PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Table of Contents
Software Updating Instructions
1
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
2
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
3
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Liebert® and the Liebert logo are registered trademarks of Liebert Corporation.
Emerson® and the Emerson logo are registered trademarks of Emerson Electric Co.
Notes:
5
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
2. In all cases perform a Save sequence and record some basic information
like unit code, network settings, and temperature set points.
A002 Unit Field Code (1-6) 001 002 003 004 005 006
A004 Unit Field Code (7-12) 007 008 009 010 011 012
A006 Unit Field Code (13-18) 013 014 015 016 017 018
7
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Fan Motors
Compressor 1A
Compressor 1B
Compressor 2A
Compressor 2B
Chilled Water
Free Cooling
HotGas / HotWater
Electric Heater 1
Electric heater 2
Electric heater 3
Humidifier
Dehumidifier
8
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
2. Start the iCOM Service Tool “iST” program by clicking on the on the
computer Desktop. Log in using the User Name and Password shown below.
Now click OK
9
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
10
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
8. Select the following files, one at a time and download the information to your computer:
Unit Diary
Spare Part List
Unit Code
Exception List
Configuration Safe
files fail to download, click on the interrupt all actions button, and skip that
file, then move to next file until downloading is complete.
Allow time for each file download to be completed. This can be determined by watching
the color of the board’s icon in the left pane of the iST.
Yellow = Busy Green = Board Complete Red = Failed
* Note: the green down - load button is unavailable during file exchanges.
11
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Unit Control
Type Board
DS / VS PAL
XD XPL
CRV CRL
12
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
13
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Unit Diary
Spare Part List
Unit Code
Exception List
Configuration Safe
Allow time for each up-load to be completed. This can be determined by watching
the color of the control board’s icon in the left pane of the iST.
Yellow = Busy Red = Failed
14
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
15
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Fan Motors
Compressor 1A
Compressor 1B
Compressor 2A
Compressor 2B
Chilled Water
Free Cooling
HotGas / HotWater
Electric Heater 1
Electric heater 2
Electric heater 3
Humidifier
Dehumidifier
16
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
2. Start the iCOM Service Tool “iST” program by clicking on the on the
computer Desktop. Log in using the User Name and Password shown below.
Now click OK
17
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
18
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
19
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Unit Control
Type Board
DS / VS PAL
XD XPL
CRV CRL
20
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
21
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Important Step
The board and display must be connected together and communicating. And both the
board and the display should have version 2 software at this point. The unit code has
been checked and the unit could be back in operating mode.
Configuration Save on the circuit board Must have been performed. If not do so.
If this step has not been performed this entire section will fail.
1. A single XML files needs to be downloaded. These files contain the present v.2 unit setups
in version v.2 format.
22
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
6. Find the Folder that has the same IP Address as the unit being worked
on. (Example) Device 192.168.254.1
7. Find the file “configsave.xml”. Note that there maybe two configsave
files, make sure you locate the one with the xml extension or xml type.
23
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
10. Look it over, there will be lines that start with the letters “<adp”.
Highlight all the lines that start with “<adp” as shown here.
11. Right Click and “Cut” or “Delete” all the “<adp” lines.
12. Now enter the following “<adp” lines into the same location where the
previous lines were deleted. The number in red is the “run hour” values
to enter into the iCOM control. The lines must be typed exactly as
shown. Any deviation will cause the information to be ignored.
13. “Save” the “configsave.xml” file when all the changes have been
made.
24
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
15. The “Configuration Save” XML file now need to be up-loaded back into the control board.
Click on the
16. Select the same “Configuration Save” file that was downloaded in the earlier steps,
and up-load the information:
Configuration Safe
Important
The next step is critical.
18. Go to “Network Setup” in the service menu.
a. Go to “Configuration Safe” and “Load”
b. Go to “Configuration Safe” and “Save”
Very important that “Load” is performed first. If not go back to upload and
repeat from that point.
Notes
26
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
In either situation.
Set to “Yes”.
2. Advance menu / factory settings Record “Unit Code” this information will
be lost during upgrade.
27
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
4. Start the iCOM Service Tool “iST” program by clicking on the on the
computer Desktop. Log in using the User Name and Password shown below.
Now click OK
5. Check to see that the IP address 192.168.254.254 is seen in the lower right corner
of the iST screen.
