AfDB NGFO PIPED SERVICES BOQ (DEC 12)

African Development Bank


Proposed Nigeria Field Office, Abuja, Nigeria

BILL OF QUANTITIES

MECHANICAL (HVAC) SERVICES INSTALLATION

KOA AfDB BOQ Piped 1


AfDB NGFO PIPED SERVICES BOQ (DEC 12)

MECHANICAL (HVAC) SERVICES INSTALLATION

TENDER SUMMARY

BILL NO. 1 - PLANT AND EQUIPMENT

BILL NO. 2 - VRF Installation

BILL NO. 3 - DUCTWORK

BILL NO. 4 - CHILLED WATER PIPING

BILL NO. 5 - CONDENSATE PIPING

BILL NO. 6 - INSTRUMENTATIONS&CONTROLS

TOTAL

..

KOA AfDB BOQ Piped 2


AfDB NGFO PIPED SERVICES BOQ (DEC 12)

Bank
a, Nigeria

TALLATION

KOA AfDB BOQ Piped 3


AfDB NGFO PIPED SERVICES BOQ (DEC 12)

TALLATION

Naira

KOA AfDB BOQ Piped 4


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

Supply, install,test,verify and commission the following


plants and equipment. Further schedules of some of the
items are given at the end of this bill. Tenderer is
expected to be familiar with the specifed manufacturers
and is to submit appropriate brochures of the specified
items (or an equivalent product of another acceptable
manufacturer as shall be agreed with the Client and
Consultants.

1 Chillers Unit shall be complete with heat recovery


accessories. Allow for anti-corrosion treatment. Controls
shall be interfaced into a BMS system. E.g. Trane air
cooled helical rotary chillers (RTAD 085) or approved
equal

Chiller 0-1&2 (duty and duty)


cooling cap: 255kW 2 Nos
temp diff: 6.0o
ambient: 40oC DB, 280C WB

2 Chilled Water Circulating Pumps e.g Pullen, Grundfos


or approved equal
Constant flow pimary circuit pumps. Pumps shall be the
vertical type mounted indoors (IP55 rating)

P 0-1&2 (duty/standby)
20 l/s @ 200kPa 2 no

3 Make-up and pressurisation unit comprising pumps, tank,


pneumatic vessel, accessories and interconnecting
pipework as detailed in drawing. 1 set

4 Chemical dosing unit comprising of tank, dosing pump


1 No
and all accessories

5 Line pressurisation vessel


- chilled water system 1 No

to bill collection

KOA: 371348736.xls 5
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

6 Allow for anti-vibration mounting of all equipment.


sum

Air Handling Units (e.g. Trane CLCP or approved


equal)
Modular double skin chilled water air handlers, coil shall
be copper/aluminum

Air handling configuration shall follow the following


modules:
I - Inlet plenum
M - Mixing box
P - Flat pleated panel filter (rated F7)
B - Bag filter (rated F9)
C - Cooling coil (chilled water)
A - Access Box
F - Centrifugal fan unit
O - Outlet plenum

Air flow rates are nominal values. The AHU shall be rated
an extra 5% to cater for duct leakage and balancing.

7 AHU 0-1 (Horizontal) 1 No


Config: M-P-B-C-A-F
airflow:- 1360 l/s
cooling load: 43.08kW
ESR: 428 Pa

8 AHU 5-1 & 2 (Vertical) - duty/duty 2 No


Config: I-P-C-A-F
airflow:- 3955 l/s
cooling load: 254.00kW
ESR: 890 Pa

to bill collection

KOA: 371348736.xls 6
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

Extract Fan e.g Flakt Woods or approved equal.

