You are on page 1of 1

STREET

GUTTER

CURB
LAWN OR SIDEWALK

1" CHAMFER
3'-0"
STEEL BASE COVER

BASE PLATE

24"
DIA. C
L
ROUND TAPERED
ALUMINUM POLE

11" BOLT CIRCLE

SONOTUBE
NOTE:

ALL LOCATIONS AND DIMENSIONS FOR ANCHOR BOLTS ETC. SHALL BE


VERIFIED IN FIELD BY THE INSTALLING CONTRACTOR WITH BOLTS
FURNISHED BY POLE MANUFACTURER.

BASE - PLAN VIEW

SHORTING CAP PROVIDED


BY INSTALLING CONTRACTOR

SINGLE OR DOUBLE LED OR


METAL HALIDE FIXTURE -
SEE FIXTURE SCHEDULE

SUPPORT ARM
ASSEMBLY

ROUND TAPERED ALUMINUM


POLE WITH BLACK FINISH

30'-0"

WIRING UP TO LUMINARIES

HAND HOLE

IN LINE FUSE HOLDERS GROUNDING LUG


LOCATED AT HANDHOLE. SEE
POLE WIRING DETAIL 26560006 PVC OR PLASTIC
TWO PIECE
BASE COVER
WITH BLACK FINISH
FULLY GALVANIZED
STEEL ANCHOR BOLTS, 1" CHAMFER
1"x36"Lx4"ELL
FOR NEW BASES
FINISHED GRADE
(LAWN OR SIDEWALK)
3000 PSI MINIMUM CONCRETE
WITH FIBERMESH & RUBBED
FINISH ABOVE GRADE 4" (SEE NOTES)

24"
FOR GROUND ROD
24"
1 14"SCHEDULE 40 PVC LOCATION SEE
(MIN)
IN & OUT OF BASES DETAIL 26560017
(TYP. OF 3)

7'-8"

8#6 VERTICALS
W/ #3 LOOPS
@ 12" O.C.

3000 PSI CONCRETE. 1


2"x 8'-0" COPPER WELD
EXPOSED CONCRETE SHALL GROUNDING ROD W/ #6
BE FREE OF HONEYCOMBS BARE COPPER WIRE TO
24" ROUND
GROUNDING LUG NEAR
BASE
HANDHOLE. PROVIDE A
#10 GREEN COPPER
CONDUCTOR TO
NOTES:
FIXTURES.

1. WHEN THE FINISHED GRADE SLOPES DOWNWARD FROM


THE CURB, ADJUST THE EXPOSED HEIGHT OF THE BASE
SO THAT THE TOP OF THE BASE IS 4" ABOVE THE TOP
OF THE CURB.

2. WHEN THE FINISHED GRADE SLOPES UPWARD FROM THE


CURB, ADJUST THE EXPOSED HEIGHT OF THE BASE SO THAT
THE TOP OF THE BASE IS 2" ABOVE THE FINISHED GRADE
AT THE BACK SIDE OF THE BASE.

3. LOCATE BASES ON CENTERLINES WHERE CENTERLINES


ARE SHOWN ON THE PLANS, OR CENTER BASES 3'-0" BACK
FROM THE CURB WHERE CENTERLINES ARE NOT SHOWN.

TYPICAL STREET LIGHT FIXTURE DETAIL


NO SCALE
26560010.dgn