SOUQ WAQIF PARKING MODIFICATION - NOVO CINEMA

CALCULATION REPORT
FOR
SMOKE MANAGEMENT CACLCULATIONS

SEP. 2017
Smoke Dilution System Sizing Summary
Project Served area:
Novo Cinemas
Name :       Cinemas
Date 27-SEP-
Prepared By : Eng.wael hassan
2017
Building Floor Smoke Extraction Flow Rate Case of Clear Hight less than
Flame Hight (z < Zf )
         
(Steady Clear Height with Upper Layer Exhaust
Method):

NFPA
92_Edition
mo = 0.0208 * qc3/5 * z 2012, 5.5.1,
  Eq.(5.5.1.1c) in
case of ZF ≥ Z
 is the convec-
qc =  * q tive fraction of
  heat release
Heat Release
(Minimum fire
for atrium with
   combustibles =
5000 BTU/S)
qc is the con-
vetive heat re-
   lease
1
NFPA
,
BTU 92_Edition
qc = 0.7 * 2000 = 4 
  /S 2012, 5.5.1,
0
Eq.(5.5.1.3)
0
ASHRAE 2007,
A.52.13 (Area of
  fire is
assumed to be

  100 ft2)
Clear Height
(selected to al-
low for people
to pass beneath
the smoke lay-
f
z = 9 er& equal for
  t
door hieght to
prevent smoke
spreading into
adjacent spac-
es).
NFPA
2/5 92_Edition
Zf = 0.533 * qc 
  2012, 5.5.1,
Eq.(5.5.1.1a)
= 0.533 * 18.13

f Checked (high-
= 10 
  t er than Z)
mo = 0.0208 * 77.2 * 9
l
b
= 14.5
  /    
S
= 6.6 kg/S
Smoke layer
( tempera-
Ts = T0 + (KS * qc) / m * CP ) ture,Equation
  o
5.5.5,NFPA
92_Edition 2012

Ts = 259.1
  C    
k
Patm = 101.3 P
  a    
Density of
Smoke,Equatio
rs = Patm / ( R  × T )  
  n 5.8a,NFPA
92_Edition 2012
= 101.3 / 0.287 x 532.1

= 0.7 kg/m3
Vo = mo / rs
= 9.9 m3/s
= 9,904 L/S

No. of Served Zones / 1.


= Zone
Floor 0
1.
No. of Fire Zones = Zone
0
1.
No. of Fire Floors = Floor
0
99
Smoke Flow rate = L/S
04 

Make‐up flow rate will be calculated based on 90% of smoke flow rate 

Make-up Flow rate =  8920  L/S