DESCRIPTIONS

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


AC

REVISIONS
N  H
PAR
(E) PROPANE TANKS

RIOT

VA
T  PL

LL
 B

EY
LV
NOTE: INTERSTITIAL SPACE OF UNDERGROUND TANK AND DOUBLE D
WALL SUMPS SHALL BE FILLED WITH A BRINE SOLUTION PROVIDED BY
TANK MANUFACTURER. UDC'S SHALL BE FILLED WITH PROPYLENE
GYCOL PROVIDED BY MANUFACTURER.

B L V D

DATE:

5/31/12
NOTE: ALL PIPING SHALL HAVE SLOPE BACK TO THE TANKS WITH A

APPROACH
MINIMUM 1/8" PER LINEAR FOOT. (N) S.W. VENT BOX

NO.
13

1
(E) EAVE
SCOPE OF WORK (NEW TANK SYSTEM)

1
PREPARE NEW TANK HOLE AND INSTALL (1) DIESEL 10,000G D.W.
(E)  HEALY  CLEAN FIBERGLASS UST (BRINE SOLUTION FILLED AND BUILT PER
AIR  SEPARATOR MANUFACTURER AND AB2481 SPECIFICATIONS). DEADMEN
PIPING  LEGEND REQUIRED.

H A C I E N D A
(E) VEEDER ROOT

NEW DIESEL VPH PRODUCT PIPING


TLS-350 MONITOR
2
INSTALL D.W. FIBERGLASS FILL AND TURBINE SUMPS (BRINE
9 FILLED), MANWAYS, AND SPILL BUCKET.
NEW DIESEL VPH VENT PIPING
3
INSTALL D.W. FIBERGLASS PRODUCT AND VENT PIPING
NEW 87 / 91 PRODUCT PIPING (NON VPH) (N) D.W. FIBERGLASS VENT
FOR DIESEL UNDER CONTINUOUS VACUUM.
PIPING FOR 87 AND 91
NEW 87 / 91 VAPOR PIPING (NON VPH) (NON VPH)
INSTALL D.W. UNDER DISPENSER CONTAINMENTS FOR
4
14 (2) NEW 3+1 DISPENSERS. (PROPLYENE GLYCOL FILLED)
NEW 87 / 91 VENT PIPING (NON VPH)
(E) 3+0 DISPENSERS
W/ NEW S.W. UDCS
(TYP. OF 4) 5
INSTALL D.W. FIBERGLASS VENT BOX (PROPYLENE
(e) direct bury
spill buckets
GLYCOL FILLED) AND DIESEL VENT RISER.
w/ manhole cover 16 12 15
(87 & 91)
7 INSTALL (2) NEW GILBARCO 3+1 DISPENSERS WITH
(E) BLDG

DESIGN:
HEALY HANGING HARDWARE AND VEEDER ROOT ISD
EQUIPMENT.
(e) 12k ”91"
ust 8
BACKFILL WITH WASHED APPROVED PEA GRAVEL, SET
MAN WAYS FOR PROPER SLOPE, AND POUR NEW
CONCRETE TO MATCH EXISTING.
EXISTING VEEDER ROOT SHALL BE RE-PROGRAMMED
9 PER AB2481 AND CURRENT CODE REQUIREMENTS.

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


(e) 12k ”87"

SCOPE OF WORK (EXIST TANK SYSTEMS)

CSLB#952213  A,  HAZ,  Exp.  09/30/12


ust

P.O.  BOX  6219,  WHITTIER,  CA  90609


1 2 SAW CUT, BREAK CONCRETE, EXCAVATE, AND REMOVE ALL

S O U T H
10
EXISTING SINGLE WALL PRODUCT, VAPOR, AND VENT PIPING.
REMOVE (4) EXISTING STEEL SHALLOW UDCS.
8
11 TAKE SOIL SAMPLES AS DIRECTED BY LADPW PERSONNEL AND
(n) 10k diesel TRANSPORT TO CERTIFIED LAB FOR ANAYLSIS. PROVIDE
xerxes ust SAMPLING REPORT TO LADPW WITHIN 30 DAYS.

12 INSTALL (4) NEW SINGLE WALL DEEP FIBERGLASS UDCS WITH


(E) CANOPY LIQUID SENSORS

CONTRACTOR:
(N) D.W. FIBERGLASS PRODUCT/
VAPOR PIPING FOR 87 AND 91
(NON VPH)
14 10 11 13
INSTALL NEW SINGLE WALL FIBERGLASS VENT BOX WITH LIQUID
(N) D.W. VENT
(N) D.W. DIESEL VPH SENSOR
PRODUCT PIPING
BOX FOR DIESEL
(n) d.w. diesel vph
vent piping 3
(N) CANOPY
14
INSTALL NEW DOUBLE WALL FIBERGLASS PRODUCT, VAPOR,
5
AND VENT PIPING (NON-VPH) FOR EXISTING 87 AND 91 TANKS.
3

15 RE-INSTALL (4) EXISTING DISPENSERS AND HANGING


HARDWARE ON EXISTING ISLANDS.

APPROACH
16
BACKFILL WITH WASHED PEA GRAVEL AND POUR NEW
CONCRETE TO MATCH EXISTING.
RELOCATE VAPOR
PRESSURE SENSOR
HERE

CITY OF INDUSTRY, CA 91745


GENERAL NOTES
-­‐  An  individual  (s)  installing  UST  components  shall  meet  the  following  requirments,  or  work  under
the  direct  and  personal  supervision  of  an  individual  physically  present  at  the  work  site  who  meets
the  following  requirements:
APP
ROA (N) 3+1 DISPENSERS

221 S HACIENDA BLVD


CH W/ NEW D.W. UDCS 1.  The  individual  has  been  adequately  trained  as  evidenced  by  a  current  cerVficate
(TYP. OF 2) of  training  by  the  manufacturer(s)  of  the  UST  components.
4 7 2.  The  individual  shall  possess  a  current  UST  system  installer  cerVficate  from  the  
ICC,  indicaVng  that  the  individual  has  passed  the  ICC  UST  installaVon  /  retrofi^ng  exam
-­‐  The  service  technician  shall  possess  or  work  under  direct  and  personal  supervision
of  an  individual  physically  present  at  the  work  site  who  possesses  a  current  cerVficate

E A
from  the  ICC,  indicaVng  that  the  individual  has  passed  the  California  UST  Service
Technician  Exam

S T
-­‐  An  ICC  Service  Technician  with  Veeder-­‐Root  manufacturer's  training  cerVficaVon
 will  perform  a  monitoring  system  cerVficaVon.
-­‐  Contractor  shall  contact  Dig  Alert  at  1-­‐800-­‐422-­‐4133  48  hours  prior  to  any

V A
excavaVon.
-­‐  New  Piping  is  NOV  (Smith  Fibercast),  New  piping  will  meet  the  revised  UL  971
standard  and  shall  be  installed  per  manufacturer's  specificaVons.

SITE PLAN
HASSAN 28
L L -­‐  All  piping  to  be  used  (piping,  couplings,  sealant,  etc.)  shall  be  compaVble  and  used
as  per  naVonally  recognized  codes.

