Professional Documents
Culture Documents
(/)
(/why-encon-harmonic-solution)
Your unstinted support since our inception in 1995 and our single-minded troubleshooting cum productivity improvement efforts have established Encon Tuned Harmonic
Filter as the most valued brand in today's global market
(/eliminate-tripping-and-failure)
Aiming right at the melting pot we had set industry standards by suppressing harmonic distortion where it is maximum. We achieve highest harmonic mitigation efficiency
among peers that eliminates tripping and failures
(/total-power-quality-solution)
Bad Power Quality arise from power system's interaction with power surge and harmonic distortion. If a power system is susceptible at a point possibilities of power quality
tripping, resonance and CMV failure are
(/green-building-design)
Global Warming opens before us a vast and uncertain expanse, as a crepuscular horizon on the plain at the dusk of our rapid industrialization looks increasingly threatening
like never before. Unfortunately, the major pie
VFD Harmonic
Abstract - VFD Harmonic forced a power plant to shutdown due to power quality failure. Starting with drive tripping it blasted switch gear, bus bar & electrical panel. This IPP
with a 25mw, 11kV, 50Hz power plant and 5000TCD sugar milling unit had completed its first anniversary without harmonic problem. But during 2nd year's operation, it
started-off with a massive blast of a 6300A Air Circuit Breaker (ACB). It was at the incomer of an electrical panel. The 415V PCC panel was supplying to sugar plant's
process load. There were two such PCC panels connected through a 6300A bus-coupler for the boiling house loads. It had several variable speed drives (VSD). In a span of
next 4-week, it sequentially blasted several other switch gears- ACBs and MCCBs. In yet another blast it caused pitting along 6300A double circuit bus bar. It was running at
the top-horizontal position inside electrical panel. That also caused 6nos holes at the side cover of electrical panel, as if each bus-bar end had fired a bullet piercing through
the panel's metal cover. The power plant's auxiliary VFD loads were powered through a double-secondary transformer. It's earth-pit started boiling surrounding water. A VFD
drive's IGBT card failed. It belonged to a 585 kW boiler feed water pump (BFP) motor.
Onsite power quality harmonic analysis revealed an unstable power system zone supplying to this industrial co generation
power plant along with a CMV issue. Harmonic Filters, one each at the double secondary transformer supplying to the
power plant Aux VFD drives, were installed in the year 2013. In-addition a large 2400A harmonic filter was installed at the
sugar plant's process drives' panel as in Fig.1. These measures eliminated all electrical blast and VFD drives' card failure
issues both with the power plant's auxiliary load and sugar plant's process drive panel.
Further in the year 2014, 4nos Harmonic Filters were installed individually at sugar Mill drive 1 to Mill 4, each with one
560kw, 690v, VFD drive for reducing harmonic stress with its sugar milling units and thereby enhancing its crushing capacity
by 30% to 6500tcd. Another 11kv harmonic filter was also installed at the 2x850kw, 6P, 11kv SRIM Fiberizer drive for energy
conservation. Once again another unusual problem surfaced unexpectedly but this time only with the Mill-1 VFD drive and
the root cause of that is bound to change the way we design and engineer dielectric insulation protection with our
equipment and electrical panels.
II. INTRODUCTION
The factory operates its 25mw power plant at 100% capacity with Bagasse as boiler fuel during the sugar milling season
which typically is between Oct. to Apr. each year, and thereafter with Coal for the remaining part of the year. It intends to
enhance its sugar crushing capacity to 6500tcd, and save enough bagasse during its milling season, and use the same in
the power plant boiler during the sugar off season period. This will enable the factory to reduce its power cost considerably.
Coal is a costlier fuel in comparison to bagasse which is a bye product from sugar milling process.
Onsite power quality harmonic analysis carried out during Jan.2013. It was done primarily to solve the most pressing issue
which was to eliminate the electrical blasting problem. In-addition there were other issues too. The power plant was tripping
because of voltage sag and fluctuations from the incoming grid at which it was synchronized at 110kv. It was also tripping
the sugar plant's process equipment which were in particular powered through the VFD.
Fig.3: 130tph boiler from 25mw power plant
Firstly, low fault level thanks to its remote location and secondly harmonic loads from its power plant auxiliary VFD drives
and other Aux. VFD drives from its sugar manufacturing process PCC panel.
