Scenario1_BTS3900A+RRU+TP48200A+MW REV OJO BTS Layout 4/21/2015 caibin

Note: Site type Outdoor,GF tower


1. The scenario use GF tower site for an AC Power supply 380V
example, and if the site is RF mast, hardware
Powe equipment RTN905/RTN950
installation is same;
2. We suggests that there should be 1U free Transmission port type FE/GE
space between two DCDU-12B; Other equipment DCDU-12B
BTS3900A free space 9U
TP48200A free space 9U
AC iuput MCB requirement 3*25A
Jumper
DC MCB distribution LLVD:2*63A,2*32A; BLVD:2*16A,1*10A;
7/8'feeder
AC power cable Battery BAT:1*125A, 2*190AH
DC cable
Grounding cable
Fiber
IF cable BTS3900A DC TP48200A
Ethernet cable
FAN(1U) Blank(1U)
SLPU(1U)
DCDU-12C (1U) POWER SUBRACK
BBU(2U) AC/DC
DCDU-12B-1 (1U)

DDF(1U)

DCDU-12B(1U)
RTNxxx

AC
BOX RFC
B B B B
A A A A
FAN T T T T
DCDU-12A (1U) T T T T
E E E E
R R R R
Y Y Y Y
R R R R R R
F F F F F F
B B B B
U U U U U U A A A A
T T T T
T T T T
E E E E
R R R R
Y Y Y Y
Scenario1_BTS3900A+RRU+TP48200A+MW_MCB Distribution
LLVD BLVD BAT Note:
1. 1~6RRUs share 1 DCDU-12B, When RRU
63A 63A 32A 32A 16A 16A 10A 125A 125A more than 6, need add 1 DCDU-12B.
2. We suggests that there should be 1U free
space between two DCDU-12B for RRU
cable route conveniently.

BTS3900A DC TP48200A
DCDU-12C (1U)
DCDU-12B(1U)
BBU(2U)
DCDU-12B-1 (1U)
DCDU-12B in TP distribution for IDU(MW)
BAT
DCDU-12B-2 (1U)

DCDU-12A (1U) BAT

BTS3900A DC TP48200A RTN9xx


FAN(1U) Blank(1U)
SLPU(1U)
DCDU-12C (1U) POWER SUBRACK
BBU(2U) AC/DC
DCDU-12B-1 (1U)
RRU Power distribution
DCDU-12B-2 (1U) DDF(1U)

DCDU-12B(1U)
1 2 3 4 5 6 7 8
RTNxxx

RFC
B B B B
A A A A
FAN T T T T
DCDU-12A (1U) T T T T
E E E E
R R R R
Y Y Y Y
R R R R R R
F F F F F F
U U U U U U
B B B B
DCDU-12B-1 DCDU-12B-2
A A A A
T T T T
T T T T
E E E E LOAD 0 LOAD 1 LOAD 2 LOAD 3 LOAD 4 LOAD 5 LOAD 6 LOAD 7 LOAD 8 LOAD 9
R R R R
Y Y Y Y D C DU-12B_1 1 2 3 4 5 6 reservation reservation reservation reservation
D C DU-12B_2 7 8 reservation reservation reservation reservation

RRU DC distribution from 3G_2100M RRUs, then 4G_1800M RRUs


Scenario1_BTS3900A+RRU+TP48200A+MW_Monitor Cable between TP&BTS

RJ485/RS232 BTS3900A TP48200A


Mon1
COM_IN COM_OUT
Mon0 FAN
SMU02B
TMC11H DCDU-12C
COM_IN UIM02C
COM_OUT B UEIU PSU PSU PSU PSU
F
Ethernet cable A UPEU
UMPTb1

DCDU-12B

COM_OUT COM_IN

FMU
Battery Battery Battery Battery

DCDU-12A

MRFU MRFU MRFU


d d d
RFC
CPRI1 CPRI1 CPRI1 Battery Battery Battery Battery

CPRI0 CPRI0 CPRI0

Note: for temporary scenario, BBU install at TP cabinet, the monitor cable from TP to BBU, BBU side is port Monitor0at UPEU board.
Scenario1_BTS3900A+RRU+TP48200A+MW_Transmission Cable between RTN&BTS

BTS3900A TP48200A
FAN
FE/GE
SLPU UFLP IN OUT
0 1 SIDE 0 1 SIDE
TMC11H DCDU-12C
Ethernet cable
B UEIU RTN905 1 2
EG6
F 3 4
A UMPTb1 UPEU

DCDU-12B

FMU
Battery Battery Battery Battery

DCDU-12A

MRFU MRFU MRFU


d d d
RFC
CPRI1 CPRI1 CPRI1 Battery Battery Battery Battery

CPRI0 CPRI0 CPRI0

NOTE:
If use the RTN950, the transmission cable should
connect to the GE electrical port 3 of EG4 board.
Scenario1_BTS3900A+RRU+TP48200A+MW_Antenna&Feeder Sysyterm & Color Ring

