You are on page 1of 58

CXR Larus 80-100-180 issue 10

September 2007

Model 5702
RouteSwitch TM

This manual applies to the following equipment:

Model Equip Issue Model Equip Issue


5702 L1 8 5702 L3A 2
5702 L1A 6 5702 L11 1
5702 L1B 1
5702 L2 1
5702 L2A 1
CXR Larus 80-100-180 issue 10
September 2007

RouteSwitch is a registered
trademark of CXR Larus Corp.
Copyright 2007
All Rights Reserved
Printed in U.S.A.
CXR Larus 80-100-180 issue 10
September 2007
_______________________________________________________________________

Contents
_______________________________________________________
1. Introduction
1.1 General 1-1

2. RouteSwitch System Description


2.1 General 2-1
2.11 Features 2-5
2.12 Specifications 2-5
2.13 Ordering Information 2-8
2.2 Detailed RouteSwitch Information 2-8
2.21 RouteSwitch Circuit Pack 2-11
2.22 Circuit Pack Operation 2-16
2.23 Circuit Pack Option Switches 2-18
2.24 RouteSwitch Powering 2-20
2.25 Maximum Cable Distance 2-20
2.26 Alarms 2-21

3. Installation
3.1 General 3-1
3.2 Equipment Installation 3-2
3.3 Circuit Pack Option Settings 3-6

4. Testing
4.1 General 4-1
4.2 Testing Equipment Required 4-1
4.3 Transmission, Protection Switching, Alarm,
and E2A Telemetry Tests 4-2
4.4 Establishing Service 4-8

5. Trouble Analysis and Maintenance 5-1

6. Warranty 6-1

7. Equipment Issue Information 7-1

i
CXR Larus 80-100-180 issue 10
September 2007

Figures
2-1 Typical RouteSwitch System Application 2-2
2-2 RouteSwitch Simplified Schematic Diagram 2-3
2-3 Jitter Transfer Function 2-6
2-4 Model 5702 L2/L2A/L11 DS1 Terminal, 2 Slots 2-9
2-5 Model 5702 L3A Six DS1 Terminal, 12 Slots 2-10
2-6 Model 5702 L1/L1A Circuit Pack Faceplate 2-12
2-7 Model 5702 L1/L1A Board Switch and LED Layout 2-13
2-8 Maximum DS1 Terminal Cable Distances 2-21
2-9 Model 5702 L2/L2A/L11 Shelf Backplane Connectors
and Terminal Block 2-22
2-10 Model 5702 L3A Shelf Backplane Connectors 2-23

3-1 Model 5702 L3A Frame Ground Connection 3-3

4-1 RouteSwitch Test Connections 4-3

Tables
2-A RouteSwitch Soft Fail Delay Settings (BER) 2-19
2-B RouteSwitch Hard Fail Delay Settings (OOF, LOS,
and AIS) 2-19
2-C RouteSwitch BER Threshold Settings 2-20
2-D Connector Designations for Model 5702
L2/L2A/L11 Shelf 2-24
2-E Connector Designations for Model 5702 L3A Shelf 2-26
2-F Alarm Conditions 2-29
2-G E2A Input Control 2-29
2-H E2A Scanner Status Conditions per System 2-30
2-I Suggested Maintenance for Circuit Pack Alarm Status
and Display 2-32

ii
CXR Larus 80-100-180 issue 10
September 2007
_____________________________________________________________________

Introduction 1
______________________________________________________________

1.1 General
1.101 The purpose of this document is to provide information to aid technicians in
understanding the Model 5702 RouteSwitch system. A general and a detailed
description of the RouteSwitch and the procedures for installing and testing it are
included.

1.102 Issue 10 of this manual applies to components referenced in Section 7, Equipment Issue
Information.

1.103 Note the admonishments in the form of CAUTIONS that appear in the text from time to
time. They indicate the presence of a hazard that can cause personal injury or
equipment damage if not avoided.

1.104 This document re-issue is intended to document Model 5702 List 1B and to explain its
relationship to List 1 and List 1A cards, as well as to clarify misleading statements and
correct errors from earlier issues of this document.

1.105 Model 5702 List 1B is extremely similar to List 1 and List 1A cards. These cards are
physically/visually identical except for the identification markings for List number and the
software contained within the PROM chips. The U3 PROM chip has different software
number markings (e.g. 058-90188-000) to agree with different List versions. Operational
differences are very slight.

1.106 If there are no intelligent network elements along the two transmission facilities, then List
1 and List 1A may be the best choices. If there are intelligent network elements, then List
1B may be the best choice.

1.107 An example of an intelligent network element would be a smart CSU. If LOS appears
on the network side, it forwards AIS to the CPE side. List 1B reacts differently to AIS as
compared with List 1 or List 1A. A dumb network element does not significantly change
the T1 signal progressing in one direction.

1-1
[This page is intentionally left
blank.]

1-2
CXR Larus 80-100-180 issue 10
September 2007
_______________________________________________________________________

RouteSwitch System Description 2


_______________________________________________________

2.1 General
2.101 The RouteSwitch is a Digital Signal Level 1 (DS1) ring diversity switch that provides cost
effective, self-healing network capabilities in the event of cable cuts, electronic failures,
or node failures. A typical RouteSwitch system application appears in Figure 2-1. As
shown, protection for the incoming DS1 signal at the central office RouteSwitch is
provided by duplicating the DS1 signal and routing the duplicated signals over separate
transmission paths (the T-carrier and fiber optic facilities). At the receiving end (customer
premises), the RouteSwitch monitors the duplicated DS1 signals and delivers the better
signal of the two (or the unfailed signal) to its destination. Protection is provided in the
same manner in the reverse direction when the incoming DS1 signal is at the customer
premises RouteSwitch. If one of the DS1 facilities has a failure, the RouteSwitch
transfers the signals from the failed DS1 facility to the working DS1 facility to restore and
improve end-to-end service. A simplified schematic diagram of the RouteSwitch system
is shown in Figure 2-2.

2.102 The RouteSwitch provides 1 + 1 single ended protection for DS1 lines and is available in
two shelf types:

Model 5702 List 2 (L2) and List 2A (L2A), DS1 terminals which provide protection for
one DS1 facility. These models include two Model 5702 List 1 (L1) or List 1A (L1A)
circuit packs, depending on the shelf type. The Model 5702 List 11 (L11), which
accepts either the L1 or L1A, is identical in configuration but circuit packs are not
included.

Model 5702 List 3A (L3A), a 19/23-inch shelf which provides protection for up to six
DS1 facilities and accepts either type of circuit pack.

2.103 The RouteSwitch system provides several switch selectable options which include
switching delay interval, bit error rate (BER) switching thresholds, revertive/nonrevertive
operating modes, and bipolar eight zero substitution (B8ZS) or alternate mark inversion
(AMI) line coding. The system automatically detects superframe (SF) and extended
superframe (ESF) framing formats in the DS1 input signal and performs the appropriate
monitoring for protection switching.

2-1
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-1. Typical RouteSwitch System Application

2-2
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-2 Simplified Schematic Diagram


CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.104 Once a failed DS1 facility has switched to protection, and if the revertive mode
option is set, the RouteSwitch can return traffic automatically to the original
DS1 facility when the failure is no longer present. An incoming DS1 signal (DS1
IN) from the digital signal crossconnect (DSX-1) is separated into two identical
signals prior to delivery to the RouteSwitch's working and protection circuit
packs. These signals are called DS1 transmit working (DS1 TW) and DS1
transmit protection (DS1 TP). Two DS1 facility signals, DS1 receive working
(DS1 RW) and DS1 receive protection (DS1 RP), are monitored by the
RouteSwitch working and protection circuit packs, respectively. Upon power up,
the RouteSwitch working circuit pack monitors the facility signal until a failure or
degraded performance level condition is detected. At such a time, a switch is
made to the protection channel provided that it has a better signal. End-to-end
communication between the RouteSwitch circuit packs is not required to
accomplish the switch. In Extended Superframe Format, the working and
protection ESF facility data links (FDLs) are passed unaltered. In Superframe
Format, there is no FDL.
2.105 A switch from the working channel to the protection channel is initiated when an
alarm is generated due either to detection of a loss of signal (LOS) condition,
out of frame (OOF) event, or alarm indication signal (AIS) condition or the BER
threshold being met or exceeded on the working channel. List 1B cards will
accept AIS as a hard fail stimulus; List 1A cards will not.
2.106 Switch-selectable switching delay intervals allow adequate time for the
completion of automatic protection switching of intermediate multiplexers or line
equipment due to equipment failure. Delay intervals are provided for both soft
and hard failures. Soft failures result from the BER exceeding the threshold.
Hard failures usually result from LOS or OOF for List 1A cards; LOS, OOF, or
AIS for List 1B cards.
2.107 The system can operate in either revertive or nonrevertive mode. In the
nonrevertive mode, once a protection switch is made the RouteSwitch switches
back to the working channel if, and only if, a failure is detected on the protection
channel that is more severe than that of the working channel. Otherwise,
service remains on the protection channel. In the revertive mode, a switched
channel automatically switches back 5 minutes after either a soft or hard failure
condition is cleared. If a second failure is detected on the protection channel
that is more severe than the original failure, the RouteSwitch switches back to
the working channel while the original failure is still present. The switchback
does not occur until at least 10 seconds after the first switch.
2.108 Both local and remote control of the RouteSwitch switching function are
possible. Manual control of the switching function is available through a button
activation on the circuit pack faceplate. Remote control is available through the
E2A interface.
2.109 All customer DS1 alarm and control connections are made through the
connectorized backplane on the equipment shelf.
2.1010 Contact closures for local alarms are accessible through a terminal block
(TB2) on the equipment shelf backplane. These include a fuse alarm, visual

