FOAM AND FLOW INTO 3. SEND SIGNAL TO CLOSE ASSOCIATED DAMPERS AND SHUT DOWN MATERIAL DESCRIPTION WITH BUILT-IN PRV
THE OPEN FOAM SPRINKLER. DRAWINGS PRIOR TO COMMENCING THE INSTALLATION WORK. HVAC WITHIN THE HAZARD AREA. FLOW METER FLM
5. THE SEQUENCE OF OPERATION FOR THE THREE PUMPS SHALL BE AS FOLLOWS : 4. DEACTIVATE MAGNETICALLY HELD DOOR. 1. FIRE PUMPS HORIZONTAL SPLIT CASE PUMPS
IMPORTANT NOTICE ! THE DETAILED SEQUENCE OF OPERATION DESCRIBED BELOW IS SPECIFICALLY 27. ALL PIPING SHALL RUN CLOSE TO BEAMS, WALLS AND SLABS, SQUARE TO 5. ACTUATE CIRCUIT TO ENERGIZE 0-30 SECOND ADJUSTABLE 2. PIPING GALVANIZED ERW STEEL Sch. 40 INSPECTOR TEST CONNECTION
WITH ORIFICE PLATE ITC
WRITTEN FOR YOUR APPLICATION. OTHER SYSTEM'S OPERATION MAY DIFFER GREATLY DEPENDING ON THE ON DETECTION OF PRESSURE REDUCTION IN THE SYSTEM PRESSURE LOWER THAN BUILDING CONSTRUCTION, CONCEALED ABOVE HUNG CEILING AND WITHIN "EVACUATION TIMER".
THE START POINT OF JOCKEY PUMPS THEN FURRED SPACES. 3. VALVES(GATE & CHECK) OS&Y, GEAR OPERATED BUTTERFLY VALVE / SWING CHECK VALVE
SYSTEM'S REQUIREMENTS AND PARTICULARS OF THE PROJECTS. ALWAYS REFER TO THE SEQUENCE OF 6. ENABLE SYSTEM ABORT SEQUENCE.
MECHANICAL ALARM GONG MAG
OPERATION PROVIDED WITH 7. SEND ALARM SIGNAL TO MAIN FIRE ALARM PANEL. 4. FLOW / TAMPER SWITCHES VANE TYPE- LISTED FLOW SWITCH / TAMPER SWITCH
YOUR UNIT FOR PRECISE INFORMATION. THE HEAT AND SMOKE DETECTORS ARE WIRED ON TWO ZONES FOR THE JOCKEY PUMP SHALL BE ACTUATED FIRST TO COMPENSATE THE REDUCTION IN 28. SPRINKLER SYSTEM SHALL BE PROVIDED IN ALL SPACES IN THE BUILDING OR
OPERATION IN CROSSED ZONES MODE. PRESSURE. AS OTHERWISE REQUIRED. C. AFTER PRE-SET TIME DELAY SEQUENCE, THE FOLLOWING SHALL OCCUR; 5. SPRINKLERS STANDARD & QUICK RESPONSE
SURFACE MOUNTED FIRE HOSE REEL CABINET CONSISTING OF:
6. CONTROL PANELS UL-LISTED/ FM-APPROVED
THE ACTIVATION OF EITHER DETECTION ZONES WILL CAUSE THE FOLLOWING: AS PRESSURE IN THE SYSTEM CONTINUOUSLY DECREASE BELOW THE STARTING 29. PROVIDE FIRE EXTINGUISHER IN ALL LOCATIONS OF FIRE HOSE REEL OR FIRE 1. ACTUATE CIRCUIT TO RELEASE THE CLEAN AGENT SYSTEM INTO THE UPPER COMPARTMENT
POINT OF MAIN ELECTRICAL PUMP, THE JOCKEY PUMP CAN'T MEET THE SYSTEM HOSE REEL IN CABINET AND ALSO IN ALL OTHER LOCATIONS AS PER NFPA-10. AFFECTED AREA. 7. DRIVERS & CONTROLLERS UL-LISTED/ FM-APPROVED 1 NO. 25mm X 30 MTRS. LONG RUBBER AUTOMATIC
ON THE CONTROL PANEL ANNUNCIATOR: DEMAND AND THE MAIN ELECTRICAL PUMP SHALL BE ACTUATED AUTOMATICALLY TO (COVERAGE: 200m.sq. - LIGHT HAZARD: 150m.sq ORDINARY HAZARD) OR AS 2. ILLUMINATE "RELEASE" INDICATOR ON THE CONTROL PANEL AND