In-duct aerofoil fans are to be mounted in acoustic


insulated enclosures (boxes) and rated IP65. Fans shall
be generally selected for speeds not exceeding 1500rpm
except otherwise agreed with the Consultant. Break out
noise (after allowing for acoustic insulation) shall not
exceed 40dB
Fans shall be duplicate operating on a duty/standby
basis

9 TEF 6-1&2 (duty/standby) - Toilet extract


2562 l/s @ 386 Pa 2 Nos

10 EF 6 - 1&2 - Atrium ventilation


Fans shall be rated 'flame proof'
2500 l/s @ 200 Pa 2 Nos

Staircase pressurisation Fan e.g Flakt Woods or


approved equal.
In-duct aerofoil fans are to be mounted in acoustic
insulated enclosures (boxes) and rated IP65. Fans shall
be generally selected for speeds not exceeding 1500rpm
except otherwise agreed with the Consultant. Break out
noise (after allowing for acoustic insulation) shall not
exceed 40dB
Fans shall be duplicate operating on a duty/standby
basis

11 SPF 6-1&2 (duty/standby) - escape stair pressurisation

2880 l/s @ 183 Pa 2 Nos

to bill collection

KOA: 371348736.xls 7
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 1 - PLANTS AND EQUIPMENT

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

Computer Room Air conditioning units (CRAC 1-1&2)


- duty/standby
Units shall have DX coils and shall be complete with
matching air cooled condensing units.

Units shall be c/w all integral microprocessor controls for


temperature and humidity, display unit, alarm indication.
Units shall have auto-restart facility. Provide dry contacts
for connections to fire alarm system and BMS.
Refrigerant shall be R410A or better (The option for
electric reheat and humidifier shall be quoted seperately
and shall be optional). Eg Airedale Logicool In-Rak (data
centre unit) or approved equal.

12 CRAC 1 - 1&2
cooling cap: 26.20kW total, 25.75kW sens.
2 No

Refrigerant piping for CRAC units. Allow for insulation


lot
and sheating

Condensate piping for CRAC units using 25mmDIA


lot
HDPE. Allow for insulation

13 Line pressurisation vessel


- chilled water system 1 No

14 Allow for anti-vibration mounting of all equipment.


lot

15 Wall Extract Fan e.g Xpelair or approved equal.


EF 0-1 - Battery extract
36 l/s 1 No

16 EF 0-2 - Disabled Toilet


50 l/s 1 No

COLLECTION

pg 1 - 1

pg 1 - 2

pg 1 - 3

pg 1 - 4

TO SUMMARY

..

KOA: 371348736.xls 8
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 9
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 10
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 11
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 12
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/1 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Supply,install,test,verify and commission the following


plants and equipment. Tenderer is expected to be
familiar with the specifed manufacturers and is to submit
appropriate brochures of the specified items (or an
equivalent product of another acceptable manufacturer
as shall be agreed with the Client and Consultants.

Outdoor air-cooled VRF condensing units, capable of


multiple indoor units and zone, with extended range
refrigerant piping. Operating outdoor temperature is
40oC. High COP. Refrigerant shall be R410A. E.g.
Daikin, LG, or approved equal. Note that the capacities
stated below are for the combined floor load and are not
additions of the individual capacities of the indoor units.

1 VRF 6-1 (serving ground floor) cap: 85.23kW 1 no

2 VRF 6-2 (serving first floor) cap: 56.03kW 1 no

3 VRF 6-3 (serving second floor) cap: 60.86kW 1 no

4 VRF 6-4 (serving third floor) cap: 61.69kW 1 no

5 VRF 6-5 (serving fourth floor) cap: 63.58kW 1 no

VRF 6-6 is for the future 5th floor development and is not
6 measured in this developmental phase.

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 13


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/2 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS)


Ceiling mounted cassette coil unit, matched to outdoor
unit, with galvanised sheeting treated for corrosion, 3-
speed fan, integral condensate pump, easily accessible
and cleanable EU4 filter with anti-bacterial and mildew
treatment, connections for remote control of fan and
space temperature, all mounting and fixing accessories.
Unit shall have port for BMS signal connection. Include
for unit cabled remote control and wall mounted
thermostat/controller. NOTE: equipment selection shall
be at low fan speed and entering condition of
23.0/16.4oC (except otherwise indicated in the
drawing schedules)

