Professional Documents
Culture Documents
Characteristics
The 19“ rack has a height of 3 HE for single Euro-
card format boards (DIN 41494). There are 20
slots available for the installation of boards.
Sub connector
Each power supply unit has a predefined slot allo-
cated to it (slot 21 and slot 19). These slots can Figure 1: Sub-connector design
be used only with PSU modules.
Slot 1 to 17 can be used for I/O boards and/or
CMU modules. If no redundant power supply is
used, slot 18 can be used for an additional I/O
board.
This interface technology minimizes the number of Besides to the process signal connections, the fol-
cable connectors as well as the space required in lowing interface possibilities are located on the
the rack 560SFR02. rear side of the printed circuit board:
A monitoring circuit on the rack 560SFR02 checks Interface to the serial peripheral bus
the supply voltages of the board (24 V DC, 5 V
DC). Supply voltage failure is indicated by a status Status relay contact for monitoring the in-
relay contact. ternal voltages (24 V DC and 5 V DC) and
status of PSU´s.
An additional circuit shows the status of the power
supplies. Power supply failure is also indicated by Interface and supply power for the
a status relay contact. 560BCU05
560PSU02
24V 24V
ERR ERR ERR ERR
5V 5V
ON ON ST ST ST
PST
OFF OFF
1 9
+ + 2 10
- - 3 11
PE PE 4 12
5 13
6 14
7 15
8 16
CO
PE PE
RJ45
Process
Connector
Technical Data
In addition to the general technical data of the Monitoring Connections
RTU560, the following applies:
PowerSupply WARNING
Operating Information
Type of Connection
Temperature -40 °C … +85 C
Peripheral boards Indirect, 48 pole, Type F
DIN 41612 with cut-out
Relative humidity 5 … 95 %
for sub-connector
non condensing
Process signal 18 pole sub-connector
connection with crimp clips
Ordering Information
23XS40R1001
23XS40R2001 560SFR02 R0001 1KGT 022200 R0001
Note:
We reserve the right to make technical changes or modify
the contents of this document without prior notice.
With regard to purchase orders, the agreed particulars
shall prevail. ABB AG does not accept any responsibility
whatsoever for potential errors or possible lack of information
in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents - in whole or in parts –
is forbidden without prior written consent of ABB AG.