Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
1
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
2
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
3
ZACT should be controlled as in (2). where kp is the proportional gain, kr is the resonant term gain
𝑍𝐴𝐶𝑇 = −(𝑍𝑡 + 𝑍𝐶 ) (2) and ω is the resonance frequency. High gain at its resonance
The hybrid branch passive impedance is composed of the frequency provides zero steady-state error for a sinusoidal
coupling transformer impedance (Zt = rt + jωLt) and the reference. The same characteristics as the PI controller
capacitor impedance (ZC = rc + 1/jωC). Hence, an active presents for a DC reference. This feature makes possible
inductance La should be created to electronically tune the tracking the current reference directly from the error signal,
Smart Impedance for a specific frequency (ω) as shown in (3). eliminating reference transformation and PLL synchronization
1 algorithm. The source harmonic current ISh is obtained from
ω=
√(𝐿𝑎 + 𝐿𝑡 )𝐶 the source current IS using a notch filter [20] with the transfer
This topology is capable of achieving multiple tuning function given by (9).
frequencies at the same time by creating different active 𝑠 2 + 𝜔02
H(𝑠) = 2 (9)
inductances for each desired harmonic. Also, it creates a 𝑠 + 2𝜔𝑐 𝑠 + 𝜔02
virtual negative resistance (rv) to eliminate the residual where ωc represents the bandwidth of the notch filter and ω0 is
resistance of the branch, as in (4), and turn it into an ideal the resonance frequency. Here, ω0 is 376.8 [rad/s] (60 Hz), the
filter for each harmonic frequency. fundamental frequency, and ωc is 31.4 [rad/s] (5 Hz), which
𝑟𝑣 = −(𝑟𝑡 + 𝑟𝑐 ) still ensures 25 dB attenuation for ±0.5 Hz variation in system
After tuning, the branch becomes an ideal active short circuit frequency. The notch filter extracts the fundamental
for the harmonic load current, by forcing the harmonic voltage component from source current (IS1), so only the harmonic
across its terminals to be zero. It has to be notice, smaller the components remains (ISh). The control strategy is based on:
Smart Impedance equivalent impedance, smaller will be the when the harmonic current flowing into the source is zero, all
PCC equivalent impedance. This is the cornerstone of the the harmonic current generated by the load is flowing through
quasi-infinite bus concept. the Smart Impedance branch. At the same time, the source
On the other hand, considering only the source voltage voltage harmonic distortion is blocked. The harmonic source
harmonic VSh contribution (ILh = 0), the harmonic current ISh current feedback automatically provides resonance damping.
due to VSh, is given by (5). Multiple resonant controllers in parallel (10), one for each
𝑉𝑆ℎ harmonic frequency, allow compensation of several harmonics
𝐼𝑆ℎ =
𝑍𝑆 + 𝑍𝑡 + 𝑍𝐶 + 𝑍𝐴𝐶𝑇 frequencies at the same time.
In this case, to ensure ISh = 0 the hybrid branch must present 21
𝑘𝑟 𝑠
infinite impedance (ZACT = ∞) for VSh in order to isolate the C(s) = 𝑘𝑝 + ∑ (10)
capacitor bank from harmonics from voltage source, and 𝑠 2 + (ℎ𝜔0 )2
h=3
dampen resonances between source impedance and capacitor Fig. 4 shows the control strategy. The summation of all
bank. P+Resonant regulators, one for each frequency, generates the
In practical terms, the active filter is a controlled harmonic voltage reference Vafh needed to tune the Smart Impedance.
voltage source VAfh . This can be seen substituting VAfh in the The tuning procedure for P+Resonant controllers used in the
place of ZACT in equation (1) and (5). The equation (6) shows Smart Impedance is addressed in [8].
this result. The gains used are kp=10 and kr=2000 for all harmonic
𝑉𝑆ℎ (𝑍𝑡 + 𝑍𝐶 )𝐼𝐿ℎ 𝑉𝐴𝑓ℎ frequencies, these gains provide reasonable tradeoff between
𝐼𝑆ℎ = + −
𝑍𝑆 + 𝑍𝑡 + 𝑍𝐶
⏟ 𝑍𝑆 + 𝑍𝑡 + 𝑍𝐶
⏟ 𝑍𝑆 + 𝑍𝑡 + 𝑍𝐶
⏟ transient and steady-state performance, system stability and
contribution from
source distortion
contribution from
load distortion
contribution from
active filter
harmonic selectivity.
