NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-074
Transformer Differential Protection Relay (87T) Page Number:
2 of 5
Commissioning Work Instruction

2.0 RESPONSIBLITIES

- Anyone working in testing location during commission stage must follow the safety
requirements as per SEC rules and CSD employees are responsible for applying
safety rules in all places which they working in.
- Project site engineer is responsible for committing the contractor to prepare testing
and commissioning places to be done in proper climate conditions as per Company
policies, procedures and accepted temperatures the relays, devices and test
equipment can be tested or operated within it.
- Any of CSD staff is responsible for testing activities according to approved
specification and design and he shall not start any test for any Transformer
Differential Protection relay (87T) until providing the following:

o Approved test forms.


o Factory Tests certificates.
o Updated Approved final settings.
o All relays must be configured.
o Relay manuals.
o Approved schematic drawings.
o Protection requirement.
o Test equipment valid calibration certificates.
o Approved Contractor organization chart.
o Contractor staff approved qualification certificates.

- Its responsibility of the commissioning contractors to provide all testing


Transformer Differential Protection relay (87T) with its valid calibration certificates
that will maybe require applying the testing / commissioning procedure in proper
manner.
- Its responsibility of the CSD Engineer/Technician to check and witness all activities
required for Transformer Differential Protection relay (87T) following all of this work
instruction.
- CSD Engineer/Technician is responsible for recording status of any test for
Transformer Differential Protection relay (87T) in its check list and test form as per
the following work instruction.
- Each check list and test form shall be signed by CSD engineer/technician and
testing contractor engineer.

Archiving System Website: http://AMAS TP-NG-6250-001-007


NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-074
Transformer Differential Protection Relay (87T) Page Number:
3 of 5
Commissioning Work Instruction

3.0 Work Instructions of Transformer Differential Protection relay (87T)


Commissioning and Testing

3.1 General Mechanical Checks and Visual Inspection

Reference / Criteria
Item Description
Limit
1. General Visual Inspection WI-NG-6460-002-056
CT ratios, and matching CT selection is correct for TX type
2.
(Star or Delta) and for Vector Group

3.2 Electrical Tests

Reference /
Item Description
Criteria Limit
As per WI-NG-
6460-002-057&
1. General Electrical Tests
WI-NG-6460-002-
058
Check Measurements:
2.
Secondary & primary current values for all phases.
Test through current restrain/stability for all phases and all
3.
types of faults
Test pick-up\drop off differential current Id> (without zero
4. sequence elimination and with it). For all phases and all types
of faults and transformer sides.
Test Pick-up\drop off differential current Id>>. For all phases
5.
and all types of faults and transformer sides.
6. Test Bias Characteristic for all phases and all types of faults
Test 2nd & 5th Harmonic restraint. For all phases and all types of
7.
faults
Test Cross Blocking Function. For all phases and all types of
8.
faults
Test negative sequence Relay Operating Angle ( if it is
9.
applicable)
Test sensitive negative sequence ( turn-to-turn fault ) ( if it is
10.
applicable)
Archiving System Website: http://AMAS TP-NG-6250-001-007
NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-074
Transformer Differential Protection Relay (87T) Page Number:
4 of 5
Commissioning Work Instruction

3.3 Related Tests

Item Description Remarks


1. Final Setting as per approved setting
2. Stability & Sensitivity Test by simulation of external and
internal faults
3. Function Test & Scheme Check
4. Final Trip Test
5. On Load Test

Archiving System Website: http://AMAS TP-NG-6250-001-007


NATIONAL GRID

Title: Index Number:


WI-NG-6460-002-074
Transformer Differential Protection Relay (87T) Page Number:
5 of 5
Commissioning Work Instruction

4.0 REFERENCES

Index Number /
Title
Reference Number
PR-NG-6460-002 Project Commissioning Procedure
WI-NG-6460-002-056 Protection Relays general mechanical checks & visual inspection
WI-NG-6460-002-057 Protection Relays general electrical tests
WI-NG-6460-002-058 Guidelines for Testing Digital& Numerical Protection & Control
Relays and IEDs
CL-NG-6460-002-074 Checklist for Transformer Differential Protection Relay (87T)

5.0 REVISION HISTORY

Version Date Brief Description of Change / Annual Review


00 2015-07-01 First issue.

This document shall comply in accordance with the existing Companys Rules and Regulations.
Any modifications therein found not conformance with the document shall be declared invalid.
For clarification and verification on this document, contact the following:

Engr. Tarek Mohammad Ahmad


Technical Support and Coordination Division
Commissioning Services Department
Technical Services Business Unit
Extension No. 77469 Email: 69608@ngrid.sa

Archiving System Website: http://AMAS TP-NG-6250-001-007


NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-074
Check List of Transformer Differential Protection Relay (87T) Page Number:
Commissioning 1 of 2

1.0 Equipment General Data and Information

Substation
Bay/Panel
Equipment Serial No

2.0 General Mechanical Checks and Visual Inspection

Item Description Done Remarks


General Visual Inspection. (marked check list CL-NG-6460-
1.
002-056 should be attached )
CT ratios, and matching CT selection is correct for TX type
2.
(Star or Delta) and for Vector Group

3.0 Electrical Tests

Item Description Done Remarks


General Electrical Tests. (Marked check lists CL-NG-6460-
1.
002-057 And CL-NG-6460-002-058 should be attached )
Check Measurements:
2.
Secondary & primary current values for all phases.
Test through current restrain/stability for all phases and all
3.
types of faults
Test pick-up\drop off differential current Id> (without zero
4. sequence elimination and with it). For all phases and all types
of faults and transformer sides.
Test Pick-up\drop off differential current Id>>. For all phases
5.
and all types of faults and transformer sides.
6. Test Bias Characteristic for all phases and all types of faults
Test 2nd & 5th Harmonic restraint. For all phases and all types
7.
of faults
Test Cross Blocking Function. For all phases and all types of
8.
faults
Test negative sequence Relay Operating Angle ( if it is
9.
applicable)
Test sensitive negative sequence ( turn-to-turn fault ) ( if it is
10.
applicable)
Archiving System Website: http://AMAS
NATIONAL GRID

Title: Index Number:


CL-NG-6460-002-074
Check List of Transformer Differential Protection Relay (87T) Page Number:
Commissioning 2 of 2

4.0 Related Tests

Item Description Done Remarks


1. Final Setting as per approved setting
2. Stability & Sensitivity Test by simulation of external and
internal faults
3. Function Test & Scheme Check
4. Final Trip Test
5. On Load Test

CSD Contractor T&C Contractor


Name
Sign.