You are on page 1of 53

Overview of IEC 61850

RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

July, 2010
Maciej Goraj
maciejgoraj@rugge

dcom.com

1
RUGGEDCOM
Agenda
1. Evolution of Protection and
INDUSTRIAL STRENGTH NETWORKS"

Control Systems
2. Overview of IEC 61850
Standard
3. Key Benefits of IEC 61850

Copyright RuggedCom Inc 2


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Evolution of Protection and


Control Systems

3
RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Typical Substation Diagram


Sub Sub
Transmi
ssion
Transmi
ssion Information provided to
Line No. Line No. SCADA via
1 2
communication
m channels -
IED 1 IED 2
LN 1 LN 2

Automatically:
IED 3

.
TB 1

IED 13
BUS 1
- Metering
- Alarm Status
- Breaker Status
- Commands to Operate
Breakers
- Lockout Status
Information required by
Engineering or
IED 14
BUS 2
Maintenance -
Accessed by authorized
personnel on demand:
- Protection & Control
IED 6 IED 7 IED 8 IED 9 IED 10 IED 11
FDR 1 FDR 2 FDR 3 FDR 4 FDR 5 FDR 6

Feeder Breakers
Status
Total: At least 50 multi-core - Oscillography Files
- Sequence of Event
cables from the Reports
HV equipment to the Control
Copyright RuggedCom Inc - Access to view 4or
RUGGED
COM
Substation Network - Past
INDUSTRIAL STRENGTH NETWORKS"

Copyright RuggedCom Inc 5


Conventional Wiring in Electrical Substations
j

Copyright RuggedCom Inc 6


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Conventional Substation P&C System

Copyright RuggedCom Inc 7


RUGGED
COM
Conventional Substation Control Panel
INDUSTRIAL STRENGTH NETWORKS"

Copyright RuggedCom Inc 8


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Substation Network - Present

Copyright RuggedCom Inc 9


RUGGED
COM
Present Substation P&C System
INDUSTRIAL STRENGTH NETWORKS"

Still a lot of copper wiring !

Copyright RuggedCom Inc 10


RUGGED
COM
Substation Network - Future
INDUSTRIAL STRENGTH NETWORKS"

Copyright RuggedCom Inc 11


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

The Future - Digital Switchyard


All digital Ethernet
based
IEC 61850
Communications
in the Switchyard
Merging Units and IEDs at
direct proximity to
High Voltage equipment

Copyright RuggedCom Inc 12


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Moder C L Tema

irtcftrp
h& : Prcs5Lre.iPi rcup
T2E F2
A
TIE TL RO K-CiVT
f B?
i-iccc^d
l 'iai-hy'ijr!
TF-IrKSIJIH
r Mins iriifc-
ans fuimar
TRFR 2 A & ZB CtferarfiaiLiiH
Details
rtddmgtem Overview rransro'-mer
rV r/aster i nucrijifr
CB Caire v.\
L- T- '.g 'T
S KC
=r-,
i . i i I rar^Q'lier ftci enbal inp 1
D m TA Ai.-l5.Kws.
A

n Substation Automation HMI


I.V Restricted raitti r aur T-ip
cemifii overview
Stsiiijf-,1 Ea-"h Faut Gtsge

Di'let onul Dwriurrerr.


Cvjrcurrcnt ' rm
11kV Ssd Wirte kV I -V hfVA
I -,v MW
1 wr.fvAj- r HT 2G 30C RC v

lilv/busions h p
|Hu tupsnasin-T
imVCB General Trips gS III ri r-V SHriijHil

31 CvsirjjiTsnl: I ii" l lspii.:il.':i-i rdr Saiten Hr tve r ait

A
h/aat-fir T- p
-.VLijhgea L-up:ly
F3il
I ;A niv hv,3-i I.H1 i V 1,0 : rn-t* Alar
ms-
ansrmfe- uni H vel Aam
rr! T, ri. :: 1 Eartn Faufile A
Transformer Details 1KVTCS Su* ervlsn Alarm
barlTi Faut" rlp 9
MA FCLvLr :1 T2= FCdDf
RHSTT. Senses cEith FaLlt ne ==
i 32 WJ Wrta Fhasfe Arrfi ~j[ GgngB
TraiEfuriier 2A
ivl.f r ri . I1
TnejutAlam
CM Level Alarn

2
1 32 KV 31-6 P"aie -J-|p
r
fli Frai
1
I ! - pr- : i:-.r --.111 ! Details J
: I kv w-ita P^ase Amp UL T-
|I T:-f iji
i Fsisiti. Ii D P h DSS Indication T nps Ro whrt El JD

l^raure
Vvi-dF j d
E

0
21.
Ttncaraor- 37
71.
11 .D
27.20
3*7
i

Copyright RuggedCom Inc 13


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Overview of IEC 61850 Standard

14
RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

What is IEC 61850 ?

