Additional stiffener

HVAC DUCT SUPPORTS LAYOUT


(75x75x6) to be
provided at the
bottom of deck plate
Provide stiffener if the
load on the support
exceeding 150 kg.
Supports (refer
sheet -3 for more
details
(MM)

NOTE: ALL VERTICAL LEG DIMESNSIONS 'B' & 'C' SHALL BE VERIFIED AT SITE BEFORE INSTALLATION. SLOPE OF CONTAINER
SHALL BE CONSIDERED AND SHALL BE ADJUSTED IN VERTICAL MEMBERS WHEREVER APPLICABLE.
kindly provide the Bolt hole shall be D+2 mm. D is dia
details for these of the bolt. Confirm the same with
Is this 100 mm bolt holes.. Can installation team. Edge distance
sufficient?? these bolt holes be 1.75 X D shall be maintained.
Please with installation team. drilled at site?

No issue. Can be
welded to roof
Support part-1 plate.
(welded to the
roof plate)
Vertical leg length varies
depending upon the slope of
Support part-2..( removable type. Bolt container. how to provide the Estimate the support height
connected to the fixed part-1) support dimensions for these based on location on the
vertical members.? roof and TOS of support.
Discuss with Palani if
guidance required.

there is gap considered between


the support part-1 and 2. Is there
any purticular space to be
maintained. Can these done at
site.

Please with installation team.