To guaranty Ish = 0, i.e., no harmonic current flowing into The resonant controller was digitally implemented in a
the source, VAfh has to be adjusted to impose the voltage TMS320F2812 32 bit fixed point DSP. The use of a correct
depicted in (7). discretization technique is fundamental, in order to get closer
𝑉𝐴𝑓ℎ = 𝑉𝑆ℎ + (𝑍𝑡 +𝑍𝐶 )𝐼𝐿ℎ digital controller from the continuous one. Resonant
The term VSh guarantees no harmonic current flowing from the controllers are especially sensible to discretization process due
source into the filter branch, which implies in infinite to its extremely narrow band and high gain, so any deviation
harmonic impedance. While the term (Zt + ZC)ILh cancels the in its resonant poles leads to performance loss.
harmonic voltage drop in the filter branch due to load current The use of inadequate discretization does not guarantee
harmonics, which means ideal short circuit (zero impedance). perfect tracking and may lead to deviation of resonance
The superposition of these two electronic generated frequency [21]. The Impulse Invariant and Zero-Order Hold
impedances characterizes the Smart Impedance behavior. (ZOH) present the best results among the others techniques
Smart Impedance control algorithm is based on [22], [23]. In this work ZOH method was used for the
Proportional Resonant Controller (P+Resonant), which is the controller discretization.
mathematical transformation of the Synchronous Frame with Another important point, in controller discrete
PI Controller [19]. P+Resonant controller expression is implementation, is the influence of the numeric resolution for
presented in (8). fixed-point representation. It has been highlighted in [20], the
𝑘𝑟 𝑠 variations in attenuation and tuning frequencies of digital
C(𝑠) = 𝑘𝑝 + 2 (8) filters due to numeric resolution. Considerable errors may
𝑠 + 𝜔2
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
4
occur, mainly in resonant controller and notch filters, when impedance, considering the Smart Impedance action, is a
implemented in 16-bit fixed point DSP’s. The use of 32-bit difficult task. The quasi-infinite bus creation is observed here
hardware provides great coefficient resolution and high in two different ways (procedures): a) change the
sampling rate (40080 Hz) ensure proper digital representation commutation angle of a full bridge diode rectifier with DC
of the resonant controllers. inductor choke; b) change in grid-forming converter voltage
and load current waveform of a full bridge rectifier with DC
capacitor filter.
The commutation angle (μ) of a full bridge single-phase
rectifier with DC inductor choke is mainly determined by the
AC side impedance given by (12) [25].
2𝜔𝐿𝑠
cos 𝜇 = 1 − 𝐼
𝑉𝑚𝑎𝑥 𝐷𝐶
Where ω is the system angular frequency in [rad/s], LS is the
source inductance, IDC is the mean value of rectifier DC
current and Vmax is the peak of AC source voltage. Notice that,
when LS is zero, cos(μ) is unity and μ is zero degree. On the
other hand, if LS becomes higher, cos(μ) decreases, while μ
increases. Hence, the commutation angle (μ) gives a measure
of the source equivalent impedance.