IEC 61850 is NOT just a communication


protocol
It is a suite of multiple protocols
It is an application focused communication
architecture
It is one of the key building blocks for the
Smart Grid

Copyright RuggedCom Inc 15


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

IEC 61850 standard defines complete


communication
architecture in Electrical Power Systems

Copyright RuggedCom Inc 16


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

IEC 61850 Key Features

Uses the strengths of the OSI 7 layer


communication model
Standardized data models for electrical
applications
Defines Data Types and Communication
Services
Models devices, functions, processes and
architectures
Describes Engineering and Configuration

Copyright RuggedCom Inc 17


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Process
Provides examples of typical applications in
electrical substations

Copyright RuggedCom Inc 18


RUGGEDCOM
IEC 61850 Key Features
INDUSTRIAL STRENGTH NETWORKS"

The data is organized in devices in a


standardized way
The devices are self-descriptive,
- either online (MMS protocol) or offline (SCL
language)
IEDs not only provide the data itself but also
the information about data types used, its
structure and complete naming.

Copyright RuggedCom Inc 19


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Parts of IEC 61850 Standard Edition I


Basic principles Part
Glossary 1
General Requirements Part
System and project 2
management Part
Communication
Substation Configuration 3
Language (SCL)
requirements Part
Basic Communication
Sampled 4
Mappin Structure
Measured Values Part
Par g to (serial)
t8 MMS Sampled 5
and Measured Values
Ethern (ethernet) Part
et Conformance 6
testing
Copyright RuggedCom Inc Part 20
RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Data Models and Services

IEC 61850 Part 7-3 defines a base set of data types for
describing objects
IEC 61850 Part 7-4 defines a set of Objects (Logical
Nodes)
IEC 61850 Part 7-2 defines a set of Services to
manipulate and access those objects. Services
are well defined procedures on how information is
exchanged.

Copyright RuggedCom Inc 21


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Application Modelling According to IEC 61850

Copyright RuggedCom Inc 22


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

IEC 61850 is Application Oriented


DNP3.0, IEC-60870-5, Modbus, etc. are industrial generic
use protocols and are not application oriented

In generic industrial protocols we talk about points or


addresses without knowledge what data is behind it

IEC 61850 is an application oriented architecture, it


introduces meaningful semantics
IEC 61850 defines application specific data like PTOC
(Protection Time Overcurrent) logical node or
XCBR (Circuit Breaker) logical node, etc.
Example of semantic: Position of the breaker XCBR1$ST$Pos$stVal

Copyright RuggedCom Inc 23


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Data Mapping Examples


Position of breaker at 345kV feeder
#1:
- Modbus: register 0x1 C1
A, bit 3
- DNP 3.0: object 1.1, point #26
- IEC 61850: XCBR1$ST$Pos$stVal
Operate the circuit breaker at 345kV
feeder #1:
- Modbus: register 0x251A, bits 0, 1
- DNP 3.0: object 12.1, point #10
- IEC 61850: XCBR1$CO$Pos
Phase A voltage for the 345kV feeder
#1:
- Modbus: register 0xB5C7, 4 bytes
- DNP 3.0: object 30.1, point #23
- IEC 61850:
MMXU1$MX$PhV$phsA$instCVal
Line frequency for the 345kV feeder

Copyright RuggedCom Inc 24


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

#1:
- Modbus: register 0xCC02, 4 bytes
- DNP 3.0: object 30.1, point #27
- IEC 61850: MMXU1$MX$Hz$nstMag

Copyright RuggedCom Inc 25


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

IEC 61850 Data Mapping Models Application


Position of breaker -
XCBR1$ST$Pos$stVal

Control of circuit breaker -


XCBR1$CO$Pos

Sum of Switched Amperes -


XCBR1$MX$SumSwARs XCBR:
Logical Node Circuit
Breaker
A group of data describing

Copyright RuggedCom Inc 26


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

the Breaker
Data is grouped based on functionality
IEC 61850 models the application