2-4
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

and audible minor alarms, and visual and audible major alarms. The L3A
RouteSwitch shelf is equipped with an alarm cutoff (ACO) button and a light
emitting diode (LED) which illuminates when the ACO button is activated.
Activation of the ACO button disables the audible alarms.

2.11 Features
2.111 The RouteSwitch system provides the following features:

Line status monitoring


Connectorized backplane connections
Automatic detection of SF or ESF framing format
Local and remote control of switching function
Toleration of controlled and uncontrolled environments
Switch-selectable options:
- Switching delay intervals
- BER switching thresholds
- Revertive or nonrevertive operating modes
- B8ZS or AMI line coding

2.12 Specifications
2.121 Data Format:
SF or ESF (automatic detection)
AMI or B8ZS
2.122 Port Impedance:
100 ohms nominal (input and output) at 772 kHz
2.123 Input Bit Rate:
1.544 Mbps 200 bps
2.124 Input Signal Range:
-7.5 dBV to +3 dBV (DSX-1 transmission level point 0 dBV 6 volts peak to
peak across 100 ohms)
2.125 Output Pulse Amplitude:
3 volts 0.3 volt (6 volts peak to peak)
2.126 Output Signal Distance:
0 to 133 feet (DSX-1 compatible)
Jitter transfer complies with PUB 43801. Refer to Jitter Transfer Function
Figure 2-3.
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-3. Jitter Transfer Function

2-6
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.127 Output Signal:


Pulse width 324 ns 30 ns
Pulse width imbalance 5 ns maximum
Pulse overshoot 10% to 30% of pulse height
20% nominal
Pulse rise and fall times 100 ns maximum

2.128 Operating Temperature:


-40C to +75C (shelf inlet air temperature)

2.129 Humidity:
0% to 95%, noncondensing

2.1210 Shelf Dimensions and Weight:


5702 L2/L2A/L11 shelf (1 DS1) 19/23"W x 12"D x 1.75"H; 14.5 lbs
5702 L3A shelf (6 DS1s) 19/23"W x 12"D x 5.25"H; 14.5 lbs

2.1211 Circuit Pack Dimensions and Weight:


5702 L1/L1A RouteSwitch CP 1.4"W x 9.5"D x 5.0"H; 12 oz

2.1212 Central Office Alarms:


Major audible and visual
Minor audible and visual

2.1213 Power:
-48 Vdc, 125 mA per circuit pack (maximum)

2.1214 Power Consumption:


4.8 watts per circuit pack in normal operation

2.1215 Power Fuse:


0.5 Amp GMT type (in holder on circuit pack)

2.1216 Fuse Alarm:


Local (CO) Closure to battery
Remote (E2A) Closure to ground
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.13 Ordering Information

2.131 Ordering information for RouteSwitch equipment is as follows:

Circuit Pack 5702 L1/L1A/L1B


RouteSwitch DT (2-slot, 19/23-inch shelf; 2 circuit
packs) 5702 L2/L2A
RouteSwitch DT (2-slot shelf only; no circuit packs) 5702 L11
RouteSwitch 19/23-inch Shelf 5702 L3A
RouteSwitch 19/23-inch Shelf Front Guard 007-00495-000

2.2 Detailed RouteSwitch Information


2.201 The RouteSwitch is comprised of an equipment shelf containing appropriate
circuit packs in one of the following shelf arrangements:

A DS1 terminal (5702 L2/L2A/L11) which has 2 slots with (L2/L2A) or


without (L11) circuit packs and provides protection for one DS1 facility
(refer to Figure 2-4).

A 19/23-inch shelf (5702 L3A) which has 12 slots for circuit packs and
provides protection for up to 6 DS1 facilities (refer to Figure 2-5). A
summary alarm module within the shelf provides alarm relay points

2.202 The L3A shelf has an ACO pushbutton and an associated yellow LED on the
right front side. The ACO button disables the shelf and E2A audible major and
minor alarms. The LED lights to indicate that the button has been pressed and
extinguishes when the alarm(s) is cleared.

2.203 Two identical circuit packs are required to protect each DS1 channel. One
monitors and controls the working channel, the other monitors and controls the
protection channel. The protection circuit pack is on the left (odd numbered
slots) and the working (service carrying) pack is on the right (even numbered
slots). The two identical circuit packs must have the same List number and
must have identical user option switch settings (except for BER, which is not
required to be identical).

2.204 A designation strip on the L3A shelf is labeled A, B, C, D, E, and F for the
protection groups. PROT and WRKG designate the protection and working
circuit pack in each group.

2.205 The L3A shelf may be equipped with an optional transparent front guard which
is labeled the same as the designation strip. The guard should remain in place
except when maintenance operations are being performed.

2-8
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-4. Model 5702 List 2/List 2A/List 11 DS1 Terminal,


2 Slots

2.21 RouteSwitch Circuit Pack

2.211 The 5702 L1 or L1A or L1B circuit pack is used in the RouteSwitch for both
protection and working channels. It can be identified by the RouteSwitch
nomenclature on the faceplate (refer to Figure 2-6), a barcode on the back side
of the faceplate, and nomenclature on the component side of the board (refer to
Figure 2-7). The list number (LIST [ ]) and issue number (ISSUE [ ]) appear on
the component side of the board. The Model number and List number also
appear prominently on one PROM chip label.

2.212 The role of each circuit pack is defined by its assigned shelf slot. A circuit pack
in an odd numbered slot functions as a protection unit and one in an even
numbered slot functions as a working unit. Note that functions are slightly
different between the two. Figure 2-6 shows the faceplate with LEDs,
pushbutton switch, seven segment display, monitor jacks, and fuse holder.
Figure 2-7 shows the circuit board with option switch locations.

2.213 The faceplate LEDs function as follows:


CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

ALARM Red LED that is off when the facility and the circuit pack are
operating properly. It lights steadily to indicate that the facility
has become faulty as defined by the OOF, LOS, and BER
criteria or to indicate a circuit pack failure. The LED flashes to
indicate an OOF, LOS, or AIS on the DS1 IN port. If the LED on
one circuit pack is glowing steadily, a minor alarm is indicated. If
the LEDs on both circuit packs are glowing steadily, a major
alarm is indicated.

DS1 IN Green LED that lights when the DS1 IN signal from the equipment
is present. It extinguishes when there is no usable DS1 IN
signal (including the AIS).

SWITCHED Yellow LED that lights on the working circuit pack when traffic is
switched to the protection circuit pack. Normally the LED is off
when the working circuit pack is carrying the traffic. It does not
light on the protection circuit pack.

ACTIVE Green LED that lights when the circuit pack is receiving traffic
(indicates a good receiver). It does not indicate transmission of
a signal.

2.214 The faceplate SWITCH pushbutton is operable only on the working circuit pack.
On the first push, service is forced from whichever channel it was on to the
opposite channel and locked there (automatic switching disabled). A decimal
point in the seven segment display indicates manual lock operation. On the
second push, automatic switching is reenabled and the decimal point is erased.
Depending upon line conditions and operating mode (revertive or nonrevertive),
a switchback may occur.

2-10
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-6. Model 5702 L1/L1A Circuit Pack Faceplate


CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-7 Component side view of Model 5702 circuit pack

_______________________________________________________
__

-x
2.215 Characters that appear in the faceplate's seven segment display (BER 10 )
include:

'-' Normally indicates that the circuit pack is operating properly and the
-9
BER is better than 10 . The dash also appears during power up while
the system is calculating the BER for the first time.

