You are on page 1of 8

Engineering method for high-voltage substations

lightning performance estimation

Prof. M.S. SaviC

Indexing terms: Lightning and lightning protection, Cables and overhead lines

presumed that every overvoltage exceeding the BIL


Abstract: A computer method for estimating the causes an insulation failure.
lightning performance of high-voltage substations
has been developed and modified for simple engin- 2 Computation methodology
eering applications in the substation design. The
main substation element representation and the 2.1 Equivalent circuit choice
equivalent circuit choice are suggested. The One of the most important tasks in the lightning per-
method is illustrated by the example of a 110 kV formance of a high-voltage substation estimation is the
substation with a cable entrance. Both shielding correct choice of the substation element representation
failures and lightning strikes to the towers or the and the selection of an equivalent circuit.
earth wires, causing back-flashovers on the in- (a) Usually the monophase representation of all con-
coming overhead lines, have been analysed and ductors by positive sequence surge impedance can be
the best variant of the overvoltage protection sug- satisfactory for a short-distance propagation process. The
gested. ground return frequency-dependent parameters cause a
decay of the wave crest of a few percent. This effect can
be neglected for the sake of simplicity and safety. The
mutual influence of the phase conductor and the earth
1 Introduction wire can be modelled by a coupling factor C , in the fol-
lowing way :
In the design of high-voltage substations one of the ver
important tasks is to perform insulation coordination by
the correct selection and location of the surge arresters.
Recently two kinds of methodologies for insulation where U , is the earth wire surge voltage and Up,, is the
coordination have been recognised. In the case of an surge voltage of the phase conductor. Factor C, can be
untypical high-voltage substation layout a com- taken from the range 0.2-0.3.
prehensive study for estimating the expected number of (b) A power transformer can be represented as an
failures due to over-voltage occurrence has been per- equivalent surge capacitance given by the manufacturers.
formed. On the other hand, in the case of a typical sub- Some authors use a surge impedance 2, = of the
station the simplified methods for overvoltage protection transformer in parallel with the surge capacitance. This
design have been applied. surge impedance can cause a decrease in the crest voltage
In this paper a general methodology for high-voltage at the transformer terminal of less than 3%, and usually
substation lightning performance estimation, convenient it can be neglected.
for engineering applications, will be described. The (c) Current transformers, voltage transformers, circuit
method is illustrated by the example of the 110 kV sub- breakers, disconnectors and even insulator strings can be
station of the power plant Nikola Tesla in Yugoslavia. represented by equivalent capacitances. In that case
The method is based on the travelling-wave technique. equivalent circuit would become very complex and the
Wave distortion due to the corona losses is taken into results would become optimistic. Owing to this it has
account [1). Frequency-dependent line parameters can been decided to neglect all capacitances except power
be involved in the computation procedure [2]. The prob- transformer surge capacitance.
ability method of limiting parameters described in Ref- (d) In the case of a strike to the earth wire causing
erences 3 and 4 is used for estimating the risk of insulation back-flash it is sufficient to investigate strikes to the first
failure at a certain place in the substation. This method is two spans in front of the substation. Strikes to the other
based on computation of the critical value of the light- spans causing back-flashovers are not dangerous for the
ning current amplitude which, if applied at a certain substation insulation, owing to the wave distortion along
point in front of the substation, causes greater overvol- the line.
tage than the basic insulation level (BIL) at the inspected (e) Every tower can be modelled as a short line with a
part of the insulation in the substation. The computation constant surge impedance dependent on the tower
is repeated for various lightning current gradients to geometry, as described in Reference 5.
obtain the relation between the current gradient and the (f)The number of back flashes is strongly dependent
critical current magnitude causing insulation failure. It is on the value of the tower impulse-footing resistance. This
parameter is a function of the lightning current magni-
Paper 6725C (P7, Pll), received 16th January 1989
tude and waveshape owing to ionisation effects, change
Prof. Savic is with the Faculty of Electrical Engineering, University of
of moisture content in the soil during the lightning dis-
Belgrade, Bulevar Revolucije 73, PO Box 816, 1101 Belgrade, Yugo- charge, and the presence of the propagation process in
slavia the case of the long buried conductors. For a simplified
222 IEE PROCEEDINGS, Vol. 136, Pt. C , No. 4, J U L Y 1989
lightning performance estimation in Reference 5 the (h) The numerical corona model is described in Refer-
application of a constant tower impulse-footing resist- ence 1. It is based on the empirical formula given in
ance equal to the low-frequency resistance is suggested. Reference 8 for the increase of the wave front duration
(9) There are two different insulation characteristic
models: for air insulation and for solid dielectrics. A line
insulation flashover voltage is computed by the constant current wave
area criterion [6] with the following mathematical for-
mulation :