28
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
29
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
30
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Unit Control
Type Board
DS / VS PAL
XD XPL
CRV CRL
31
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
32
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
33
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
2. Start the iCOM Service Tool (iST) program by clicking on the on the
Desktop. Log in using the following information:
OK
Then click the button.
34
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
3. Check to see that the IP address 192.168.254.254 is seen in the lower right corner
of the iST.
OK
button from the bottom
right corner of the option window.
4. Now select the “magnifying glass” from the toolbar. This will search for the
connected unit.
OK
Click the button.
35
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
36
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
37
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Unit Large
Type Display
DS / VS PAB
XD XPB
CRV CRB
38
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
39
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
40
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
The computer will need to have an Ethernet and Serial port connection.
1. Push and hold the FAN OFF button on the cooling module for 5 seconds.
a. If both red and green LEDs turn on solid, the software will communicate.
b. If both red and green LEDs do not turn on solid the XDIO board needs
updated.
2. Check the software version on the XD unit iCOM control board. It must be version
XDP1.00.007.STD or higher. If unit iCOM software is not correct, upgrade the unit
unit software first.
3. Sensor “B” must be re-connected to the last XDIO board in the group to be updated.
4. Re-connect the can cable to the first XDIO board in the group to be updated.
5. Verify that both senor “A and B” temperature values are visible on the display.
41
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Original firmware version XDIOv1.00.003 will not communicate to iCOM. Other later
versions will communicate with iCOM, but updating during startup, it is considered
easier to use the XDIO updater to upgrade. After complete communication has been
established using ExtrapuTTY is the preferred method.
42
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
2. Connect a serial cable between your PC’s COM1 port and the XDIO board serial
port.
3. Double click on the file “XDIOUpdater.exe” and follow the prompts until the
application has completed the upgrade. Note that you will need to respond to
various prompts throughout the procedure. Shown below are the expected dialogs
using the XDIO updater application.
43
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
8. Once XDIOv3.04.001 is loaded to the board, it will ask to program the serial number,
click Yes.
9. If the serial number is successfully written to the XDIO board, a confirmation is given.
Click OK.
At this point, the board is fully upgraded and any future upgrades may be performed
through the CAN bus communications using service tool.
44
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
45
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
1. Connect a serial cable between the computer COM port and serial port on the smart
card.
46
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
2. “canr” will show the present Node ID assignment. In this case 80.
3. “canw nid XX” is used to change the Node ID. XX is the new Node ID.
47
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Command Description
almlist Display all the alarms that are currently active.
binf Display the build information for the code image, including version number and
checksums.
canr Show current CAN node id and Identity Object serial number.
canw nid Set the EEPROM CAN node ID to <value>, where <value> is interpreted as a decimal
<value> number. The allowable range of <value> is 80 – 105. Note that this node ID will not be
used by the board until it is rebooted.
cool Show calculated cooling capacity in kW and percent of maximum.
fan For each of the four possible fans, display the last sampled value of the fan current
(converted to amperage) and the state of the fan. The state can be one of the following:
1) Not Supported – Indicates that a physical fan is not expected to be connected.
Setting of the model number determines if a fan is supported.
2) Disabled – Fan is not turned on.
3) Enabled, no TC – Fan is turned on, and is not subject to temperature control.
4) Enabled, TC – Fan is turned on, and is subject to temperature control.
5) Enabled, TC shutdown – Fan is turned on, but has been shut down due to
temperature control.
menu Display a list of all public commands (all commands in this table).
modr Show the current value of the configuration model number. The configuration model
number should match that of the connected XD system for proper operation.
Modw Set the configuration model number of connected XD system. After setting the model
number, the board will automatically reboot.
NOTE: The model number must be manually set; it is not read from the connected XD
system.
mux Display the last sampled values of the mux inputs:
Input 0: Group 1, fan 1 current
Input 1: Group 1, fan 2 current
Input 2: Group 2, fan 1 current
Input 3: Group 2, fan 2 current
Input 4: Power source 1 voltage
Input 5: Power source 2 voltage
Two values are shown for each input: (1) the actual sample value read, and (2) the
sample value recomputed to take into account error compensation, which is only
applicable to fan current values.
reboot Reboot the board.
schlist List all tasks in the task scheduler. The information given is task name, task ID (TID),
the originally requested time to run (RT), and the remaining time until task is run (TTR).
temp Display the last sampled values of the four temperature sensors, converted to degrees
Fahrenheit. If the sensor is disconnected or shorted, it will display this information
instead of a temperature reading.