E Y -­‐  Tank  System(S)  shall  be  inspected  by  all  required  agencies  at  three  (3)  separate  construcVon
phases:
1.  Tracer  Tight  ELD  tesVng,  Primary  piping  pneumaVcally  tested  for  30  minutes.  Inert

B L APP
gas  will  be  used.
2.  InspecVon  of  all  secondary  containment,  including  tesVng,  in  accordance  with
manufacturer's  guidlines.  New  Sumps  shall  be  hydrostaVcally  tested  for  60  minutes.

V D
ROA

PROJECT:
CH
3.  At  the  compleVon  of  the  upgrade  project  a  licensed  tank  integrity  tester  will
perform  a  pipeline  integrity  test  prior  to  the  final  inspecVon.
4.  Final  inspecVon,  including  all  porVons  of  the  leak  detecVon  system.
-­‐  State  Water  Resourses  Forms  B  and  C  shall  be  completed  and  submiied
 to  L.A.C.D.P.W.
-­‐  All  work  will  be  performed  as  per  manufacturer's  specificaVons.
DATE  DRAWN:

5/4/16
SCALE:

1  :  10
DRAWN  BY: CHECKED  BY:

VEEDER  ROOT  VACUUM  ZONE  TABLE B.  BURNS


ZONE PIPE VOLUME
GRAPHIC  SCALE PROJECT  #
PRODUCT LENGTH (FT) (GALLONS)

1 50 11.5
10' 0' 20' 221SHACIENDA-­‐001
DIESEL (3”X2” SMITH PIPE = 0.23 GAL/FT) PRODUCT
DIESEL (3”X2” SMITH PIPE = 0.23 GAL/FT) 2 VENT LINE 31 7.13 SHEET:

SP-­‐1
APP.
BY:

BB
#
NOTES: UST INSTALLATION
1 SLOPE CONCRETE AWAY FROM ALL MANHOLES 1" RISE OVER 12" RUN.

CL 2 FIBER REINFORCEMENT TO BE USED. PREMIX UNIFORMLY THROUGHOUT


CONCRETE.

REINFORCING BARS TO BE NO LESS THAN 2" AND NO MORE THAN 4" FROM

DESCRIPTIONS
3

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


SURFACE.

REVISIONS
4 REINFORCE CONCRETE SLAB AROUND MANHOLE WITH (4) #4 REBAR 60" IN
LENGTH. PLACE REBAR 6" FROM SIDES OF BOX.

SINGLE 1" CONDUIT TO EACH SUBMERSIBLE PUMP. PROVIDE SEAL-OFF AT


10,000 GALLON CAPACITY 5 SUMP & BUILDING WIRING TROUGH. CONTAINS LINE VOLTAGE WIRING. LAST
TWO FEET TO SUMPS SHALL BE PVC COATED RIGID.

1 ONE 1" STANDARD MONITORING HOMERUN CONDUIT TO EACH TANK AND ONE
8" 8" 1" VACUUM MONITORING HOMERUN CONDUIT TO EACH TANK. FOR STANDARD
MONITORING DEVICES, LOOP CONTAINMENT SUMP SENSORS, PLLD & TANK
GAUGE TO TANK INTERSTITIAL SENSOR LOCATION AND HOMERUN TOBLDG.

MONITOR
FOR VACUUM MONITORING LOCATIONS ROUTE CROSSOVER CONDUITS

RISER
TANK LIFTING LUGS CONTAINING VACUUM TUBING BETWEEN FILL AND TURBINE SUMP. A
(TYP.) 48" DIA. TURBINE SUMP 6 SEPARATE CONDUIT FROM TURBINE SUMP IS USED FOR VACUUM SENSORS TO
42" DIA. FILL SUMP BUILDING. PROVIDE SEAL-OFFS IN BUILDING & PRIOR TO LEAVING HAZARDOUS
BRINE TANK GAUGE AREA. ROUTE TO INTRINSICALLY SAFE TROUGH IN BUILDING. CONDUITS SHALL
RESERVOIR AND LOCATION CONTAIN ONLY LOW VOLTAGE WIRING FOR SENSORS. LAST TWO FEET TO
SUMPS SHALL BE PVC COATED RIGID.

DATE:
INTERSTITIAL
7’-8” O.D. SHELL
8’-0” O.D. RIBS

MONITOR

5/31/12
8"
CL CL

8"
USE PEA GRAVEL CONSISTING OF NATURALLY ROUNDED AGGREGATE, MIN

NO.
1/2" & MAX OF 3/4" IN SIZE, FREE OF CLAY, SLAG, CINDERS, OR DEBRIS. ALL

1
7 SUBSTITUTES MUST BE APPROVED BY MANUFACTURER'S & OWNER'S FIELD
REPRESENTATIVE.
ANCHOR STRAP
LOCATIONS

CL
8 NOT USED.

RISER
FILL
9 NOT USED.

TANK PAD MINIMUM 2'-0" OFF OUTSIDE WALLS OF TANKS, AND MUST COVER
10 THE FOOTPRINT OF THE TANKS. REQUIRED TO PROVIDE FOR PROPER TANK
HOLD DOWN, AND TO PREVENT ACCIDENTAL DRILLING INTO TANK.

11 CUT CORNER WHERE MEETING ASPHALT PAVING ONLY. SQUARE CORNERS


WHERE MEETING CONCRETE.

DESIGN:
31' - 61/2"

MANUFACTURER
SUPPLIED 18"X8"X30' DEADMAN
10K DIESEL UNDERGROUND TANK PLAN VIEW (TYP. OF 2)

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


CSLB#952213  A,  HAZ,  Exp.  09/30/12
P.O.  BOX  6219,  WHITTIER,  CA  90609
8" THICK CONCRETE SLAB 2 3
(TYP.)
(TYP.) 3 4

(TYP.) 1 10 11 (TYP.)

10 11 (TYP.)

CONTRACTOR:
3" PEA GRAVEL MIN. TO
J-BOX PREVENT LOAD TRANSFER
TO TOP OF TANK 7
7
66 4" FIBERGLASS

MINIMUM BURY DEPTH


ANNULAR RISER

4'-0"
DUAL FLOAT HYDROSTATIC 6
MONITORING SENSOR 118 (N) 3"X2" FIBERGLASS 5

CITY OF INDUSTRY, CA 91745


VENT PIPING
(N) 3"X2" FIBERGLASS
6 PRODUCT PIPING
HOME RUN TO
BUILDING 1

10K DIESEL UST DETAILS


HYDROSTATIC 12
RESERVOIR
SLOPE SIDES OF TANK HOLE OR USE
SHORING FOR ALL TANK
EXCAVATIONS IN ACCORDANCE WITH
OSHA 1926 SUBPART P, OSHA

221 S HACIENDA BLVD


STANDARDS - EXCAVATIONS; FINAL
RULE OCTOBER 1, 1989

DROP TUBE
12 W/ FLAPPER
SET @ 95%

BACKFILL WITH PEAGRAVEL


7 AS PER TANK TANK LEVEL GAUGE
119 121 ALARM AT 90%

HASSAN 28
MANUFACTURER

8'-0"
SPECIFICATIONS. (TYP.) CAPACITY

PROJECT:
12"x12"x11GA STEEL STRIKER PLATES TYP. 12"x24"x11GA STEEL STRIKER PLATES TYP.
5 1/2"
MAX.

UNDER ALL OPENINGS W/O MANWAYS ON UNDER ALL OPENINGS W/ MANWAYS ON


ONLY IF CONDITIONS

FIBERGLASS TANK (BY TANK MANF.) FIBERGLASS TANK (BY TANK MANF.)
MIN.