Copyright RuggedCom Inc 27


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Logical Node
Standardizes which elements of specific
functions related to power system should be
contained in substation devices
A Logical Node is an abstract model of a real
device or function
A Logical Node is a collection of data that is
grouped taking into account its functionality

V UHU
1

Logical Nodes
IHHU1 MMKU2

Logical Device is.g R^lLll

Copyright RuggedCom Inc 28


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Physical Device MMXU2


Feeder #1 Current
(network address)
$MK$A
Measurements

Copyright RuggedCom Inc 29


RUGGEDCOM
Communication Services in IEC 61850
INDUSTRIAL STRENGTH NETWORKS"

GetDataValues/SetDataValue
s
Unbuffered Reports
Buffered Reports
Control Operations
Logging
Time Synchronization
File Transfer
Substitution
GOOSE
Sampled Values

Copyright RuggedCom Inc 30


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

SCL - Substation Configuration Language


Description language for communication in
electrical substations
Defined in IEC 61850-6
Based on XML language
Defines common file format and allows formal
description of:
- Substation automation system and the switchyard and the
relation between them
- Communications parameters
- IED configuration
Makes an efficient engineering process of a
substation
Eases the integration process of devices from
Copyright RuggedCom Inc 31
RUGGEDCOM
multiple vendors
INDUSTRIAL STRENGTH NETWORKS"

Copyright RuggedCom Inc 32


Engineering process using SCL
ICD
Files
ICD- from SSD-
Files
V
other
vendor
File

I System Specification
Tool
specifies single-line
diagram,
IED make bindings of IEC
Configuration 61850
Tools generate Logical Nodes to
ICD files physical lEDs.
System Configuration
Tool
configures
communication network
parameters, configure
GOOSEs and
Reports.
Station Station Controller
Controller Configuration Tool parses IE
ICD files or SCD Ds
CID File
IED Configuration or
Tools import SCD file parame-
and extract from it
info relevant to its
IED
ter file
PP
t
Copyright RuggedCom Inc 33
RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

IEC 61850 Architecture


Future use of IEC
Level 3 - 61850:
Dispatch Center Substation-to-Subs
tation
Corporate Substation-to-Disp
WAN atch Center
Rou Synchrophasors
ter over 61850
Level 2 - 61850
Substation Station Bus
SAS
Client-Server,
GOOSE

Level 0 - 61850
Switchyard Process Bus
Intelligent ^Sampled Values,
Sensors, I/Os
GOOSE

Copyright RuggedCom Inc 34


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Station Bus and Process Bus


Station bus
- Communication between lEDs and master
stations
- Data polled by Master from lEDs or
asynchronously sent by lEDs
- Inter IED data exchange through multi-cast
GOOSE messages
Process bus
Communication between plant equipment
(intelligent switchgear, Instrument
transformers) and lEDs
Exchange of sampled values

Copyright RuggedCom Inc 35


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

(digitized measurements)

Copyright RuggedCom Inc 36


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Communication Schemes in IEC 61850


Client-Server communication
- Information exchange like fault record, event record,
measurement values, etc.
- Data size much greater, can run into kB or MB
- Uses the full services of the OSI model (MMS over TCP),
reliable data transfer
- Not time critical data
GOOSE messages
- Time critical data eg. trip, block, interlock, etc.
- Initiation of data transfer only on occurrence of the event.
- Compensated by multicasting (repeated transmission)
Sampled Values
- Time critical data - sampled values of current /
voltage signals from nonconventional instrument
transformers or lEDs

Copyright RuggedCom Inc 37


RUGGEDCOM
- Continuous stream
INDUSTRIAL STRENGTH NETWORKS"
of data, rate determined by the
sampling frequency of the data
- Data size depends on the resolution of the sample
- Not reliable data transfer (like Goose messages)

GOOSE Usage for Interlocking & Tripping


GOOSE messages Conventional
Hardwired
IEDs interconnected via interconnections
Ethernet network

Copyright RuggedCom Inc 38


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Copyright RuggedCom Inc 39


RUGGED
COM
INDUSTRIAL STRENGTH NETWORKS"

IEC 61850 GOOSE


Device to multi-device communication
Layer 2 Multicast message
Fast transmission of substation events, blocking,
permissive signals, etc.
Also transmission of analog values (voltage,
frequency, etc.)
Limited to LAN segment, for transmitting over
router tunneling is needed
Event driven transmission sent on change of state
Periodic heartbeat messages to enable detection