These high frequency harmonics had triggered a power quality harmonic disturbance within its electrical power system. It
consists of a 25mw, 11kv, 1500rpm, 50Hz, steam Turbine Generator (TG), a 31.5mva, 11/110kv export transformer at the
grid's main incoming PCC, a 130tph, 110kg/cm2, 545oC Boiler with VFD drives for its auxiliary loads, and a 5,000tpd sugar
plant with 4sets of 560kw, 690v VFD Mill drives, a set of 2x850kw, 6P,11kv, SRIM Fiberizer drive and a scores of VFD
drives in the sugar manufacturing process.
Fig.4: Boiler's BFP, IDF, FDF and SAF During the Yr.2013, 2sets each of 723A, 415v, tuned harmonic filters were installed at the duel secondary of the power
plant's auxiliary VFD transformer of 2500kva, 11kv/415v- 415v. Dyn11Zn0 as show in Fig.5.
This VFD transformer supplies to all VFD drives which comprise of all nonlinear loads for this 25mw power plant's auxiliary
supply. All VFD drives are of ABB ACS 800 make. Its single line diagram with the installed harmonic filters and VFD drive
ratings are shown in Fig.6 (Top caption photo). The boiler's major VFD drives are namely boiler feed water pump (BFP),
induced draft fan (IDF), forced draft fan (FDF) and supply air fan (SAF) are shown in Fig.4.
In-addition 1set 2400A, 415v tuned harmonic filter was installed at the secondary side of the 3150kva, 11/415v transformer
which supplies to the sugar plant's process manufacturing section.
A detailed Power Quality harmonic measurement was carried out during Jan.2013 using a high quality 3phase power
quality harmonic analyzer of type PowerPro. The instrument measures at a sampling rate of 256 samples/ cycle and
calculates RMS value of all measured parameters at every cycle basis. It measures all steady state power parameters and
power quality that including individual phase and neutral harmonics up to 64th, Total current harmonic distortion (THDi),
Fig.5. Boiler Aux Transformer- 3winding Total voltage harmonic distortion (THDv), switching Inrush current, waveforms, voltage and current spikes, sags, swells and
voltage fluctuations with 65uS precision recording. Further details of the instrument can be obtained at www.candura.com (http://www.candura.com).
The current and voltage harmonic distortions and its waveforms at the 415v VFD transformer secondary PCC which
supplies power to all ABB ACS800 VFD drives for the power plant auxiliary loads are as shown in Fig.7, before installation
of the 2sets Tuned Harmonic Filters at the 2500kva two secondary three winding transformer. Because of major
nonlinear loads in the form of VFDs, the harmonic distortions were very high. The total current harmonic distortion (THDi)
was at 36% with I5, I7, and I11 as major current harmonics. The total voltage harmonic distortion (THDv) was at 6% with I5,
I11, and I7 as major voltage harmonics.
The current and voltage harmonic distortions and its waveforms at the 415v VFD transformer secondary PCC which
supplies power to all ABB ACS800 VFD drives for the power plant auxiliary loads are as shown in Fig.8, after installation
of the 2sets Tuned Harmonic Filters at the 2500kva two secondary three winding transformer. Post harmonic filter
scenario the harmonic distortions of both current and voltage harmonics were fully mitigated. The total current harmonic
distortion (THDi) was at 8% with I5, I7, and I11 as major current harmonics. The total voltage harmonic distortion (THDv)
was at 1% with I5, I11, and I7 as major voltage harmonics.
Fig.7: ACS 800 VFD harmonics before HF
Simultaneously, a similar harmonic distortion mitigation results for both current and voltage harmonics were also achieved
after the installation of the 2400A tuned harmonic filter at the 3150kva, 11kv/ 415v, Dyn11 transformer for the sugar
plant's process manufacturing loads. Because of these power quality harmonic mitigations, the factory's major problem of
repetitive electrical blasts got eliminated and did not repeat thereafter. In-addition it also solved the tripping problem with the
power plant and with other process loads that used to happen whenever there used to be some grid voltage fluctuations and
voltage sags.
Considering the enormous and frightening issue of electrical blasts that happened repeatedly before the installation of
harmonic filters across the power plant and sugar plant process loads, post solutions, the factory's electrical power system
was thoroughly analyzed for any possible indication that might still need to be tackled. Apart from power quality harmonic
measurements, we also tracked other physical evidences, if any, and such details are usually best known to the plant
operators.
Fig.9: 690v VFD drives with harmonic filter Physical verification is an essential process for an effective
troubleshooting engineer. These feedbacks are the difference between a "job well done" and a "job is in process".