'A' Indicates that a working or protection circuit pack has been abandoned,
that is, it has not received a status message from its corresponding
protection or working circuit pack within the last 2 seconds. This
character disappears when the necessary status message is received
from the appropriate circuit pack.

'd' Flashes to show that the circuit pack is changing equipment side
framing format from ESF to SF. This character flashes only momentarily
and is then overwritten by the BER character.

'E' Flashes to show that the circuit pack is changing equipment side
framing format from SF to ESF. This character flashes only momentarily
and is then overwritten by the BER character.

'F' Indicates that a circuit pack has experienced a loss of frame

2-12
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

synchronization from the facility framer.

'P' Appears at power up. A protection circuit pack displays the P and a
decimal point (P.).

If the _P_ is not followed by a second character, the sanity and self check tests
have failed. Remove and replace the pack to prevent possible service interruption.

'C' Flashes to indicate circuit pack failure. Further definition of failure is


provided by the C flashing alternately with one of the following:

'P' Power converter or front panel fuse failure


'E' Failed equipment framer chip
't' Failed equipment line chip
'F' Failed facility framer chip
'y' Failed facility line chip

Any of these five failure conditions causes a CP card alarm and a


minor alarm. The 'E', 't', 'F', and 'y' conditions take the circuit pack out
of service and cause a traffic switch. The 'P' condition does not take
the circuit pack out of service since the remaining circuitry is
d f th 8 lt b Th b ll th i it k t
_0_ thru _9_
Indicate the facility BER. If the BER falls below its defined threshold
switch setting, the BER character starts flashing. If the BER falls below
-9
10 but is above the set BER threshold, the solid BER character is
displayed. If a condition other than BER exceeding the threshold is
causing the alarm, the display will not flash. Neither will it flash when an
alarm timeout is in process (up to 20 seconds). A decimal point
indicates that the system has been locked into manual mode by means
of the SWITCH button.

Intermittent failures may cause one or more status characters to be


displayed in rapid sequence. Observe displays carefully to determine
causes.

2.216 There are two test monitoring (MON) jacks:

DS1 IN Monitor point for test set access of DS1 IN signal from the equipment.

DS1 OUT Monitor point for test set access of DS1 OUT signal to the
equipment.
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.217 A fuse holder, located in the lower portion of the circuit pack's faceplate,
requires a 0.5 Amp GMT type fuse. Refer to Figure 2-6.

2-14
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.22 Circuit Pack Operation

2.221 The RouteSwitch circuit packs switch the terminal equipment to and from a
transmission facility based on certain failure conditions. The decision to switch
is made in the following order of priority:

a. (Hard Failure) List 1, 1A, or 1B. OOF event declared upon the detection of
2 out of 5 consecutive framing bits in error or LOS declared upon detection
of 175 75 consecutive zeros (no pulses) on a DS1 channel. A circuit pack
declares a failure 10 milliseconds after the declaration of an OOF or LOS
event to verify that the event is genuine and not a temporary interruption
due to other causes.

b. (Hard Failure) List 1B only. A facility AIS which causes the associated
circuit pack to transmit AIS (continuous unframed 1s toward the equipment
side, also called blue signal) until the facility becomes protected. The switch
only occurs from an AIS which originates on either DS1 receive working
(RW) or DS1 receive protection (RP). The OOF or LOS or AIS failure
condition is declared clear after 20 seconds of continuous in-frame
operation.

c. (Soft Failure) List 1, 1A, or 1B. BER which meets or exceeds the selected
BER threshold on the circuit pack if the protection channel has a better
calculated BER. A BER failure condition is declared clear when the
calculated BER improves beyond the BER threshold.

2.222 The facility LOS or OOF is detected at the receiving end circuit pack. It takes
the circuit pack a certain number of milliseconds to verify that hard fail condition
and decide to transfer. The transfer is quickly completed under normal
circumstances. It would not complete (traffic would stay on the original path) if a
partner circuit pack were failed, removed, inhibited, or otherwise in alarm

2.223 With the 5702 L1A circuit pack, AIS is sent only while a faulted signal is seen
on the facility receive. The 20-second alarm will remain but the AIS will not. AIS
is not sent during the full 20-second alarm unless a faulted signal is verified
during the 20-second alarm. The blue signal will not be transmitted after the
good signal is detected.

Scenario for selecting this option: The user has a channel bank at the far end.
When a near end experiences a short LOS burst, the LOS propagates to the far
end facility receive and the alarm is turned on for 20 seconds. During the
20-second time period, AIS is sent to the channel bank and causes the channel
bank to go to Carrier Group Alarm. Thus, AIS is sent only while a faulted signal
is seen on the facility receive. The 20-second alarm remains but the AIS does
not.

2.224 With either the L1 or L1A, at power up the equipment side framing format is
initialized to SF and thereafter is automatically configured. If the equipment side
format is not SF, an equipment side loss of framing (LOF) is detected. The
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

circuit pack waits 7 seconds to verify that the LOF is not temporary. Once LOF
has been verified, the circuit pack tries the opposite format (ESF) on the
equipment side. If LOF is still present after 100 milliseconds, the circuit pack
reverts to the original framing format.

2.225 The circuit pack calculates the BER depending on the framing format of the
DS1 signal. For ESF formatted DS1 signals, a facility BER is calculated from
cyclic redundancy check (CRC6) algorithm and bipolar violations (BPVs) not
part of a B8ZS pattern and from framing bit errors. For example, when the BER
threshold switch is set to 5, a protection switch is performed if the working
channel BER is 1X10-5 or worse and if the protection channel has a better BER
than the working channel. When the circuit pack is set for the revertive mode, a
switch back to the original channel does not occur until that channel's BER
-6
crosses the 3X10 threshold and stays there for 5 minutes. This transition
-6 -6
between 1X10 and 3X10 prevents sporadic switching and unswitching
(toggling) when the BER is near its threshold setting. Any time a BER exceeds
its threshold setting, the BER on the seven segment display flashes. During
normal operation of the circuit pack, the seven segment display indicates the
BER of the facility.

2.226 When a failure occurs on a working circuit pack, its ALARM LED lights. If the
protection circuit pack has a higher integrity, the working pack switches traffic to
the protection pack and the protection pack's ACTIVE LED comes on. This
indicates that the protection circuit pack is successfully carrying the traffic. The
ACTIVE LED on the working pack is extinguished and the SWITCHED LED
lights.

2.227 If both channels experience a failure or degraded condition, the RouteSwitch


system selects the channel that is less degraded. In all operating conditions,
the system switches within 50 milliseconds unless a soft or hard fail delay is set
by S1 or S2. Refer to paragraph 2.231 below.

2.228 A manual switch may be initiated by pressing the SWITCH button on the
faceplate of the working circuit pack. The ALARM LED and relay are not
activated on either circuit pack but the seven segment display on the working
pack shows a decimal point. The first press of the button disables automatic
protection switching and forces service to the opposite channel, thereby locking
the protection circuit pack into a manual service mode. When the SWITCH
button is pressed a second time, the manual mode is unlocked, automatic
protection switching resumes, and the decimal point disappears. Depending
upon line condition and operating mode (revertive or nonrevertive), a
switchback may occur. A manual switch cannot be activated at the protection
circuit pack.

2-16
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.229 The E2A status lines are so-called open collector electronic grounds that
expect to see an external current-limited negative bias voltage. In other words,
a customer-provided alarm concentrator with -48 Vdc bias will sense the E2A
lines going open or electronic ground. If a positive external bias (e.g., +5
Vdc) exists, the E2A status line will not function.

2.23 Circuit Pack Option Switches

2.231 Options are manually selected with switches located on the circuit pack board
(refer to Figure 2-7). The switches function as follows:

SOFT FAIL DELAY (S1). Rotary type switch sets BER switching delay from 0 to
10 seconds. Switch positions and corresponding values are listed in Table 2-A.
The 0, 7, 8, and 9 positions give a delay interval of 0. However, switching
occurs within 50 milliseconds.

HARD FAIL DELAY (S2). Rotary type switch sets switching delay resulting from
an OOF, LOS, or AIS from 0 to 5 seconds. Switch positions and corresponding
values are listed in Table 2-B. The 0, 5, 6, 7, 8, and 9 positions give a delay
interval of 0. However, switching occurs within 50 milliseconds.

BER THRESH (S3). Rotary type switch sets bit error rate threshold to zero or
-3 -9
from 10 to 10 . Switch positions and corresponding values are listed in Table
2-C. The 0, 1, and 2 positions will not allow a switch regardless of the bit error
rate.

REV/NON REV (S4). Two-position switch sets circuit pack to operate in either
revertive (REV) or nonrevertive (NON REV) mode.

AMI/B8ZS (S5). Two-position switch sets circuit pack to operate with AMI or
B8ZS line coding.