1" x 30 MTR. FIRE HOSE REEL AS PER EN 671-1 IN STEEL CABINET HOSE REEL FHRC-01
1. THE ZONE IN ALARM WILL BE DISPLAYED. MEET THE SYSTEM DEMAND. THE ELECTRIC PUMP WILL STOP AUTOMATICALLY AFTER SHOWN IN DRAWINGS. DISPLAY CUSTOM MESSAGE FOR DISCHARGE INDICATION. 8. HOSE & HOSE REELS W/ CABINETS
1 NO. 25mm GATE VALVE
2. THE ALARM LED WILL FLASH ALL THE STARTING CAUSES HAVE RETURN TO NORMAL AND 10 MINUTE MINIMUM RUN 3. ENERGIZE VISUAL INDICATOR (STROBE LIGHT) OUTSIDE THE HAZARD 9. BREECHING INLETS TWIN TYPE 4-WAY BREECHING INLET WITH 6" OUTLET 1 NO. 25mm PRESSURE REDUCING VALVE
3. THE LOCAL BUZZER WILL SOUND. TIME HAS ELAPSED. 30. FOR AREAS WHERE FALSE CEILING VOID IS MORE THAN 800 mm IN HEIGHT, IN WHICH OCCURED WITH STROBE/HORN.
FHRC-01 LOWER COMPARTMENT
CONTRACTOR SHALL SUPPLY UPRIGHT AND/OR PENDENT SPRINKLERS AS PER 10.AIR RELEASE VALVE 1" AIR RELEASE VALVE 1 NO. 4.5 KG. DRY POWDER FIRE EXTINGUISHER
SYSTEM OUTPUT ACTIVATION: IN CASE OF ELECTRICAL POWER SUPPLY FAILED, DIESEL PUMP SHALL BE ACTUATED NFPA -13 IRRESPECTIVE OF THE DRAWINGS. II-MANUAL OPERATION:
1. AN ALARM CONTACT FOR THE ALARM TRANSMISSION TO THE MAIN FIRE ALARM BUILDING PANEL AUTOMATICALLY TO COMPENSATE THE REQUIRED DEMAND TILL FINISHING THE FIRE 11. DRAINS TEST & DRAIN CONNECTION (UL/FM)
ACTIVATION OF MANUAL RELEASE STATION SHALL DUPLICATE THE "CROSS-ZONED
WILL BE ACTIVATED. FIGHTING PROCESS THEN SWITCH OFF THE DIESEL PUMP MANUALLY. 31. CONRACTOR SHALL COORDINATE WITH OTHER SERVICES TO IDENTIFY THE DETECTION" SEQUENCE DESCRIBED ABOVE EXCEPT TIME DELAY AND ABORT 12. SPECIAL SYSTEMS CLEAN AGENT SYSTEM, AEROSOL SYSTEM, FOAM SYSTEM
2. AN ALARM SIGNALLING CIRCUIT WILL BE ACTIVATED. ACTUAL OBSTRUCTIONS AT SITE. ADDITIONAL SPRINKLERS SHOULD BE FUNCTIONS. RECESSED MOUNTED FIRE HOSE REEL CABINET CONSISTING OF:
TO GUARANTEE THE PROPER AND EFFICIENT SEQUENCE OF OPERATION PROVIDED BELOW THE FIXED OBSTRUCTIONS MORE THAN 1200mm WIDE
THE ACTIVATION OF BOTH DETECTION ZONES (CROSSED ZONES) WILL CAUSE THE FOLLOWING: WITHOUT VARIATIONS CLAIM. III-ABORT OPERATION: UPPER COMPARTMENT
THE FOLLOWING PRESSURE SETTING VALUE TO BE ARRANGED AS RECOMMENDED BY IF ABORT SWITCH IS ACTIVATED WITHIN PRE-DISCHARGE PERIOD, THE FOLLOWING 1 NO. 25mm X 30 MTRS. LONG RUBBER AUTOMATIC
ON THE CONTROL PANEL ANNUNCIATOR: NFPA-20 : 32. SPRINKLERS LOCATED AT LOW LEVELS OR CRITICAL HEIGHT BELOW 2.20 SHALL OCCUR; HOSE REEL FHRC-02