A= 1% - uo] dt (2)

where uo is the reference voltage, V I t a g e

u0 = E,d (3)
E, is the mean electrical field along the air gap at 50%
flashover probability level, d is the air gap length, u(t) is
the transient voltage across the air gap, to is the time
instant when u(t) exceeds the reference voltage and t , is
the moment of flashover when the computed area A
becomes greater than A,, ,
The flashover criterion can be written in the following
form :
A > Acr (4)
Fig. 1 Equivalent circuit to explain procedure of current crest
The critical area A , can be calculated from the following computation
relation: d , = utg; d - utF
U = propag:tsn speed
A , = Cd (5) uF = line insulation flashover voltage
ug I transformer BIL
where C is the empirical constant deduced from experi-
mental data. The constants C and E, are computed to owing to the corona effect. The applied empirical formula
obtain the 50% flashover voltage from a standard labor- is
atory test on the completely equipped insulator string
with the standard 1.2/50ps lightning wave. The com-
puted constants from the test results described in Refer-
ence 7 are C = 677 kV ps/mm and E, = 5.067 kV/mm. In
this way all possible air insulation weak points (line or where d is the propagation distance (m). U is the propaga-
busbar insulators) are modelled. tion speed (300 m/& B is the empirical coefficient
It is supposed that the solid dielectric breakdown dependent on the conductor radius given in Fig. 2 (l/kV).
voltage in such high-voltage equipment as power trans-
formers, current or voltage transformers, high-voltage
cables or other equipment can be modelled by constant 10
voltage-time characteristics equal to the BIL. Any light-
k g overvoltage exceeding the BIL is considered an
hulation failure. If the method of limiting parameters is
applied, whenever a computed surge for a certain current
gradient at a inspected part of the equipment becomes
greater than the BIL, the transient process computation
is stopped for this current gradient and the current mag-
nitude sufficient to produce this voltage is computed as
1, = I(tB + t,) (6)
where t, is the time interval from the moment of
occurrence of the voltage surge at the observed part of
the substation equipment to the moment of insulation 10 20
breakdown. t , is the time interval from the moment of R,mm
the lightning strike (to the top of the tower or earth wire) Fig. 2 Dependence of coefficient of corona on conductor radius
to the moment of back-flashover on the tower in front of
the substation. I is the linearised wavefront current gra- U is the instantaneous value of the voltage (kV) and U,, is
dient. the corona inception voltage (kV).
In Fig. 1 the computation of the current magnitude
sufficient to cause insulation failure is explained. The time 2.2 Computationof risk of substation insulation
interval t, sufficient to cause back-flashover on the tower, failure due to back-flashover on incoming line
together with the time interval t, from the appearance of In the statistical estimation method of the substation
the voltage wave on the inspected part of the insulation lightning performance due to direct strikes to the earth
to the moment of reaching the BIL, gives the total linear- wire or tower and back-flashover, the place of the dis-
ised front time duration of the current wave, sufficient to charge is varied along the first few spans, as presented in
produce insulation failure at the inspected place. Fig. 3. Usually two spans are enough.
IEE PROCEEDINGS, Vol. 136, Pt. C , No. 4, JULY 1989 223
Instead of a continuous variation of the point of dis- flashovers, is
charge along the span only a few (usually 5 ) equidistant
points of discharges at every span are analysed. The N = 1jR (1 1)

