Highest voltage level 380 kv is calculated from 80% of factory Hi Voltage injection Level
304 kV is 80% of 380kv
170 kv is 1.2X Un/ rot 3
132 kv is Un/ rot 3
converted by W eb2PDFConvert.com
Thursday, April 26, 2012
THE STORY OF TRANSFORMER STABILITY
The transformer stability test used to conform the CT connections for Differential and REF protection.
This test also used as a primary injection test for HV & LV side BCT's.
PRIMARY SIDE : -
HV side full load current = Power / √3 x Voltage = 100×10^3 = 100000000 = 251 Amps
√3 × 230× 1000 399050
HV side Impedence/ Phase = HV side Impedence X % Impedence = 916 X 12.24 = 112 Ohms
100
LV side SIDE : -
converted by W eb2PDFConvert.com
HV LV
3.326<0° 22.201<181.141
°
3.205<241.5 22.935<59.28°
°
3.288<121.5° 23.573<299.34°
Note : -
Test connection: Three phase short circuit outside protected zone on LV side. Three phase voltage
injected on HV side = 380V
PRIMARY INJECTION TERTIARY WINDING :
Test connection : The shorting and grounding bar was removed from the Delta winding and current
was injected with Severker Test Kit and secondary currents were measured in the Transformer LCP
panel.
converted by W eb2PDFConvert.com
Newer Posts Home Older Posts
Blog Archive
► 2017 (3)
► 2016 (17)
► 2014 (3)
► 2013 (24)
▼ 2012 (46)
► December (3)
► October (2)
► September (4)
► August (5)
► July (7)
► June (1)
► May (3)
▼ April (3)
HV TEST FOR 230 KV GIS High Voltage level of inje...
THE STORY OF TRANSFORMER STABILITY The transformer...
TIMINGS & TIME SETTINGS
► March (3)
► February (6)
► January (9)
► 2011 (35)
► 2010 (13)
converted by W eb2PDFConvert.com
About Me
SIVAKUMAR
THIS IS SIVA T&C ENGINEER IN NCC LTD - SAUDI.
View my complete profile
converted by W eb2PDFConvert.com