For a rectifier with DC capacitor filter, the commutation
Fig. 4. Multiple frequency resonant control. effect is not observed. However, it presents characteristic
current waveform and hence voltage waveform which are
V. QUASI-INFINITE BUSBAR strongly dependent from AC source equivalent impedance.
An isolated microgrid is considered “weaker” than the While the bridge diodes are conducting, just the source
interconnected grid. An AC system can be considered weak impedance limits the instantaneous current flowing into the
from two aspects [24]: a) the system impedance is high; b) the DC capacitor. Therefore, this impedance determines the
system inertia is low. A measure of the system strength is its current waveform. Larger the source impedance, larger is the
short-circuit power (SC), which is given by (11). current rise time and conduction time and smaller is the
𝑉𝑆2 current peak. Then, during diode conduction time, the terminal
𝑆𝐶 = voltage is “clipped” to the DC capacitor voltage causing
𝑍𝑡ℎ
Where VS is the microgrid voltage and Zth is the equivalent voltage drop in the source impedance leading to a very
Thevenin impedance. characteristic voltage distortion. Feeding by a strong source,
A system with high short-circuit power is considered a the rectifier current will have a narrow but high current peak.
strong grid, being less susceptible to voltage problems. An In this case the voltage drop is small because the impedance is
infinite bus would have infinite short-circuit power, which very low causing little voltage distortion.
implies in zero impedance, so the bus has constant voltage and
no disturbance can affect its terminal voltage. VI. PRACTICAL RESULTS
The Smart Impedance creates an ideal active short-circuit Practical tests on microgrid of Fig. 1 in islanded mode
for each harmonic frequency (h), as shown in Fig. 5(a). This demonstrate the Smart Impedance current harmonic
effect reduces drastically the source equivalent impedance for compensation, voltage disturbances mitigation and microgrid
each harmonic component (Zabh), as shown in Fig. 5(b). This equivalent impedance changing. The parameters of the grid-
short-circuit is created for one specific frequency or several forming converter and the Smart Impedance prototype are
frequencies at the same time. In this way, changing the PCC shown in Table I.
impedance, the system will behaves like an infinite bus for the TABLE I
chosen frequencies, in other words, a quasi-infinite busbar. SYSTEM SETUP
Grid-forming Converter
Rated Voltage 220 VRMS – 60 Hz
Rated Power 5 kVA
Sampling and Switching Frequency 10 kHz
Digital Signal Processor TMS320F2812
L1: 37 μH. L2: 500 μH.
LCL Filter
C1: 10 μF.
Coupling Transformer 5 kVA – 23 V:220 V
DC link Voltage 48VDC
(a) (b)
Smart Impedance
Fig. 5. (a) Microgrid equivalent circuit for harmonic componet “h”, with Coupling Transformer 7.5 kVA – 440 V:127 V
Smart Impedance. (b) System equivalent impedance for harmonic “h”.
Active Filter H-Bridge IGBT VSI
Sampling and Switching Frequency 40 kHz
The dynamic evaluation of the microgrid equivalent
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
5
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
6
Fig. 13. Microgrid voltage and Smart Impedance current during Load I active
compensation.
Fig. 11. Grid-forming converter voltage and current with Load I after active
compensation.
Fig. 14. Microgrid voltage and Load I current after active compensation.
(a) (b)
Fig. 12. Microgrid voltage (a) and current (b) harmonic spectrum after active
compensation of Load I.
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
7
Fig. 18. Microgrid voltage and Load II current after active compensation.
(a) (b)
The remaining voltage ripple in VC, observed in Fig. 15, is Fig. 19. Load I power comparison (a) before and (b) after compensation.
caused by a grid-forming converter dead-time compensation
mismatch. This distortion was not compensated because, in Fig. 20 depicts power measurements for Load II. The load
this implementation, just the load current effect is mitigated, active power increases about 15%, from 0.97kW in Fig. 20(a),
which indirectly improves the microgrid voltage. before compensation, to 1.12kW in Fig. 20(b), after
Nevertheless, voltage THD is kept inside an acceptable value. compensation. In this case, the reduction of voltage drop on
The displacement factor between voltage and current, grid-forming converter output impedance causes an
presented in Fig. 11 and Fig. 15, is due Smart Impedance improvement on AC voltage, which reflects in higher DC
capacitor bank. When the load has an inductive displacement capacitor voltage, consequently increasing the power delivered
power factor (DPF), which is the usual case for mixed loads to the load. For Load II, the CosΦ, which considers only
composed by linear and nonlinear loads, this capacitor fundamental frequency, presents a small variation, from 0.99
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
8
(Fig. 20a) to 0.98 (Fig. 20b). The PF, which considers the Personnel (CAPES), Minas Gerais Research Foundation
harmonic current content, is reduced from 0.76 (Fig. 20a) to (FAPEMIG), and Brazilian Electricity Regulatory Agency
0.61 (Fig. 20b). This happens because the Load II current Research and Development (ANEEL R&D) for supporting
THD increases when the source impedance gets smaller, in this project, and the Editor and the reviewers for improving
other words the grid gets stronger. the quality of this paper.