1. THE ZONES IN ALARM WILL BE DISPLAYED. METERS SHALL BE EQUIPPED WITH SPRINKLER GUARDS.
1 NO. 25mm GATE VALVE
FIRE EXTINGUISHER TYPE AND SCHEDULE

the provided CAD data. CAD data is not intended to be issued to any third party without AEB's written consent for the same. In providing you with this CAD data, AEB does not assume any liability whatsoever unless expressed otherwise.
2. THE ALARM LED WILL FLASH 1. THE JOCKEY PUMP PRESSURE STOP POINT SHALL BE = MAIN PUMP CHURN PRESSURE + THE 1. ILLUMINATE "ABORT" INDICATOR ON THE CONTROL PANEL AND 1 NO. 25mm PRESSURE REDUCING VALVE
3. THE LOCAL BUZZER WILL SOUND. MINIMUM STATIC SUPPLY PRESSURE 33. A MINIMUM OF 40mm FLUSHING CONNECTION MUST BE PROVIDED AT THE END DISPLAY CUSTOM MESSAGE FOR PROPER ZONE INDICATION. LOWER COMPARTMENT
4. THE RELEASE LED WILL ILLUMINATE OF EACH CROSS-MAIN SECTION. 2. RELEASE OF GAS IS HELD IF ABORT SWITCH IS PRESSED NFPA 10- 2013 EDITION TABLE 6.2.1.1 FHRC-02 1 NO. 4.5 KG. DRY POWDER FIRE EXTINGUISHER
5. THE DISCHARGE LED WILL ILLUMINATE 2. THE JOCKEY PUMP START POINT SHALL BE AT LEAST 10 PSI LESS THAN THE JOCKEY PUMP CONTINUOUSLY. FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS-A HAZARD:
STOP POINT. 34. SPRINKLER SYSTEMS SHALL HAVE INSPECTOR TEST CONNECTION FITTED TO 3. AGENT WILL RELEASE IF ABORT SWITCH IS DEACTIVATED AND
SYSTEM OUTPUT ACTIVATION: THE MOST REMOTE SPRINKLER(S) ON EACH FLOOR/ZONE. AN ORIFICE TO COUNTDOWN IS COMPLETED.
3. THE ELECTRICAL FIRE PUMP START POINT SHALL BE 5 PSI LESS THAN THE JOCKEY PUMP SIMULATE A SINGLE SPRINKLER OPERATION SHALL BE FITTED TO THE END OF LIGHT ORDINARY EXTRA SURFACE MOUNTED FIRE HOSE REEL CABINET CONSISTING OF:
1. AN ALARM CONTACT FOR THE ALARM TRANSMISSION TO THE MAIN FIRE ALARM BUILDING PANEL (LOW)
CRITERIA (MODERATE) (HIGH)
WILL BE ACTIVATED. START POINT. USE ADDITIONAL 10 PSI INCREMENTS FOR EACH ADDITIONAL PUMP. IT.
HAZARD HAZARD HAZARD UPPER COMPARTMENT
2. AN ALARM SIGNALLING CIRCUIT WILL BE ACTIVATED. OCCUPANCY OCCUPANCY OCCUPANCY
FIRE PUMP PRESSURE SETTING: 35. FIRE DRAIN RISERS , PIPING & ALL WATER PIPING MATERIAL INSIDE PUMP 1 NO. 25mm X 30 MTRS. LONG RUBBER AUTOMATIC
