Professional Documents
Culture Documents
L x T x C x 500 x sg
Q =
H
Where:
Q = Condensate load in Lbs/hr
L = Liquid flow in GPM
T = Temperature rise in F
C = Specific heat of liquid in BTU/lb--F
500 = 60 min/hr x 8.33 lbs/gal
sg = Specific Gravity of liquid
H = Latent heat of Steam in BTU/lb
SAFETY FACTOR: 2
EXAMPLE:
20 x 80 x 1 x 500 x 1
Q =
953
Q= 839 lbs/hr