2.3 Computation of risk of substation insulation


failure due to shielding failure on incoming line
In estimating the risk of occurrence of lightning overvol-
tages exceeding the substation equipment BIL due to the
shielding failures on the line, it is supposed that a direct
strike hits the substation entrance or overhead line cable
junction in the case of cable entrance.
The probability of strike penetration to the shielding
zone denoted Psh as a function of the lightning current
magnitude can be computed by means of the electro-
geometrical method described in References 10 and 11.
A direct strike to the phase conductor causes an over-
voltage wave propagating to the substation. This over-
voltage can be computed by means of the travelling-wave
technique. The probability of exceeding the BIL of the
Fig. 3 Variation of place of discharge
substation equipment for a strike at the substation
entrance can be calculated in the following manner:
mean value of the probability of occurrence of overvol-
tages exceeding the BIL of the equipment in the sub-
station due to a strike somewhere on the analysed span,
denoted P,, can be computed by means of the trape-
P1 =
b f(Z, Z')Psh(Z)dZ dZ'

f(Z, Z') is the joint frequency distribution of the lightning


(12)

zoidal rule in the following form :


current magnitudes and wave front gradients. PJZ) is the
probability of the shielding failure as a function of the
current magnitude. D is the failure zone, limited by the
minimum lightning current magnitudes and rates of rise
+ +
+ ... P,,- 1 0.5 K , Pf,J (8) causing the insulation failure. The limiting set of param-
PZi(i = 1, n) is the probability of occurrence of the light- eters forming the failure zone is illustrated in Fig. 4.
ning over-voltages exceeding the BIL of the equipment in
the substation if the strike hit the top of tower 1 or n in
Fig. 3, causing back-flashover. Pi(i = 2, 3, ..., n - 1) is
the probability of occurrence of the over-voltage exceed-
ing the BIL in the substation if the strike hit certain
points (2, 3, ..., n - 1) on the span, causing back-
flashover on the nearest tower. K , is the coefficient of cor-
rection of the discharge probability to the top of the
tower, which is presumed to be 1.3. In this way it is sup-
posed that the probability of discharge to the top of the
tower is 30% greater than that to the span.
The risk of occurrence of lightning overvoltages
exceeding the BIL of the equipment in the substation can I I I
be computed in the following way: I I I I 1
(9) 1; 1; 1; 1; 1;
I , kAlps
P,, is the mean probability of occurrence of overvoltages Fig. 4 Method of limiting parameters
exceeding the BIL of some equipment in the substation if
the discharge hit thejth span. d j is the length of thejth
span. Sa, is the attractive area of the overhead line per
unit length. N , is the annual lightning density of the dis- The failure zone D can be expressed as a sum of ele-
charges to the ground per km2. m is the number of mentary zones AD,, A D 2 , ...,AD,,, presented in Fig. 4.
observed spans. n

The attractive area of the overhead line is a band on D = CAD,


i= 1
both sides of the line in which the most of the lightning
discharges occur to the line and the minority to the The curve of lightning limiting parameters can be defined
ground. It can be estimated for a line of unit length as by sets of limiting values (Zl,r1),( I , , I;), ..., (Z,,,Z3,or
corresponding overvoltage wave parameters on the phase
Sa, = 6 he, (km) (10) conductor at the struck point defined by
where he, is the effective height of the earth wire along
U i = Z, lJ4 and Ut = Z, 174 (13)
the span (m).
The mean number of years without lightning overvol- where 2, is the surge impedance of the phase conductor,
tages exceeding the BIL of the substation equipment, due Ui is the overvoltage wave magnitude and U;is the over-
to strikes to the towers or earth wire causing back- voltage wave gradient.
224 IEE PROCEEDINGS, Vol. 136, Pt. C , No. 4, JULY 1989
In the case of a strike at a certain distance from the substation if shielding failure occurred at points j and
substation entrance, the incoming wave gradient is j+ 1 in front of the substation.
reduced. The distance of this point from the substation The total risk R of substation insulation failure due to
entrance can be determined in such a way as to reduce shielding failure on the line in front of the substation can