GROUND FLOOR

1 CAS 0-1 1 no
Cooling cap: 2.99kW
Nominal airflow: 186 l/s

2 CAS 0-2 1 no
Cooling cap: 2.99 kW
Nominal airflow: 186 l/s

3 CAS 0-3 1 no
Cooling cap: 2.99kW
Nominal airflow: 186 l/s

4 CAS 0-4 1 no
Cooling cap: 2.99kW
Nominal airflow: 186 l/s

5 CAS 0-5 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

6 CAS 0-6 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

7 CAS 0-7 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 14


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/2 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


ground floor
8 CAS 0-8 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

9 CAS 0-9 1 no
Cooling cap: 2.65kW
Nominal airflow: 225 l/s

10 CAS 0-10 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

11 CAS 0-11 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

12 CAS 0-12 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

13 CAS 0-13 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

14 CAS 0-14 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

15 CAS 0-15 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

16 CAS 0-16 1 no
Cooling cap: 3.00kW
Nominal airflow: 245 l/s

17 CAS 0-17 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

18 CAS 0-18 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 15


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/2 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


ground floor
19 CAS 0-19 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

20 CAS 0-20 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

21 CAS 0-21 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

22 CAS 0-22 1 no
Cooling cap: 3.35kW
Nominal airflow: 260 l/s

23 CAS 0-23 1 no
Cooling cap: 2.15kW
Nominal airflow: 188 l/s

24 CAS 0-24 1 no
Cooling cap: 2.15kW
Nominal airflow: 188 l/s

25 CAS 0-25 1 no
Cooling cap: 2.15kW
Nominal airflow: 188 l/s

26 CAS 0-26 1 no
Cooling cap: 2.32kW
Nominal airflow: 175 l/s

27 CAS 0-27 1 no
Cooling cap: 1.80kW
Nominal airflow: 136 l/s

28 CAS 0-28 1 no
Cooling cap: 2.72kW
Nominal airflow: 252 l/s

29 CAS 0-29 1 no
Cooling cap: 3.00kW
Nominal airflow: 225 l/s

30 CAS 0-30 1 no
Cooling cap: 2.63kW
Nominal airflow: 228 l/s

SUB-COLLECTION

page 2/2- 1

page 2/2- 2

page 2/2- 3

to bill collection (ground floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 16


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/3 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


first floor

1 CAS 1 -1 1 no
Cooling cap: 2.40kW
Nominal airflow: 200 l/s

2 CAS 1 - 2 1 no
Cooling cap: 2.40kW
Nominal airflow: 200 l/s

3 CAS 1 - 3 1 no
Cooling cap: 3.67kW
Nominal airflow: 335 l/s

4 CAS 1 - 4 1 no
Cooling cap: 3.67kW
Nominal airflow: 335 l/s

5 CAS 1 - 5 1 no
Cooling cap: 2.43kW
Nominal airflow: 220 l/s

6 CAS 1 - 6 1 no
Cooling cap: 2.43kW
Nominal airflow: 220 l/s

7 CAS 1 - 7 1 no
Cooling cap: 2.95kW
Nominal airflow: 258 l/s

8 CAS 1 - 8 1 no
Cooling cap: 2.95kW
Nominal airflow: 258 l/s

9 CAS 1 - 9 1 no
Cooling cap: 1.76kW
Nominal airflow: 165 l/s

10 CAS 1 - 10 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

11 CAS 1 - 11 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 17


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/3 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


first floor
12 CAS 1 - 12 1 no
Cooling cap: 2.84kW
Nominal airflow: 243 l/s

13 CAS 1 - 13 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

14 CAS 1 - 14 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

15 CAS 1 - 15 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

16 CAS 1 - 16 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

17 CAS 1 - 17 1 no
Cooling cap: 3.48kW
Nominal airflow: 307 l/s

18 CAS 1 - 18 1 no
Cooling cap: 1.91kW
Nominal airflow: 172 l/s

19 CAS 1 - 19 1 no
Cooling cap: 0.88kW
Nominal airflow: 76 l/s

SUB-COLLECTION

page 2/3- 1

page 2/3- 2

to bill collection (first floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 18


