Optimizacin de sistemas de cogeneracin para


calefaccin y refrigeracin de distrito

Article January 2004

CITATIONS READS

7 144

3 authors, including:

Miguel A Lozano Jos Ramos-Saravia


University of Zaragoza University of Zaragoza
131 PUBLICATIONS 2,121 CITATIONS 21 PUBLICATIONS 158 CITATIONS

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

DISTRITES: Integration of thermal energy storage (TES) into district heating and cooling (DHC)
systems to increase the solar fraction and renewable energy sources (RES) View project

All content following this page was uploaded by Miguel A Lozano on 20 May 2014.

The user has requested enhancement of the downloaded file.


Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

Optimizacin de sistemas de cogeneracin para calefaccin y


refrigeracin de distrito

Miguel A. Lozano, Jos Ramos y Roberto Monzn

Grupo de Ingeniera Trmica y Sistemas Energticos (GITSE)


Dpto. de Ingeniera Mecnica Universidad de Zaragoza
Maria de Luna s/n 50018 Zaragoza (Espaa)
Tel: 976762039 E-mail: miguel.lozano@unizar.es

Resumen
En este trabajo se propone una metodologa sencilla para seleccionar las tecnologas que se
instalarn y decidir el nmero de equipos que constituirn la estructura de un sistema de
suministro energtico para el sector residencial-comercial. El sistema podr incluir adems
de calderas y enfriadoras mecnicas, mdulos de cogeneracin con motor a gas, mquinas
de refrigeracin por absorcin, acumuladores de calor y acumuladores de fro. El
procedimiento de diseo emplea modelos matemticos de optimizacin basados en
programacin lineal-entera. La funcin objetivo a minimizar es el coste total anual que
incluye los costes de amortizacin del capital invertido y los costes de operacin y
mantenimiento. La metodologa desarrollada se aplica al diseo de una instalacin de
trigeneracin para una urbanizacin residencial de 5000 viviendas ubicada en Zaragoza.

Palabras Clave: Cogeneracin, Trigeneracin, Optimizacin. Calefaccin de distrito.

1. Introduccin

Los edificios pertenecientes al sector residencial-comercial (urbanizaciones, centros


comerciales, hoteles, hospitales, etc.) demandan servicios energticos tales como
electricidad, agua caliente sanitaria (ACS), calefaccin y refrigeracin, que suponen una
fraccin importante del consumo energtico en los pases mediterrneos. Los sistemas
energticos integrados de cogeneracin y calefaccin-refrigeracin de distrito (plantas
de trigeneracin) podran ser una opcin energtica-econmica viable y sostenible para
el sector residencial-comercial. Los resultados de este trabajo as lo sugieren.

Entre los factores importantes que caracterizan el consumo de energa en los grandes
edificios y complejos urbanos se encuentran: i) la simultaneidad del consumo de
distintos servicios energticos: iluminacin, accionamiento de electrodomsticos, ACS,
calefaccin, refrigeracin, etc.; ii) variabilidad temporal de los consumos (horaria, diaria
y mensual); y iii) opcionalidad del tipo de facturacin elctrica.
Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

Los sistemas de calefaccin de distrito (incluyendo aquellos con cogeneracin) han


demostrado ser un mtodo eficiente, fiable y rentable de suministro energtico en los
pases del norte de Europa. En el diseo de las plantas de energa para complejos
urbanos y grandes edificios en el sur de Europa parece interesante el uso de sistemas de
trigeneracin (electricidad-calor-fro). El calor cogenerado que atiende necesidades de
calefaccin en los meses de invierno sirve para accionar mquinas de refrigeracin por
absorcin durante los meses de verano. Un sistema energtico integrado que emplee las
tecnologas de cogeneracin y absorcin puede inducir ahorros econmicos-energticos
del orden de 10-40%, respecto del uso de instalaciones energticas convencionales, para
la misma cantidad/calidad de suministro energtico.

La variacin de la demanda de calefaccin y refrigeracin a lo largo del ao implica que


la seleccin de la estructura ms adecuada de la planta de produccin de energa
(nmero de mdulos de cogeneracin a instalar, instalar o no mquinas de refrigeracin
por absorcin, acumuladores de calor, acumuladores de fro, etc.) slo pueda hacerse
teniendo en cuenta la operacin ptima anual, hora a hora, que se desarrollara para cada
una de las estructuras candidatas. El gran nmero de combinaciones a valorar da origen
a un problema complejo y difcil de resolver.