(continued)
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.231 (continued)
Table 2-A

RouteSwitch Soft Fail Delay Settings (BER)

S1 Rotary Switch Delay Interval


Position (Seconds)
0 0
1 0.5
2 1.5
3 2.0
4 3.0
5 5.0
6 10.0
7 0
8 0
9 0

Table 2-B

RouteSwitch Hard Fail Delay Settings


(OOF, LOS, and AIS)

S2 Rotary Switch Delay Interval


Position (Seconds)
0 0
1 0.14
2 0.50
3 1.50
4 5.00
5 0
6 0
7 0
8 0
9 0

2-18
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.231 (continued)
Table 2-C

RouteSwitch BER Threshold Settings

S3 Rotary Switch BER BER Detection


Position Threshold Time (Seconds)
0 0 -
1 0 -
2 0 -
-3
3 10 1
-4
4 10 1
-5
5 10 3
-6
6 10 7
-7
7 10 70
-8
8 10 700
-9
9 10 7000

2.24 RouteSwitch Powering

2.241 If there is no -48VDC central office battery plant, then AC-DC power rectifer
modules may be used. It would be important to have separate modules to
power the A side and B side power input to the RouteSwitch shelf.

2.242 The RouteSwitch can be powered directly by the -48 Vdc central office battery
through a feeder fuse. Two -48 Vdc power leads are required (A and B feeders)
for the protection channel(s) and working channel(s). For the L3A shelf, each
feeder should be fused at 7.5 Amps. The A feeder powers the odd-numbered
slots and the B feeder powers the even-numbered slots. The L2/L2A/L11 shelf
is diode-ORed and the fuses should be 2 Amps. Adjacent odd and even circuit
packs can share low voltage power to maintain operation in the event of card
power converter failure.

2.25 Maximum Cable Length

2.251 In normal operation, the maximum cable length from the RouteSwitch to either
the facility side or terminal equipment side DSX-1 crossconnect is 133 feet. The
RouteSwitch is designed so that, in the unlikely event of a total system failure,
the signal simply passes through the RouteSwitch over the cabling from the
facility to the equipment. In this metallic pass through mode, signal levels at the
DSX-1 crossconnect may be outside the pulse

(continued)
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.251 (continued)

mask specification until RouteSwitch service is restored if the total cable length
from the facility side to equipment side DSX-1 crossconnect exceeds 133 feet.
Cable distance limits are shown in Figure 2-8.

Note: Lengths between RouteSwitch and DSX-1s are for normal protected
operation. In a metallic pass through mode, DSX-1 level signals may be
outside pulse mask specification until the RouteSwitch is restored.

Figure 2-8. Maximum DS1 Terminal Cable Lengths

2.26 Alarms

2.261 The RouteSwitch provides both local and remote alarm status and control.
Alarm indications are at the circuit pack and shelf levels and at an E2A scanner
(if connected). The interface to the E2A scanner is through shelf connectors J3
on the backplane of the 5702 L2/L2A/L11 shelf (refer to Figure 2-9) and P3 and
P4 on the backplane of the 5702 L3A shelf (refer to Figure 2-10. Alarm and
control connector designations for the RouteSwitch shelves are listed in Tables
2-D and 2-E. Alarm status conditions and control status appear in Tables 2-F
and 2-G, respectively. The E2A scanner status conditions are provided in Table
2-H.

Connector J1 on the 5702 L2/L2A/L11 shelf is not currently in use and should be
ignored by the installer.

2-20
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-9. Rear Panel View of Two-Slot Shelf


CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 2-10 Rear Panel View of 12-Slot Shelf

2-22
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Table 2-D (Sheet 1 of 2)

Connector Designations for Model 5702 L2/L2A/L11 Shelf

Connector J2
DS1 IN/OUT, CPE
DA15S
Pin Number Lead Function

1 DS1 IN Tip
9 DS1 IN Ring
2 Shield
4 Shield
3 DS1 OUT Tip
11 DS1 OUT Ring

Note 1: 'IN' refers to signal FROM terminal equipment to the shelf.


'OUT' refers to signal TO terminal equipment from the shelf.

Note 2: Mating cable connector: Subminiature D-type


15 pin, male
DA15-P or equivalent

Connector P4 Connector P5
DS1 Working, Network DS1 Protection, Network
DA15P DA15P
Pin Number Lead Function Pin Number Lead Function

1 DS1 WRKG OUT Tip 1 DS1 PROT OUT Tip


9 DS1 WRKG OUT Ring 9 DS1 PROT OUT Ring
2 Shield 2 Shield
4 Shield 4 Shield
3 DS1 WRKG IN Tip 3 DS1 PROT IN Tip
11 DS1 WRKG IN Ring 11 DS1 PROT IN Ring

Note 1: 'IN' refers to signal FROM the network.


'OUT' refers to signal TO the network.

Note 2: Mating cable connector: Subminiature D-type


15 pin, female
DA15-S or equivalent
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Table 2-D (Sheet 2 of 2)

Connector Designations for Model 5702 L2/L2A/L11 Shelf

Connector J3
E2A Interface
Pin Number Lead Function

1 Minor Alarm
2 Major Alarm
3 DS1 Protection Line Failed
4 DS1 Working Line Failed
5 Reserved
6 Equipment DS1 Failed
7 Protection On Line
8 Working On Line
9 Fuse Alarm
10 Shield (Ground)
11 CP Card Alarm
13 Shield (Ground)
14 Transfer
15 Manual Control

Note: Mating connector: Subminiature D-type


15 pin, male
DA15-P

2-24
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Table 2-E (Sheet 1 of 3)

Connector Designations for Model 5702 L3A Shelf*

Connector P1 - Network, Protection DS1


Pin No. Function Pin No. Function

1 Pair 1 DS1 TP Out Ring 26 Pair 1 DS1 TP Out Tip


2 Pair 2 DS1 TP Out Ring 27 Pair 2 DS1 TP Out Tip
3 Pair 3 DS1 TP Out Ring 28 Pair 3 DS1 TP Out Tip
4 Pair 4 DS1 TP Out Ring 29 Pair 4 DS1 TP Out Tip
5 Pair 5 DS1 TP Out Ring 30 Pair 5 DS1 TP Out Tip
6 Pair 6 DS1 TP Out Ring 31 Pair 6 DS1 TP Out Tip
14 Pair 1 DS1 RP In Ring 39 Pair 1 DS1 RP In Tip
15 Pair 2 DS1 RP In Ring 40 Pair 2 DS1 RP In Tip
16 Pair 3 DS1 RP In Ring 41 Pair 3 DS1 RP In Tip
17 Pair 4 DS1 RP In Ring 42 Pair 4 DS1 RP In Tip
18 Pair 5 DS1 RP In Ring 43 Pair 5 DS1 RP In Tip
19 Pair 6 DS1 RP In Ring 44 Pair 6 DS1 RP In Tip
25 Shield 50 Shield

Connector P2 - Network, Working DS1


Pin No. Function Pin No. Function

1 Pair 1 DS1 TW Out Ring 26 Pair 1 DS1 TW Out Tip


2 Pair 2 DS1 TW Out Ring 27 Pair 2 DS1 TW Out Tip
3 Pair 3 DS1 TW Out Ring 28 Pair 3 DS1 TW Out Tip
4 Pair 4 DS1 TW Out Ring 29 Pair 4 DS1 TW Out Tip
5 Pair 5 DS1 TW Out Ring 30 Pair 5 DS1 TW Out Tip
6 Pair 6 DS1 TW Out Ring 31 Pair 6 DS1 TW Out Tip
14 Pair 1 DS1 RW In Ring 39 Pair 1 DS1 RW In Tip
15 Pair 2 DS1 RW In Ring 40 Pair 2 DS1 RW In Tip
16 Pair 3 DS1 RW In Ring 41 Pair 3 DS1 RW In Tip
17 Pair 4 DS1 RW In Ring 42 Pair 4 DS1 RW In Tip
18 Pair 5 DS1 RW In Ring 43 Pair 5 DS1 RW In Tip
19 Pair 6 DS1 RW In Ring 44 Pair 6 DS1 RW In Tip
25 Shield 50 Shield

* See Notes at end of table.


CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Table 2-E (Sheet 2 of 3)

Connector Designations for Model 5702 L3A Shelf*

Connector P3 - E2A Interface


Pin No. Function Pin No. Function

1 (not recommended for use) 26 Fuse Alm


2 Minor Alm-Visual 27 Major Alm-Visual
3 CP Card Alm 28 Not Used
4 Pair 1 Minor Alm 29 Pair 1 Major Alm
5 Pair 1 PROT Fac. Alm 30 Pair 1 WKG Fac. Alm
6 Pair 1 Reserved 31 Pair 1 Equipment Alm
7 Pair 1 Transfer 32 Pair 1 Manual Mode
8 Pair 1 PROT On Line 33 Pair 1 WKG Fac. On Line
9 Pair 2 Minor Alm 34 Pair 2 Major Alm
10 Pair 2 PROT Fac. Alm 35 Pair 2 WKG Fac. Alm
11 Pair 2 Reserved 36 Pair 2 Equipment Alm
12 Pair 2 Transfer 37 Pair 2 Manual Mode
13 Pair 2 PROT On Line 38 Pair 2 WKG Fac. On Line
14 Pair 3 Minor Alm 39 Pair 3 Major Alm
15 Pair 3 PROT Fac. Alm 40 Pair 3 WKG Fac. Alm
16 Pair 3 Reserved 41 Pair 3 Equipment Alm
17 Pair 3 Transfer 42 Pair 3 Manual Mode
18 Pair 3 PROT On Line 43 Pair 3 WKG Fac. On Line
19 Pair 4 Minor Alm 44 Pair 4 Major Alm
20 Pair 4 PROT Fac. Alm 45 Pair 4 WKGFac. Alm
21 Pair 4 Reserved 46 Pair 4 Equipment Alm
22 Pair 4 Transfer 47 Pair 4 Manual Mode
23 Pair 4 PROT On Line 48 Pair 4 WKG Fac. On Line
24 Not Used 49 Not Used
25 Shield 50 Shield

* See Notes at end of table.

2-26
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Table 2-E (Sheet 3 of 3)

Connector Designations for Model 5702 L3A Shelf

Connector P4 - E2A Interface


Pin No. Function Pin No. Function

1 Pair 5 Minor Alm 26 Pair 5 Major Alm


2 Pair 5 PROT Fac. Alm 27 Pair 5 WKG Fac. Alm
3 Pair 5 Reserved 28 Pair 5 Equipment Alm
4 Pair 5 Transfer 29 Pair 5 Manual Mode
5 Pair 5 PROT On Line 30 Pair 5 WKG Fac. On Line
6 Pair 6 Minor Alm 31 Pair 6 Major Alm
7 Pair 6 PROT Fac. Alm 32 Pair 6 WKG Fac. Alm
8 Pair 6 Reserved 33 Pair 6 Equipment Alm
9 Pair 6 Transfer 34 Pair 6 Manual Mode
10 Pair 6 PROT On Line 35 Pair 6 WKG Fac. On Line
25 Shield 50 Shield

Connector J13 - CPE DS1


Pin No. Function Pin No. Function

1 Pair 1 DS1 In Ring 26 Pair 1 DS1 In Tip


2 Pair 2 DS1 In Ring 27 Pair 2 DS1 In Tip
3 Pair 3 DS1 In Ring 28 Pair 3 DS1 In Tip
4 Pair 4 DS1 In Ring 29 Pair 4 DS1 In Tip
5 Pair 5 DS1 In Ring 30 Pair 5 DS1 In Tip
6 Pair 6 DS1 In Ring 31 Pair 6 DS1 In Tip
14 Pair 1 DS1 Out Ring 39 Pair 1 DS1 Out Tip
15 Pair 2 DS1 Out Ring 40 Pair 2 DS1 Out Tip
16 Pair 3 DS1 Out Ring 41 Pair 3 DS1 Out Tip
17 Pair 4 DS1 Out Ring 42 Pair 4 DS1 Out Tip
18 Pair 5 DS1 Out Ring 43 Pair 5 DS1 Out Tip
19 Pair 6 DS1 Out Ring 44 Pair 6 DS1 Out Tip
25 Shield 50 Shield

Note 1: 'Pair' refers to the associated RouteSwitch circuit packs (working and protection)
required per DS1 for each end.

Note 2: P1, P2, P3, and P4 are 25-pair _Telco_ type male connectors. J13 is a 25-pair _Telco_
female connector.

Note 3: IN refers to signal FROM terminal equipment to the shelf. OUT refers to signal TO
terminal equipment from the shelf.
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Table 2-F

Alarm Conditions

Terminal Block (reference TB1 for L2/L2A/L11 shelf, TB2 for L3A shelf)

Alarm Indicator Alarmed Nonalarmed


Major (L2/L2A/L11) E2A GND Open
Minor (L2/L2A/L11) E2A GND Open
Major, Vis or Aud (L3A) GND Open
Minor, Vis or Aud (L3A) GND Open
Fuse -48V via GMT fuse Open

E2A (reference Connector J3 on L2/L2A/L11, P3 on L3A)

E2A Status Alarmed Nonalarmed


Indicator
All leads GND Open
(external pulldown to -48V)
Note that some of the E2A leads indicate an alarm condition, and some
of them indicate a normal condition.

Table 2-G

E2A Input Control

(Reference Connector J3 on L2/L2A/L11, P3 on L3A)

Control Function GND


Transfer Momentary GND
(per circuit pack pair) Toggles traffic between
one facility side and the
other.

2-28
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Table 2-H

E2A Scanner Status Conditions per System

(Reference Connector J3 on L2/L2A/L11 shelf, P3 on L3A shelf)

Scanner Display Condition


P On Line Protection passing traffic

W On Line Working passing traffic

Manual Mode System locked in manual mode

P Fac Alm Protection facility alarmed

W Fac Alm Working facility alarmed

E1 Alm Equipment in alarm

Min Alm LOS, OOF, AIS, or BER timer

Maj Alm Alarm on both circuit packs

CP Card Alm Circuit pack failure

There are very few E2A scanners or scanner displays left in service. If you do not have
an E2A scanner or scanner display, then ignore this table.
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.261 (continued)

At any single end, most E2A alarm interface pins are status outputs. Only
"Transfer" is an event trigger input to cause a transfer action. Transfer pins can be
connected to external telemetry/surveillance equipment set to generate momentary
Ground as the active/transfer trigger; anything else leaves the system in automatic
mode.

Be aware that, if you attempt a rapid transfer back and forth between 5702-1 circuit
packs, you may notice that the E2A status output is lagging behind. This is
because the original E2A specifications prohibited E2A status changes lasting less
than 10 seconds. (This limitation does not apply to the -1A or -1B circuit packs.)

2.262 Alarm indications are classified as either major or minor. A major alarm is
defined as a condition in which both the working and protection circuit packs of
a pair in the shelf are in an alarm state. A minor alarm is a condition in which
only one of the circuit pack pair is in an alarm state.

A major alarm is always accompanied by a minor alarm.

2.263 A fuse alarm condition does not refer to any blown feeder fuse but to an internal
fuse in the blown (alarm) state. The fuse alarm sends negative battery out on
that lead.

2.264 Circuit pack alarm LEDs and relay closures correspond to the condition of the
associated facility. If a facility is failing, the alarm LED lights and an alarm
closure is activated on the corresponding RouteSwitch circuit pack. Summary
major and minor alarm outputs are provided on the equipment shelf (refer to
Figures 2-9 and 2-10 for terminal block identification). Individual RouteSwitch
circuit pack remote alarm information is provided through E2A connectors on
the L3A shelf. Refer to Table 2-E for specific pin designations.

2.265 Alarm LED and relay status conditions on the circuit pack and suggested
maintenance procedures are listed in Table 2-I.

2-30
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.266 The 0.5 Amp fuse on each RouteSwitch circuit pack shares the same shelf
alarm contact that provides the shelf fuse alarm. The shelf fuse alarm is located
on terminal 2 of TB1 on the 5702 L2/L2A/L11 shelf (Figure 2-9) and terminal 1
of TB2 on the L3A shelf (Figure 2-10). With no fuse alarm present, the fuse
alarm signal is open. With an alarm present, the fuse alarm circuit closes to -48
Vdc.

Table 2-I

Suggested Maintenance for Circuit Pack


Alarm Status and Display

Alarm Suggested
Condition Alarm Display Indication Maintenance
BER Minor* BER number flashed Check facility

AIS List 1 or F Check facility


1A: None
List 1B:
Minor*

OOF Minor* F Check facility

LOS Minor* F Check facility

CP Card Alarm Minor* C (alternates with CP card Replace circuit


alarm character) pack

Power Supply Minor* C (must alternate with P) Replace circuit


Failure pack

DS1 IN Failure None ALARMED LED flashes, Check terminal


DS1 IN LED extinguished equipment

Self Test/Sanity None P (alone) Replace circuit


Test Fail** pack

* If the other card in a RouteSwitch working/protection circuit pack pair has an alarmed
condition, a major alarm results.

