You are on page 1of 3

By Timothy Allinson, P.E., Popov Engineers, Inc., Irvine, Calif.

Hot Water Circulation


between good and bad plumbing design. tains 1.14 gallons of water that is wasted

H
ave you ever stood at a sink,
waiting for hot water and are Hot water delivery is dictated by in anticipation of the hot supply.
amazed at how long it takes to code. Most codes require that hot water There are three primary considera-
arrive? The hot water at my own kitchen dead-ends not exceed 50 feet without tions when designing a hot water circula-
sink used to take two minutes and twen- some form of temperature maintenance. tion system, namely piping configura-
ty seconds to reach its destination. Thats This is often done with a circulation sys- tion, circulation pump flow rate and
a long time when you are just standing tem, but also can be accomplished with pump head.
there, waiting for the hot water so that heat tracing cable. The reasons for tem-
you can wipe your babys messy face perature maintenance are twofold. First Piping Configuration
with a warm towel rather than a chilly is the practicality of the user not having The general arrangement of the hot
one. I became so frustrated that I eventu- to wait too long for hot water, and sec- water circulation system is dictated by
ally added a local electric heater below ond is for water conservation. A great architecture. Along, narrow, single-story
the sink (refer to my May 2003 column deal of water is wasted when you flow a building with fixtures scattered through-
in Plumbing Engineer). It is at these fixture waiting for hot water. Fifty feet out the floor would probably have a sin-
times that one realizes the difference of three-quarter-inch copper tubing con- Continued on page 20

Circle 012 on Reader Service Card


Page 18/Plumbing Engineer Copyright 2003 TMB Publishing. All Rights Reserved. September 2003
Designers Guide
Continued from page 18

gle loop down and back the length of the flowing downward and back to the have the proper amount of water circulat-
building. A tall hotel might have multi- heater. ing through it. There are valves sold
ple, circulated risers, collected at their There are two key elements in detail- specifically for this purpose with cali-
tops with a single return riser. An office ing the piping configuration. First, a brated markings on the valve handle.
building with typical core mens and building with multiple hot water risers (or Alternately, a throttling valve, such as a
womens toilet rooms might have one loops) must be provided with a balancing globe valve, can be used for balancing.
riser feeding the mens lavatories flowing valve on each loop prior to connecting to However, a gate valve or ball valve does
upward, with an offset at the top of the the hot water circulation main. This is not work well for balancing, as they do
building to feed the womens lavatories necessary to ensure that each loop will not easily control low flow rates.
Second, hot water circulation must not
have inverted traps in the piping. The rea-
son for this is the fact that air is released
from solution at an increasing rate with
temperature. Consequently, hot water
piping tends to become air-bound more
readily than cold water. If a hot water cir-
culation leg becomes air-bound it can
disrupt the flow and prevent circulation.
One means of avoiding air in circulation
piping is to run the circulation loop on the
level below the top floor of plumbing fix-
tures. This allows trapped air to be
released from the fixtures when they are
used. If this approach is not possible,
high points in the circulation loop can be
vented with automatic air vent valves
(AVV).

Pump Flow Rate


The pump in a hot water circulation
system must be capable of moving water
through the system nearly as fast as it
cools down. The rate at which the water
cools is a function of the thickness of
insulation and the temperature differen-
tial. Table 1 indicates standard BTU loss
values for hot water piping with 1" fiber-
glass insulation and a 50-degree temper-
ature differential (120-degree water in a
70-degree environment). These numbers
are fairly standard, but would have to be
modified for accuracy if a different insu-
lation thickness or water temperature
were used.