48
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
49
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
After device is highlighted minimize the window. The program must stay
open and running in the background while continuing with next step.
2. Click on iCOM
50
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
51
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Macros have been created to assist and make it easier to work through the steps. To
use the macros, double click on the commands on the left side of the page to enter
them into the black interface screen. After clicking on the macros, let the command
operation finish before moving to the next step. With the exception of the login and
password, the operation is complete when the new line appears and displays the “#”
sign.
52
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
General Commands
53
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
General Commands
54
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
General Commands
55
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
56
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
The “ExtraPuTTY” program should still be open and communicating the XDIO
boards. If the program has closed reopen and continue.
57
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
General Commands
You can now close the iCOM Service Tool (iST) and reconnect the
Ethernet crossover cable between the display and control board.
58
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
59
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
60
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
To perform a field-installation:
1. Find the Liebert IntelliSlot bay on your Liebert equipment—It may have a
plastic cover.
NOTE: The card will only fit one way in the Liebert IntelliSlot bay because the circuit
board is not centered on the faceplate. The slot in the Liebert IntelliSlot bay also is
not centered.
For a direct connection from a computer to the card, we need to know how the customer
has set up the card. However if you are installing a new card or servicing an existing
card it is recommended to reset the cards Ethernet communication parameter to factory
defaults to make connection consistent with these instruction. If not reset, these
instructions may not work. To reset card use a small device like a paper clip and double
push in on the reset switch. See picture for location.
61
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
3. You should see a screen similar to this one. Go to Local Area Network
4. Click on Properties.
62
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
63
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
4. And this screen should appear. This confirms communication using Ethernet. This
example is a DSE.
64
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
1. Menus are on the left side of the screen. Tabs at the top of page will
show the units menus, or the unit card menus. Click on the desired
to navigate to the correct menu list.
a. Default
i. User Liebert
ii. Password Liebert
b. Click OK
65
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
11. If rebooting is required, click on UNITY tab. Click on SUPPORT at bottom of menus.
a. Click on EDIT
b. Click on Restart
c. Wait, process may take 10 minutes.
66
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
3. Click on Protocols.
67
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Note: the process for changing any parameter is the same in all menus.
7. Click Save.
68
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
69
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
13. Confirm Modbus TCP settings. Customer can change settings after communication with
our computer is complete.
a. Limit Network Access Same Subnet
b. Port 1
c. Maxim mum Client Connection Count 4
15. Confirm Modbus RS-485 settings. Customer can change settings after communication
with our computer is complete.
a. Node ID 1
b. Baud Rate 9600
70
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
3. Click on Protocols.
71
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Note: the process for changing any parameter is the same in all menus.
7. Click Save.
72
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
73
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
74
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
4. Click on Support.
5. Click on Edit.
6. Click on Web.
75
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
NOTE: Do not navigate away from the Firmware Update screen and do not close the
browser once the update begins. Either action will interrupt the download.
13. After the firmware update is completed, the card will reinitialize.
76
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
77
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
1. Install the OpenComms Web Card in an open bay in the intelliSlot housing using the
instructions provided with the card.
2. Verify that the DC power cable is connected between plug P3 on the intellislot
housing and plug P61 on the unit control board. If cable is not plugged in make the
connection.
3. Verify that the communications cable is connected between plug P65 on the
intellislot housing and plug P65 on the unit control board. If cable is not plugged in
make the connection.
4. Verify that the intellislot housing is powered and that your computer is on. Connect
the null modem serial cable between port DB-9 on the Web card and the serial port
on your computer.
Note: Some computers do not have a serial port and require a USB to serial
adapter. Follow the instructions that came with the adapter to properly setup the
communications port.
78
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Click “OK”
Select / Enter
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
Click “OK”
79
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
The reset process will take several minutes. When complete press the ”Enter” key
then “ESC” twice to return to the main menu.
80
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
11. Any changes to the Boot/IP Settings must be saved for the changes to take effect.
Return to the main menu screen by pressing
“ESC” twice.