** This represents a failure of the circuit pack to complete its self checks. An interruption of
service may result unless the pack is removed from the shelf.
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.267 The major and minor alarm interfaces for the TB1 terminal block on the
L2/L2A/L11 shelf are defined as Form A relay closures to ground. Alarm
interfaces for the TB2 terminal block on the L3A shelf are defined as follows:

Fuse Alarm Closure to battery on any fuse failure


Minor Visual Relay closure to ground on minor alarm
Minor Audible Open collector ground on minor alarm
Major Visual Relay closure to ground on major alarm
(includes power bus failure)
Major Audible Open collector ground on major alarm
(includes power bus failure)

2.268 The E2A alarm interfaces for the summary alarm module on the rear of the
RouteSwitch L3A shelf are as follows (note that these closures are commonly
shared by the circuit packs on a shelf basis):

Major
Minor
Fuse
Card alarm

2.269 Alarm and control interface definitions for the RouteSwitch L3A shelf system
(working and protection circuit pack pair numbers 1 through N) are as follows:

Minor Alarm System #N E2A open collector ground indicating minor


alarm on system #N

Major Alarm System #N E2A open collector ground indicating major


alarm on system #N

Protection Facility Alarm E2A open collector ground indicating


System #N incoming protection facility has failed

Working Facility Alarm E2A open collector ground indicating


System #N incoming working facility has failed

Equipment Alarm System #N E2A open collector ground indicating DS1 IN


from equipment to RouteSwitch has failed

Transfer System #N E2A input (open collector ground from a


positive potential) to cause a manual
switch or switchback; same function as
SWITCH button (refer to paragraph
2.228)

2-32
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

2.269 (continued)

Manual Mode on System #N E2A open collector ground indicating system


is in manual mode

Protection on Line System #N E2A open collector ground indicating


service is presently using protection
channel

Working on Line System #N E2A open collector ground indicating


service is presently using working
channel
CXR Larus 80-100-180 issue 10
September 2007
________________________________________________________________________

Installation 3
_________________________________________________________________

3.1 General
3.101 The RouteSwitch is a rack mounted shelf with integrated working and protection circuit
packs. The general order for installing the RouteSwitch is as follows:

1. Mount the RouteSwitch shelf or shelves.

2. Route, install, connect, and label cables.

3. Verify feeder fuses at power source.

4. Connect power.

5. Verify power.

6. Verify cable connections and grounds.

7. Set options on circuit packs to prepare them for installation.

8. Perform acceptance testing.

9. Establish service.

3.102 Cable distance limits between the RouteSwitch and the digital signal crossconnect
(DSX-1) bays, or equivalent terminations, are shown in Figure 2-8. When making
connections to the RouteSwitch, use the following figures and tables:

5702 L2/L2A/L11 RouteSwitch distant terminal - Figure 2-9 and


Table 2-D

5702 L3A RouteSwitch 19/23-inch shelf - Figure 2-10 and Table 2-E

3-1
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

3.2 Equipment Installation

Step Procedure

1 Unpack and inspect the RouteSwitch equipment.

2 If there is no electrostatic discharge (ESD) terminal in the bay frame (relay


rack) to be used or an adjacent one, mount such a terminal in the bay frame.
(The terminal screws into the frame.) Attach the ground symbol label near the
terminal.

3 Install the mounting brackets on the shelf in a position that allows the shelf to
be contained within the footprint of the bay frame. Install the shelf into the bay
frame and tighten the mounting bracket screws.

In a central office (CO) environment where power is provided by office battery, a


bay can contain a maximum of eight RouteSwitch shelves. Two -48 V feeders (A
and B) per shelf are required from office battery and connect to the fuse and alarm
panel.

For each of the A and B feeders, provide 7.5 Amp fuses for the L3A shelves and 2
Amp fuses for the L2/L2A/L11 shelves.

If using a power supply with current limiting feature, set the current limit point as
high as possible to avoid a problem of the initial power-on spike activating that
feature and causing card damage due to low voltage.

4 Install heat baffles in the bay frame between the L3A shelves if more than two
shelves are to be installed.

5 Route and place the cables into the cable duct on each side of the bay frame.
Route the appropriate cables to the rear of each shelf.

- For CO battery and ground, the -48 Vdc A and B feeders and ground lead
should be of sufficient gauge size so voltage drop is not exceeded. Refer to
Figure 3-1 for a diagram of the L3A ground connection.

- To ground the RouteSwitch shelf to the bay frame (frame ground), use 14
or 16 gauge stranded or solid wire.

- For the fuse alarm, major and minor visual alarms, and major and minor
audible alarms, use 26 gauge wire.

(continued)

3-2
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 3-1 Grounding on the rear of the shelf

3-3
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________
3.2 (continued)

Step Procedure

Remove any feeder fuses or unplug the power modules before wiring the shelf.

6 Using 26 gauge wire, label the fuse alarm and the major and minor visual and
audible alarm leads that will be connected to the corresponding terminals on
TB1 (Figure 2-9 or 2-10). Leave these leads disconnected for now; they will be
connected during acceptance tests. Wire wrap the other ends of the office
alarms at the central office alarm or other panel.

If wiring external relays to the major and minor visual and audible alarms, a diode
must be connected across the relay coils (to prevent the de-energizing spike from
the relay coil from damaging the Model 5702 equipment).
7 Connect the 14 or 16 gauge frame ground wire to the frame ground terminal on
the L3A shelf as shown in Figure 3-1. For the L2/L2A/L11 shelf, connect the
frame ground wire to the FRM GND terminal of TB1 (refer to Figure 2-9).

8 Connect the -48 Vdc power A and B feeders and ground leads to the
appropriate terminals on TB1 (refer to Figure 2-9 or 2-10).

9 Connect customer equipment Digital Signal Level 1 (DS1) signal cable to the
designated shelf connector on the appropriate backplane (refer to Figure 2-9
and Table 2-D or Figure 2-10 and Table 2-E). Wire wrap the loose ends of this
cable at the equipment DSX-1 crossconnect. Outside of the factory, ignore
connector J1 on the rear of the 5702 L2/L2A/L11 shelf. You may have a real
DSX-1 crossconnect panel that uses bantam jacks, or you may have something
different that uses RJ45 jacks, or it is possible that you have no crossconnect
panel at all (and this will make testing difficult).

10 Connect the protection and working DS1 facility cable assemblies to the
designated shelf connectors on the appropriate backplane with references as
above. Attach the ends of these cables at the facility DSX-1 crossconnect bay.

11 Connect the E2A cable assembly(s) to the designated shelf connector(s) on the
appropriate backplane with references as above. Wire wrap the loose ends of
this cable at the telemetry equipment or distribution frame.

3-4
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________
3.2 (continued)

Step Procedure

12 Verify that all cables are properly labeled and have been connected (except for
the office alarm cables).

Make certain that, if any circuit packs have been placed into the shelf, they do not
make connection to the backplane.

13 Apply voltage to the shelf by placing two feeder fuses (one for the A feeder and
the other for the B feeder) in the alarm and fuse panel for the shelf to be tested.
Instead, if the shelf is powered by a power module, insert the AC power plug
into a properly fused AC outlet.

14 Using a volt ohmmeter, measure the voltage between the -48V A terminal and
the PWR GND terminal at TB1 (refer to Figure 2-9 or 2-10). Verify that the
voltage is between -41.75 Vdc and -60 Vdc. (Ideally, the voltage should be
between -45 Vdc and -53 Vdc.)

15 Measure the voltage between the -48V B terminal and the PWR GND terminal.
Verify the voltage as in the previous step.

16 If the voltage is not within the range specified, verify that proper wiring
connections have been made. Correct any wiring errors and follow local
procedures to troubleshoot any further problems.

17 If the voltage is correct, you have completed the shelf installation. Continue
installation by setting the circuit pack options.

3.3 Circuit Pack Option Settings

A grounded wrist strap connected to the ESD jack must be worn while handling the
circuit packs.

3-5
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Step Procedure

1 With reference to Figure 2-7, set the following option switches on each circuit
pack as called out in the customer engineering records:

S1 Set the soft fail delay (refer to Table 2-A).


S2 Set the hard fail delay (refer to Table 2-B).
S3 Set the bit error rate (BER) threshold (refer to Table 2-C).
S4 Set mode to revertive (REV) or nonrevertive (NON REV).
S5 Set line coding to bipolar eight zero substitution (B8ZS) or alternate mark
inversion (AMI).

2 Slide the circuit packs part way into the proper slots, starting from the left of the
shelf and moving to the right.

Do not seat the circuit packs at this time since the shelf must first be acceptance
tested.

