You are on page 1of 12

DISEO DE VIGAS DE UN TRAMO

SIMPLEMENTE APOYADA
METODO DE LOS COEFICIENTES
hernan_p@msn.com
PROYECTO : FACHADA - CASA HABITACION VIGA ESTRUCT N : V - 102
PROPIETARIO : SRA DE TAVARA Ubic. EJE : 1 - 1
UBICACIN : SULLANA - PIURA FECHA : Dec-2017
ING CALCULIST : Ing Civil PEA VINCES HERNAN C.I.P : 118028

5.50
4.60

4.60
t t
A/T 3.20

EJE 1 b VIGA EN ANALISIS b 1 EJE


1.80

1.80

L=
5.50

Mu(-) = 0.00

MU(+) = WL/8

c=0.0003 0.85f 'c

a
c Cc a=c
h d centroide eje neutro

e t=Asfs t = Asfs d= a/2


b s
1.- DATOS DE ENTRADA PARA EL DISEO

CARGAS :
- Resistencia del Concreto(f 'c) = 210 Kg/cm - Peso de Tabiqueria = 0.12 t/m
- Fluencia del Acero (fy) = 4,200 Kg/cm - Peso de Piso/Termd = 0.10 t/m
- t = 0.30 m - Peso de cieloraso = 0.05 t/m
Dimensionamiento de la columna
b = 0.30 m - Peso Losa/aligerada = 0.30 t/m
- Espesor de la losa Aligerada = 0.20 m - Peso de Viga = 2.40 t/m
- Recubrimiento de la Viga = 2.50 cm - Sobre Carga = 0.25 t/m

- TIPO DE ESTRUCTURA A EDIFICAR = 5 (De acuerdo a la Norma E= 020)

2.- PREDIMENSIONAMIENTO DE LA VIGA EN ANALISIS

L
Altura de la Viga h = L Luz del tramo mayor de la viga en analisis
Tipo de Est.

5.50
h = h = 0.46 Tomamos h = 0.50 m
12.00

h
- b = ; bmm = 0.25 b 0.25 m
2

0.50
b = = 0.25 m > 0.25 m OK CUMPLE
2

b = 0.25 m Tomamos b = 0.30 m


###
5/8
d = h - r - /2 - [] =
5/8" 5/8 Asumido
[] = 3/8 "
0.31 ###
d = 50.00 - 2.50 - - 0.71 = 47.00 cm
2 ### ###
### ###
d = 47.00 cm ### ###
### ###
POR LO TANTO LA VIGA EN ANALISIS ES DE 30 x 50 cm
b h
3.- METRADO DE CARGAS

a.- Carga Muerta (WD)


- Peso de Tabiqueria = 0.12 t/m x 3.20 m = 0.38 t/m
- Peso de Piso/Termd = 0.10 t/m x 3.20 m = 0.32 t/m
- Peso de cieloraso = 0.05 t/m x 3.20 m = 0.16 t/m
- Peso Losa/aligerada (e= 0.20 ) = 0.30 t/m x 3.20 m = 0.96 t/m
- Peso de Viga = 2.4 t/m x 0.30 x 0.50 = 0.36 t/m
WD 2.18 t/m

b.- Carga Viva (WL) 5


- Sobre Carga = 0.25 t/m x 3.20 m = 0.80 t/m
WD 0.80 t/m

Wu = 1.4 2.18 + 1.7 0.80 = 4.42 t/m

Wu = 4.42 t/m

4.- CALCULO DEL MOMENTO ULTIMO (Mu)

Wu x L
Mu =
8
4.42 x 30.25
Mu = = 16.70
8

Mu = 16.70 t/m

5.- CALCULO DEL Ku


5
Mu 16.70 x 10
Ku = = Ku = = 25.21
b x d 30 2,209

f'c = 210 Kg/cm


Para = fy = 4,200 Kg/cm = 0.00730
Ku = 25.21

6.- CALCULO DEL AREA DEL ACERO (As)

As = 0.0073 30 47 = 10.29 cm

As = 10.29 cm

0.70 f'c b d
Acero Mnimo en Vigas =
fy

0.70 210 30 47
Acero Mnimo en Vigas = = 3.41 cm
4,200

Usar : 5/8
As + = 10.29 6 de3 5/8
5/8" = 11.88 cm
### OK CUMPLE
Se tolera + - 0.50 cm
Verificacin de la Cuantia :
As 11.88
=
b d
=
30 47
= 0.0084

14 14
Cuantia Minima :
mn =
fy
=
4,200
= 0.0033

0.80 f 'c
mn =
fy
= 0.0028

f 'c 6000
Cuantia Blanceada : b = 1 0.85
fy 6000 + fy
= 0.0213
Cuantia Maxima : max = 0.75 b = 0.0159

Entonces :
OK
0.0084 > min 0.0033
CUMPLE

OK
0.0084 < max 0.0159
CUMPLE

VIGA SUB-
0.0084 < b 0.0213
REFORSADA(Falla Ductil)