3. THE RELEASE CIRCUIT WILL BE ACTIVATED AND THE CAF DISCHARGE WILL OCCUR.
ROOM SHALL BE ERW GALVANIZED STEEL PIPE SCHEDULE 40. HOSE REEL
4. THE DISCHARGE CONTACT WILL BE ACTIVATED FOR AUXILIARY FUNCTION. MINIMUM RATED SINGLE EXTINGUISHER 2-A 2-A 2-A
JOCKEY PUMP STOP PRESSURE 335 PSI 1 NO. 25mm GATE VALVE
MAXIMUM FLOOR AREA PER UNIT OF "A" 3,000 FT2 1,500 FT2 1,000 FT2 FHRC-03
36. INTERFACING OF FIRE ALARM SYSTEM SHALL BE DONE BY THE FIRE ALARM 1 NO. 25mm PRESSURE REDUCING VALVE
THE ACTIVATION OF ELECTRICAL EMERGENCY MANUAL RELEASE
JOCKEY PUMP START PRESSURE 325 PSI CONTRACTOR. MAXIMUM FLOOR AREA FOR EXTINGUISHER 11,250 FT2 11,250 FT2 11,250 FT2 LOWER COMPARTMENT
STATION WILL CAUSE THE FOLLOWING:
1 NO. 4.5 KG. DRY POWDER FIRE EXTINGUISHER
MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER 75 FT 75 FT 75 FT FHRC-03 1 NO. 65mm LANDING VALVE
ON THE CONTROL PANEL ANNUNCIATOR: ELEC. FIRE PUMP START PRESSURE 320 PSI 37. All FIREFIGHTING PIPES FOR FIRE SAFETY APPLICATION PENETRATING THRU
1. THE ZONE IN ALARM (MANUAL PULL) WILL BE DISPLAYED. WALLS AND SLABS SHALL BE SEALED WITH FIRE RETARDANT MATERIAL WITH 1 NO. 65mm X 30 MTRS. FIRE HOSE WITH NOZZLE
2. THE ALARM LED WILL FLASH DIESEL FIRE PUMP START PRESSURE 310 PSI RATING OF NOT LESS THAN THE FIRE RATING OF THE WALL OR SLAB BEING
SPRINKLERS IN CONCEALED CEILING NFPA 10- 2013 EDITION TABLE 6.3.1.1
FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS-B HAZARD:
3. THE LOCAL BUZZER WILL SOUND. PENETRATED. AND RAISED FLOOR SPACES RECESSED MOUNTED FIRE HOSE REEL CABINET CONSISTING OF:
4. THE RELEASE LED WILL ILLUMINATE. NOTE: BASIC MAXIMUM
38. PROVISION FOR EXPLOSION PREVENTION SHALL BE INSTALLED IF THE TYPE OF UPPER COMPARTMENT
5. THE DISCHARGE LED WILL ILLUMINATE TYPE OF MINIMUM TRAVEL
TRANSFORMER TO BE USED ARE OIL FILLED. 1 NO. 25mm X 30 MTRS. LONG RUBBER AUTOMATIC
PUMP CHURN PRESSURE TO BE VERIFIED AT SITE BY THE SPECIALIST CONTRACTOR AS 1. CONCEALED CEILING AND FLOOR SPACES NOT EXCEEDING 400mm IN DEPTH HAZARD EXTINGUISHER DISTANCE TO HOSE REEL
SYSTEM OUTPUT ACTIVATION: PER THE ACTUAL FIRE PUMP SELECTION. FIRE PUMP PRESSURE SETTINGS TO BE NEED NOT BE PROTECTED BY SPRINKLER. RATING EXTINGUISHER
39. THE EXHAUST PIPE SHALL BE COVERED WITH HIGH TEMPERATURE 1 NO. 25mm GATE VALVE
1. AN ALARM CONTACT FOR THE ALARM TRANSMISSION TO THE MAIN FIRE ALARM BUILDING PANEL UPDATED ACCORDINGLY. FHRC-04
INSULATION. 5-B 30 FT 1 NO. 25mm PRESSURE REDUCING VALVE
WILL BE ACTIVATED. 2. CONCEALED CEILING AND FLOOR SPACES EXCEEDING 400mm BUT NOT LIGHT
LOWER COMPARTMENT
2. AN ALARM SIGNALING CIRCUIT WILL BE ACTIVATED. EXCEEDING 800mm IN DEPTH AND DO NOT CONTAIN COMBUSTIBLE MATERIAL (LOW) 10-B 50 FT A 11/05/17 ISSUED FOR TENDER KAS