45°
4'-0" MAX.

5"
2"
PERMIT

DATE  DRAWN:

{1'-0" MIN. PEA GRAVEL


9/21/15
INSTALLED OVER
1'-0"

2'-0"
COMPACTED SOIL} TRAPPER SCALE:
TANK SHALL BE SET DEAD LEVEL SCREEN

1  :  10
DRAWN  BY: CHECKED  BY:
NATIVE
END OF TANK VIRGIN SOIL END OF TANK
2' MIN.
10
31' - 61/2" 2' MIN.
10
B.  BURNS
PROJECT  #
DEADMEN NOT SHOW FOR CLARITY. SEE UST PLAN VIEW
ABOVE FOR DETAILS AND ANCHOR STRAP LOCATIONS 221SHACIENDA-­‐001
10K DIESEL UNDERGROUND TANK SECTION DETAIL SHEET:

DT-­‐1
APP.
UDC / DISPENSER DETAILS FOR NEW DIESEL TANK SYSTEM (TYP. OF 2)

BY:

BB
3+1 MPD DISPENSER
24 (TYP. OF 2)

1" N.P.T. VAPOR ADA COMPLIANCE NOTE:


1-1/2" N.P.T. INLET (3) RECOVERY OUTLET, WHEN DISPENSERS ARE INSTALLED AS
OPTIONAL

DESCRIPTIONS
1'-5" 1'-5" SHOWN ON THIS DRAWING, THE

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


REQUIREMENTS REGARDING HANDICAPPED

REVISIONS
VERTICAL AND HORIZONTAL ACCESSIBILITY
ARE FULLY MET.

CL 25
30
CL

26 31

PRODUCT #1 (DIESEL) 5/8" x 2" SLOTS FOR ANCHOR


BOLTS, 6 SPACES
SIDE "A"
JUNCTION BOX

DATE:
32
27

5/31/12
A-A DISPENSER MOUNTING DIAGRAM
SCALE: 1"=1'-0"

NO.

1
3'-7"

9"

6" 6"

33

SEE ADA COMPLIANCE NOTE


STABILIZER
BAR 28

DISPENSER
SUMP FRAME
1'-7"

4'-6"

3'-0"

DESIGN:
DISPENSER ISLAND
6" 6" NOTE: CONDUITS SHALL (TYP.)
PENETRATE SUMP FRAME
AT EITHER "A" OR "B" SIDE
9" RUN CONDUITS THROUGH HOLES IN OF THE DISPENSER. DO
DISPENSER SUMP FRAME (TYP.) NOT CUT CUT SIDE PANELS
OF DISPENSER CONCRETE SLAB
B-B DISPENSER CONTAINMENT SUMP PLAN VIEW

6"
6"
SCALE: 1" = 1'-0"

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


6"

6"

CSLB#952213  A,  HAZ,  Exp.  09/30/12


P.O.  BOX  6219,  WHITTIER,  CA  90609
SUMP SENSOR
J-BOX DISPENSER

1'-6"
J-BOX

DISPENSER PRODUCT SHEAR


SKIN 77
VALVE (TYP.)

ELBY CAPPED VAPOR SHEAR


ELBOW (TYP.) 78 VALVE (TYP.)
ELECTRICAL CONDUITS
SEAL OFF (TYP.) GLYCOL RESERVOIR DISPENSER CONTAINMENT
35 SUMP
(PROVIDED BY BRAVO)

CONTRACTOR:
1” CONDUITS
ROUTED THROUGH 127 HYDROSTATIC SENSOR ADA REQUIRES 48"x30" MIN. AREA IN FRONT OF
HOLES IN SUMP {\LBOTH SIDES} OF MPD, SLOPE NOT TO EXCEED
FRAME (TYP.) 2%. THERE SHALL BE A 10" MIN DISTANCE FROM
THE EDGE OF PLATFORM TO DISPENSER FACE FOR
SIDE REACH

SIDE ELEVATION
1-1/2"x18" FLEX
FRONT ELEVATION - DISPENSER W/DIESEL (3+1)
76 CONNECTOR (TYP. OF 4)

3+1 UDC/DISPENSER DETAILS


CITY OF INDUSTRY, CA 91745
3"X2" D.W. FIBERGLASS
ENTRY FITTING 104 3" INSIDE 4" FRP
57 66 VAPOR RECOVERY LINE
2" INSIDE 3" FRP 51 57 87 LINE 91 LINE vapor line
PRODUCT LINE DSL LINE (NON (NON VPH) 4”X3” D.W. FIBERGLASS
(VPH) (non vph) 107
VPH) ENTRY FITTING

DOUBLE WALL UNDER


SUMP SENSOR IN 35 DISPENSER

221 S HACIENDA BLVD


117
HOLDER CONTAINMENT SUMP
DISPENSER AT ISLAND INSTALLATION DETAILS
SCALE: 1" = 1'-0"
ELEVATION DETAIL @ DISPENSER W/DIESEL (3+1)
SCALE: 1"=1'-0"

NOTE: GLYCOL HYDROSTATIC RESERVOIR


NOT SHOWN FOR CLARITY
29 HEALY VAC MOTOR
NOTE: FOR ALL NON-VPH ENTRY/TEST FITTING: DRAIN VALVE TO BE
VP  1000
 HEALY

INSTALLED POINTING DOWNWARDS, AT THE 6'OCLOCK POSITION"


GLYCOL RESERVOIR
(PROVIDED BY BRAVO)
132 VAPOR PRESSURE SENSOR
(ONLY 1 PER SITE)

HASSAN 28
SUMP SENSOR J-BOX DISPENSER
131 VAPOR FLOW SENSOR
DISPENSER JUNCTION NOTE: ONLY MANUFACTURER APPROVED PROPYLENE GYCOL
WAYNE OVATION DISPENSER BOX (TYP.)
FRAME PRODUCT SHEAR SOLUTION CAN BE USED TO FILL UDC INTERSTITIALS
77
VALVE (TYP.)
DISPENSER SUMP FRAME 127 HYDROSTATIC SENSOR
78 VAPOR SHEAR VALVE
(TYP.)

PROJECT:
1-1/2"x18" FLEX CONNECTOR 76
ELBY CAPPED ELBOW
(TYP.) SEAL-OFF (TYP.)
U
RL

4”X3” D.W. FIBERGLASS


ENTRY FITTING 107 DISPENSER
2" FRP TEE FITTING W/ ISLAND (TYP.)
3 WAY VALVE FOR DIESEL REDUCER BUSHINGS AT 1
PRODUCTSECONDARY IN 135 DISPENSER ONLY, 2" FRP
3+1 UDC'S FOR TESTING ELBOW AT ALL OTHERS RUN CONDUITS THROUGH DATE  DRAWN:
VACUUM OF PIPING SYSTEM HOLES IN DISPENSER SUMP
FRAME "A" SIDE OR "B" SIDE
O.K. (TYP.) 9/21/15
3" INSIDE 4" FRP
VAPOR RECOVERY 57 66 SCALE:
LINE 1” DISPENSER SENSOR