REFERENCES
[1] J. He, Y. W. Li, R. Wang, and C. Zhang, "Analysis and Mitigation of
Resonance Propagation in Grid-Connected and Islanding Microgrids",
IEEE Trans. Energy Conversion, vol.30, no.1, pp.70-81, March 2015.
[2] J. M. Guerrero, P. C. Loh, T. L. Lee, and M. Chandorkar, "Advanced
Control Architectures for Intelligent Microgrids—Part II: Power
Quality, Energy Storage, and AC/DC Microgrids," IEEE Trans.
Industrial Electronics, vol. 60, no. 4, pp. 1263-1270, April 2013.
[3] A. Micallef, M. Apap, C. Spiteri-Staines, J. M. Guerrero, and J. C.
Vasquez, "Reactive Power Sharing and Voltage Harmonic Distortion
Compensation of Droop Controlled Single Phase Islanded Microgrids,"
(a) (b) IEEE Trans. Smart Grid, vol.5, no.3, pp.1149-1158, May 2014.
[4] M. Savaghebi, A. Jalilian, J. C. Vasquez, and J. M. Guerrero,
Fig. 20. Load II power comparison (a) before and (b) after compensation. "Secondary Control for Voltage Quality Enhancement in Microgrids,"
IEEE Trans. Smart Grid, vol.3, no.4, pp.1893-1902, Dec. 2012.
VII. CONCLUSIONS [5] S. Munir and Y. W. Li, "Residential Distribution System Harmonic
Compensation Using PV Interfacing Inverter," IEEE Trans. Smart Grid,
Distributed generation (DG) is a very important issue vol.4, no.2, pp.816-827, June 2013.
nowadays. Most DG implementations use power electronics [6] X. Luo, Z. Akhtar, C. K. Lee, B. Chaudhuri, S. C. Tan, and S. Y. R. Hui,
converters as front-end and are integrated in microgrids that "Distributed Voltage Control with Electric Springs: Comparison with
STATCOM," IEEE Trans. Smart Grid, vol.6, no.1, pp.209-219, Jan.
can operate isolated from the main grid. These microgrids are 2015.
much weaker, concerning equivalent impedance, than the [7] T.-L. Lee, Y.-C. Wang, J.-C. Li, and J. M. Guerrero, "Hybrid Active
interconnected power system, what makes them more Filter With Variable Conductance for Harmonic Resonance Suppression
in Industrial Power Systems," IEEE Trans. Industrial Electronics,
susceptible to power quality problems. Converter output LCL vol.62, no.2, pp.746-756, Feb. 2015.
filters can become a source of harmonic parallel resonance [8] R. B. Gonzatti, S. C. Ferreira, C. H. da Silva, R. R. Pereira, L. E. Borges
when supplying nonlinear loads, degrading microgrid voltage. da Silva, and G. Lambert-Torres, "Smart Impedance: A New Way to
Look at Hybrid Filters," IEEE Trans. Smart Grid, vol.7, no.2, pp.837-
Smart Impedance working principle was presented and 846, March 2016.
practical results have shown that it is a reasonable solution to [9] R. B. Gonzatti, S. C. Ferreira, C. H. da Silva, R. R. Pereira, L. E. Borges
mitigate harmonic currents undesired effects in isolated da Silva, G. Lambert-Torres, and R. M. R. Pereira, "Implementation of a
grid-forming converter based on modified synchronous reference
microgrids. The elimination of these harmonic currents reduce frame," 40th Ann. Conf. of the IEEE Industrial Electronics Society,
voltage distortions and suppress parallel resonances, IECON 2014, pp.2116-2121, Oct. 29-Nov. 1 2014.
improving microgrid voltage quality. Finally, these features [10] D. E. Olivares, A. Mehrizi-Sani, A.H. Etemadi, C. A. Canizares, R.