Fig. 5 Equivalent circuit

the overvoltage wave gradient from the given value U ; at be computed as the sum of the risks of failure due to
the point to the value UJ at the substation entrance, both strikes to certain parts of line Adj ( j= 1,2, . . . , n).
belonging to the sets of limiting values of the curve of
limiting parameters computed for the case of discharge at R=CRj
the substation entrance. The wave front is prolonged This method is pessimistic because wave distortion due
owing to corona distortion for the time increment A t j . to other effects is neglected.
Atj = ( U J U ; - U l f U ; ) (14)
3 Computation of lightning performances of
The value T = U , / U ; is a front time of the voltage wave 110 kV substation with cable entrance
at the point, and T + A t j = U j / U Jis a voltage wave front
time at the substation entrance after propagation along 3.1 System data
distance d j . It is supposed that the wave front remains The equivalent circuit of the analysed 110 kV system is
linear after corona distortion. presented in Fig. 5. The 110 kV cable is analysed in 5
The distance d j necessary to reduce voltage wave gra- uniformly distributed points to get the maximum voltage
dient from U', to U J can be calculated from eqn. 7 for the distribution along the cable due to the lightning strike.
front of wave time increase Atj owing to the corona. All system parameters taken from the substation
layout or estimated are given in Table 1. A lightning
strike to the earth wire on the first and second spans, and
to the phase conductor in front of the substation, owing
to shielding failure is analysed. In Fig. 5 and Table 1
The probability of occurrence of lightning parameters system data for a strike to the second span in front of the
causing substation insulationfailure for the case of a cable are presented. In the case of the element modelled
point struck at distance d j from the substation entrance, as an equivalent line, the surge impedance and the line
denoted P i , can be computed by the application of eqn. length are also presented in Table 1.
12 in the areas A D j , ADj+ 1, . .., AD,,. The system rated voltage is 110 kV. The BIL of all
Eqn. 12 is applied only to lightning current rate rise equipment is 550 kV. Classical Sic surge arresters of the
greater than ZJ or corresponding lightning overvoltage type HMM 108, rated voltage 108 kV, [14] are modelled
wave gradients U J at the point. Discharge with the with the voltageftime characteristic of the spark gap
lightning current gradient less than ZJ , causing corre- given in Table 2.
sponding overvoltage wave gradient to be less than U J ,is The current/voltage characteristics of the surge
reduced, owing to propagation at the station entrance, to arrester nonlinear resistor is given in Table 3. The char-
voltage wave gradient less than U ; . This voltage gradient acteristics are linearly extrapolated for smaller current
is - not enough to cause insulation failure in the sub- magnitudes.
station.
The risk of insulation failure due to a lightning strike 3.2 Lightning parameters
to the line length Adj = ( d j + - di) is The joint log-normal lightning current magnitude and
front of wave gradiefit distribution suggested in Reference
R j = 0.5(Pj+ + Pj)AdjSa,N , (16) 9 is in the following form :
1
where Pi and are the probabilities of occurrence of
overvoltages exceeding the BIL of some equipment in the
F(x, Y ) =
2 d G G exp (- +x2 2(1y 2--p2)
2pxy) d x

IEE PROCEEDINGS, Vol. 136, Pt. C , No. 4, JULY 1989 225


Table 1 : Substation layout Parameters cl,,1, = current gradient logarithmic
Branch Type of element Resistance, Length, standard deviation
R m p = correlation coefficient of I and I'
1 earth wire 400 W
2 tower height to 156 30.6 1000
cross arm
3 tower grounding 10
resistance 800
4 earth wire support 156 2
5 cross arm 156 2
6 air gap after 200 2
back-flash 600
7 phase conductor 370 03 >
Y

