You are on page 1of 4

Worldwide

www.tyco-fire.com
Contacts

Model AMD-1 Automatic Air Maintenance Device


Pressure Reducing Type with
Field-Adjustable Pressure Regulator
General Technical
Description Data
The TYCO Model AMD-1 Automatic Air Approvals
Maintenance Device is an automatic, UL and C-UL Listed
field-adjustable, pressure reducing FM Approved
device. It is used to control the pres- NYC Approved under MEA 206-02-E
sure in a dry pipe sprinkler system, pre- Maximum Inlet Air (or Nitrogen)
action system, or dry pilot line system Supply Pressure
of a dry pilot actuated deluge or preac- 200 psi (13,8 bar)
tion valve.
Field-Adjustable Outlet Pressure
The Model AMD-1 Device is utilized Range
in applications where there is a com- 5 to 70 psi (0,4 to 4,8 bar)
pressed air (or nitrogen) source con-
trolled at a higher pressure than the Assembly
desired system pressure. Pressure Major components illustrated in Figure
sources include plant air supplies with
their own automatic compressor con-
1 are factory assembled with galva-
nized steel nipples and malleable iron
Installation
trols or nitrogen supplies with single- pipe fittings. The TYCO Model AMD-1 Automatic
stage, cylinder-mounted pressure Air Maintenance Device should be
regulators. Operation installed in the horizontal position as
shown in figure 1, as well as in accor-
The Model AMD-1 Automatic Air Main- dance with the following instructions:
The By-Pass Valve in the Model AMD-1
tenance Device is a re-designation for
Automatic Air Maintenance Device is
the Central Model D-2, Gem Model
opened to quickly fill the system during NOTICE
F324, and Star Model S460.
initial pressurization. Once the required Moisture build-up can adversely affect
system pressure has been reached, performance. Suitable consideration
NOTICE the By-Pass Valve is closed and the must be given to the removal of exces-
The Model AMD-1 Automatic Air Main- Air Supply Control Valve is left open to sive moisture from the compressed air
tenance Devices described herein must place the Model AMD-1 Device in auto- supply.
be installed and maintained in compli- matic operation.
ance with this document and with the 1. Make connections a minimum of
When there is a small leak in the 1/2 inch (DN15) pipe size between
applicable standards of the National system, the Pressure Regulator auto-
Fire Protection Association, in addi- the inlet air supply and the Model
matically maintains system pressure at AMD-1 Device, as well as between
tion to the standards of any authorities the preset level. The 3/32 inch (2,4 mm)
having jurisdiction. Failure to do so the Model AMD-1 Device and the
orifice in the Restrictor Check Valve system to pressurize.
may impair the performance of these limits the flow of air from the Pressure
devices. Regulator into the system to a value 2. Place a 1/2 inch (DN15), non-spring
Owners are responsible for maintain- significantly less than that exhausted loaded, rubber-faced, swing-type
ing their fire protection system and by the operation of a 5.6 K-factor check valve between the Model
devices in proper operating condition. sprinkler. AMD-1 Device and the system to
The installing contractor or sprinkler pressurize. A check valve of this
manufacturer should be contacted type is provided in the air supply
with any questions. trim of TYCO dry pipe valves, pre-
action valves, and dry pilot trim.

Page 1 of 4 AUGUST 2015 TFP1221


TFP1221
Page 2 of 4

2" 16-1/8""
(50,8 mm) (409,6 mm)
BY-PASS VALVE
1/4" NPT
(NORMALLY
GAUGE
CLOSED)
TEST PORT
3-1/4" 1/2" NPT P/N 46-047-1-004
(82,6 mm) OUTLET
CONNECTION
(TO SYSTEM)
8-1/2"
(215,9 mm) 1/2" NPT
LABEL INLET CONNECTION
(FROM COMPRESSED
AIR SUPPLY)

RESTRICTOR
CHECK VALVE
P/N 92-326-1-003
PRESSURE AIR SUPPLY
REGULATOR STRAINER CONTROL VALVE
(ADJUSTABLE) P/N 52-353-1-002 (NORMALLY OPEN)
P/N 92-324-1-012 P/N 46-048-1-002
FIGURE 1
MODEL AMD-1
AUTOMATIC AIR MAINTENANCE DEVICE

