Plumbing Fixtures

Trap &
trap arm Total
Ground Floor Qty DFU Total DFU size (inch) WSFU WSFU
Watercloset/ bidet 2 4 8 3 5 10
Kitchen Sink 1 2 2 1.5 2 2
Wash basin 2 1 2 1.25 1 2
Floor drain 2 2 4 2
Urinal 3 0 2 0
Hose bib 2 0 3 6
Shower 1 2 2 2 2
Footwash 1 0 2 2
Clothes washer 1 2 2 2 2
Second Floor Comparisson of Nspc and NPC
Watercloset 2 4 8 3 5 10 20 mm/m
Wash basin 2 1 2 1.25 1 2
Floor drain 2 2 4 2 0.25 in/ft
Shower 1 2 2 2 2 20.828 mm/m
Footwash 1 0 2 2
Hose bib 1 0 3 3
Bath tub 2 0 2 0
Roof Deck Elevated Tank
Watercloset 4 0 3 5 0
Wash basin 1 0 1.25 1 0 No Of Occupants #VALUE!
Floor drain 2 0 2 5 265 gals
Shower 2 0 2 0 Fixture qty discharge time/ usageVolume
Footwash 0 2 0 Watercloset 2 20 li/flush 5 200
Wash basin 2 20 li/min 20 800
Watercloset 4 0 5 0 Shower 2 30 li/min 15 900
Wash basin 1 0 1 0 Footwash 2 15 li/min 5 150
Floor drain 2 0 2050 li 541.612 gal
Shower 2 0 2 0 Elevated Tank Volume: 265 US
Footwash 0 2 0 Hydropneumatic: 32.5 say 50 gals
Net Elevated Tank Volume: 215 say 200 US Gal
GRAND TOTAL 36 45
References: Diameter 0.5 m
DFU p.80 NPCP (94/230) Peak demand= 67.5 WSFU Height 5.10836438 m
WSFU p.56 NPCP (87/230)
HEAD LOSS Shower pressure head requirement
NSPC Pipe Length HL Discharge rate: 7 gpm
Table 16.3.7 Sewage Flow per day 20mm 6.04 0.6052684 0.00044 m3/s
Table 16.6.1 Capacity of Septic Tanks 15mm 26.313 2.99889261 Velocity: 2.49885 m/s
3.60416101 Head requirement:
0.31826 m
Note: As per table B-2 (Capacity of septic tanks) the min septic tank capacity
for 5 or 6 bedroom is 1500 gals plus 150 gals. Per extra bedroom Standard Requirement for Grohe "Rain Pan" Shower Head:
Pump discharge: 10 gpm 14.47 psi
(See Table B-2, NPCP) Total head: 73.9726833 ft 10.19 m
Single Family/ No. of Minimum Capacity: Power: 139.566494 watts
Bedrooms Hydroneumatic Tank Sizing:
3 1000 gals= 3.79 m3

where:
` Vu= (5mins)x(largest booster/transfer pump capacity in gpm)= Usable volume in gallons
Pin= cut-in pressure in psi
Pout= cut-out pressure in psi

Total clear dimensions of septic tank: Booster/Transfer pump max cap= 20.00 gpm
width= 1.20 Vu= 100.00 gallons
Fluid depth= 1.20 q(Select) (See septic tank construction p. 181, NPCP) P in = 25.00 (cut-in pressure)
length= 2.63 say 2.70 P out = 40.00 (cut-out pressure)
Volume: 3.888 m3 (Capacity is sufficient) Gross Volume= 364.67 U.S. gals
1.38 m3
Length Tank height= 2.75 m (assuming 0.8m diameter)
Primary= 1.80 say 1.80
Secondary= 0.90 say 1.50 References:
*See page 245 Gillesania
*Storage Tank Design and Guidelines.pdf
Chamber Length Width Depth Volume * difference between cut-in and cut-out pressure should be 15-20psi
Digestion 1.80 1.20 1.20 2.59 m 3
Leaching 1.50 1.20 1.20 2.16 m 3
Total Capacity: 4.75 m 3 = 1256 gals

m
a= 1.50 m
b= 1.80 m
c= 0.60 m
d= 1.30 m
wtotal= 1.60 m
ltotal= 3.70 m
h= 1.20 m
htotal= 1.80
Septic Tank Depth (m):
0.6
0.8
1
1.2
1.4
1.6
1.8

Water Supply:

Use Table of Conversion of WSFU to GPM. Pdf


WSFU: 45 SAY 50 GPM