8 part of earth wire 370 0-1 34 3-


9 lightning channel 300 CO
10 part of earth wire 370 134-0 4 00
11 tower height to 156 30.6
cross arm
12

13
14
15
tower grounding
resistance
earth wire support
cross arm
air gap after
156
156
200
10

2
2
2
2ooii
0~
5 10 15
back-flash
16 phase conductor 370 134 t,P5
17 earth wire 400 30 Fig. 6 Transient voltage at place of cross arm
18 portal 125 16.6
19

20
tower grounding
resistance
horizontal part of
10

140 2
1000 -
portal
21 air gap after
back-flash
200 2
800 -
22 phase conductor 370 30
23 connection conductor 370 20
24 busbars 370 15.5 600 -
25 connection conductor 370 11 >
Y

26 lead to thesurge 370 4 3


-
arrester
27 conductor to cable 370 4 400 -
termination
28,29,30,32 parts of cable 33.8 4x65
32
33

34
phase conductor
lead to the surge
arrester
connection to the
370
370

370
21

10
4
2mt I
power transformer 0 a ' ' ' ' a 5 ' * ' ' ' ' ' ' ' * ' J

5 10 15
Capacitance, t, P S
nF Fig. 7 Transient voltage on phase conductor at place of backflash
35 power transformer 5
surge capacitance
36 voltage transformer 3 The presumed lightning strike parameters corresponding
surge capacitance to Berger's measuring results according to Reference 9
are
Table 2: Voltageltime characteristic of surge arrester
I = 30 k~
Front of wave spark-over t , = 0 . 3 2 4 ~ U,
~ = 292 kV
voltage at instant r" = 14 k A / p
Minimum 100% sparkover t , = 1.2 ps U, = 248 kV
voltage at instant Oln 1 = 0.68
Minimum switching spark-over t , = 250 ps U, = 259 kV
g l n r * = 0.55
voltage at instant
p = 0.38
Table 3: Current/voltage surge arrester characteristic
Current, kA 5 10 20
3.3 Classical approach to overvoltage computation
Residual voltage, kV 227 248 281 The classical approach to overvoltage computation of
choosing the representative current magnitude and mean
waveform gradient is used to investigate the voltage
where distribution along the cable, and to investigate the
x = In (IIQIOln r
,,
y = In (I'/I')/oln
voltage waveforms in different points of the equivalent
circuit.
[ = random current amplitude In the classical methodology of overvoltage computa-
Z = mean current amplitude tion the critical lightning parameters with the probability
r_' = random current gradient of exceeding the chosen values by 2% are determined.
I' = mean current gradient The computed critical values are
olnI = current magnitude logarithmic
standard deviation I , = 121 kA and r:, = 43.2 kA/p
226 IEE PROCEEDINGS, Vol. 136, Pt. C , No. 4, J U L Y 1989
Lightning channel surge impedance is presumed to be (a) A surge arrester is placed in front of the junction of
300 n. the cable and the overhead line.
It is supposed that the lightning strike happened at the (b) A surge arrester is placed at the other end of the
middle of the second span to the earth wire. Three differ- cable.
600 r
variant a

variant b
480

variant c
360

Fig. 8
t . p5
Transient voltage at different points on cable
2401
120

01
0
t
75 150 225
1
300
700 r d , rn
Fig. 10 Peak voltage distribution along cable for various overvoltage
protection variants