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/4 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


second floor

1 CAS 2-1 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

2 CAS 2-2 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

3 CAS 2-3 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

4 CAS 2-4 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

5 CAS 2-5 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

6 CAS 2-6 1 no
Cooling cap: 3.58kW
Nominal airflow: 318 l/s

7 CAS 2-7 1 no
Cooling cap: 1.79kW
Nominal airflow: 166 l/s

8 CAS 2-8 1 no
Cooling cap: 1.76kW
Nominal airflow: 165 l/s

9 CAS 2-9 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

10 CAS 2-10 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

11 CAS 2-11 1 no
Cooling cap: 3.04kW
Nominal airflow: 278 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 19


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/4 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


second floor

12 CAS 2-12 1 no
Cooling cap: 3.04kW
Nominal airflow: 278 l/s

13 CAS 2-13 1 no
Cooling cap: 3.46kW
Nominal airflow: 300 l/s

14 CAS 2-14 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

15 CAS 2-15 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

16 CAS 2-16 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

17 CAS 2-17 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

18 CAS 2-18 1 no
Cooling cap: 3.05kW
Nominal airflow: 271 l/s

19 CAS 2-19 1 no
Cooling cap: 1.62kW
Nominal airflow: 145 l/s

20 CAS 2-20 1 no
Cooling cap: 1.08kW
Nominal airflow: 90 l/s

SUB-COLLECTION

page 2/4- 1

page 2/4- 2

to bill collection (second floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 20


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/5 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


third floor

1 CAS 3-1 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

2 CAS 3-2 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

3 CAS 3-3 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

4 CAS 3-4 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

5 CAS 3-5 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

6 CAS 3-6 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

7 CAS 3-7 1 no
Cooling cap: 3.35kW
Nominal airflow: 297 l/s

8 CAS 3-8 1 no
Cooling cap: 1.76kW
Nominal airflow: 165 l/s

9 CAS 3-9 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

10 CAS 3-10 1 no
Cooling cap: 4.17kW
Nominal airflow: 345 l/s

11 CAS 3-11 1 no
Cooling cap: 3.09kW
Nominal airflow: 266 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 21


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/5 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


third floor

12 CAS 3-12 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

13 CAS 3-13 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

14 CAS 3-14 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

15 CAS 3-15 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

16 CAS 3-16 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

17 CAS 3-17 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

18 CAS 3-18 1 no
Cooling cap: 3.20kW
Nominal airflow: 283 l/s

19 CAS 3-19 1 no
Cooling cap: 1.57kW
Nominal airflow: 140 l/s

20 CAS 3-20 1 no
Cooling cap: 1.08kW
Nominal airflow: 90 l/s

SUB-COLLECTION

page 2/5- 1

page 2/5- 2

to bill collection (third floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 22


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/6 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


fourth floor

1 CAS 4-1 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

2 CAS 4 - 2 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

3 CAS 4 -3 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

4 CAS 4-4 1 no
cooling cap: 2.94kW
Nominal airflow: 259 l/s

5 CAS 4-5 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

6 CAS 4-6 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

7 CAS 4-7 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

8 CAS 4-8 1 no
Cooling cap: 3.20kW
Nominal airflow: 288 l/s

9 CAS 4-9 1 no
Cooling cap: 1.99kW
Nominal airflow: 187 l/s

10 CAS 4-10 1 no
Cooling cap: 4.20kW
Nominal airflow: 348 l/s

11 CAS 4-11 1 no
Cooling cap: 4.20kW
Nominal airflow: 348 l/s

to sub collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 23


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/6 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Indoor VRF Cassette Units (CAS):


fourth floor

12 CAS 4-12 1 no
Cooling cap: 3.12kW
Nominal airflow: 269 l/s

13 CAS 4-13 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

14 CAS 4-14 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

15 CAS 4-15 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

16 CAS 4-16 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

17 CAS 4-17 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

18 CAS 4 - 18 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

19 CAS 4-19 1 no
Cooling cap: 3.24kW
Nominal airflow: 287 l/s

20 CAS 4-20 1 no
Cooling cap: 1.59kW
Nominal airflow: 142 l/s

21 CAS 4-21 1 no
Cooling cap: 1.24kW
Nominal airflow: 115 l/s

SUB-COLLECTION

page 2/6- 1

page 2/6- 2

to bill collection (fourth floor CAS)