En este trabajo se presenta una metodologa sencilla para el diseo de sistemas de


trigeneracin con acumulacin trmica. La metodologa se basa en el anlisis
energtico/econmico anual de todas las configuraciones de planta que se corresponden
con todas las combinaciones posibles de todos los equipos candidatos. Para ello se han
adaptado tcnicas de programacin lineal-entera que ya han demostrado ser una
herramienta til en el proceso de optimizacin de la estructura de plantas simples de
cogeneracin y trigeneracin [1-2]. La funcin objetivo a minimizar es el coste total
anual que incluye los costes de amortizacin del capital invertido y los costes de
operacin y mantenimiento. La metodologa desarrollada se aplica al diseo ptimo de
un sistema energtico que habr de suministrar ACS, calefaccin y refrigeracin a una
urbanizacin residencial (aprox. 5000 viviendas) ubicada en Zaragoza.
Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

2. Macroestructura

La Figura 1 muestra la macroestructura de los sistemas de suministro energtico


analizados en este trabajo. Hablamos de macroestructura en el sentido de que la
estructura representada contiene diversas soluciones (estructuras) para la configuracin
del sistema. Precisamente, resolver la incgnita de que solucin (estructura) es ms
conveniente es la decisin primera y prioritaria del proceso de optimizacin.

Como puede apreciarse en la macroestructura aparecen 5 tipos de unidades de


produccin: 1) mdulos de cogeneracin (mc) formados por un motor alternativo de
combustin interna (MACI) y equipos de recuperacin de calor, 2) calderas (aux), 3)
enfriadoras con ciclo de compresin mecnica (mf) que producen fro a partir de
electricidad, 4) mquinas frigorficas de absorcin (abs) y 5) torres de refrigeracin (tr)
para evacuar los calores residuales al ambiente. Tambin aparecen sendos acumuladores
de calor (ACUc) y fro (ACUf).

Una instalacin convencional estar formada nicamente por unidades del tipo aux, mf
y tr. Los sistemas de cogeneracin tpicos contendrn adems unidades del tipo mc.
Hablamos de sistemas de trigeneracin al aadir unidades del tipo abs. Obsrvese que
otro sistema de suministro posible (no cogenerativo) contendra abs pero no mc. Los
acumuladores ACUc y ACUf pueden incluirse en cualquiera de los sistemas anteriores.

Qmfd Qmfd
Ev Wm Qabsd Qref
Ec Wmf tr
Qcd
Wmf Qod
mf

Faux Rmf DF
aux Qabsd
Rabs DESf
Qgd Qga Qaux Qabs CARf
abs
Qg Qca ACUf PERf
Wm Qc Qcat DQ + DACS
DESc
mc Qcd
Fm Qo Qoa CARc

Qod ACUc PERc

Figura 1. Estructura del sistema de trigeneracin con acumulacin trmica de calor y fro
Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

3. Modelo

Una versin simplificada del modelo de programacin lineal-entera desarrollado se


muestra en la Tabla 1.

La funcin objetivo, a minimizar, es el coste total anual Ctot necesario para atender la
demanda de servicios energticos (calefaccin DQ, agua caliente sanitaria DACS y fro
para climatizacin DF). Este coste tiene dos componentes: i) la amortizacin de la
inversin I necesaria para la compra e instalacin de los equipos y ii) los gastos
variables de operacin que incluyen la facturacin energtica (combustible y energa
elctrica) y el coste de operacin del sistema de evacuacin de calor. La frmula y
unidades de la funcin objetivo se muestran a continuacin

Ctot [/ao] = Cfijo [/ao] + Cvar [/ao] = fam [ao-1] j Ij [] + i ci [/kWh] Xi [kWh/ao]

donde fam es el factor de amortizacin anual, Ij la inversin realizada para la compra e


instalacin de los equipos de tecnologa j y ci el coste precio unitario de cada uno de
los flujos energticos Xi con repercusin econmica que el sistema intercambia con el
exterior (se excluyen los servicios energticos prestados).

Para cada periodo representativo de la operacin (da tipo d, hora h) se conocen de


antemano la demanda de servicios energticos, su duracin anual HPA(d,h) y los
precios de compra cEc(d,h) y venta cEv(d,h) de la energa elctrica.

Las variables que corresponden al nmero de equipos instalados de cada tecnologa


(NmcIns, NauxIns, NmfIns, NabsIns y NtrIns) se declaran enteras y con cota superior
determinada. En general dichas variables sern libres cuando se optimiza, pero tambin
pueden fijarse a voluntad. Por ejemplo, imponiendo NmcIns = 0 y NabsIns = 0,
encontraremos como solucin el sistema convencional ptimo constituido slo por
calderas, enfriadoras mecnicas y torres de refrigeracin. La capacidad instalada de los
acumuladores de agua caliente ACUcIns y agua fra ACUfIns completan las variables de
diseo relativas a los equipos. Estas variables corresponden a las decisiones ms
importantes adoptadas por el programa de optimizacin.