40. CLEAN AGENT SYSTEM SHALL COMPLY WITH NFPA 2001 AND INTEGRITY TEST 1 NO. 4.5 KG. DRY POWDER FIRE EXTINGUISHER
3. THE RELEASE CIRCUIT WILL BE ACTIVATED AND THE CAF DISCHARGE WILL OCCUR. NEED NOT BE PROTECTED BY SPRINKLERS.
DIESEL ENGINE FUEL TANK CAPACITY SHALL BE CONDUCTED IN THE PRESENCE OF QCDD AUTHORIZED 10-B 30 FT FHRC-04 1 NO. 65mm LANDING VALVE
4. THE DISCHARGE CONTACT WILL BE ACTIVATED FOR AUXILIARY FUNCTION. ORDINARY
(DIESEL PUMP) REPRESENTATIVES. 3. CONCEALED CEILING AND FLOOR SPACES EXCEEDING 400mm BUT NOT (MODERATE) 1 NO. 65mm X 30 MTRS. FIRE HOSE WITH NOZZLE NO. DATE DESCRIPTION APPROVED
20-B 50 FT
THE ACTIVATION OF MECHANICAL EMERGENCY MANUAL STATION EXCEEDING 800mm IN DEPTH AND CONTAINING COMBUSTIBLE MATERIAL AEB STAMP PLANNING APPROVAL
INSIDE THE FOAM DELUGE SYSTEM WILL CAUSE THE FOLLOWING: ENGINE DRIVEN FIRE PUMP FUEL TANK CAPACITY 650 GALS. 41. CLEAN AGENT SYSTEM PIPES SHALL BE SEAMLESS BLACK STEEL SCHEDULE 80 SHALL BE PROTECTED BY SPRINKLERS INSTALLED ON THE EXTENDED BASIS. EXTRA 40-B 30 FT FIRE EXTINGUISHERS & FIRE BLANKET:
GRADE-B PAINTED WITH RED PAINT. THE FITTINGS SHALL BE SUITABLE TO SCH. SPRINKLER PROTECTION MAY BE OMITTED WHERE THE SPACE IS (HIGH) 80-B 50 FT
ON THE CONTROL PANEL ANNUNCIATOR: DIESEL DRIVEN FIRE PUMP 1000 GPM 80 PIPES AND IN ACCORDANCE WITH NFPA 2001. SUBDIVIDED BY FIRE AND DRAUGHT STOPS AT INTERVALS NOT EXCEEDING SYMBOL DESCRIPTION CLASS CAPACITY
1. THE ZONE IN ALARM (WATERFLOW) WILL BE DISPLAYED. 15m IN ANY DIRECTION.
TOTAL HEAD 295 PSI 42. CLEAN AGENT FIRE EXTINGUISHING SYSTEM SHALL BE SUPER-PRESSURIZED PFE DRY POWDER FIRE EXTINGUISHER ABC 4.5 KG.
2. THE ALARM LED WILL FLASH CLASS-C LOCATION:
3. THE LOCAL BUZZER WILL SOUND. AT 500PSI AND INSTALLED,TESTED AND COMMISSIONED IN ACCORDANCE WITH 4. CONCEALED CEILING AND FLOOR SPACES EXCEEDING 800mm SHALL BE C 4.5 KG.
CLASS C EXTINGUISHERS ARE REQUIRED WHERE ENERGIZED ELECTRICAL EQUIPMENT IS POTENTIALLY DIRECTLY INVOLVE IN PFE CLEAN AGENT FIRE EXTINGUISHER
4. THE DISCHARGE LED WILL ILLUMINATE DIESEL ENGINE HORSEPOWER 282 BHP NFPA-2001-(2012). PROTECTED BY SPRINKLER INSTALLED IN ACCORDANCE WITH THE
OR SURROUNDS ELECTRICAL EQUIPMENT. NORMALLY CLASS C FIRES ARE IN DIRECT LOCATION OF CLASS A OR CLASS B FIRES,
REQUIREMENT FOR THE PARTICULAR HAZARD. PFE WET CHEMICAL FIRE EXTINGUISHER K 6 LT.