3 Perform acceptance testing as outlined in Section 4.

3-6
CXR Larus 80-100-180 issue 10
September 2007
________________________________________________________________________

Testing 4
_______________________________________________________________________

4.1 General
4.101 Acceptance testing of the RouteSwitch verifies customer cable connections, Digital
Signal Level 1 (DS1) facility cable assembly connections, and circuit pack operation.
These tests must be performed while the RouteSwitch is out of service. Procedures test
the following:

Transmission and receiving and protection switching.


Office alarms and alarm cutoff (ACO).
E2A telemetry.

Office alarm cables were left unconnected during installation of the RouteSwitch.
This was intentional to prevent alarming in the office during acceptance tests. The
cables will be connected during the office alarm and ACO test.

Interruption of service will result if the acceptance tests are run on a system that is
in service.

4.2 Testing Equipment Required


4.201 The following items are required to perform the acceptance tests:

Ground wrist strap


Two digital signal crossconnect (DSX-1) loopback cables
DS1 transmitter data test set and cables
DS1 receiver data test set and cables
Volt ohmmeter

In general, most DS1 test sets have the transmitter and receiver functions contained
within one case.

4-1
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

4.3 Transmission, Protection Switching, Alarm, and E2A


Telemetry Tests
4.301 These tests verify proper operation of the circuit packs, circuit pack positions,
and cabling between the RouteSwitch and DSX-1 crossconnect bays.

4.302 DS1 signals to the RouteSwitch are required. They are generated by means of
DS1 transmitter and receiver data test sets. These tests cannot be performed if
such test sets are not available.

4.303 The procedures that follow are designed to test each circuit pack pair
(channel), one pair at a time, until all pairs in a RouteSwitch shelf have been
tested.

Step Procedure

1 Configure the DS1 transmitter data test set for the following. Most test sets
have the transmitter and receiver contained within one case. Refer to the
manufacturer's instruction manual for the type of data test set you are using.

Pseudo-random binary-pulse sequence (PRBS) [quasirandom signal


source (QRSS)] pattern
Bit errors inject (error free)
Superframe (SF) framing format
Bipolar eight zero substitution (B8ZS) or alternate mark inversion (AMI) line
coding according to circuit pack settings

2 Configure the DS1 receiver data test set for the following. Refer to the
manufacturer's instruction manual for the type of data test set you are using.

PRBS (QRSS) pattern


Bit errors measurement (total)
SF framing format
B8ZS or AMI line coding according to circuit pack settings

3 With reference to Figure 4-1, connect the transmitter data test set to the
equipment DS1 IN jack at the DSX-1 crossconnect for the channel to be tested.
Connect the receiver data test set to the corresponding equipment DS1 OUT
jack at the DSX-1 crossconnect for the channel to be tested.

(continued)

4-2
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

Figure 4-1 Testing

4-3
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

4.3 (continued)

Step Procedure

4 Place a loopback cable between the corresponding working DS1 facility IN and
OUT jacks at the DSX-1 crossconnect for the channel to be tested. Place a
loopback cable between the corresponding protection DS1 facility IN and OUT
jacks at the DSX-1 crossconnect for the channel to be tested.

5 Set the revertive (REV)/nonrevertive (NON REV) switch on the circuit packs to
be tested to REV.

6 Seat the DS1 working and protection circuit packs to be tested, leaving all
others unseated.

7 Verify that no ALARM light emitting diodes (LEDs) are illuminated on the circuit
packs. If any ALARM LEDs are on, determine whether the problem is with the
shelf or the circuit pack. Replace the faulty unit.

8 Verify that the DS1 IN LEDs are illuminated on the working and protection
circuit packs. This indicates that the circuit packs are receiving a DS1 signal on
the equipment side.

Transmission and Protection Switching Test

9 Press the SWITCH button on the working circuit pack (even numbered slot)
until the ACTIVE LED on this circuit pack lights and the decimal point in the
seven segment display on this circuit pack disappears.

10 Verify that the SWITCHED LED on the working circuit pack and the ACTIVE
LED on the protection circuit pack are extinguished.

11 Verify that error free transmission is being received on the DS1 receiver data
test set through the working channel. If a signal is not detected, that is, loss of
signal (LOS) is observed, isolate and correct the problem by:

Verifying that the data test set cables are connected to the correct
crossconnect position.

Verifying that the DS1 cables are present and connected to both the
RouteSwitch and the DSX-1 crossconnect.

4-4
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

4.3 (continued)

Step Procedure

12 If a signal with errors is observed, isolate and correct the problem. Most
problems can be cleared by checking the receiver data test set for a loss of
frame (LOF) or an all 1s pattern and performing the following:

If LOF occurs, verify that the transmitter and receiver data test sets are set
for a framed format.

If an all 1s pattern occurs [alarm indication signal (AIS) detected], verify that
the equipment DS1 OUT cable is connected to the correct terminals at the
DSX-1 crossconnect.

13 If error free transmission is observed, press the SWITCH button on the working
circuit pack until the ACTIVE LED on the protection circuit pack turns on and
the decimal point in the seven segment display disappears.

14 Verify that the SWITCHED LED on the working circuit pack is on and the
ACTIVE LED is off.

15 Verify that error free transmission is being received on the DS1 receiver data
test set through the protection channel by observing that the ACTIVE LED on
the protection faceplate is on.

16 Unseat the protection circuit pack to inhibit protection switching. Note that an 'A'
flashes in the seven segment display on the working circuit pack. (Protection
has been abandoned.)

17 Verify that the ACTIVE LED on the working circuit pack is on. (This verifies
automatic switching.)

18 Verify that error free transmission is being received on the DS1 receiver data
test set through the working channel.

19 Reseat the protection circuit pack. Note that the flashing 'A' in the seven
segment display on the working circuit pack disappears.

20 Verify that the ACTIVE LED on the working circuit pack remains on and the
ACTIVE LED on the protection circuit pack is extinguished.

(continued)

4-5
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

4.3 (continued)

Step Procedure

Alarm and E2A Telemetry Test

If the office is equipped with E2A telemetry, communication between personnel at


the RouteSwitch shelf and the E2A scanner display is required. Refer to Table 2-H
for messages that can appear on the E2A scanner display. These are examples
only and may differ from office to office. If the office is not equipped with E2A
telemetry, verify local Major and Minor alarm operation and ignore E2A
requirements
21 Remove the 0.5 Amp fuse from the faceplate of the protection circuit pack and
replace it with a 'blown' fuse. The protection circuit pack seven segment display
alternately flashes a 'C' and 'P'. The 'C' indicates a circuit pack failure and the
'P' (in this case) indicates a front panel fuse failure.

22 Verify that service remains on the working circuit pack by observing that its
ACTIVE and DS1 LEDs are on and a dash ('-') appears in the seven segment
display.

23 Verify that the ALARM LED on the protection circuit pack is on and that the fuse
alarm and minor visual and audible office alarms are activated.

24 Press the alarm cutoff (ACO) button on the front of the RouteSwitch shelf (L3A
only).

25 Verify that minor audible office alarms are retired and visual indications remain
activated.

26 Verify that both the working circuit pack alarm and working facility passing
traffic messages appear on the E2A scanner display (if applicable). Refer to
Table 2-H.

27 Remove the blown fuse and replace it with a good 0.5 Amp fuse.

28 Verify that the ALARM LED on the protection circuit pack is extinguished and all
alarms are retired.

29 Verify that the working circuit pack passing traffic message appears on the E2A
scanner display (if applicable). Refer to Table 2-H.

4-6
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

4.3 (continued)

Step Procedure

30 Remove the loopback between the working DS1 IN and DS1 OUT facility at the
DSX-1 crossconnect.

31 Verify that the ACTIVE LED is extinguished and the SWITCHED and ALARM
LEDs are illuminated on the working circuit pack. The seven segment display
will show an 'F'.

32 Verify that the ACTIVE LED on the protection circuit pack is on.

33 Verify that a minor office alarm is activated.

34 Press the ACO button on the front of the RouteSwitch shelf (L3A only).

35 Verify that the minor audible alarm is retired.

36 Verify that both the protection circuit pack passing traffic and working facility
alarmed messages are received at the E2A scanner (if applicable). Refer to
Table 2-H.

37 Reconnect the loopback between the working DS1 IN and DS1 OUT facility at
the DSX-1 crossconnect.

38 Verify that the minor visual office alarm is retired in about 20 seconds.

39 Verify that the ALARM LED on the working circuit pack is extinguished.

40 Verify that in about five minutes service switches back to working, if the
revertive switching mode option is set, by observing that the DS1 and ACTIVE
LEDs light on the working circuit pack.

41 Verify that the working circuit pack passing traffic message appears on the E2A
scanner display (if applicable). Refer to TabIe 2-H.