NTC
1" CONDUITS MONITORING MOUNTING
ROUTED THROUGH CONDUIT HANGER KIT (TYP.)
2" INSIDE 3" FRP DIESEL HOLES IN SUMP 1" SPARE
PRODUCT LINE. (87 & 91 FRAME (TYP.)
LINES DO NOT HAVE 3- 1” DISPENSER POWER 117 SUMP MONITOR DRAWN  BY: CHECKED  BY:
WAY VALVES) 51 57 & DATA CONDUIT LIQUID SENSOR
SUMP SENSOR IN IN HOLDER
117 HOLDER B.  BURNS
PEA GRAVEL COMPACTED OR
3”X2” D.W. FIBERGLASS NATIVE SOIL PROJECT  #
ENTRY FITTING 104 (TYPICAL)
DOUBLE WALL UNDER
35 DISPENSER CONTAINMENT
SUMP
221SHACIENDA-­‐001
DISPENSER CONTAINMENT SUMP CONDUIT ROUTING DETAIL SHEET:
SIDE VIEW @ DISPENSER W/DIESEL (3+1) SCALE: NONE
SCALE: 1"=1'-0"

DT-­‐2
APP.
BY:
80 MECHANICAL LINE LEAK DETECTOR

BB
13 15
MINI HYDROSTATIC SENSOR 18" MANHOLE
IN BRINE FACTORY SUPPLIED 127 18" 1-1/2" MIN. CROWN
RESERVOIR 16 (TYP. ALL OPENINGS) 134 4" RISER PIPE CAP
(TYP.) J-BOX (TYP.) (#330020-435)

3" PEA GRAVEL MIN. TO 79 2 HP TURBINE MOTOR


PREVENT LOAD TRANSFER

DESCRIPTIONS

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


TO TOP OF TANK

REVISIONS
J-BOX (TYP.) 48" XERXES DOUBLE WALL BRINE
1 FILLED SUMP PEA GRAVEL 9
7
BACKFILL
SEAL-OFF (TYP.)
SEAL OFF 16 4" FRP ANNULAR
RISER 66
2 SENSOR-NO TANK VACUUM SENSOR 75 2"x24" FLEX (TYP.)
ASSEMBLY KIT W/ MOUNTING BRACKET 130 129 128
6
3/4" HOME RUN TO
BUILDING (VAC SENSORS) LOOP VACUUM TUBING FROM
PRODUCT PIPING TO VAC SENSOR 6 TO TURBINE
FIBERGLASS ENTRY FITTING 103 SUMP

DATE:
HOME RUN
103 FIBERGLASS ENTRY FITTING

5/31/12
6
3/4" POWER CONDUIT BRINE RESERVOIR
2" INSIDE 3" FIBERGLASS
VENT PIPING 3/4" MONITORING CONDUIT TO FILL SUMP

NO.
51 57
(VACUUM MONITORED)

1
51 57 2" INSIDE 3" FIBERGLASS HYDROSTATIC
PRODUCT PIPING TO DISPENSER SENSOR 118
(VACUUM MONITORED)
3”X2” D.W. FIBERGLASS 104
ENTRY FITTING
104 3”X2” D.W. FIBERGLASS
ENTRY FITTING
4 1/2"

NOTE: D.W. SUMPS TO BE FILLED WITH MANUFACTURER


APPROVED BRINE SOLUTION.

DESIGN:
SUMP LIQUID MONITORING SENSOR
(IN SENSOR HOLDER BELOW APEX 117
OF TANK AT LOWEST POINT)
ELEVATION - INTERSTITIAL SPACE MONITOR (NEW
DIESEL TANK)

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


CSLB#952213  A,  HAZ,  Exp.  09/30/12
P.O.  BOX  6219,  WHITTIER,  CA  90609
SECTION VIEW - STP SUMP (DIESEL)

MINI HYDROSTATIC 127

CONTRACTOR:
SENSOR

FACTORY SUPPLIED
SUMP RESERVOIR

1'-0"
10"
TRIM AT BOTTOM TO SUIT
ROUND BODY
EXTENSION

DSL STP SUMP / ANNULAR DETAILS


1', 2', 3' OR 4'-0"

CITY OF INDUSTRY, CA 91745


(VARIES BASED ON TRIM)
SLIP ON RISER {48" I.D.}

LOOP VACUUM TUBING FROM FIELD SEALED


PRODUCT PIPING TO VAC SENSOR JOINT.
(ADHESIVE
117 SUPPLIED W/ KIT)

221 S HACIENDA BLVD


127 MINI HYDROSTATIC SENSOR
SENSOR CABLE LOOPED TO TURBINE SUMP
BRINE RESERVOIR
3/8 X 1/4 SS 1
3/4” MONITORING CONDUIT (ROUTED TO INTERSTITIAL) BUSHING
INSTALLED AT

2'-0"
19"
103 FIBERGLASS ENTRY FITTING FACTORY 1
FACTORY
2" INSIDE 3" FIBERGLASS PRODUCT PIPING LAY-UP
3/4” HOME RUN TO 51 57 TO DISPENSER (VACUUM MONITORED)
BUILDING VAC SENSOR COLLAR
BONDED TO

4"
3"X2" D.W. FIBERGLASS FRP
FIBERGLASS ENTRY FITTING 103 104 ENTRY FITTING TANK

HASSAN 28
6"
JOINT DETAILS
48" DIA. POLYGON SUMP BODY
2" INSIDE 3" DOUBLE WALL (16) 9-1/2" FLAT PANELS
51 57 FRP VENT PIPING (VACUUM MONITORED) 1/4" DRAIN/TEST BUSHING.
FACTORY INSTALLED

PROJECT:
75 2"x24" FLEX (TYP.)
DIESEL DOUBLE WALL TURBINE SUMP
2 SENSOR-NO TANK VACUUM SENSOR
130 129 128 79 2 HP TURBINE MOTOR RISER
ASSEMBLY KIT W/ MOUNTING BRACKET
DATE  DRAWN:
48" DOUBLE WALL BRINE
MONITORED SUMP
1 103 3/4" POWER CONDUIT 9/21/15
*NOTE: SCALE:
CONTRACTOR SHALL BE HELD RESPONSIBLE FOR PROPER INSTALLATION &
NOTE: THE LAST 2 FEET (MINIMUM) OF CONDUITS
THAT ENTER THE DOUBLE WALL SUMP SHALL BE
PREPARATION PER MANUFACTURERS INSTRUCTIONS AND SHALL REINSTALL
SUMPS IF HYDROSTATIC TESTING SHOWS LEAKING IN THIS AREA OF THE
1  :  10
PVC COATED RIGID. SUMP. DRAWN  BY: CHECKED  BY:

CONTRACTOR TO ADDITIONALLY GLASS WRAP & LAMINATE AT CONNECTION


B.  BURNS
1
FOLLOWING CURING OF ADHESIVE. SPECIFIC ATTENTION MUST BE GIVEN TO PROJECT  #
SURFACE PREP AS TESTING REQUIREMENTS WILL DETECT THE SMALLEST
OF FLAWS. ALL MATERIALS MUST BE COMPATIBLE WITH
GASOLINE,GASOLINE WITH 15% MTBE (METHYL TERTIARY-BUTYL ETHER), OR
GASOLINE WITH 10% ETOH (ETHANOL). FIBERGLASS AND RESIN MUST
221SHACIENDA-­‐001
PLAN VIEW - STP SUMP (DIESEL) EXTEND 1/2" BEYOND COVERAGE OF ADHESIVE. SHEET:

DT-­‐3
APP.
BY:

BB
# - NOTES

1 SLOPE CONCRETE AWAY FROM ALL MANHOLES 1" RISE OVER 12" RUN

2 FIBER REINFORCEMENT TO BE USED. PRE-MIX UNIFORMLY THROUGHOUT CONCRETE.

DESCRIPTIONS

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


REVISIONS
3 REINFORCING BARS TO BE NO LESS THAN 2" AND NO MORE THAN 4" FROM SURFACE.
5 GALLON SPILL BUCKET 5 42" SINGLE PORT MANWAY 81

4 REINFORCE CONCRETE SLAB AROUND MANHOLE WITH 4-#3 REBAR 60" IN LENGTH.
PLACE REBAR 6" FROM SIDES OF BOX.

CONTRACTOR TO ONE 1" STANDARD MONITORING HOMERUN CONDUIT TO EACH TANK AND ONE 1" VACUUM
INSTALL PLYWOOD MONITORING HOMERUN CONDUIT TO EACH TANK. FOR STANDARD MONITORING DEVICES,
FORM AROUND
5 LOOP CONTAINMENT SUMP SENSORS, PLLD & TANK GAUGE TO TANK INTERSTITIAL

1'-4" MIN.
SUMP FOR SENSOR LOCATION AND HOMERUN TOBLDG. FOR VACUUM MONITORING LOCATIONS

(TYP.)
CONCRETE AROUND ROUTE CROSSOVER CONDUITS CONTAINING VACUUM TUBING BETWEEN FILL AND
3"

3"
SKIRT OF FILL BOX TURBINE SUMP. A SEPARATE CONDUIT FROM TURBINE SUMP IS USED FOR VACUUM
(TYP.) 6 SENSORS TO BUILDING. PROVIDE SEAL-OFFS IN BUILDING & PRIOR TO LEAVING

DATE:
HAZARDOUS AREA. ROUTE TO INTRINSICALLY SAFE TROUGH IN BUILDING. CONDUITS

5/31/12
SHALL CONTAIN ONLY LOW VOLTAGE WIRING FOR SENSORS. LAST TWO FEET TO SUMPS
8 6 SHALL BE PVC COATED RIGID.
PEA GRAVEL BACKFILL (TYP.)
MINI HYDROSTATIC SUMP 127
SENSOR
JUNCTION

NO.
BOX 4" STEEL RISER (TYP.) 85
6 PEA GRAVEL BACKFILL. ALL SUBSTITUTES MUST BE APPROVED BY MANUFACTURER

1
AND OWNER'S FIELD REPRESENTATIVE.
42" DIA. BRINE MONITORED DOUBLE WALL
1 CONTAINMENT SUMP (TYP.)
PIPING SHALL BE LAID AND CONTINUOUSLY SUPPORTED ON A 6" COMPACTED PEA
7 GRAVEL BEDDING. PIPING SHALL NOT BE SUPPORTED BY BLOCKS, PLANKS, OR OTHER
DEBRIS.
122
TANK GAUGE
ADAPTER & CAP
VEEDER ROOT 8' .1 GPH MAGNOSTRICTIVE 8 ALL ENTRIES TO BE PERPENDICULAR TO CONTAINMENT SUMP. OFFLINE INSTALLATION
119 PROBE TANK LEVEL PROBE W/ TLS CAP & SHALL BE BE PERMITTED WHEN USING FLEXIBLE ENTRY BOOTS
RING. OVERFILL ALARM SET @ 90%
121 CAPACITY.
3/4" D.W. FIBERGLASS 8 9 REAM ALL RISERS FOR FULL PIPE BORE IF REQUIRED.
103
ENTRY FITTING

18" MIN.
10 INSTALL TANK ID MARKERS IN THE SPILL CONTAINMENT MANHOLES. COVERS SHALL BE
5 PRIMED AND PAINTED ACCORDING TO SPECIFICATIONS.
3/4" MONITORING CONDUIT
(TYP.)
11 SECONDARY CONTAINMENT IS REQUIRED FOR ALL VENT AND STAGE II VAPOR
RECOVERY PIPING.

DESIGN:
12 COAT ALL BURIED GALVANIZED STEEL WITH COAL TAR EPOXY.

13 LAYOUT TANKS & STAGE II VAPOR RECOVERY PIPING SUCH THAT THE STAGE II PIPING
DRAINS & ENTERS INTO REGULAR UNLEADED TANK FIRST W/ 3" CONNECTIONS, AND
CONTINUES 3" TO OTHER TANKS.
SUMP MONITOR LIQUID SENSOR
MOUNTED IN HOLDER 117
CONCRETE SHALL BE THICKENED AT THE THE FILL SUMPS DOWN TO BELOW THE TOP

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


DROP TUBE W/ FLAPPER 14 OF CONTAINMENT OF THE DOUBLE WALL SUMP AS REQUIRED. DIMENSION OF SLAB

CSLB#952213  A,  HAZ,  Exp.  09/30/12


12

P.O.  BOX  6219,  WHITTIER,  CA  90609


(SET @ 95%) THICKNESS VARIES WITH SITE CONDITIONS.

CROSSING FLEX CONNECTORS MUST MAINTAIN A MINIMUM OF 2 INCH CLEARANCE OR


15 THE USE OF AN ANTI CHAFING DEVICE MUST BE INSTALLED.

SECTION VIEW - FILL SIDE SUMP (DIESEL)


XX NOTE: INDICATES ITEMS
FOUND ON MATERIALS LIST

CONTRACTOR:

CITY OF INDUSTRY, CA 91745


MINI HYDROSTATIC 127
SENSOR
SUMP MONITORING
127 LIQUID SENSOR
8"
FACTORY SUPPLIED
HYDROSTATIC
ATG RISER
FILL RISER

10"
RESERVOIR
VEEDER ROOT .1 GPH MAGNOSTRICTIVE

221 S HACIENDA BLVD


PROBE TANK LEVEL PROBE W/ TLS CAP FACTORY BONDED
3/4" MONITORING CONDUIT (TYP.) JOINT (TYP.)
& RING
119 121 122
CL

CL

DSL FILL SUMP DETAILS


SLIP ON RISER
8

2'-0"'
103
FIELD SEALED JOINT.
(ADHESIVE SUPPLIED
W/ KIT)

5'-4"

HASSAN 28
CL 3/8 X 1/4 SS
TANK BUSHING
INSTALLED AT
FACTORY
SPILL CONTAINMENT FILL BOX 5

2'-0"
19"
1
1

PROJECT:
FACTORY
4"
LAY-UP

DW COLLAR
BONDED TO

6"
TANK
DATE  DRAWN:
81 42" SINGLE PORT MANWAY 42" DIA. BRINE MONITORED DOUBLE WALL
1 CONTAINMENT SUMP (TYP.) JOINT DETAILS 2 9/21/15
CONTRACTOR TO ADDITIONALLY GLASS WRAP & LAMINATE AT CONNECTION FOLLOWING CURING 42" DIA. POLYGON SUMP BODY SCALE:
1 (12) 11 3/4" FLAT PANELS
OF ADHESIVE. SPECIFIC ATTENTION MUST BE GIVEN TO SURFACE PREP AS TESTING
REQUIREMENTS WILL DETECT THE SMALLEST OF FLAWS. ALL MATERIALS MUST BE COMPATIBLE
WITH GASOLINE,GASOLINE WITH 15% MTBE (METHYL TERTIARY-BUTYL ETHER), OR GASOLINE
1  :  10
WITH 10% ETOH (ETHANOL). FIBERGLASS AND RESIN MUST EXTEND 1/2" BEYOND COVERAGE OF 1/4" DRAIN/TEST BUSHING.
FACTORY INSTALLED DRAWN  BY:
PLAN VIEW - FILL SIDE SUMP (DIESEL) ADHESIVE. CHECKED  BY:

2
THE STRAP CHANNEL IF PRESENT ON THE FILL SIDE SUMP DOES NOT "COMMUNICATE" WITH B.  BURNS
THE INSIDE OF THE SUMP. CONTRACTOR TO BE SURE TO LEAVE UNOBSRUCTED PATH FOR
STRAP TO PENETRATE INTO THE CHANNEL SO THAT TANKS MAY BE PROPERLY ANCHORED. PROJECT  #

221SHACIENDA-­‐001
DOUBLE WALL FILL SUMP RISER (DIESEL)
SHEET:

DT-­‐4
APP.
BY:

BB
DESCRIPTIONS

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


REVISIONS
82 DIESEL VENT CAP

DATE:
UNISTRUT PIPE

5/31/12
SUPPORTS 82 DIESEL VENT CAP

NO.

1
DESIGN:
DIESEL VENT
RISER

12'-0" MIN.
(E) VENT RISERS

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


CSLB#952213  A,  HAZ,  Exp.  09/30/12
P.O.  BOX  6219,  WHITTIER,  CA  90609
(N) VENT RACK

CONTRACTOR:

CITY OF INDUSTRY, CA 91745


GLYCOL RESERVOIR
(PROVIDED BY BRAVO)

221 S HACIENDA BLVD


J-BOX
HYDROSTATIC SENSOR 127

DSL VENT SUMP DETAILS


GLYCOL RESERVOIR
(PROVIDED BY BRAVO)

3-WAY VALVE FOR EACH


SEAL OFF VENT PIPING RUN FOR 135
TESTING VACUUM
HYDROSTATIC SENSOR 127
3" X 2" D.W. FIBERGLASS
51 57

HASSAN 28
VENT PIPING
1-1/2"x18" FLEX
3" X 2" D.W. FIBERGLASS OFFSET ELECTRICAL CONDUIT 75 CONNECTOR
VENT PIPING 51 57

3-WAY VALVE FOR EACH D.W. FIBERGLASS


36 VENT SUMP (PROPYLENE
D.W. FIBERGLASS 135 VENT PIPING RUN FOR
VENT SUMP (PROPYLENE 36 TESTING VACUUM GLYCOL FILLED)
GLYCOL FILLED)

PROJECT:
SUMP SENSOR IN
117 HOLDER
3" X 2" D.W. FIBERGLASS
ENTRY FITTING 104
1-1/2"x18" FLEX
3" X 2" D.W. FIBERGLASS 75 CONNECTOR SUMP SENSOR IN
ENTRY FITTING 104 117 HOLDER
DATE  DRAWN:

9/21/15
SCALE:

1  :  10
DOUBLE WALL VENT SUMP @ VENT RISER SECTION VIEW (DIESEL ONLY) DOUBLE WALL VENT SUMP @ VENT RISER SECTION VIEW (DIESEL ONLY) DRAWN  BY: CHECKED  BY:
SCALE: N.T.S.
SCALE: N.T.S.
B.  BURNS
PROJECT  #

221SHACIENDA-­‐001
SHEET:

DT-­‐5
APP.
NOTE: ALL PARTS SHALL BE INSTALLED BY AN ICC
CERTIFIED TECHNICIAN PER MANUFACTURER'S

BY:
SPECIFICATIONS.

BB
TOP OF DISPENSER ISLAND

13" ISLAND FORM

TOP OF CONCRETE SLAB

DESCRIPTIONS

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


REVISIONS
(E) 3+0 DISPENSERS
(TYP. OF 4)

DISPENSER CONTAINMENT
+
6" CONCRETE

-
(n) product shear (n) 4"x3" frp
(e) vapor flow valve (87 / 91) vapor piping

18 3/8"
meter
77 PEA GRAVEL
131 57 66
GRAVEL

7” +/-
69
(n) vapor shear valve
78
70

DATE:

5/31/12
GRADE

.
IN

NO.
M
2"

1
1/
1
V
4" MIN

7 1/2"

10 1/8"
64
(N) 1-1/2" X 18" FLEX (n) 3"x2" frp
CONNECTOR product piping
OFFSET ELECTRICAL CONDUIT 76
51 57
65
(N) 4"X3" FIBERGLASS

6"
P P
VAPOR PIPING
(N) S.W. FIBERGLASS UDC 57 66
(TYP. OF 4)
37

(N) 3" FIBERGLASS 6" 10" 10"


ELBOW (N) 4”X3” FIBERGLASS 106 MIN. MIN. MIN.
ENTRY FITTING
59 (TYP.) (TYP.)

DESIGN:
(N) SUMP SENSOR
117
PIPING CROSS OVER DETAIL (TYP.)
(N) 3"X2" FIBERGLASS
PRODUCT PIPING (87, 91)
(N) 2" FIBERGLASS 51 57
ELBOW
(N) 3"X2" FIBERGLASS

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


53
ENTRY FITTING

CSLB#952213  A,  HAZ,  Exp.  09/30/12


P.O.  BOX  6219,  WHITTIER,  CA  90609
105

3+0 UDC SIDE VIEW (GASOLINE ONLY) NOTE: TEST PORTS IN PENETRATION FITTINGS 1

TO BE INSTALLED POINTING DOWNARDS IN


THE 6'OCLOCK POSITION.

CONTRACTOR:
UDC FRAME
25 (e) healy whip hose

(E) 3+0 DISPENSERS 26 (e) healy breakaway


(TYP. OF 4)
(n) 4" frp 45
degree secondary
fitting
69

(e) healy curb hose (n) 4" frp

CITY OF INDUSTRY, CA 91745


27
EDGE OF TRENCH secondary
tee
70
PLUS SUPER UNLEADED

3+0 UDC DETAILS (NON VPH)


(n) 4"x3" frp piping

221 S HACIENDA BLVD


57 66

28 (e) healy nozzle


VAPOR
MANIFOLD

64 (n) 3" frp


45 degree
secondary fitting

(n) vapor shear (n) product shear


valve valve (n) 3"x2" frp piping (n) 3" frp
65 secondary
78

HASSAN 28
77 51 57 tee

PRODUCT
REG GAS

(N) 1-1/2" X 18" FLEX

PROJECT:
CONNECTOR 76
(N) 4”X3” FIBERGLASS PRODUCT
ENTRY FITTING PREM GAS
106
(N) 3"X2" FIBERGLASS
ENTRY FITTING
(N) S.W. UDCS 105 DATE  DRAWN:
(TYP. OF 4)
37 9/21/15
117 (N) SUMP SENSOR (N) 3”X2” FRP
PIPING (PREMIUM)
51 57 SCALE:
EDGE OF TRENCH

(N) 4”X3” FRP PIPING


(N) 3”X2” FRP PIPING
(REGULAR)
1  :  10
(VAPOR)
57 66 51 57 DRAWN  BY: CHECKED  BY:

3+0 UDC PLAN VIEW B.  BURNS


3+0 DISPENSER ELEVATION (GASOLINE ONLY PROJECT  #
- TYP. OF 4) 221SHACIENDA-­‐001
SHEET:

DT-­‐6
APP.
NOTE: ALL PARTS SHALL BE INSTALLED BY AN ICC
CERTIFIED TECHNICIAN PER MANUFACTURER'S

BY:
SPECIFICATIONS.

