You are on page 1of 4

PROBLEMA N° 1

CARACTERISTICAS DE FUNCIONAMIENTO DEL MATJA

P = 45 KW EF = 0.922
V = 220 V FP = 0.81
RPM = 880 Ip/In = 7.8
F.S. = 1.15 F = 60 HZ
Inom = 158 TIPO = ALTA EFIC.
Clase = F ΔV = 2.50%

ARRANQUE DIRECTO - COORDINACION TIPO I

PROBLEMA N° 1.- Dimensione y seleccione el cable tipo NYY, en ducto

PARAMETROS CABLE NYY - MOTOR ITM - MOTOR


ITEM DESCRICION GENERAL P F.P EF T L Inom Idisen Scu Capac. DV Inom Idisen Icomer
KW V m A A mm² A % A A
1 MOTOR 45 KW, 08 POLOS 45 0.81 0.922 220 35 158 198 50 186 0.73 190 200

CONFIGURACION DEL CABLE: 3-1x35 mm² NYY + 1x10 mm² TW, PVC SAP Φ 40 mm RT 0.79
RM 6

BANCO DE CONDENSADORES LOCALIZADO 220 VOLTIOS 60 HZ


PARAMETROS ELECTRICOS CORRIENTE CABLE NYY ITM
PINST. F.Pi F.Pf θi θf Qc T Qc C INOMI Idisen Scu Cap. ITMdis ITM
ITEM DESCRIP. GENER KW KAR KAR A A mm² A A A
1 MOTOR 45 KW, 08 POLOS 48.81 0.810 0.96 35.90 16.26 21 18 47 66.1 10 77 61 80
21 x 1.09 = 23 RT 0.59
PARA SELECCIONAR LOS
ELIJO 10 + 10 = 20 RM 2
BANCOS DE CONDENSADORES
20 x 0.91 = 18 0K
BANCOS DE
CONDENSADORES
ELECGTRONICON

230 380 V 480 V 525


60 HZ 60 HZ 60 HZ 60 HZ
7.5 6.3 10 12
10 9.4 15 18
15 18.8 30 30

PROBLEMA N° 2
CARACTERISTICAS DE FUNCIONAMIENTO DEL MATJA

P = 15 KW EF = 0.91
V = 220 V FP = 0.8
RPM = 875 Ip/In = 7.5
F.S. = 1.15 F = 60 HZ
Inom = 54.4 TIPO = EFIC. ESTANDAR
Clase = F ΔV = 2.50%

BANCO DE CONDENSADORES LOCALIZADO 220 VOLTIOS 60 HZ


PARAMETROS ELECTRICOS CORRIENTE CABLE NYY ITM
PINST. F.Pi F.Pf θi θf Qc Qc C INOMI Idisen Scu Cap. ITMdis ITM
ITEM DESCRIP. GENER KW KAR KAR A A mm² A A A
1 MATJA 15 KW, 08 POLOS 16.6 0.80 0.96 36.87 16.26 8 7 18 25.7 6 58 24 25
8 x 1.09 = 8 RT 0.73
PARA SELECCIONAR LOS
ELIJO 7.5 + 0 = 7.5 RM 3
BANCOS DE CONDENSADORES
7.5 x 0.91 = 7 0K
PROBLEMA N° 3.-
CARACTERISTICAS DE FUNCIONAMIENTO DEL MATJA

P = 370 KW EF = 0.96
V = 460 V FP = 0.88
RPM = 1790 Ip/In = 6.6
F.S. = 1.15 F = 60 HZ
Inom = 549 TIPO = ALTA EFIC.
Clase = F DV = 2.50%

BANCO DE CONDENSADORES LOCALIZADO 460 VOLTIOS 60 HZ


PARAMETROS ELECTRICOS CORRIENTE CABLE NYY ITM
PINST. F.Pi F.Pf θi θf Qc Qc C INOMI Idisen Scu Cap. ITMdis ITM
ITEM DESCRIP. GENER KW KAR KAR A A mm² A A A
1 MATJA 370 KW, 04 POLOS 384.6 0.88 0.96 28.36 16.26 95 92 115 162 50 186 150 160
95 x 1.09 = 104 RT 0.72
PARA SELECCIONAR LOS
BANCOS DE CONDENSADORES ELIJO 30 30 30 10 = 100 RM 3
100 x 0.92 = 92 0K
PROBLEMA N° 1.- INDUSTRIA PAPELERA EL CHATO
TENSION 460 VOLTIOS 60 HZ BANCOS DE
CALCULOS PREVIOS PARA HALLAR LA POTENCIA TOTAL CONDENSADORES
CUADRO DE CARGAS PINST. F.P INOMI θ Ical θ Ical θ Ical θ ELECGTRONICON
KW A A 230 380 V 480 V 525
1 CCM1 295 0.96 386 -16.26 60 HZ 60 HZ 60 HZ 60 HZ
572.16 -6.1
2 MATJA 204 CV 158.4 0.89 223 -27.13 7.5 6.3 10 12
1581.4 20.77
3 CCM2 550 0.85 812 -31.79 1882.2 23.72 10 9.4 15 18
1037.95 28.79
4 DATA CENTER 175 0.95 231 -18.19 15 18.8 30 30
5 SERV. AUXILIARES 395 0.78 636 -38.74 636 38.74 314 38.74
POT. TOTAL ing 1373 KW

BANCO CONDENSADORES CENTRALIZADO AUTOMATIZADO 460 VOLTIOS 60 HZ


PARAMETROS ELECTRICOS CORRIENTE CABLE NYY ITM
PINST. F.Pi F.Pf θi θf Qc T Qc C INOMI Idisen Scu Cap. ITMdis ITM
ITEM DESCRIP. GENER KW KAR KAR A A mm² A A A
POTENCIA TOTAL 1373 0.916 0.985 23.72 9.94 363 358 455 637.6 480 682 592 3x630
PARA SELECCIONAR LOS 363 x 1.09 = 395
BANCOS DE ELIJO 30 30 30 30 30 60 60 60 60 390
CONDENSADORES 390 x 0.92 = 358 0K

SELECCIÓN DE CABLES 426 0.80 2.000 = 682 240 2.0 480

PARAMETROS ELECTRICOS PARA LOS BANCOS CABLE THW


PASOS Qcat. Qreal IN ITMt ITMc Idcablet Scable CAPAC.
KVAR KVAR A A A A mm² A
1 30 27.60 34.64 45 50 48 3x6 58
2 30 27.60 34.64 45 50 48 3x6 58
3 30 27.60 34.64 45 50 48 3x6 58
4 30 27.60 34.64 45 50 48 3x6 58
5 30 27.60 34.64 45 50 48 3x6 58
6 60 55.20 69.28 90 100 97 3x16 102
7 60 55.20 69.28 90 100 97 3x16 102
UTILIZAR UN REGULADOS DE
8 60 55.20 69.28 90 100 97 3x16 102
POTENCIA REACTIVA DE 12
9 60 55.20 69.28 90 100 97 3x16 102
PAZOS DE LOS CUALES SOLO
10 100 0 3x16 102
SE UTILIZAN 09
11 100 0 3x16 102
12 100 0 3x16 102
TOTAL 390 358 450 584 630 629 480 682