Copyright RuggedCom Inc 40


of device or link failure
Reliability effected through message
retransmission scheme
Uses VLAN ID and priority tagging

Copyright RuggedCom Inc 41


RUGGED
COM
GOOSE Example - False Bus Differential
INDUSTRIAL STRENGTH NETWORKS"

VT
Substation without dedicated

Distance
Busbar protection
Protection

CT 3. Transformer relay receives


HV the message that feeder
had seen the fault. It is a
Block message
preventing tripping the
CT

Trafo
whole busbar.
Prot
2. Feeder IED sees the fault
M
CT ______ and
V immediately sends a
GOOSE message

1. A fault
occurs

Copyright RuggedCom Inc 42


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Process Bus Overview


IEC 61850-9-2
Digitization of CTs/PTs and connection of Intelligent
Switchgear
Merging Units - electronic interfaces to measured
values from switchyard
Defines communications service mapping of Sampled
Values
SV messages encapsulated in Ethernet and sent via
Layer 2 Multicast
Does not define types of data and number of elements
in SV message
The streams of sampled values generated by Merging
Units must be synchronized in time
The required time synchronization accuracy is
Copyright RuggedCom Inc 43
RUGGEDCOM
few microseconds as lEDs are using sampled
values for protection
INDUSTRIAL STRENGTH NETWORKS"

Copyright RuggedCom Inc 44


RUGGEDCOM
Process Bus Overview
INDUSTRIAL STRENGTH NETWORKS"

IEC 61850-9-2 LE (Lite Edition)


Is an Implementation Agreement to facilitate
interoperability
Is maintained by UCA, not by IEC. Is a defacto
standard.
Specifies fixed message format, fixed Data Set with:
- 4xVoltages & 4xCurrents
Specifies two sampling rates:
- 80 samples/cycle and 256 samples/cycle
Specifies types of Ethernet connectors and physical
layer:
- 100Base-FX with ST, 100Base-FX with MTRJ,
100Base-TX with RJ45
Specifies 1PPS as synchronization mechanism
Future revision of IEC 61850-9-2 most probably will
add IEEE 1588 time synchronization and more
Ethernet connector types and physical layers

Copyright RuggedCom Inc 45


RUGGEDCOM
IEEE 1588 time synchronization will replace
1PPS
INDUSTRIAL STRENGTH NETWORKS"

Copyright RuggedCom Inc 46


RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Key Benefits of IEC 61850

47
RUGGEDCOM
INDUSTRIAL STRENGTH NETWORKS"

Key Benefits of IEC 61850

Increases flexibility
by connecting protection, control, measurement and
monitoring devices to common Ethernet network within
substation
Reduces copper wiring
through GOOSE messaging that enables fast
and reliable applications like interlocking,
distributed bay tripping, breaker failure, etc.
Reduces total installation cost
by enabling Process Bus with electronic CT/VTs and
intelligent switchgear and by replacing conventional copper
wiring by Ethernet digital communications
Eases system engineering and integration process

Copyright RuggedCom Inc 48


RUGGEDCOM
through graphical configuration tools based on SCL
INDUSTRIAL STRENGTH NETWORKS"

language - XML common file format designed for


exchange of configuration information.

Copyright RuggedCom Inc 49


RUGGEDCOM
Key Benefits of IEC 61850
INDUSTRIAL STRENGTH NETWORKS"

Improves application performance and security


through fast Ethernet communications and redundancy
(IEC 61850 Edition II)
Provides easy way of implementing typical applications
due to standardized naming conventions
Saves time and money in setup & commissioning
because of object-oriented structure and high-level
services that enable selfdescription of devices and
automatic data discovery.
Minimizes costs of technological obsolescence
because of a global acceptance and adoption and
future-proof concept of abstract services as well
as independence of mapping to protocols

Copyright RuggedCom Inc 50


RUGGED
COMIEC 61850 is currently used
Where
INDUSTRIAL STRENGTH NETWORKS"

Transmission substations
Distribution substations
Distribution automation
Power plants
Wind farms
Railway traction substations
Substations in industrial plants
and big infrastructure:
Aluminum
Oil&Gas
Mines
Airports

Copyright RuggedCom Inc 51


RUGGEDCOM
Other
INDUSTRIAL STRENGTH NETWORKS"

52
Questions?

Copyright RuggedCom Inc 53