You are on page 1of 6

Estimated by : Sheet No.

Checked by: E.G.O


Job Name: Date
Address: Estimated for
Space Used For: GROUND FLOOR ,BEDROOM
SPACE SIZE CONDITIONS 0
FDB 0
FWB %RH 0
FDP gr / lb
Length (ft) Width (ft) Area (sq.ft) Height (ft) Size (cu.ft) Outside 110 108
16.4 33 23 9.84 226 Room 76 68
SOLAR GAIN-GLASS Difference 34 xxx xxx xxx 40
ITEM Area (sq.ft) Temp. Difference Factor BTU / HR VENTILLATION

N Glass 21.5 11 0.56 132.44 2 People 15 CFM/Per 30


NE Glass 138 0.65 0 23 sq.ft 0 CFM/ sq.ft 0
E Glass 163 0.75 0 226 cu.ft 0.00 0.00
SE Glass 85 0.75 0 * No of Fersh Air Charges per Hour
S Glass 128 0.75 0 CFM VENTILATION 30
SW Glass 85 0.75 0 INFILTRATION
Swinging
W Glass 0 163 0.65 0.00 /Revolving Doors 1 People 15 CFM/Per 15
NW Glass 138 0.75 0 Open Door Door CFM/Door 0
Skylight 0 Exhaust Fan 0
SOLAR & TRANS GAIN WALLS & ROOF Crack 20 Feet 5 CFM/ft. 3.26
ITEM Area (sq.ft) Temp. Difference Factor CFM infiltration 15
Wall - North 139.8 27.5 0.38 1460.91 CMF OUTSIDE AIR THROUGH APPARATUS
Wall - West 193.6 27.5 0.38 2023.12 SENSIBLE HEAT FACTOR & APPARATUS DEWPOINT
Wall - East 34 0.38 0 Room Sense, Ht 10339.26
0.91746 Sens heat factor
Partition 64.5 29 0.33 617.265 Room total heat 11269.48
Roof Sun 23 47.5 0.24 262.2 Indicated ADP 0F Selected ADP 55
Roof Shaded 0 DEHUMIDIFIED AIR RISE
TRANS GAIN - EXCEPT WALLS & ROOF (1-BF) 0
RM Temp. 0
ADP Dehumidified Air Rise

ITEM Area (sq.ft) Temp. Difference Factor 0.88 76 55 18.48


All Glass 21.50 34 1 731 10339.26
= 514.73 Dehum air CFM
Partition 64.5 34 1 2193 1.08 18.48
Ceiling 0 Total Air CFM
Floor 23 0 0 0 514.73 18.48
452.96
INFILTRATION AND OUTSIDE AIR 76 55
Temp.
ITEM Air flow (CFM) Factor * 1.08 factor used only for normal air conditioning applied adjust for dehumidified
Difference
INFILTRATION 15 34 1.08 550.8
Temp. ** To be compensatedfor temperature rise due to fan motor duct heat gain to first outlet.
ITEM Air flow (CFM) Factor
Difference
Outside Air 30 34 0.12 1.08 132.19 NOTES
INTERNAL HEAT

ITEM NO.Of Peoples Internal heat

People 2 230 460


ITEM Total hp Internal heat
hp 0
Total
ITEM watts/sq ft Factor
Power(Watts)
Light 23 2 3.4 156.40
ITEM Total Internal heat
Appliances etc 200 3.4 680
Room sensible heat sub total 9399.33
Duct Leak
Duct Heat Gain
Loss
Fan H.P Safety Factor 10% 939.93
Room sensible heat 10339.26
ROOM LATENT HEAT
ITEM CFM gr/lb Factor
Infiltration 15 40 0.68 408
Out Side Air 30 40 0.12 0.68 97.92
ITEM lb/hr Factor
Steam 0
item total latent heat
people 2 190 380
Room latent heat sub total 885.92
Supply Duct
Leakage Loss
Safety Factor % 5% 44.30

Room latent heat 930.22


Room Total Heat 11269.48
OUT SIDE AIR HEAT
Item CFM F Factor
Sensible 30 34 0.88 1.08 969.41
Item CFM gr/lb Factor
Latent 30 40 0.88 0.68 718.08
TONS 1.08 Grand total heat 12956.96
Outside Temp Inside Temp Temp Difference
110 76 34
grains/lb 108 68 40
DBT Inside(f) RH% Sensible Heat factor ADP
76 50 0.92 55
Deg. F grains/lb City Code
Outside Temp 110 106 Makkah 1
Inside Temp. 76 68
City 1
Wall Type 8"
U 0.38
Partition 6"
U 0.33
Month Longitude
City 1 May
N 11
NE 138
E 163
SE 85
S 128
SW 85
W 163
NW 138
HORIZONTAL 118
20Deg Latitude