La Tabla 2 muestra los parmetros tcnicos y econmicos ms relevantes del modelo de


optimizacin.
Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

Tabla 1. Modelo de optimizacin (simplificado)

Minimizar Ctot = Cfijo + Cvar

Cfijo = fam ( NmcIns Imc + NauxIns Iaux + Cvar = HPA(d,h) [ cF (Fm(d,h) + Faux(d,h)) +
NmfIns Imf + NabsIns Iabs + cQref Qref(d,h) +
NtrIns Itr + iuACUc ACUcIns + cEc(d,h) Ec(d,h)
iuACUf ACUfIns ) cEv(d,h) Ev(d,h) ]

Sujeto a
NmcIns NmcMax NauxIns NauxMax NmfIns NmfMax
NabsIns NabsMax NtrIns NtrMax
ACUcIns ACUcMax ACUfIns ACUfMax

Para cada periodo horario (d,h)


Motor Wm(d,h) NmcIns WmNom Fm(d,h) = RFW Wm(d,h)
Qg(d,h) = RQG Wm(d,h) Qc(d,h) = RQC Wm(d,h)
Qo(d,h) = RQO Wm(d,h)
Caldera Qaux(d,h) NauxIns QauxNom Faux(d,h) = Qaux(d,h)/RQF
Enfriadora Rmf(d,h) NmfIns RmfNom Wmf(d,h) = Rmf(d,h)/COPmf
Absorcin Rabs(d,h) NabsIns RabsNom Qabs(d,h) = Rabs(d,h)/COPabs
Torre Qref(d,h) NtrIns QrefNom
Balances Qg(d,h) = Qgd(d,h) + Qga(d,h) Qc(d,h) = Qcd(d,h) + Qca(d,h)
Qo(d,h) = Qod(d,h) + Qoa(d,h) Qmfd(d,h) = Wmf(d,h) + Rmf(d,h)
Qabsd(d,h) = Qabs(d,h) + Rabs(d,h)
Qga(d,h) + Qca(d,h) + Qaux(d,h) = Qabs(d,h) + Qcat(d,h)
Qcat(d,h) + Qoa(d,h) + DESc(d,h) = CARc(d,h) + DQ(d,h) + DACS(d,h)
Rmf(d,h) + Rabs(d,h) + DESf(d,h) = CARf(d,h) + DF(d,h)
Qcd(d,h) + Qod(d,h) + Qmfd(d,h) + Qabsd(d,h) = Qref(d,h)
Ec(d,h) + Wm(d,h) = Ev(d,h) + Wmf(d,h)
Qcog(d,h) = Qga(d,h) + Qca(d,h) + Qoa(d,h)
Acumulacin ACUc(d,h) ACUc(d,h-1) = (CARc(d,h) DESc(d,h) PERc(d,h)) NHD(d,h)
ACUc(d,h) ACUcIns PERc(d,h)) = FPC ACUc(d,h-1)
ACUf(d,h) ACUf(d,h-1) = (CARf(d,h) DESf(d,h) PERf(d,h)) NHD(d,h)
ACUf(d,h) ACUfIns PERf(d,h)) = FPF ACUf(d,h-1)

Condiciones de operacin
HPA(d,h) Wm(d,h) 0,55 HPA(d,h) (Fm(d,h) Qcog(d,h)/0,9) Rendimiento elctrico equivalente
Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

Tabla 2. Datos tcnicos y econmicos

Precios y costes de los flujos energticos (/kWh)