Iravani, M. Kazerani, A.H. Hajimiragha, O. Gomis-Bellmunt, M.
can be interpreted as a transformation of a weak microgrid Saeedifard, R. Palma-Behnke, G. A. Jimenez-Estevez, and N.D.
into a quasi-infinite bus when its equivalent impedance is Hatziargyriou, "Trends in Microgrid Control," IEEE Trans. Smart Grid,
reduced. This effect, in regular power grids, is achieved with vol.5, no.4, pp.1905-1919, July 2014.
the addition of more generators in parallel. The proposed [11] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodríguez, "Control of Power
Converters in AC Microgrids," IEEE Trans. Power Electronics, vol.27,
approach does not require additional generation capacity no.11, pp.4734-4749, Nov. 2012.
(active power supply) to obtain a similar effect. The Smart [12] D. Dong, T. Thacker, I. Cvetkovic, R. Burgos, D. Boroyevich, F. Wang,
Impedance achieve similar result just dealing with harmonic and G. Skutt, "Modes of Operation and System-Level Control of Single-
Phase Bidirectional PWM Converter for Microgrid Systems," IEEE
power. Trans. Smart Grid, vol.3, no.1, pp.93-104, March 2012.
Comparing to other techniques, based on modifying output [13] S. Kouro, J. I. Leon, D. Vinnikov, and L. G. Franquelo, "Grid-
converter admittance, this approach is meant to be a “plug and Connected Photovoltaic Systems: An Overview of Recent Research and
Emerging PV Converter Technology," IEEE Industrial Electronics
play” solution, not requiring any modification in already Magazine, vol.9, no.1, pp.47-61, March 2015.
installed converters. In addition, it provides both current and [14] C. Huang, F. Li, and Z. Jin, "Maximum Power Point Tracking Strategy
voltage harmonic mitigation, which is not commonly reached for Large-Scale Wind Generation Systems Considering Wind Turbine
Dynamics," IEEE Trans. Industrial Electronics, vol.62, no.4, pp.2530-
in harmonic droop schemes. The solution has shown to be 2539, April 2015.
robust, concerning the operational behavior, low power rate [15] R. E. Cosse, M. D. Alford, M. Hajiaghajani, and E. R. Hamilton,
relating to load apparent power and, due to its shunt "Fundamentals of Turbine/Generator Speed Control: A Graphical
Approach for Islanding Applications," IEEE Industry Applications
connection, do not compromise the basic microgrid operation Magazine, vol.19, no.4, pp.56-62, Jul/Aug. 2013.
in case of failure. [16] W. Sinsukthavorn, E. Ortjohann, A. Mohd, N. Hamsic and D. Morton,
"Control Strategy for Three-/Four-Wire-Inverter-Based Distributed
ACKNOWLEDGMENT Generation," IEEE Trans. Industrial Electronics, vol.59, no.10, pp.
3890-3899, Oct. 2012.
The authors would like to thank the National Council for [17] H. Bevrani and S. Shokoohi, "An Intelligent Droop Control for
Scientific and Technological Development (CNPq), Simultaneous Voltage and Frequency Regulation in Islanded
Microgrids," IEEE Trans. Smart Grid, vol.4, no.3, pp. 1505-1513, Sept.
Coordination for the Improvement of Higher Education 2013.