THE EXTINGUISHER SHALL BE SIZED PER THE CLASS A OR CLASS B HAZARD.
SYSTEM OUTPUT ACTIVATION: FUEL CONSUMPTION 43. THE SPECIALIZED CONSULTANT FOR CLEAN AGENT FIRE EXTINGUISHING AND
35.25 Gal/Hr FB FIRE BLANKET N/A 6' X 6'
1. AN ALARM CONTACT FOR THE ALARM TRANSMISSION TO THE MAIN FIRE ALARM BUILDING PANEL (=282 Bhp x 1Gal / Hp-8Hr) AUTOMATIC FIRE SUPPRESSION SYSTEM SHALL SUBMIT DETAILED DRAWING
CLASS-D LOCATION:
WILL BE ACTIVATED. AND CALCULATION FOR QCD APPROVAL PRIOR TO WORK COMMENCEMENT.
FIRE EXTINGUISHERS FOR CLASS D LOCATION SHALL NOT BE LOCATED MORE THAN 75 FT. FROM THE HAZARD.
2. AN ALARM SIGNALLING CIRCUIT WILL BE ACTIVATED. AS PER NFPA 20, 11.4.2.1 FUEL TANK CAPACITY, DIESEL ENGINE DRIVE FUEL
SIZE DETERMINATION FOR CLASS D LOCATIONS IS BASED ON THE SPECIFIC COMBUSTIBLE METAL, PARTICLE SIZE, SPRINKLER HEADS CONSULTANT:
3. THE CAF DISCHARGE WILL OCCUR AND THE DISCHARGE CONTACT WILL BE ACTIVATED FOR SUPPLY TANK(S) SHALL HAVE A CAPACITY AT LEAST EQUAL TO 1 GAL. PER 44. THE SPECIALIZED CONSULTANT FOR FIRE SUPPRESSION SYSTEM SHALL
AREA TO BE COVERED, AND MANUFACTURER RECOMMENDATIONS.
AUXILIARY FUNCTION. HORSEPOWER, PLUS 5 PERCENT VOLUME FOR EXPANSION AND 5 PERCENT SUBMIT DETAILED DRAWING AND CALCULATION FOR QCD APPROVAL PRIOR TO SYMBOL DESCRIPTION K-FACTOR
VOLUME FOR SUMP. WORK COMMENCEMENT.
AUTOMATIC DISCHARGE
CLASS-K LOCATION:
UPRIGHT SPRINKLER HEAD 5.6 Arab Engineering Bureau
45. THE KITCHEN HOOD SHALL BE PROVIDED WITH FIRE SUPPRESSION SYSTEM BY CLASS K HAZARDS SHALL HAVE A FIRE EXTINGUISHER LOCATED WHERE IS A POTENTIAL FOR A FIRE INVOLVING COMBUSTIBLE COOKING AEB HEADQUARTERS:
THE DELUGE FOAM SYSTEM DISCHARGE WILL OCCUR FOR 10 MINUTES. AT THE END OF FUEL TANK VOLUME
564 Gals. THE SPECIALIZED CONTRACTOR. . MEDIA (VEGETABLE OR ANIMAL OILS AND FATS). THE EXTINGUISHER SHALL BE LOCATED NOT MORE THAN 30 FT. FROM THE HAZARD. UPRIGHT SPRINKLER HEAD 8.0 P.O. Box 1148 Doha, Qatar Tel +974 4406 88 88 Fax +974 4447 78 68
THE SOAK TIMER, THE DELUGE FOAM SYSTEM DISCHARGE WILL AUTOMATICALLY STOP. (1 GAL/HP / 8 HR. X 282 HP X 16HR. OPERATION) Email aeb@aeb-qatar.com Web www.aeb-qatar.com
THE RELEASE LED WILL THEN START FLASHING. CONCEALED PENDENT HIGH TEMPERATURE SPRINKLER HEAD 5.6 OTHER BRANCHES:
SUMP & EXPANSION 10% 46. SPECIAL TYPE OF FIRE SUPPRESSION SYSTEMS LIKE, CLEAN AGENT SYSTEM, ABU DHABI * MANILA * KUALA LUMPUR * MUSCAT
FOAM DELUGE SYSTEM, KITCHEN HOOD SYSTEM, AEROSOL SYSTEM, & ETC. TO PENDENT SPRINKLER HEAD 5.6
KITCHEN HOOD FIRE PROTECTION MINIMUM TANK SIZE 620.4 Gals.