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 24


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/7 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Accessories
Supply and install accessories associated with the VRF
units indicated above

1 Remote control and thermostat unit incorporating 3-


speed fan control. Allow for cabling

- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

Instrumentation and controls


2 Supply and install system logic-based electrical and
auto-control panel. Control unit to include for desktop PC
and monitor (mounted in the 5th floor plant room). Panel
shall allow for all electrical power protections - phase
failure, under/over current, surge protection, etc. Include 1 no
for step down transformer for controllers all to give a fully
functional system

3 Allow for control cabling from all indoor and outdoor units
to the control panel
- outdoor units lot

- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

4 Allow for power cabling to outdoor units. Include for


lot
outdoor mounted local isolators.

5 Allow for cable fixing, hangers, conduits, supports


lot

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 25


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/7 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

Refrigerant piping
6 Supply and install all refrigerant piping using copper (BS
2871). The tenderer shall submit computer based pipe
sizing calculations appropriate to the product being
tendered and a breakdown of the costings for each floor
extended and totalled to the figures inserted in this BOQ.
The refrigerant installation shall be from the roof
mounted outdoor units to the indoor units on each floor.
Rates shall include for all fittings and accessories

- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

7 Supply and install insulations to all refrigerant piping


using armaflex tubing (or approved equivalent) of
appropriate thickness. Rates shall include for all fittings
and accessories

- ground floor units lot

- first floor units lot

- second floor units lot

- third floor units lot

- fourth floor units lot

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 26


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 2/7 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

8 Condensate piping
Supply and install all condensate piping to the indoor
units using HDPE piping. The layout shall be as indicated
in the design drawings. Rates shall include for all fittings
and accessories. Rates shall includes for 20mm thick
armaflex (or approved equal) insulation tubing.

ground floor units


25mm dia 62 m
50mm dia 144 m
80mm dia (stack for entire installation and connection to
72 m
drain channels)

first floor units


25mm dia 46 m
50mm dia 96 m

second floor units


25mm dia 46 m
50mm dia 96 m

third floor units


25mm dia 44 m
50mm dia 96 m

fourth floor units


25mm dia 44 m
50mm dia 96 m

9 Allow for pipe fixing, brackets, hangers, supports


lot

to sub collection

COLLECTION

page 2/7- 1

page 2/7- 2

page 2/7- 3

to bill collection

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 27


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - VRF Installation

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE TOTAL

BILL COLLECTION

bill 2/1

bill 2/2

bill 2/3

bill 2/4

bill 2/5

bill 2/6

bill 2/7

TO SUMMARY

KOA: AfDB Abuja (Priced BOQ)- HVAC (Apr. 2013).xls 28


AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - DUCTWORK

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

Supply,install,test,verify and commission the following


(refer to drawing and specification for details).

All air diffusion units shall be extruded aluminum (except


otherwise indicated) and shall be to RAL colour to be
approved by the architect

Ductwork

1 Galvanised sheet metal ductwork (using appropriate


1398 m2
guages as specified).

2 Provided for insulation to duct using 25mm foil faced


mineral fibre insulation and vapour barrier. 978 m2

3 Provided for internal thermal and acoustic duct liner to


duct above using 50mm thick non fibre medical grade
insulation and vapour barrier with anti-bacterial and anti-
fungal treatment e.g. Armaflex/Armacell, KFlexUSA or
approved equal. Include for fasterners, etc 420 m2
Insulations within plantrooms shall be internal. Also
insulations up to 10m from (airhandling) AHUs shall
be internal.