Table 1
Pipe Size BTUH/ft
1/2" 6
3/4" 7
1" 8
1-1/4" 9
1-1/2" 10
2" 11
2-1/2" 13
3" 15
4" 18
Circle 014 on Reader Service Card
Page 20/Plumbing Engineer Copyright 2003 TMB Publishing. All Rights Reserved. September 2003
With these BTU loss numbers known,
system losses can be determined by mea-
Table 2
suring the lengths of piping of various
Size gpm loss/100' length Total
sizes and multiplying them by the corre-
3/4" 1 0.46 100 0.46
sponding BTU loss value. For example,
3/4" 2 1.5 50 0.75
the system in Figure 1 has 500' of three-
3/4" 3 3.2 50 1.6
quarter-inch piping, 300' of 1" 200' of
3/4" 4 5.1 50 2.6
11/4" and 400' of 11/2", so the total sys-
3/4" 5 7.6 50 3.8
tem heat loss rate is (500 x 7) + (300 x 8)
1" 2 0.46 100 0.46
+ (200 x 9) + (400 x 10) or 11,700
1" 5 2.5 200 5
BTUH. Next, pump flow rate can be
1-1/4" 3 0.35 200 0.7
determined based on the allowable tem-
1-1/2" 4 0.23 200 0.46
perature drop. In this example the return
1-1/2" 5 0.42 200 0.84
temperature is desired to be no less than
Total: 16.67
5 degrees less than system temperature.
Pump flow can be obtained from the
equation: tem. Done properly, it must include fric- tion pump, when the user complaints of
tion losses for each portion of the system no hot water are endless.
8.33 Q T= BTUH where the flow increases due to accumu- Also, be aware that some clients may
lation of each circulated loop. In our have hot water circulation requirements
8.33 x gpm x 60 min/hr x 5 deg. = 11,700 example, the pressure loss through the that exceed code. I have worked on pro-
furthest loop would look like that which jects where the criteria stated hot water
Therefore, the required flow rate is is presented in Table 2. delivery in 15 seconds rather than the
about 5 gpm for this system. Each riser Therefore, the minimum pump head code-driven 50-foot maximum. For
would have 1 gpm circulated through it required is about 17' to circulate through three-quarter-inch piping and a 2.25
to maintain temperature. Note that the furthest riser (on the left). Once it can gpm faucet, 15 seconds translates to
increasing the temperature differential, if overcome this friction it will have suffi- about 25' of pipe.
this is acceptable, can reduce the flow cient pressure to circulate through the Be aware that there is such a thing
rate. Also, when measuring the system other risers. Remember, you do not need called natural circulation. Some older
piping, branch piping need not be includ- to include the friction through all of the buildings were designed to take advan-
ed; only the portions of the system that risers, only the furthest loop. Note that tage of the fact that in a closed loop, hot
have circulated water should be included. friction factors were taken from a stan- water rises and cold water falls. As a
dard friction chart for result, if the hot water piping is gener-
copper pipe. Also note ously sized, the hot water system will
that hot water circula- tend to circulate naturally without a
tion pumps should be of pump. In order to achieve this, the pip-
either bronze or stain- ing must be sized for a maximum fric-
less steel construction. tion loss of about 1' per 100'. In todays
market, the cost of labor and material to
OtherConsiderations achieve this is impractical.
Keep in mind that hot
water circulation is not
as exact a science as the
calculations would About the Author
imply. It is no simple Timothy Allinson is an associate with
Popov Engineers, Inc., in Irvine, Calif.
task to balance a system
Prior to moving to the West Coast he
with exactly 1 gpm spent 15 years in New York City with the
flowing through each firm of Jaros Baum & Bolles. Mr.
Figure 1 riser. For this reason, it Allinson holds a BSME from Tufts
is a good idea to put a University and an MBA from New York
Pump Head little fat into the circulation pump. As University. He is a professional engineer
Lastly, the pump head needs to be cal- illustrated in Table 2, I would probably licensed in both mechanical and fire pro -
culated. The pump must be capable of double the flow rate of the pump to tection engineering in various states. Mr.
overcoming the friction through the fur- allow for errors in balancing the system. Allinson is the president of the Orange
There is nothing more frustrating than a County Chapter of ASPE, past president
thest part of the system. To determine
of the New York City Chapter and sits on
this, the friction loss associated with the hot water circulation system that bal-
the board of the Society of American
circulated flow rate through the furthest ances on paper but not in the field. Military Engineers, Orange County
riser or loop must be calculated. This cal- Nobody will thank you for saving them Post.
culation can be tedious for a large sys- 1/25th of a horsepower on the circula-

Plumbing Engineer Copyright 2003 TMB Publishing. All Rights Reserved. September 2003/Page 21

You might also like