82
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
83
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
2. In Address bar type in the static IP address used in setting up the Liebert
OpenComms Web card.
84
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
4. To view unit information click on the various menu folders in the left side of the
displayed window.
85
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
7. When this screen appears enter the user name and password.
6. The Control Screens will now appear that shows the various unit pragrammed
values. To change any of the visable parameters click the “EDIT” button at the
bottom of the screen.
8. Once the screen appears make some changes to the control. Highlight the
paramenter to be changed, change it and click “Save” at the bottom of the screen.
86
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
9. Now click on the Configure tab at the top of the window and view the displayed
information.
10. Now click on the Support tab at the top of the window and view the displayed
information.
87
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
88
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
89
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
6. Open a connection to the Liebert IntelliSlot card using Internet Explorer. See
instruction earlier in book.
7. Click on the Configure tab, and then click on Web (under Firmware Update) in
the left panel. The connection to box opens for you to enter the username and
password.
90
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
10. Select the file, (The one you downloaded in a previous step). This is the file with
the extension “.bin”
91
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
92
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
This section will explain the steps to setup the OC-485 card using
HyperTerminal.
1. Install the OC-485 Card in an open bay in the IntelliSlot housing using the
instructions provided with the card.
2. Verify that the DC power cable is connected between plug P3 on the Intellislot
housing and plug P61 on the unit control board. If cable is not plugged in make the
connection.
3. Verify that the communications cable is connected between plug P65 on the
Intellislot housing and plug P65 on the unit control board. If cable is not plugged in
make the connection.
4. Verify that the Intellislot housing is powered and that the computer is on. Connect
the blue serial cable (null modem) between port DB-9 on the OC-485 card and the
serial port on your computer.
Note: Some computers do not have a serial port and require a USB to serial adapter.
Follow the instructions that came with the adapter to properly setup the
communications port.
93
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Click “OK”
Select / Enter
Click “OK”
94
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
95
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
The Server ID must be setup for each OC–485 Card. Each card on the network
must have a different number. It is recommended that they be in order: 1, 2, 3 and
so forth.
96
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
97
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
98
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
99
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Open HyperTerminal
100
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Communication settings
101
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
10. Click on the Connect To tab and click the Configure button.
This opens Port Settings tab in the COM1 Properties window, as
shown below right.
11. Choose 115200 from the Bits Per Second drop-down list and
click OK, then click OK to close the Properties window.
102
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Click Send.
103
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
19. Choose 9600 from the Bits Per Second drop-down list and
click OK, then click OK to close the Properties window.
Upgrade is complete.
104
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
105
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
6. On the left are the command lines and you should all ready have this list of commands. If
you do not have these commands or if you need to make a change, we will discribe the
process later.
Uint shows 220. This is the actual temperature setpoint in Celsius times 10. Or 220 is
the same as 22.0ºC
106
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Standard Address is the registry number of the information field. 30023 is the field for
Temperature set point in a DS unit.
See Liebert’s IntelliSlot 485 Modbus Reference Guide manual SL-28170 for more
detailed information. This manual can be view and / or downloaded from Liebert’s
website:
www.liebert.com
9. Double Click on
Write Multiple Registers Starting at 40023 for 1:
230
This will change the temperature setpoint to
23ºC.
107
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
A close-up view of the first line. The value has changed to 230 or 23ºC.
12. Testing Modbus is complete. We have read and wrote to iCOM through modbus.
108
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
4. Make necessary change to the bottom part of screen and click Edit TCP Connection.
109
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Click Edit.
Click Edit.
Click OK
7. Command edit is complete. For adding a command click add instead of edit.
110
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
5. Click on Search.
111
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
10. BACnet test is complete. We are only able to test Read. We will assume if read works,
Write will work.
112
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
113
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
http://applications.liebert.com/ICOMv2/Login.aspx
2. Enter the Password to open iCOM Service Access. Log in using the following
information:
Log IN
Then click the button
Now that you have accessed the service portal you will see the software and
documentation available for downloading.
114
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
115
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
116
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
2. Click on Properties
You should a screen like this screen. Different computers may have a different
version of the screen.