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TSG.2016.2590986, IEEE
Transactions on Smart Grid
9
[18] C. H. da Silva, R. R. Pereira, L. E. Borges da Silva, G. Lambert-Torres, Rondineli Rodrigues Pereira (M’14) received the
J. O. P. Pinto, and S. U. Ahn, "Dead-time compensation in Shunt Active B.Sc. degree in computation engineering, the
Power Filters using fast feedback loop," 13th International Conference M.Sc., and D.Sc. degrees in electrical engineering
on Harmonics and Quality of Power, 2008. ICHQP 2008, Wollongong, from the Itajuba Federal University, Itajuba, Brazil,
NSW, 2008, pp. 1-4. in 2007, 2009, and 2011, respectively. From 2010
[19] D. N. Zmood, D. G. Holmes, and G. H. Bode, "Frequency-domain to 2012, he was a Professor at Federal Center of
analysis of three-phase linear current regulators" IEEE Trans. Industry Technological Education of Minas Gerais,
Applications, vol.37, no.2, pp.601-610, Mar/Apr 2001. Leopoldina, Brazil. Since 2013, he is a Professor at
[20] M. J. Newman, D. N. Zmood and D. G. Holmes, "Stationary frame Itajuba Federal University. His research interests
harmonic reference generation for active filter systems," IEEE Trans.
include digital signal processing, adaptive filters,
Industry Applications, vol.38, no.6, pp. 1591- 1599, Nov/Dec 2002.
control algorithms for active power filters, harmonics, and power quality. Dr.
[21] D. N. Zmood and D. G. Holmes, "Stationary frame current regulation of
Pereira was a recipient of the Second Prize Paper Award from the Industrial
PWM inverters with zero steady-state error," IEEE Trans. Power
Electronics, vol.18, no.3, pp. 814- 822, May 2003. Automation and Control Committee of the IEEE Industry Applications
[22] F.J. Rodriguez, E. Bueno, M. Aredes, L.G.B. Rolim, F.A.S. Neves, and Society (2009).
M.C. Cavalcanti, "Discrete-time implementation of second order
generalized integrators for grid converters," 34th Ann. Conf. of IEEE
Industrial Electronics, 2008. IECON 2008. pp.176-181, Nov. 10-13, Luiz Eduardo Borges da Silva (M’88–SM’13)
2008. received the B.S. and M.Sc. degrees in electrical
[23] A. G. Yepes, F. D. Freijedo, J. Doval-Gandoy, O. Lopez, J. Malvar and engineering from Itajuba Federal University
P. Fernandez-Comesaña, "Effects of Discretization Methods on the (UNIFEI), Itajuba, Brazil, in 1977 and 1982,
Performance of Resonant Controllers," IEEE Trans. Power Electronics, respectively, and the Ph.D. degree from École
vol.25, no.7, pp.1692-1712, July 2010. Polytechnique de Montréal, Montréal, QC, Canada,
[24] P. Kundur “Power System Stability and Control” McGraw-Hill in 1988.
Education, 1st Ed., 1994. 1176p. He was a Visiting Professor with the University
[25] N. Mohan, T. M. Undeland, and W. P. Robbins, “Power Electronics: of Tennessee, Knoxville,TN, USA, in 1998. He is
Converters, Applications and Design” Wiley, 3 rd Ed., 2002. 824p. currently a Professor of the Electronic Engineering
[26] F.Z. Peng, "Harmonic sources and filtering approaches,” IEEE Industry Institute and Head of Power Electronics at UNIFEI. He has directed many
Applications Magazine, vol.7, no.4, pp.18-25, Jul/Aug. 2001. projects in the field of industrial electronics, and coauthored over 300
[27] F. Wang, J. L. Duarte and M. A. M. Hendrix, "Grid-Interfacing technical papers. He has supervised more than 80 master and doctoral thesis.
Converter Systems With Enhanced Voltage Quality for Microgrid
His research focuses on power electronics, electronic power systems, power
Application—Concept and Implementation," IEEE Trans. Power
converters, and applications of adaptive and intelligent control in industrial
Electronics, vol.26, no.12, pp.3501-3513, Dec. 2011.
problems.
1949-3053 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.