Furthermore, during the Yr.2014, and fresh from the effective troubleshooting experience with its VFD card failures for the ABB ACS 800 VFD drives in the power plant
auxiliaries and elimination of Electrical blasts, the factory installed yet another 4sets of tuned 458A, 690V harmonic filters across each of 560kw, 690v VFD drives for Mill-1,
2, 3 and 4.
The four mill motors are fed from 2nos three winding transformers of capacity 2500kva, 11kv/690v-690v, Dyn11Zn0 which is
similar as the rating of the power plant VFD transformer except for the secondary voltage. Mitigating and cleaning up VFD
harmonics right from its point of generation at 690v which is also the VFD's input power terminal, increases its milling
capacity by a ballpark figure of 30%. In the past, and since few decades, we have installed over several dozens of harmonic
filters across such 12pulse drives at various medium voltage ratings most of which were 690v.
The current harmonic distortions and its waveforms at the 690v Mill VFD transformer secondary PCC which supplies power
to Siemens Sinamics VFD drives for each of the mill drives is as shown in Fig.11, before and after the installation of Tuned
Harmonic Filter for Mill-1. The first mill, the mill-1 and the last mill, the mill-4 are always loaded 20-40% higher than that of
other mills in the middle. The total current harmonic distortion (THDi) was at 76% with I5, I7, and I11 as major current
harmonics before the installation of harmonic filter, and after its installation the total current harmonic distortion reduced at
27% with I5, I7, and I11 as major current harmonics.
Post harmonic solutions, as sheen in Fig.11, the harmonics at the 690v motor terminal reduced substantially from 76% to 27% with an overall improvement in motor terminal
power quality, which reconstructed the heavily distorted waveform back into near a sinusoidal waveform.
The next step, besides power quality harmonic measurement of a well done harmonic distortion correction project is
physical verification. We have observed noise, vibration, and running temperature of the 560kw, 690v VFD mill motor
closely before and after commissioning of the 458A, 690v harmonic filter across it. By listening to vibrations using simple
screwdriver method, and sensing with bare hands and ears, the reduction in motor's vibration, noise and temperature was
distinctly verifiable and found quiet substantial.
But after the new installation unexpectedly a new problem surfaced which was increasingly becoming difficult to diagnose.
However, it was restricted only to Mill-1&2 section VFD Drives and did not occur with the other section of Mil-3&4 VFD
drives. While commissioning the 690v harmonic filters, months ago, we observed Mill-1&2 VFD drives tripped couple of
Fig.12: 110kv, 31.5mva Electrical SS times on earth fault. On detailed check the plant personnel does not get any clue of it, and restarted the drive, and this
process continues. It was thus considered merely a localized issue, and not with the plant's entire electrical power system.
It's main incoming substation is as shown in Fig.12.
The Mill-1 VFD drive has 2sets of 630A, 690v, incoming ACB, as shown in Fig.9, and either one of them was tripping randomly on earth fault. It in turn was tripping the Mill's
two parallel VFD drives, one at the Star side and another at the Zig-Zag side of its 3-winding Mill VFD transformer.
After usual maintenance check and since no earth fault could be found the VFD drives were reset and restarted at every
such instance. It continued until at one such restart the entire two parallel VFD drive cards blasted heavily. Almost all
converter thyristors and inverter IGBTs blasted off, as shown in Fig.13. The short circuit inside the VFD panel was so heavy
that its upstream ACB's arc chute got blackened from interrupting a huge short circuit current.
The damage was so heavy and complete that the OEM took several days in organizing spares and reassembling the
blasted VFD in its working condition. After carrying out mandated checks the OEM engineer switched ON the drive but
within 30 minutes it tripped again, on the same old earth fault, which is annunciated through a low DC voltage fault in the
VFD panel.
After working so hard around the clock for several days no one expected to come back to square one. It was evident that
the same old root cause persisted. It would not be wise to restart the drive without a satisfactory diagnosis. The OEM once
Fig.13:VFD's failed Thyristor and IGBT cards
again performed all its recommended tests, checked megger values for Motor, Cable, Bus Bar and still there was no trace
of the elusive earth fault, and everyone was at it wit's end.
Finally, the root cause emerged. Our engineering design practice extensively use transparent Acrylic sheet and Hylam
insulation sheet in panels for touch voltage protections, and further complicating the practice, there are several national
and international standards that give us little choice but to use those for human safety against accidental touch voltage.