t . lJ5
Fig. 9 Transformer terminal overvoltage
Table 4: Overvoltages at different points
Nodeno. 11 24 25 26 27 28 31
Variant
(a1 976 425 489 550 557 528 659
(b1 976 595 579 493 485 449 417
(C) 975 333 339 354 359 352 404 0 50 100 150 200
struck point distance, rn
ent overvoltage protection variants are analysed. In the Fig. 11 Expected number of strikes causing overvoltages less than the
first variant the surge arrester was connected only in power transformer BIL as a function of position of strike
front of the overhead line-cable junction. In Fig. 6 the
transient response of the tower computed at the cross (c) A surge arrester is placed on each end of the cable.
arm is presented. The computed overvoltages of the three protection
In Fig. 7 the transient voltage on the phase conductor variants analysed are presented in Table 4.
at the place of back-flashover is presented; the infinitely The peak voltage distributions along the cable are pre-
steep wavefront after backflash can be seen. There is an sented in Fig. 10 for overvoltage protection variants (a),
overvoltage on the cross arm exceeding the BIL after (b) and (c).
back-flashover, owing to the large current wave magni-
tude. 3.4 Estimation of risk of power transformer insulation
In Fig. 8 the transient overvoltages at different places failure
along the cable are presented. The surge front gradient is
decreased owing to the cable capacitance charging effect 3.4.1 Risk of power transformer insulation failure due
and wave distortion owing to the corona. The trans- to the back-flashover: In the statistical approach to the
former terminal voltage is presented in Fig. 9. risk of occurrence of overvoltages exceeding the power
Three analysed overvoltage protection variants were transformer BIL the annual lightning density N, = 4.5 (1/
investigated : year x km2) is taken according to the meteorological
IEE PROCEEDINGS, Vol. 136, Pt. C , No. 4, JULY 1989 221
data [l2]. The analysis is performed for the same three system elements and the equivalent circuit selection is
variants of overvoltage protection. especially emphasised.
The point of discharge to the earth wire is varied The results of lightning performance studies show that
along the first two spans. In Fig. 11 the expected number strikes to the earth wire or tower in the vicinity of the
of strikes causing one overvoltage exceeding the trans-
former BIL as a function of the position of the strike is
presented. It can be seen that the most dangerous point

r-
of strike is the first tower just in front of the cable termi-
nation. The expected number of strikes causing one over-
voltage exceeding the BIL increases for strikes to the
earth wire in the middle of the span and decreases again
-
for strikes to the top of the second tower. Strikes to the
earth wire on the second span produce overvoltages
which are sufficiently damped owing to propagation that
dangerous overvoltages are extremely seldom.
Discharges to the top of the third tower or even m
further away cannot cause dangerous overvoltages at all. w
N
The total risk of occurrence of overvoltages exceeding
the power transformer BIL is presented in Table 5. The

Table 5: Risk of power transformer insulation failure


Variant Risk, l/year N = l/Risk, year

(a) 6.01 x 1664


(6) 5.09 x lo-' 196 7
(c) 1.88 x 0.532 x lo6 ////// / /,
Fig. 12 Line geometry with effective dimensions for whole span
expected number of years without transformer insulation
failure as a reciprocal value of the risk of insulation 0.081
failure is also presented.
In Reference 13 an equipment failure rate of N = 800
years or N = 400 years, depending on the equipment
importance, is suggested. According to this criterion,
0 06-
variant (a) with only one set of surge arresters in front of
the cable and overhead line junction can be recommend-
ed.
3.4.2 Risk of power transformer insulation failure due Go.o4[
to incoming overhead line shielding failures: An inves-
tigation of the risk of exceeding the power transformer
BIL due to shielding failures on the line and substation
was performed. The analysed line configuration with the
effective heights of the earth wire and phase conductor is 0.02-
presented in Fig. 12.
The probability of shielding failures on the line is
analysed by means of the electrogeometrical method
described in References 5, 10 and 11.
The probability of occurrence of lightning current """"""" , ' I " ' """"""""""'
6 7 8 9 10 11
magnitude penetrating the shielding zone and hitting the I, kA
phase conductor in front of the cable and overhead line
Fig. 13 Probability of penetration of lightning currents of certain
junction is presented in Fig. 13. It can be seen that the magnitude into shielding zone and hitting phase conductor
greatest lightning current magnitude which can cause
shielding failure is 11.1 kA. This current magnitude is not substation entrance or the overhead line and cable junc-
sufficient to cause dangerous overvoltage for transformer tion causing back-flashover are most dangerous for the
insulation; the minimum current magnitude which can transformer insulation in the analysed case of a 110 kV
produce overvoltage equal to the transformer BIL is system. Strikes on the third tower or further from the
24 kA. substation entrance are not dangerous for the substation
The probability of penetration of lightning into the insulation.
shielding zone of the substation is extremely small, due to The overvoltages produced by shielding failures on the
the effective shielding geometry with negative shielding line are not dangerous for the substation equipment.
angles, and it will not be presented here. Shielding failures in a substation with effective shielding
geometry, realised with negative shielding angles, are
4 Conclusion impossible.