5. You will need to copy the new license file to your computer. Copy the new license
to: C:/Programs Files/EmersonNetworkPower/iCOM Service Tool
117
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
118
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
U2U Address
It is critical that the iCOM network designer understand the importance and implications
of the U2U address. In Teamwork Mode 1 the U2U address will be used to stage units
on. During Standby – Lead / Lag operation resting units will follow U2U address. It is
recommended that U2U addresses jump around room so operating and resting units
are not all in the same area and cooling is distributed evenly.
The U2U addresses of each control board must be in sequential order, starting with 1,
2, 3, 4 and so on within each group. The U2U addresses of large display must also be
in sequential order starting with 33, 34, 35 and so on within each group.
Teamwork
The units with iCOM control offers four (4) different methods of operating together to
maintain room environmental control. Each group will operate independent of other
groups. Each separate group may have the same or different teamwork setups.
IP Address
An individual IP address must be assigned to each unit control board and large display
connected to the network. It works like a phone number in a telephone. Computers
and microprocessors use IP addresses to manage communication between devices.
The IP address is made up of 4 groups of 3 digit numbers. (XXX.XXX.XXX.XXX) The
first 3 groups should be the same while the last segment must be different. Example all
IP address should start with 192.168.254._ _ _. The last segment can be any number
between 001 and 253.
119
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Planning a Network
When preparing to network units, one should always make a plan. The plan should be
a drawing on the room with locations of cooling units and rack layout. Then answer
these questions in order.
Groups, is it best to leave all units in one big group or divide into multiple groups?
o Add this to plan.
How should the unit boards be numbered (U2U Address)? Remember, number
must be in order, 1,2,3,4,… This will be used to standby mode and start-up on
power failure.
o Add this to plan.
How should the displays be numbered (U2U Address)? The displays should be
in sequence, 33,34,35,36,…
o Add this to plan.
Assign the IP addresses to the unit boards and displays. Easiest way is to match
the last segment of the IP to the U2U address. Example: A U2U address of 23,
then the IP address would be 192.168.254.023.
o Add this to plan.
Copies of the plan should be left with customer and placed inside equipment, for
future use.
CRAC 5
U2U 3
120
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
121
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
122
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
123
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Notes
Customer Course Critique
Name: _____________________________________ Date: _______________
2. How do you rate the technical training session for the amount of time? ______
8. Does the training facility meet your needs? Yes _____ No ______
10. What 3 things did you learn in this class that will benefit you the most?
A.
B.
C.
124
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual
11. What type of Liebert class(es) would you like to see presented in the future?
Additional Comments
125
PCT401 iCOM - iST Service Tool and XDIO Smart Board Programming Lab Manual
Being permitted to enter upon the premises of Emerson Network Power and to participate in
Emerson Network Power’s Air Products Training Program, the undersigned agrees never to use
or disclose any of the details of the publication's contents. Also other information which is revealed
to him/her should be considered confidential with the exception of other members of his/her
organization.
The undersigned agrees and understands that there are significant business reasons for
entering into this agreement and that this agreement is necessary to protect legitimate business
interests of Emerson Network Power. The undersigned further acknowledges that any breach
of this agreement may result in irreparable and continuing damage to Emerson Network
Power’s business for which there is no adequate remedy at law.
In the event of any breach of this agreement, Emerson Network Power and its
successors and assigns shall be entitled to injunctive relief and to such other and further
relief as may be proper. This agreement shall be governed by and construed in
accordance with the laws of the State of Ohio.
Safety - In consideration of permission to enter the premises of Emerson Network Power and
further in consideration of permission to participate in Emerson Network Power’s Educational
Services training programs concerning the operation of various Emerson Network Power’s Air
products, the undersigned hereby releases Emerson Network Power, its agents, officers, and
employees from all claims, demands, actions, causes of action, and from all liability for damage,
loss or injury of whatever kind, nature or description that may arise or be sustained by the
undersigned, while in, on, or upon said premises or any premises leased to, owned by, or under
the control of Emerson Network Power.
The undersigned is aware of the risks and hazards inherent in entering these premises and has
further been made aware by Emerson Network Power of any special potential dangers
associated with the equipment and machinery located on the premises. With those concerns in
mind, the undersigned hereby voluntarily assumes all risks of loss or
injury, including death, that I may sustain either to person or property while in, on, or upon said
premises.
126
PCT401 iCOM – iST Service Tool and XDIO Smart Board Programming Lab Manual