The problem with these sheets, that we had faced in the past, is that a thin layer of electrically conductive air is formed all
along inside the Acrylic and Hylam Sheets which remains in near contact status with bare electrical bus bars and other live
components of the VFD drive. This phenomenon happens due to a combination of factors. Those include trapped air in the
surrounding, loose contacts in the VFD panel's power circuit, and those in conjunction with dust and a prolonged exposure
in harmonic rich environment. We observed pitting at the terminal end of the bus bar and heavy arc flash mark at the inside
surface of the Acrylic sheet that was closer to the live bus bar.
Further complicating the problem, the OEM has much reduced the dielectric insulation clearance from the required
distance of IEC 61439 standard, ostensibly to reduce equipment footprint. In view of these finding our engineering
practices concerning with touch voltage protections and dielectric insulation clearances are bound to take a material shift.
Fig.14: VFD drive panel 690v for 560kw motor Eventually with the root cause identified and associated precautions taken to the extent feasible given the stated facts, it
brought instant relief and joy to the project team that comprised of engineers from several companies across India. It instilled the much-needed courage and the confidence
in restarting the Mill-1 VFD drive once again. And the plant management happy with the outcome arranged for a Krishan River Fish curry dinner party, a local delicacy for the
project team.
IV. CONCLUSION
The enumerated case study and its yearlong performance verification report clearly establish all round improvement of major power system parameters for the plant's total
power management, safely and without electrical blast.
Going by the saying what goes around comes around, it reconfirms the fact that doing power quality engineering at the downstream, at the point of harmonic generation of
VFD drives either collectively or individually (which is 415v and 690v in this case study) mirrors optimum power system stability both within the plant and within its connected
grid supply zone.
Such an engineering effort prevents electrical harmonic pollutions from entering the electrical power system of the grid supply zone which could then percolate into another
plant's electrical power system. Which could create a similar problem of electrical blast or tripping or equipment failure.
In-addition, it reduces carbon emission by enhancing productivity, removing barriers to energy efficiency, and promoting efficient use of energy all along. That starts from
downstream plant to neighboring users, and up to the upstream power plant, the IPP power supplier and the grid company.
The cost saving when looked narrowly in comparison with the electricity bill alone might seem moderate, but when compared holistically with substantially reduced
investment cost, lower carbon footprint, uninterrupted production, MTBF, inventory cost of components and workforce motivation coupled with the ever rising cost of energy,
the economic benefits far outweigh the cost of the solution.
V. BIOGRAPHIES
Kanai Banerjee graduated in Electrical Engineering from Indian Institute of Engineering Science and Technology, Shibpur, India in the year
1983. Worked at Bharat Heavy Electricals Limited from 1983 to 1995 and thereafter until date, as a promoter at Encon Engineers
(www.enconengineers.in/ (http://www.enconengineers.in/)) at Bangalore.
His special fields of interest include power quality engineering, harmonic solutions and manufacturing passive tuned harmonic filter and triplen
harmonic filter of all size LV and HV, troubleshooting failures, energy conservation, electrical consultancy and HVAC engineering for setting up
truly green building and retrofitting large centralized HVAC projects.
He has been instrumental in building up the company's impressive growth and reputation as a knowledge-based technology solution provider on power quality, energy
efficiency, process optimization and in Total Power Management fields
An energy auditor certified by the bureau of energy efficiency under the ministry of power government of India, a member and chartered professional engineer with the
institute of engineers, India, a member at the Indian society of heating, refrigerating and air-conditioning engineers, ISHRAE and a member at the Canadian and American
EMTP-ATP user group.
Place: Bangalore
Date: 30 December 2014
Previous
Next
(/residence-mauritius-energy-savings- (/taj-vivanta-hotel-energy-savings- (/mitsubishi-heavy-industries-cnc-failure- (/sterlite-technologies-harmonic
verified) verified) elimination-verified) performance-verified)
CONTACT INFO
Encon Engineers
FACTORY DIRECTION
Google Map
(https://www.google.co.in/maps/place/Encon+Engineers/@13.013971,77.495438,15z/data=!4m5!3m4!1s0x0:0x77743be9939e7f23!8m2!3d13.013971!4d77.495438)
I AM SOCIAL
LinkedIn (https://www.linkedin.com/in/harmonicfilter/)
Facebook (https://www.facebook.com/)
Google+ (https://plus.google.com/+EnconEngineersBangalore)
Twitter (https://twitter.com/)
Pinterest (https://in.pinterest.com/enconengineers/)
USEFUL LINKS
ATPDraw (http://www.atpdraw.net/)
ATP-EMTP (http://www.emtp.org/)
(http://www.histats.com/viewstats/?sid=3722606&ccid=511)