42 Remove the loopback between the protection DS1 IN and DS1 OUT facility at
the DSX-1 crossconnect..

43 Verify that the minor audible and visual office alarms are activated.

44 Verify that the ALARM LED lights on the protection circuit pack. The seven
segment display on the protection circuit pack will show an _F_.

(continued)

4-7
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

4.3 (continued)

Step Procedure

45 Verify that the minor alarm, protection passing traffic, and protection facility
alarmed messages appear on the E2A scanner display (if applicable). Refer to
Table 2-H.

46 Reconnect the loopback between the protection DS1 IN and DS1 OUT facility
at the DSX-1 crossconnect.

47 Verify that the minor visual and audible office alarms are retired in about 20
seconds.

48 Verify that the DS1 IN LED is on and the ALARM LED is extinguished on the
protection circuit pack.

49 Unseat the DS1 working and protection circuit pack pair seated in Step 6.

50 Repeat Steps 3 through 49 for the remaining circuit pack pairs to be tested.

51 Disconnect all test equipment and loopbacks and ensure that all circuit packs
are unseated. This completes the transmission, protection switching, alarm,
and E2A telemetry tests.

52 Set the REV/NON REV switch on all circuit packs to the position specified in
the customer engineering records.

4.4 Establishing Service


4.401 The RouteSwitch system is ready to be placed in service once it is installed and
acceptance tested. After acceptance tests are performed, the shelf is left with
all circuit packs optioned and in the circuit pack slots but not firmly seated in the
shelf connectors.

4.402 As the final step, seat the circuit pack pairs corresponding to each channel
designated for service. In each case, alarms will be present until a DS1 terminal
signal is generated.

4-8
CXR Larus 80-100-180 issue 10
September 2007
________________________________________________________________________

Trouble Analysis and Maintenance 5


________________________________________________________________________

5.01 Service interruption can be caused by power or transmission failure. For the
RouteSwitch system, power failures are first addressed by replacing any blown fuses or
circuit packs whose individual fuses continue to blow. If fuse or circuit pack replacement
does not clear the power problem, shelf wiring and/or cabling must be checked to be
consistent with local procedures. Transmission failures are addressed by replacing the
applicable circuit pack(s). Option switches on the replacement circuit pack must be set to
match those of the failed circuit pack. If transmission is not restored by this replacement,
follow local procedures to clear the problem.

5.02 The seven segment display on the faceplate of each circuit pack indicates most
problems that the RouteSwitch system might encounter. Refer to Table 2-I for an
explanation of these indications and suggested maintenance. Dont ignore the decimal
point in the front status indicator since that means manually locked and no automatic
operation is possible.

5.03 If the problem symptom is resolved by circuit pack replacement, call CXR Larus
Corporation Customer Service Department to obtain a return merchandise authorization
(RMA) number for the failed circuit pack. Please be prepared to state the technical
complaint (e.g. C P flashing on faceplate). If the problem is not resolved by this
substitution or by suggested maintenance, call the Customer Service Department for
assistance.

5.04 All requests for assistance and returned equipment inquiries should be directed to:

CXR Larus Corporation


Customer Service Department
894 Faulstich Court
San Jose, CA 95112-1361

(408) 573-2700 Telephone


(800) 999-9946 Toll-free
(408) 573-2708 FAX

(continued)

5-1
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

5.04 (continued)

When handling or returning electrostatic discharge (ESD) sensitive products, all


standard ESD precautions should be followed. ESD sensitive equipment is considered
to be any electrical equipment aside from sheet metal products. Standard ESD
precautions include, but are not limited to, the following:

All personnel handling the equipment should be properly grounded (prior to


removal of the equipment from the housing/shelf). This will preclude ESD through the
equipment.

Once the equipment has been removed from the housing/shelf, it should
immediately be placed in an ESD protective bag.

All returned equipment should be packaged as originally received (i.e., placed in an


ESD conductive or antistatic bag and put back in the original box with foam
packaging). Individual equipment boxes should be placed into a master container box
with appropriate fill to ensure safe transportation.

Any ESD or transportation related damage to equipment will void the equipment
warranty.

5.05 All returned shipments must be prepaid by the customer and bear the RMA
number on the exterior of the package.

5-2
CXR Larus 80-100-180 issue 10
September 2007
________________________________________________________________________

Warranty 6
________________________________________________________________________

6.01 Products Manufactured by CXR Larus Corporation

Limited Warranty:

a. Larus products, except as stated otherwise in an applicable price list, are warranted
to the original end user against defects in workmanship and material for a period of
one year from date of delivery as evidenced by CXR Larus' packing slip or other
transportation receipt. Warranty under contract may differ. Components in Larus
products manufactured by others shall be assigned the original manufacturer's
warranty. Refer to paragraph 6.03.

b. CXR Larus' sole responsibility under this warranty shall be either to repair or replace,
at its option, any component which fails during the applicable warranty period
because of a defect in workmanship and material, provided purchaser/original end
user has promptly reported same to CXR Larus in writing. All replaced products or
parts shall become CXR Larus' property.

c. CXR Larus will only honor the warranty at its repair facility in San Jose, California,
unless stipulated differently under contract. It is the purchaser/original end user's
responsibility to return, at its expense, the allegedly defective product to CXR Larus.
The purchaser/original end user must obtain a return merchandise authorization
(RMA) number and shipping instructions from CXR Larus prior to returning any
product under warranty. Transportation charges for the return of the product to the
purchaser/original end user shall be paid by CXR Larus within the United States. For
all other locations, the warranty excludes all costs of shipping, customs clearance,
and other related charges. If CXR Larus determines that the product is not defective
within the terms of this warranty, the purchaser/original end user shall pay CXR
Larus all costs of handling, transportation, and repairs at the then prevailing repair
rates.

d. All the above warranties are contingent upon proper use of the product. These
warranties will not apply (I) if adjustment, repair, or parts replacement is required
because of accident, unusual physical, electrical, or electromagnetic stress, neglect,
misuse, failure of electric power, environmental controls, transportation, not
maintained in accordance with CXR Larus specifications, or abuses other than
ordinary use; (ii) if the product has been modified by the purchaser/ original end user
or has been repaired or altered outside CXR Larus

(continued)

6-1
CXR Larus 80-100-180 issue 10
September 2007
___________________________________________________________________
________

6.01 (continued)

factory, unless Larus specifically authorizes such repairs or alterations; (iii)


where CXR Larus serial numbers, warranty data, or quality assurance
decals have been removed or altered.

e. CXR Larus also reserves the right to make product improvements without
incurring any obligation or liability to make the same changes in products
previously manufactured or purchased. In no event shall CXR Larus be
liable for any breach of warranty in an amount exceeding the net selling
price of any defective product. No person, including any dealer, agent, or
representative of CXR Larus, is authorized to assume for CXR Larus any
other liability on its behalf except as set forth herein. Non-payment of any
invoice rendered within the stated payment terms automatically cancels any
warranty or guarantee stated or implied. If any payment is due CXR Larus
for services performed hereunder, it shall be subject to the same payment
terms as the original purchase.

f. Except for the express warranties stated herein, CXR Larus disclaims all
warranties on products furnished hereunder, including, without limitation, all
implied warranties of merchantability and fitness, and the stated express
warranties are in lieu of all obligations or liabilities on the part of CXR Larus
arising out of or in connection with the performance of the products.

6.02 Repaired Products and Repair Parts

Products repaired within the warranty period continue to be warranted to the


end of that period or for 90 (ninety) days, whichever is longer. Repair work
done on products repaired outside the warranty period is warranted against
defects in workmanship and material for a period of 90 (ninety) days.

6.03 Products and Components Manufactured by Others

For products or components not manufactured by CXR Larus, the original


manufacturer's warranty shall be assigned to the purchaser/original end user to
the extent permitted and is in lieu of any other warranty, expressed or implied.
For warranty information on a specific product, a written request should be
made to CXR Larus.

NOTE: Features and specifications are subject to change without notice.

6-2
CXR Larus 80-100-180 issue 10
September 2007
________________________________________________________________________

Equipment Issue Information 7


________________________________________________________________________

7.01 CXR Larus manual 80-100-180, Issue 10, applies to the following equipment:

Description Model NumberEquipment Issue

Circuit Pack 5702 List 1 8


5702 List 1A 6
5702 List 1B 1

RouteSwitch DT 5702 List 2 1


(2-slot shelf and 2 circuit packs) 5702 List 2A 1

RouteSwitch DT 5702 List 11 1


(2-slot shelf only; no circuit packs)

RouteSwitch 19/23" Shelf 5702 List 3A 2


(without circuit packs or front guard)

5702-3A ESD Transparent 007-00495-000 1


Front Guard (optional)

7-1

You might also like