Setting 6. Open the Air Supply Control Valve


in the Model AMD-1 Device.
10. Open the control valve in the
air supply trim to the system to
Procedure 7. While observing the relocated
pressure gauge, adjust the output
pressurize.
11. Open the Air Supply Control Valve
The TYCO Model AMD-1 Automatic pressure of the Pressure Regula- in the Model AMD-1 Device.
Air Maintenance Device must be tor. Pull the knob out and away 12. Open the By-Pass Valve in the
set in accordance with the following from the Pressure Regulator body Model AMD-1 Device.
instructions: and then slowly turn the knob
clockwise, as viewed from the 13. Close the By-Pass Valve after the
1. Determine the pressure that meets system is pressurized to approxi-
knob end of the Pressure Regu-
the minimum requirements of the mately 5 psi (0,4 bar) less than the
lator, to increase pressure, and
system to pressurize. minimum required system pres
counter-clockwise to decrease
2. Close the Model AMD-1 By-Pass pressure. sure determined in Step 1.
Valve, and close the Model AMD-1 14. After the system pressure sta-
When decreasing pressure, the air
Air Supply Control Valve. bilizes, note the value and com-
pressure must be relieved down
3. Open the control valve in the air stream of the Pressure Regulator pare with the requirement. Re-
supply trim of the system to pres- by temporarily opening the control adjust the Pressure Regulator, as
surize and then reduce the system valve in the air supply trim of the required.
air pressure to 0 psi. system to pressurize, assuming that
4. Close the control valve in the the system to pressurize is at 0 psi. NOTICE
air supply trim of the system to After the Pressure Regulator is set, If the system was over-pressurized
pressurize. push the knob in and towards the during manual fill, open a suitable
5. Remove the system pressure Pressure Regulator body to snap connection to the system and manu-
gauge from its connection and it in a locked position. ally reduce the pressure to the desired
temporarily install it in the 1/4 inch 8. Close the Air Supply Control Valve value. The Model AMD-1 Automatic Air
NPT Model AMD-1 Gauge Test in the Model AMD-1 Device. Maintenance Device then automatically
Port. maintains the preset system pressure.
9. Return the system air pressure The Restrictor Check Valve prevents
gauge to its normal location. Re- the Pressure Regulator from bleeding
CAUTION install the 1/4 inch pipe plug in the down the system pressure.
Before removing the plug, make certain Model AMD-1 Gauge Test Port.
Apply pipe-thread sealant spar- In order to minimize the time for system
that the piping to which the Model
ingly to the plug threads only. trip in the event of a sprinkler opera-
AMD-1 Gauge Test Port is connected
tion, set the system pressure at the
is at 0 psi. Failure to do so may result
minimum required value.
in personal injury or property damage. CAUTION
Before removing the pressure gauge,
make certain that the piping to which
the Model AMD-1 Gauge Test Port is
connected is at 0 psi. Failure to do so
may result in personal injury or prop-
erty damage.
TFP1221
Page 3 of 4

Care and Automatic sprinkler systems are rec-


ommend to be inspected, tested, Limited
Maintenance and maintained by a qualified Inspec-
tion Service in accordance with local Warranty
The TYCO Model AMD-1 Automatic requirements and/or national code. For warranty terms and conditions, visit
Air Maintenance Device must be main- The Model AMD-1 Device must be www.tyco-fire.com.
tained and serviced in accordance with inspected quarterly in accordance with
the following instructions, in addition to
any specific requirements of the NFPA.
the following instructions: Ordering
1. Verify that the By-Pass Valve is
Any impairment must be immediately
corrected.
closed. Procedure
2. Close the Model AMD-1 Air Supply Contact your local distributor for avail-
NOTICE Control Valve and clean out the 1/4 ability. When placing an order, indi-
inch Strainer located at the inlet cate the full product name, including
Before closing a fire protection system to the Restrictor Check Valve. Be
main control valve for maintenance description and Part Number (P/N).
sure to reinstall the strainer screen
work on the fire protection system and tighten the cap securely. Model AMD-1 Device
that it controls, obtain permission to Specify: Model AMD-1 Automatic Air
shut down the affected fire protec- 3. Open the Model AMD-1 Air Sup- Maintenance Device, P/N 52-324-2-002
tion system from the proper authori- ply Valve and verify that the control
ties and notify all personnel who may valve in the air supply trim to the Replacement Parts
be affected by this action. system to pressurize is open. Specify: (description), P/N (specify per
Figure 1)
It is recommended that accumulated 4. Verify that the system pressure is
moisture be removed from air supply essentially the same as the previ-
moisture filtration equipment at least ously established requirement. If
quarterly. More frequent inspections not, adjust the system pressure
may be necessary in particularly humid as follows:
environments. a. Close the systems main con-
After placing a fire protection system trol valve and open the main
in service, notify the proper authori- drain valve. If the system is so
ties and advise those responsible for equipped, close the Accelera-
monitoring proprietary and/or central tor Control Valve.
station alarms. b. Follow Steps 1 through 14 in
Responsibility lies with owners for the the Setting Procedure section.
inspection, testing, and maintenance of c. Slowly open the Accelerator
their fire protection system and devices Control Valve, as applicable.
in compliance with this document, as
well as with the applicable standards of d. Slowly open the main con-
the National Fire Protection Association trol valve. After water begins
(for example, NFPA 25), in addition to to flow, slowly close the main
the standards of any other authorities drain valve, then completely
having jurisdiction. Contact the install- open the main control valve.
ing contractor or sprinkler manufac- The Model AMD-1 Automatic
turer regarding any questions. Air Maintenance Device is now
ready for service.
TFP1221
Page 4 of 4

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.

You might also like