4 Supply Diffuser (SD) ceiling mounted. Units shall be


square face adjustable multi-louvre type with round neck
(or square neck) supply. Units shall be complete with iris
(or opposed blade) damper. E.g. GDL, Trox or approved
equivalent. Neck diameters are indicated below

150 dia 103 nos


200 dia 5
250 dia 1

5
Sidewall Supply Diffuser (SWD) Units shall have
double deflection grilles c/w opposed blade dampers.
E.g. GDL, Trox or approved equivalent
300 x 100 1 nos
900 x 300 4 "

6
Return Grille (RG) ceiling mounted. Units shall be
rectangular face adjustable egg crate type. Units shall be
complete with opposed blade damper. E.g. GDL, Trox or
approved equivalent
1200 x 600 1 no

To Conclusions

KOA: 371348736.xls 29
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - DUCTWORK

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

7
Sidewall Air Jet Grille (AJG) High capacity supply air
jets to have concentric rings assembled with a pivoting
eyeball adjustment c/w opposed blade dampers. E.g.
GDL J frame, Trox or approved equivalent
350 x 350 (single jet) 4 nos

8
Extract Grille (EG) ceiling mounted. Units shall be
rectangular face adjustable egg crate type. Units shall be
complete with opposed blade damper. E.g. GDL, Trox or
approved equivalent
150 x 100 35 nos

10 Flow control / Balancing Dampers single or multi leaf.


E.g GDL, Trox or approved equivalent

Allow for the provision of balancing dampers as indicated


on drawing and/or specification and/or schedules lot

11 Door Transfer Grille non-vision


600 x 150 6 Nos

12 Fire Dampers 2hr rating c/w fusible link, . E.g GDL, Trox
or approved equivalent
Allow for the provision of fire dampers as indicated on
drawing and/or specification, schedules

200 x 150 5 nos


300 x 100 1 "
300 x 150 5 "
400 x 300 4 "
500 x 400 1 "
600 x 400 6 "
800 x 400 1 "
900 x 300 4 "
950 x 400 1 "

150dia 5 nos

To Conclusions

KOA: 371348736.xls 30
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 3 - DUCTWORK

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

13 Allow for clean outs, test holes and access doors.


lot

14 Allow for support, brackets, vibration dampers etc.


lot

15 Allow for flexible duct connectors from duct to ceiling


lot
terminals.

To Conclusions

CONCLUSION

pg 3 - 1

pg 3 - 2

pg 3 - 3

TO SUMMARY

..

..

KOA: 371348736.xls 31
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 32
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 33
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 34
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

Supply,install,test,verify and commission the following

Pipework shall be black mild steel to BS 1387 Class C


Heavy Grade. Large diameter pipes shall be grooved.

1 Pipes
25mm 6 m
32mm 6 m
50mm 18 m
100mm 54 m
125mm 216 m

2 900 Bend
25mm 6 nos
32mm 6 "
50mm 10 "
100mm 16 "
125mm 30 "

3 1350 Bend
100mm 4 nos
125mm 14 "

4 Tee
125mm 10 nos

5 Isolating Ball Valve


50mm 2 nos

To Conclusions

KOA: 371348736.xls 35
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

6 Isolating Butterfly Valve


100mm 6
125mm 8

7 Double Regulating Valve (c/w test points and seals)


50mm 1
100mm 6
125mm 2

9 2-Way Modulating Valves (c/w motor actuator)


50mm 1
100mm 2

10 Check (NRV) Valve


32mm 1
125mm 2

11 Strainer (Line)
50mm 1
100mm 4
125mm 2

To Conclusions

KOA: 371348736.xls 36
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

12 Flexible Connector
50mm 2
100mm 8
125mm 4

13 Flange (c/w) gasket


50mm 12
100mm 30
125mm 24

14 End Flange (Cap)


125mm 2

15 Capped Flushing Tee


25mm 5 nos

16 Drain Cock
25mm 5 nos

17 Valved Flushing Inlet


50mm 2 nos

18 Safety Relief Valve


10bar setting 2 nos

19 Automatic Air Valve (AAV) 5 no

20 Flow Switch 1 no

21 Air Eliminator 5 no

22 Test point (sealed) 6 no

23 Pressure guage (0 - 15bar) c/w cock 10 no

To Conclusions

KOA: 371348736.xls 37
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 4 - CHILLED WATER PIPING