BB
DESCRIPTIONS

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


REVISIONS

DATE:

5/31/12
NO.

1
DESIGN:

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


CSLB#952213  A,  HAZ,  Exp.  09/30/12
P.O.  BOX  6219,  WHITTIER,  CA  90609
(N) 4”x3" fiberglass
entry fitting 109
(e) stp sump

(n) 4"x3" fiberglass


vapor piping
(87 and 91)

57 66

(n) 3"x2" fiberglass

CONTRACTOR:
vent piping
(87 and 91)
51 57 GRADE

6-0"
(n) 3"x2" fiberglass
entry fitting (e) conduit
108

18" Min.

CITY OF INDUSTRY, CA 91745


(n) 3"x2" fiberglass
product piping PEA  GRAVEL
(87 and 91)
tank top
51 57

221 S HACIENDA BLVD

87 / 91 STP SUMP DETAILS


PRODUCT  PIPING
6" Min.

(e) sump sensor


(e) flex connectors 75
v/r-208
6" Min. 4" Min.

HASSAN 28
(E) 87 AND 91 STP SUMP DETAILS PIPING TRENCH REQUIREMENTS (TYP.)

PROJECT:
NOTE: TEST PORTS ON ENTRY FITTINGS
TO BE INSTALLED POINTING DOWNWARDS, DATE  DRAWN:
AT THE 6'OCLOCK POSITION
9/21/15
SCALE:

1  :  10
DRAWN  BY: CHECKED  BY:

B.  BURNS
PROJECT  #

221SHACIENDA-­‐001
SHEET:

DT-­‐7
APP.
NOTE: ALL PARTS SHALL BE INSTALLED BY AN ICC
CERTIFIED TECHNICIAN PER MANUFACTURER'S

BY:
SPECIFICATIONS.

BB
DESCRIPTIONS

REVISIONS  MADE  FOR  L.A.  COUNTY  DPW


REVISIONS

DATE:
(N) P/V VENT VALVE

5/31/12
HUSKY 5885
83

NO.

1
(E) HEALY TANK
84

DESIGN:
(N) BLACK STEEL
VENT RISERS

(N) 2” BLACK STEEL

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


VENT RISERS

CSLB#952213  A,  HAZ,  Exp.  09/30/12


P.O.  BOX  6219,  WHITTIER,  CA  90609
FLAMMABLE
VAPORS

NO SMOKING

CONTRACTOR:
3
1

J-BOX

CITY OF INDUSTRY, CA 91745


GRADE
3/4" CONDUIT (OFFSET)

(N) J-BOX

87 / 91 VENT SUMP DETAILS


221 S HACIENDA BLVD
GRADE (N) 3"X2" FIBERGLASS
VENT PIPING
(N) SEAL OFF (87 AND 91) (N) S.W. VENT SUMP
51 57 38
3/4" CONDUIT (OFFSET)
(N) FLEX CONNECTORS
(TYP. OF 2)
36 (N) S.W. VENT SUMP 75

HASSAN 28
(N) 3"X2" FIBERGLASS
VENT PIPING (N) FLEX CONNECTORS
117 (N) SUMP SENSOR (87 AND 91) (N) 3"X2" FRP (TYP. OF 2)
ENTRY FITTING 105
75
51 57 NOTE: TEST PORTS ON TEST FITTINGS W/TEST PORT
TO BE INSTALLED POINTING DOWNWARDS,
(N) 3"X2" FRP
AT THE 6'OCLOCK POSITION

PROJECT:
105
ENTRY FITTING (N) SUMP SENSOR 117
W/TEST PORT

DATE  DRAWN:

9/21/15
87 AND 91 VENT BOX DETAILS 87 AND 91 VENT BOX SIDE VIEW SCALE:

1  :  10
DRAWN  BY: CHECKED  BY:

B.  BURNS
PROJECT  #

221SHACIENDA-­‐001
SHEET:

DT-­‐8
APP.
BY:

BB
MATERIAL LIST

TANKS FIBERGLASS PIPING AND FITTINGS PENETRATION FITTINGS

DESCRIPTIONS
ITEM DESCRIPTION MANUFACTURER ITEM DESCRIPTION MANUFACTURER ITEM DESCRIPTION MANUFACTURER

REVISIONS
10,000 GALLON DOUBLE WALL FIBERGLASS UNDERGROUND STORAGE
1 W/ 42” POLYSIDED FILL SUMP, W’48” POLYSIDED TURBINE SUMP XERXES MODEL XER10K 51 2" (PRIMARY) FIBERGLASS PIPE, 22'-25' LENGTH & GLUE KITS "NOV FIBERCAST" MODEL #011020-069-2 103 D.W. 3/4" FIBERGLASS ENTRY FITTING BRAVO F-17-RR-D
DIESEL PRODUCT (BRINE FILLED TANK / SUMP INTERSTITIAL) PER AB2481 SPECS

2 52 2" COUPLING (PRIMARY) "NOV FIBERCAST" MODEL #012020-101-8 104 BRAVO F-32-TS-D
D.W. 3"X2" FIBERGLASS ENTRY FITTING

3 53 2" 90 DEGREE ELBOW (PRIMARY) "NOV FIBERCAST" MODEL #012020-360-4 105 S.W. 3”x2” FIBERGLASS ENTRY FITTING BRAVO F-32-TS-T-MP

4 54 2" 45 DEGREE ELBOW (PRIMARY) "NOV FIBERCAST" MODEL #012020-310-4 106 S.W. 4”X3” FIBERGLASS ENTRY FITTING BRAVO F-43-TS-T-MP

STAGE I EQUIPMENT 55 2" TEE (PRIMARY) "NOV FIBERCAST" MODEL #120020-410-4 107 D.W. 4”X3” FIBERGLASS ENTRY FITTING BRAVO F-43-TS-D

"NOV FIBERCAST" MODEL #012020-191-4


5 SPILL CONTAINERS OPW MODEL#2100 56 2" THREADED ADAPTER BELL x MALE FRP 108 3”X2” FIBERGLASS ENTRY FITTINGS (SINGLE WALL SUMPS) BRAVO F-32-TS-T-MP-RND
"NOV FIBERCAST" MODEL #012020-191-7

DATE:
3" (PRIMARY) FIBERGLASS PIPE, 22'-25' LENGTH & GLUE KITS "NOV FIBERCAST" MODEL #011030-069-2
6 PRODUCT DUST CAP OPW MODEL #634TT-EVR 57 109 4”X3” FIBERGLASS ENTRY FITTINGS (SINGLE WALL SUMPS) BRAVO F-43-TS-T-MP-RND
3" (SECONDARY) FIBERGLASS PIPE, 22'-25' LENGTH & GLUE KITS "NOV FIBERCAST" MODEL #011030-069-5
3" COUPLING (PRIMARY) "NOV FIBERCAST" MODEL #012030-101-8
7 58 110
3" COUPLING (SECONDARY) "NOV FIBERCAST" MODEL #012030-101-9