(SAY 650 Gals.)
BE DESIGNED, CALCULATED, & VERIFIED BY THE SPECIALIST CONTRACTOR. PROJECT :

SEQUENCE OF OPERATION 18.44 Hrs.


THERE SHALL BE NO VARIATION CLAIMS IN THIS REGARD. CONCEALED PENDENT SPRINKLER HEAD 5.6
PROPOSED QATAR AIRWAYS RESIDENTIAL TOWER
DURATION OF USE SIDEWALL SPRINKLER HEAD 5.6
( AT FULL TANK ) 47. GRP LINING SHALL BE PROVIDED ON ALL INTERNAL WALLS INSIDE THE FIRE (4B+G+29 FLOORS)
D:\REVIT FILES\1245-16_MF_QA RES.TOWER_CF_AEB_R17_Wilson.rvt

FIRE IS DETECTED BY THE MECHANICAL LINK, OR ELECTRIC LINEAR HEAT DETECTION CABLE, OR THE SYSTEM IS WATER TANKS.
MANUALLY ACTIVATED BY A REMOTE PULL STATION. ABBREVIATION OWNER :
QATAR AIRWAYS
THE CONTROL SYSTEM ACTIVATED PRESSURIZED AGENT STORAGE CONTAINERS. RN RISER NIPPLE UP PIPE UP
SITE :
T/B PIPE TO BELOW PIPE DIAMETER AL DAFNA, WEST BAY DOHA, QATAR
THE FUEL SUPPLY IS SHUT DOWN BY INTERFACING SOLENOID VALVE.
FUEL TANK BUND WALL CALCULATION T/A PIPE TO ABOVE DP DRAIN PIPE
TITLE :
THE FIRE ALARM SYSTEM IS ACTIVATED BY AN INTERFACING MODULE.
F/A PIPE FROM ABOVE WSP WET STANDPIPE
GENERAL NOTES, LEGENDS, ABBREVIATIONS,
PLOTTED DATE: 11/05/2017 8:07:40 AM

MINIMUM TANK SIZE IN GALLONS 650 gals.


THE WET CHEMICAL AGENT, DESIGNED SPECIFICALLY FOR THE CHALLENGES POSED BY OIL AND GREASE IN A
KITCHEN ENVIRONMENT, IS PROPELLED THROUGH THE SYSTEM PIPING BY THE STORED PRESSURE
F/B PIPE FROM BELOW SRP SPRINKLER PIPE & DRAWINGS LIST FIRE FIGHTING LAYOUT
MINIMUM TANK SIZE IN CUBIC METERS 2.46 m DRAWN BY : DESIGN BY : CHECKED BY : APPROVED BY :
CONTAINER. DN PIPE DOWN HRP HOSE REEL PIPE WLC SP MH KAS
THE WET CHEMICAL AGENT DISCHARGES FROM STRATEGICALLY POSITIONED NOZZLES PROTECTING THE REQUIRED BUND WALL CAPACITY 2.46 m DATE : SCALE @ A0:
HOOD, DUCT AND APPLIANCES APC AGENT QUICKLY SUPPRESSES THE FLAMES AND FORMS A PROTECTIVE NOVEMBER 2016 NTS.
LAYER THAT NOT ONLY EXTINGUISHES THE FIRE, BUT ALSO PREVENT RE-IGNITION. ADDING 20% SAFETY FACTOR 2.95 m REVISION
PROJECT NO : DRAWING NO :

TOTAL BUND WALL CAPACITY L = 2.50 m W = 1.50 m H = 0.80 m V = 3.00 m 1245-16 1245-F-A0-0001 A

You might also like