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

24 Thermometer (Dial type 150mm) 10 no

25 Miscellaneous Items
Union, connectors, nipples, 135o bends, etc lot
Bracket, hangers, supports, etc lot

26 Thermal Insulation (using preformed rigid mineral wool


insulation or armaflex tubings. Allow for vapour seal) -
thickness as specified but minimum 50mm

25mm 6 m
32mm 6 m
50mm 18 m
100mm 54 m
125mm 216 m

27 Carry out resin protective coating on pipes installed in


plantrooms, risers and external.
25mm 6 m
32mm 6 m
50mm 18 m
100mm 54 m
125mm 216 m

To Conclusions

CONCLUSION

pg 4 - 1

pg 4 - 2

pg 4 - 3

pg 4 - 4

TO SUMMARY

,,

KOA: 371348736.xls 38
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 39
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 40
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 41
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 42
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

BILL No. 5 - CONDENSATE PIPING (for chilled water)

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

Supply,install,test,verify and commission the following

Pipework shall be HDPE. All condnsate pipes shall be


appropriately insulated.

1 Pipe
50mm 12
100mm 48

2 Bend
50mm 6
100mm 2

3 Tee
50mm 2
100mm 1

4 Trap Connections
50mm (for AHUs) 3

5 Turndish
100mm 2 nos

6 Miscellaneous Items
Brackets, anchors, etc lot
Flanges, gaskets, sockets, reducers, etc lot

7 Thermal Insulation
using 20mm armaflex lot

TO SUMMARY

,,

KOA: - 371348736.xls 43
AfDB NGFO HVAC SYSTEM BOQ (APR 13)

TOTAL

KOA: - 371348736.xls 44
AfDB NGFO HAVC SYSTEM BOQ (APR 13)

BILL No. 6 - INSTRUMENTATIONS AND CONTROL

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

Supply,install,test,verify and commission the following.


Refer to drawing, design report and specification for
details

1 Thermostat
duct 2 nos

2 Temperature Gauge (pipe mounted) - dial type 2 nos

3 Test point with cock 10 nos

5 Flow Switch 1 No

6 Differential Pressure Switch 3 Nos

7 Duct mounted dial thermometer 2 Nos

8 Duct mounted dial pressure gauge 2 Nos

9 Smoke Detector Probe 4 Nos

10 Control cabling, terminator, etc Lot

11 CO2 Monitor (e.g Greystone Energy Systems) - duct


1 nos
mounted

12 Control Panel

The controls shall be fully digital. Allow for control panel


and system as detailed in the specifications, schedules
and drawings. Include for all electrical control elements 1 nos
including the step-down transformer, (230/24 VAC),
relays, switches, contactors, timers, including all current
and voltage protective devices, e.t.c to give a fully
function system. Note provisions for future upgrade.
System shall be integrated into the building BMS

13 Control cabling
Allow for control cabling to connect all controlled plants
and the control panel. Rates to include for termination lot
items.

14 Electrical Power cabling


Allow for power cabling from the control panel and/or
local distribution panel to all item of equipment for final
connections. Provide appropriate termination devices. lot
Only wireways shall be provided by others.

15 Local isolators to all items of equipment (some shall be


lot
suitable for outdoor installation)

to conclusion

KOA: 371348736.xls 45
AfDB NGFO HAVC SYSTEM BOQ (APR 13)

BILL No. 6 - INSTRUMENTATIONS AND CONTROL

ITEM DESCRIPTION
QTY UNIT SUPPLY RATE FIXED RATE TOTAL RATE

16 Allow for equipontential bonding of the equipment lot

17 Allow for brackets, mountings, pads. lot

18 Allow for linkage to the building BMS including provisions lot


for cabling

19 Allow for linkage to the building fire alarm panel including lot
provisions for cabling

to conclusion
..

CONCLUSION

pg 6 - 1

pg 6 - 2

TO SUMMARY

..

..

KOA: 371348736.xls 46
AfDB NGFO HAVC SYSTEM BOQ (APR 13)

TOTAL

KOA: 371348736.xls 47
AfDB NGFO HAVC SYSTEM BOQ (APR 13)

TOTAL