Gas natural cF = 0,014175 /kWh Evacuacin calor cQref = 0,0003 /kWh
cEc = 0,03721 (v)
Compra electricidad Venta electricidad cEv = 0,05766 (n)
= 0,06527 (ll)
(/kWh) (/kWh) = 0,06054 (d)
= 0,11097 (p)
Mdulos de cogeneracin Calderas
Potencia nominal WmNom = 2928 kW Potencia nominal QauxNom = 4070 kW
Combustible/Trabajo RFW = 2,390 Rendimiento RQC = 0,905
Calor gases/Trabajo RQG = 0,567 Inversin Iaux = 162,8 k
Calor camisas/Trabajo RQC = 0,376 Torres de refrigeracin
Calor aceite/Trabajo RQO = 0,111 Potencia nominal QrefNom = 8000 kW
Inversin Imc = 2342,4 k Inversin Itr = 144,0 k
Mquinas de refrigeracin por absorcin Mquinas de refrigeracin mecnica
Potencia nominal RabsNom = 2112 kW Potencia nominal RmfNom = 4220 kW
Coeficiente de operacin COPabs = 0,70 Coeficiente de operacin COPmf = 4,02
Inversin Iabs = 264,0 k Inversin Imf = 422,0 k
Acumulador de calor Acumulador de fro
Coste unitario iuACUc = 26 /kWh Coste unitario iuACUf = 48 /kWh
Factor de perdidas FPC = 0,01 kW/kWh Factor de perdidas FPF = 0,01 kW/kWh

Las condiciones de operacin en cada periodo se establecen mediante restricciones de


igualdad y desigualdad que expresan limites del desempeo de los equipos y el
cumplimiento de los principios termodinmicos (balances de energa).

Supuestas decididas las variables estructurales, el funcionamiento ptimo de cada uno


de los periodos horarios en que se desagrega la operacin anual podra resolverse de
modo independiente si no fuera por: i) las condiciones que afectan al conjunto de la
operacin anual como las de rendimiento elctrico equivalente, autoconsumo elctrico,
etc. y ii) la existencia de acumuladores que liga la operacin de los periodos horarios
sucesivos de un da tipo a travs del nivel de calor/fro almacenado (debe imponerse
adems que al final del da dicho nivel sea igual que al principio).

Las tcnicas de optimizacin de programacin lineal-entera [3] permiten resolver el


problema de combinatoria de encontrar la estructura de planta ms adecuada
comparando implcitamente la operacin anual ptima de todas las estructuras posibles
y garantizando que la solucin encontrada es un ptimo global. Para la formulacin del
modelo y su resolucin se utiliz la aplicacin LINGO [4].
Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

4. Aplicacin

En la Tabla 3 se muestran los resultados obtenidos para el diseo ptimo bajo diferentes
condiciones que pasamos a explicar.

El diseo 0 corresponde a la planta convencional constituida por calderas para producir


calor, enfriadoras mecnicas para producir fro y torres de refrigeracin para evacuar el
calor excedente. Se ha comprobado que la acumulacin de calor no implica ventajas
econmicas en plantas de este tipo. Tanto la incorporacin de mquinas de refrigeracin
por absorcin (diseo 1) como la de acumulacin de fro (diseo 2), que en el ptimo
resultan excluyentes entre s, suponen ahorros poco relevantes.

Grosso modo la cogeneracin (sin refrigeracin por absorcin ni acumulacin, diseo 3)


reduce los costes anuales de suministro energtico a menos de la mitad. Resulta por
tanto muy interesante econmicamente. El mayor inconveniente es que la inversin a
realizar se triplica. La incorporacin de acumuladores de calor (diseo 4) supone
todava una mayor inversin pero tambin un reduccin significativa del coste anual.

Tabla 3. Diseos ptimos para diferentes configuraciones (fam = 0,15 ao-1)

Capacidad
Numero de equipos instalados F E I Cvar Ctot
(kWh)

mc aux mf abs tr ACUc ACUf MWh/ao k k/ao

0 - 5 6 - 4 - - 32103 2421 3920 632 1220

1 - 5 5 1 4 - - 33003 2279 3764 629 1194

2 - 5 3 0 4 - 23090 32103 2471 3473 607 1128

3 3 3 6 - 4 - - 117823 -44644 10627 -1002 592

4 3 1 6 - 4 69813 - 158403 -63627 12113 -1521 296

5 3 3 4 - 3 - 10174 117823 -44621 10127 -1007 512

6 3 1 4 - 3 69813 10174 158387 -63600 11613 -1527 215

7 3 3 4 3 5 - - 156360 -62210 10713 -1469 138

8 3 1 4 3 5 48310 - 185522 -75973 11647 -1849 -102

9 3 3 1 3 3 - 31541 177709 -71723 10673 -1715 -114

10 3 1 2 3 3 26425 19043 186924 -76396 10860 -1855 -226

11 1 3 3 0 2 11997 23092 78598 -22968 5807 -236 635


Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

La incorporacin a la estructura productiva de mquinas de absorcin da lugar a plantas


de trigeneracin que resultan an ms interesantes. En el caso de instalaciones sin
acumulacin trmica (diseo 7) el coste anual equivale al diezmo del de una instalacin
convencional. En este caso, tanto la acumulacin de calor como la de fro resultan
econmicamente atractivas como puede verse en los diseos 8 y 9. La combinacin de
ambas es todava mejor (diseo 10). En resumen, la incorporacin de enfriadoras de
absorcin es muy adecuada en el caso de demanda y precios que aqu planteamos y
fomenta la utilidad de la acumulacin de fro.