NO.
8 PRODUCT ADAPTOR OPW MODEL #61SALP 59 3" 90 DEGREE ELBOW (PRIMARY) "NOV FIBERCAST" MODEL #012030-360-4 111

9 60 3" 45 DEGREE ELBOW (PRIMARY) "NOV FIBERCAST" MODEL #012030-310-4 112

10 61 3" TEE (PRIMARY) "NOV FIBERCAST" MODEL #120030-410-4 113

"NOV FIBERCAST" MODEL #012030-191-4


11 62 3" THREADED ADAPTER BELL x MALE FRP 114
"NOV FIBERCAST" MODEL #012030-191-7

12 DROP TUBE OPW MODEL#61T 63 3" 90 DEGREE ELBOW (SECONDARY) "NOV FIBERCAST" MODEL #012030-360-3
OVERFILL PREVENTION VALVE OPW MODEL #61SO VEEDER ROOT EQUIPMENT
3" 45 DEGREE ELBOW (SECONDARY FLAT) "NOV FIBERCAST" MODEL #012030-310-3
13 TURBINE SUMP MANWAY FIBERLITE #FL42/SKID SKIRT 64 ITEM DESCRIPTION MANUFACTURER
3" 45 DEGREE ELBOW (SECONDARY CROSSOVER) "NOV FIBERCAST" MODEL #012030-311-3
3" TEE (SECONDARY FLAT) "NOV FIBERCAST" MODEL #120030-410-3
14 SINGLE PORT FILL MANWAY OPW #6-571-EVRL-164042RT051 65 115
3" TEE (SECONDARY CROSSOVER) "NOV FIBERCAST" MODEL #120030-411-3 NOT USED

15 18” INTERSTITIAL MANWAY OPW #6110-18-WT 66 4" (SECONDARY) FIBERGLASS PIPE, 22'-25' LENGTH & GLUE KITS "NOV FIBERCAST" MODEL #011040-069-5
ALSO USED FOR ANNULAR RISER NOT USED
116
16 TURBINE SUMP COVER BRAVO #CTS-37 67 4" COUPLING (SECONDARY) "NOV FIBERCAST" MODEL #012040-101-9
117 SUMP LIQUID SENSOR "VEEDER-ROOT" MODEL NO. 794380-208

DESIGN:
17 68 4" 90 DEGREE ELBOW (SECONDARY) "NOV FIBERCAST" MODEL #012040-360-3
118 HYDROSTATIC SENSOR-DUAL FLOAT "VEEDER-ROOT" MODEL NO. 794380-303
4" 45 DEGREE ELBOW (SECONDARY FLAT) "NOV FIBERCAST" MODEL #012040-310-3
18 69
4" 45 DEGREE ELBOW (SECONDARY CROSSOVER) "NOV FIBERCAST" MODEL #012040-311-3
119 TANK LEVEL 8' MAGNETOSTRICTIVE PROBE-0.1 GPH (USE 2" FLOAT IN KIT) "VEEDER-ROOT" MODEL NO. VR-847390-107
4" TEE (SECONDARY FLAT) "NOV FIBERCAST" MODEL #120040-410-3
19 70
4" TEE (SECONDARY CROSSOVER) "NOV FIBERCAST" MODEL #120040-411-3
120 NOT USED
20 71
121 2" FLOAT PROBE INSTALL KIT FOR MAG 1 TANK LEVEL PROBE (DIESEL) "VEEDER ROOT" MODEL # VR-849600-001
21 72

(562)  762-­‐8492  PH  /  (562)  325-­‐8888  FAX


TANK GAUGE PORT CAP AND RING KIT
122 "VEEDER ROOT" MODEL # VR-312020-952

CSLB#952213  A,  HAZ,  Exp.  09/30/12


P.O.  BOX  6219,  WHITTIER,  CA  90609
PER CARB EVR EXEC ORDER VR-101-E & VR-102-E
22 73
123 NOT USED
23 74
124 NOT USED
DISPENSERS MISCELLANEOUS EQUIPMENT
ITEM DESCRIPTION MANUFACTURER ITEM DESCRIPTION MANUFACTURER 125 NOT USED

24 3+1 MPD FUEL DISPENSER WAYNE OVATION 75 2"X24" FLEX CONNECTORS FLEX-ING #FF20X24M346XHM 126 NOT USED

25 UNLEADED COAXIAL WHIP HOSE HEALY #75B-010-S4F2 76 1-1/2"X18" FLEX CONENCTOR FLEX-ING #FF15X18M346XHM

CONTRACTOR:
127 MINI HYDROSTATIC SENSOR-SINGLE POINT "VEEDER-ROOT" MODEL NO. 794380-304

26 UNLEADED BREAKAWAY HEALY #8701VV 77 PRODUCT SHEAR VALVE OPW #10BFP-5726 128 "VEEDER-ROOT" MODEL NO. 857280-100
INDIVIDUAL VACUUM SENSOR

27 COAXIAL 8' FUEL HOSE HEALY # 75B-085-S2S2 78 VAPOR SHEAR VALVE OPW #60VSP-1001 129 INDIVIDUAL VACUUM SENSOR MOUNTING KIT "VEEDER-ROOT" MODEL NO. 330020-448

28 UNLEADED NOZZLE HEALY #900-EVR-FS 79 2 HP TURBINE MOTOR FE PETRO #STPVS2-VL2 130 2 SENSOR/NO TANK VACUUM SENSOR KIT "VEEDER-ROOT" MODEL NO. 330020-480

29 VAPOR VAC MOTOR HEALY VP1000 80 MECHANICAL LINE LEAK DETECTOR FE PETRO #STP-MLD-D 131 VAPOR FLOW METER FOR ISD "VEEDER-ROOT" MODEL NO. 331847-002

30 DIESEL WHIP HOSE GOODYEAR #53232712421269 81 SINGLE PORT STEEL MANWAY OPW 42" 132 VAPOR PRESSURE SENSOR FOR ISD (EXISTING - RELOCATED) "VEEDER-ROOT" MODEL NO. 331946-001

CITY OF INDUSTRY, CA 91745


31 DIESEL BREAKAWAY OPW #OP11B-320 82 DIESEL VENT CAP OPW 23-0033 133 NOT USED

32 DIESEL HOSE GOODYEAR #53223712400869 83 GAS P/V VENT VALVE HUSKY 4885 134 4" RISER PIPE CAP "VEEDER-ROOT" MODEL NO. 330020-435

33 DIESEL NOZZLE OPW #OP11B-100 84 CLEAN AIR SEPARATOR TANK HEALY 9961 135 3-WAY BALL VALVE "VEEDER-ROOT” MODEL NO. 576008-649

221 S HACIENDA BLVD


34 85 4” STEEL RISER BLACK STEEL (TYP)

UDC'S / VENT SUMP 86

35 D.W. FIBERGLASS DISPENSER SUMP BRAVO B8000-D-AB 87

36 D.W. FIBERGLASS VENT SUMP BRAVO B500-D-AB PLANTER 88

37 S.W. FIBERGLASS DISPENSER SUMP BRAVO B8000 89

MATERIAL LIST
38 S.W. FIBERGLASS VENT SUMP BRAVO B500 PLANTER 90

HASSAN 28
39 91

40 92

41 93

PROJECT:
42 94

43 95

44 96
DATE  DRAWN:
45 97
6/22/16
46 98
SCALE:
47 99
AS  SHOWN
48 100 DRAWN  BY: CHECKED  BY:

49 101
B.  BURNS
PROJECT  #
50 102

221SHACIENDA-­‐001
SHEET:

MT-­‐1