OK CUMPLE
Verificacin de la Base de la Viga : b 0.25

b mn = 0.25 < 0.30 base de Viga OK CUMPLE

Verificacin de la separacin de la cantidad de barras: b= 30 cm

S 2.5 cm
b - (2r) - N de Barras x
S =
N de Barras - 1
30 - 5 - 6 x 1.59
S = = 6.03 > 2.5 OK CUMPLE
6 - 1

7.- CALCULO DEL MOMENTO RESISTENTE : (Mor)

Mo r = Mu

Mo r = Ku b d = Mo r = 25.21 x 30 x 2,209 = 16.70

Mo r = 16.70 = Mu 16.70 CONFORME

8.- CALCULO DEL MOMENTO NOMINAL : (Mor)

a a = 11.88 4.20
Mn = As fy ( d - ) 9.32
2 0.85 0.21 30

0.093
Mn = 11.88 x 4.20 x ( 0.470 - ) 21.13
2

Mn = 21.13 t-m > Mo r 16.70 OK CUMPLE


:
:
:
:
Tipo de Est. S/C
DEPOSITOS 1 1.00
COLEGIOS 2 0.75
GARAGE 3 0.50 DEPOSITOS 1 1.00 ######
OFICINAS 4 0.30 COLEGIOS 2 0.75 ######
VIVIENDA 5 0.25 GARAGE 3 0.50 ######
OFICINAS 4 0.30 ######
0.25 VIVIENDAS 5 0.25 ######

Tipo de Est. L/
DEPOSITOS 8.00
ESCUELAS 9.00
GARAJE 10.00
OFICINAS 11.00
VIVIENDA 12.00
<
>
=
>
<
2
1/2" 1###
5/8" 2###
1/2 3/4" 3###
1/4 1"### 4 1

0
3/8" 1 3/8
1/2" 2 1/2
5/8" 3 5/8
3/4" 4 3/4
1" 5 1

1
0.85

0.72250
0.0500
0.5882
<
>

<
>

<
>

30.16
5
CALCULO DE LOS ESTRIBOS

Vmax

Vmax

So Ld/4,8db,30 cm Sd/2 60 cm So Ld/4,8db,30 cm

5 cm So/2 5 cm So/2

2d 2d

Zona de confinamiento Zona de confinamiento

Espaciamiento del Refuerzo transversal pata elementos


Sismoresistentes en flexin

DONDE:
d = Peralte efectivo de la Viga en analisis = 0.50 cm
So = Separacin del estribo dentro de la zona de confmto = 10 cm
S = Separacin del estribo fuera de la zona de confmto = 25 cm
2d = Zona de confinamiento = 5 cm
DISEO DE LOS ESTRIBOS
- Primer Estribo:
So 10.2
S = = 5.075 cm
2 2
Separacion
S = 5cm = 5 cm

0.1
Separacion = 0.05 m Asumido 0.05 m

- Estribos dentro de la Zona de Confinamiento:


d 0.50
S 4
=
4
= 0.13 cm
Separacion
S 8 db = 8 1.27 = 10.16 cm
S 30 cm = 30.00 cm
0.1
Separacion = 0.13 m Asumido 0.10 m
10.16
- Estribos fuera de la Zona de Confinamiento:

d 0.50
Separacion
S 2
=
2
= 0.25 cm

S 60 cm = 60.00 cm
0.3
Separacion = 0.25 m Asumido 0.25 m
- Zona de Confinamiento:
0.1
Zc = 2 d = 2 1 = 1 cm Asumido 0.05 m

N.T.P [] 3/8 " para 3/4 "


[] 1/2 " para 3/4 "

DISTRIBUCION DE LOS ESTRIBOS :


0.20 0

[] 3/8 " , 1 @ 0.05 , 5 @ 0.10 Rto ; @ 0.25 m (En c/extremo)


0.10
1
1
5.50

6 1

1 5/8 " 1 5/8 "


1.35 1 2 5/8 " 1.35

[] 3/8 " 1 @ 0.05 , 5 @ 0.10 Rto @ 0.25 c/e [] 3/8 " 1 @ 0.05 , 5 @ 0.10 Rto @ 0.25 c/e

Colocar 2 1/2" Confinamiento de Viga 0.20


0.50 ___________________________________________________________________________________________________________________________________

0.65 0.65
1
2 5/8 " 1 5/8 " 2 5/8 "
Colocar 2 1/2" Confinamiento de Viga
5.20

0.30 0.30
___________________________________________________________________________________________________________________________________
1 5/8 "
2 5/8 VIGA
6
[]
5/8 "
3/8 " 1 - 1
ESPECIFICACIONES TCNICAS

1 @ 0.05 Concreto f 'c = 210 kg/cm2


0.50 . 5 @ 0.10 Acero f 'c = 4,200 kg/cm2
Rto 0.25 c/e Recubrimiento = 2.50 cm
Espesor de la losa aligerada = 0.20 cm
Sobre carga NTP E020 = 250 Kg
1 5/8 "
2 5/8 "
0.35
Proyecto:
SECCION

1 1
HP FACHADA - CASA HABITACION

Fecha: Ing Resp:


Ingeniero Civil Dec-2017 Ing Civil PEA VINCES HERNAN