Todos los diseos 3 a 10 cumplen la condicin de rendimiento elctrico equivalente


mayor que 55%, pero no cumplen la condicin de que la propia instalacin diseada
para el suministro energtico de los edificios tenga un autoconsumo elctrico del 10%.
Este queda limitado por el trabajo requerido por las enfriadoras mecnicas. Por ello el
diseo ptimo 11, que se obtiene cumpliendo la condicin de autoconsumo, slo instala
1 mdulo de cogeneracin frente a los 3 de los diseos anteriores y no instala mquinas
de refrigeracin por absorcin pues su operacin limitara el consumo de trabajo.
Podemos afirmar que la condicin de autoconsumo elctrico perjudica seriamente el
inters pblico. Queda abierta la cuestin de justificar como autoconsumo el consumo
de energa elctrica de las viviendas y la necesidad de normas que permitan superar
dicha barrera al ahorro de energa primaria y al bienestar econmico nacional.

Tabla 4. Operacin anual del sistema ptimo de cogeneracin (Configuracin 10)


DC Cog Aux DF Abs Mec F Qcog Ev
Mes
(MWh) (%) (%) (MWh) (%) (%) (MWh) (MWh) (MWh)
Enero 6412 85 15 0 - - 16985 5508 6535
Febrero 4583 100 0 0 - - 14108 4685 5903
Marzo 3334 100 0 0 - - 15619 3525 6535
Abril 1390 100 0 0 - - 15116 1581 6324
Mayo 404 100 0 0 - - 15619 601 6535
Junio 334 100 0 1401 100 0 15116 2695 6324
Julio 203 100 0 4089 90 10 15619 4114 6144
Agosto 113 100 0 3041 95 5 15619 3861 6376
Septiembre 283 100 0 1201 100 0 15116 2365 6324
Octubre 935 100 0 0 - - 15619 1131 6535
Noviembre 3854 100 0 0 - - 15116 4033 6324
Diciembre 7208 75 25 0 - - 17572 5501 6535
AO 29054 91 9 9732 94 6 186924 39600 76396
Anales de Ingeniera Mecnica
Vol. 15, No. 2, pp. 1385-1393 (2004)

El diseo 10, que incorpora refrigeracin por absorcin y acumulacin trmica tanto de
calor como de fro, corresponde al ptimo global de la funcin objetivo. Un anlisis de
sensibilidad con relacin a los parmetros econmicos demuestra que su configuracin
(tecnologas instaladas y nmero de equipos) se mantiene estable para amplios rangos
del factor de amortizacin anual y de precios de combustible y energa elctrica. Esto
indica que la decisin de invertir en ella tiene una elevada probabilidad de resultar
acertada en el futuro salvo para variaciones extremas del entorno econmico.

En la Tabla 4 se describe mes por mes la operacin anual correspondiente al diseo


ptimo. Lo ms destacable es que los 3 motores instalados pueden estar funcionando a
plena capacidad a lo largo de todo el ao cumpliendo la condicin de rendimiento
elctrico equivalente. Esto es posible gracias a que el trabajo de las mquinas de
absorcin y los acumuladores de calor y fro permite un aprovechamiento ms completo
del calor producido por los motores. Tambin es notable el hecho de que la caldera y las
dos enfriadoras mecnicas instaladas se limitan a jugar el papel auxiliar de cubrir las
cargas punta de calor en invierno y de fro en verano, respectivamente.

cuando se pone a prueba la capacidad instalada de los equipos.

5. Referencias

1. M.A. Lozano, Diseo ptimo de sistemas simples de cogeneracin, Informacin


Tecnolgica, Vol. 12, No. 4, pp. 53-58 (2001).
2. M.A. Lozano et al, Optimizacin del diseo de sistemas de trigeneracin, Revista
Iberoamericana de Ingeniera Mecnica, Aceptado para publicacin (2004).
3. G. Nemhauser, L. Wosley, Integer and Combinatorial Optimization, Wiley (1999).
4. LINGO: The modeling language and optimizer. LINDO Systems (www.lindo.com).

6. Agradecimientos

Este trabajo ha sido financiado por el Plan Nacional de I+D+I 2000-2003

Proyecto DPI 2003-00603