In this paper the general methodology of the risk of the 5 Acknowledgment


lightning outage estimation is presented and illustrated
with the example of a 110 kV substation with cable I acknowledge the support of 'Energoprojekt, Depart-
entrance. The importance of the correct modelling of ment of thermal and nuclear plants', and in particular
228 I E E PROCEEDINGS, Vol. 136, Pt. C , No. 4, JULY 1989
Engineer M.Pekovil: for obtaining all the necessary data 6 THIONE, L.: The dielectric strength of large air insulation in
and the late Engineer B. Miletil: for study organisation. I RAGALLER, K. (Ed.):Surges in High Voltage Networks (Plenum
Press, New York and London, 1979),pp. 197-200
am also very grateful to the Community of Science of the 7 Laboratory testing of the insulator strings for unpoluted areas.
Republic of Serbia for the financial support of this study. Internal report No. 1986,Energoinvest, Sarajevo, 1978
8 DOLGINOV, A.: High voltage technique in electrical power
systems, Energy (Moskow), 1968,pp. 280-282
6 References 9 BROWN, G.: Joint frequency distributions of stroke current rates
of rise and crest magnitudes to transmission lines, 1EEE Trans.
1 BICKFORD, J., and SAVIC, M.: Some aspects of system modelling Power Appara. Syst., 1978,P a w , (l), pp. 53-58
for the estimation of lightning performance of high voltage sub- 10 WHITEHEAD, E.: Protection of transmission lines in GOLDE,
stations, 1EE Proc. C , Gener., Transm. Distrib., 1984, 131, (5), R.H. (Ed.): Lightning, Vol. 2: Lightning protection (Academic
pp. 204-209 Press, London, 1977),pp. 699-706.
2 AMETANI, A.: Modified travelling wave techniques to solve elec- 11 BERGER, K.:Lightning surges in RAGALLER, K. (Ed.): Surges
trical transients on lumped and distributed constant circuits, Proc. in high voltage networks (Plenum Press, New York and London,
lEE, 1973,120,(4),pp. 497-504 1979), pp. 4249
3 COOPER, J., and HILEMAN, A.: A probabilistic approach in esti- 12 PLAZINIC, S.: Metereological parameters for transmission lines
mating the BIL or 1200kV gas insulated stations. CIGRE Session design, Engineering-transmission of El. Energy, 1978, (22),pp. 103-
1982,Paper 33-02 115 (in Serbo-Croatian)
4 BAZUTKIN, V., LARIONOV, V., and PINTALJ, J.: High-voltage 13 Draft - Revision of the application guide for insulation coordi-
technique-Insulationand Overvoltages in Power Systems (Moskva, nation (IEC Publication 71-2 and 71-3), IEC/TC-w 1987,pp. 3 6
Energoatomizdat 1986),pp. 258-266 (in Russian) 35
5 IEEE working group: A simplified method for estimating lightning 14 Lightning Arrester type HMM, Mine1 Belgrade, Catalogue OP-504-
performance of transmission lines, IEEE Trans. Power Appara. 02-1/1980
S y ~ t . 1983,
, PAS-164,(4),pp. 919-927

1EE PROCEEDINGS, Vol. 136, Pt. C , No. 4, JULY 1989 229

You might also like