Sector A Sector B Sector C Sector D


Blue Red Yellow White
900M_GSM 2100M_3G 1800M_4G 900M_GSM 2100M_3G 1800M_4G 900M_GSM 2100M_3G 1800M_4G 900M_GSM 2100M_3G 1800M_4G
TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6

Sector A Sector B Sector B Sector B

1800M 2100M 1800M 2100M 1800M 2100M 1800M 2100M

RRU3939 RRU3839 RRU3939 RRU3839 RRU3939 RRU3839 RRU3939 RRU3839


900 1800 2100 900 1800 2100 900 1800 2100 900 1800 2100

AISG cable AISG cable AISG cable AISG cable

MFRU 900M MFRU 900M MFRU 900M MFRU 900M


REVISIONS

Temporary Scenario_TP48200A+RRU+MW REV OJO BTS Layout 4/21/2015 caibin

Note:
1. The scenario use GF tower site for an example, and if the
site is RF mast, hardware installation is same;
2. We suggests that there should be 1U free space between
two DCDU-12B;

Site type Outdoor,GF tower


AC Power supply 380V
Powe equipment RTN905/RTN950
Transmission port type FE/GE
Other equipment DCDU-12B
TP48200A free space 9U
AC iuput MCB requirement 3*25A AC LLVD BLVD BAT
DC MCB distribution LLVD:2*63A,2*32A; BLVD:2*16A,1*10A; 63A 63A 32A 32A 16A 16A 10A 125A 125A
SMU02B UIM02C
Battery BAT:1*125A, 2*190AH
PSU PSU PSU PSU

B UEIU
F
A UPEU
AC power cable UMPTb1
DC cable DDF(1U)
Grounding cable
1 2
Fiber RTN905 EG6
3 4
IF cable
Ethernet cable Free space(1U)
AC
BOX

Battery Battery Battery Battery

Battery Battery Battery Battery


REVISIONS

Scenario2_DBS3900A+TP48200A_Micro on pole REV OJO BTS Layout 4/21/2015 caibin

Note: Site type Outdoor,GF tower


1. The scenario use GF Micro on pole site for AC Power supply 380V
an example
Powe equipment RTN905/RTN950
2. the AC cable,RRU fiber,RRU DC cable
need use PVC pipe protection. Transmission port type FE/GE
3. we suggest customer install 1pcs ODF in Other equipment DCDU-12B
APM30H cabinet
APM30H DC free space 9U
TP48200A free space 9U
AC iuput MCB requirement 3*25A
DC MCB distribution LLVD:2*63A,2*32A; BLVD:2*16A,1*10A;

AC power cable Battery BAT:1*125A, 2*190AH


DC cable
Grounding cable
Fiber
Fiber pigtail TP48200A
Blank(1U)

POWER SUBRACK
AC/DC
AC
DDF(1U)
BOX

DCDU-12B(1U)

APM30H DC

FAN(1U)
B B B B
SLPU(1U)
A A A A
DCDU-12C (1U)
T T T T
BBU(2U) T T T T
DCDU-12B-1 (1U) E E E E
R R R R
Y Y Y Y

B B B B
A A A A
T T T T
T T T T
E E E E
ODF
R R R R
Y Y Y Y
Scenario2_DBS3900A+TP48200A_Micro on pole _MCB Distribution
LLVD BLVD BAT

63A 63A 32A 32A 16A 16A 10A 125A 125A

BTS3900A DC TP48200A
DCDU-12C (1U)
DCDU-12B(1U)
BBU(2U)
DCDU-12B-1 (1U)
BAT

BAT

TP48200A
Blank(1U)

POWER SUBRACK
RRU Power distribution
AC/DC

DDF(1U)

DCDU-12B(1U)
1 2 3 4 5 6

APM30H DC

FAN(1U)
B B B B
SLPU(1U)
A A A A
DCDU-12C (1U)
T T T T
BBU(2U) T T T T
DCDU-12B-1 (1U) E E E E
R R R R DCDU-12B-1
Y Y Y Y

B B B B
A A A A
T T T T
T T T T
E E E E
ODF
R R R R
Y Y Y Y

DC distribution from 2G_900M, then 3G_2100M, at last 4G_1800M RRU


Scenario2_DBS3900A+TP48200A_Micro on pole_Monitor Cable between TP&APM30H

TP48200A

SMU02B
UIM02C
RJ485/RS232 PSU PSU PSU PSU
Mon1
Mon0

Ethernet cable(Monitor cable from TP to BBU)

APM30H DC

COM_IN COM_OUT
FAN

DCDU-12C
B UEIU Battery Battery Battery Battery
F
A UPEU
UMPTb1

DCDU-12B

Battery Battery Battery Battery


Scenario2_DBS3900A+TP48200A_Micro on pole_Transmission Cable between ODF&BBU

TP48200A

FE/GE1(optical port) SMU02B


Fiber pigtail UIM02C

PSU PSU PSU PSU

APM30H DC
FAN

SLPU UFLP IN OUT


0 1 SIDE 0 1 SIDE

DCDU-12C Battery Battery Battery Battery

B UEIU
F
A UMPTb1 UPEU

DCDU-12B-1

Battery Battery Battery Battery

ODF