Professional Documents
Culture Documents
ABSTRACT
To estimate lightning stroke overvoltages exactly, the occurrence probability of lightning
stroke current waveforms must be accurately evaluated. This paper firstly formulated the
occurrence probability distribution of lightning stroke current waveforms, taking into
account the correlation between the current amplitude and the front duration. Next,
lightning overvoltages were calculated, with the current amplitude and the front duration
of lightning current as statistical parameters for Gas Insulated Switchgears (GIS’s) and
transformers in UHV substations. While overvoltages caused by back-flashovers at GIS’s
are affected by the front duration of lightning current, overvoltages at transformers are
relatively less dependent on the front duration. Finally the failure rate was evaluated by
considering not only the current amplitude but also the front duration. These values were
smaller than those evaluated from the frequency of occurrence of current amplitude
alone. Further, the proposed front duration of 1.7 ȝs was examined.
Index Terms = Lightning stroke current, current waveform, front duration,
overvoltage, failure rate, substation equipment, lightning impulse withstand voltage.
z(tf): the difference in log value between the front duration of 180
0.002
lightning stroke current and the regression curve of the 150
120
0.001
90 0
distribution of the front duration, ıf : the standard deviation Current 60 1
0
amplitude [kA] 30 2
of log z(tf), and log (m2) : the mean value of the difference of 0
5
4
3
Front duration [ȝs]
the front duration from the average regression curve (the
difference in log value). z(tf) is obtained from the following (a) Three-dimensional display
equation.
0.0
i ½ (3) Front duration of lightning current; y=0.717e
x/230
0.5
z (tf ) log tf log ®1.31 exp( )¾
¯ 230 ¿ 1.0
1.5
The probability density of the occurrence P(i,tf) of the 200kA,1.7ȝs Front
lightning stroke current waveform with the current amplitude i 2.0
duration [ȝs@
and the front duration tf is derived from equations (1) to (3), 2.5
2
ª i ½ º ½ Current amplitude [kA]
«log t f log®1.31exp( 230 )¾ log(m2 )» °
(4) (b) Two-dimensional display (relationship between the current amplitude and
¯ ¿ °
¬ 2
¼
¾ the regression curve of the average front duration )
2V f °
° Figure 1. Occurrence probability of lightning stroke current waveforms as a
¿ function of the amplitude and the front duration.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 1; February 2011 223
Table 2. Analysis conditions. Japan [9]. 5000 cases of patterns for lightning stroke current
waveform analysis were prepared. The analysis used ATP-
Location
Upper phase back-flashover due to a lightning EMTP [13].
stroke to the first transmission tower
Lightning stroke
Transmission
line
8 phase Semlyen model simplified method is used in this study because it has been
4-story transmission tower model (constant adopted by the conventional design guidelines for back-
Transmission
tower
determined by actual measurement), Grounding flashovers [9]. Regarding the relationship between the
resistance: 10 :
transmission tower height “h” and the frequency of lightning
Gantry 2- story model, Grounding resistance: 4 : strokes, the frequency of lightning strokes is proportional to h
Corona effect Not considered. if the tower is assumed to be a stand alone-structure. If,
however, in the case of horizontally long structures such as
All GIS Double bus - 4 bus tie system - 4 circuits - 4 banks transmission lines, this is proportional to, as in studies based
Configurat
Open circuit breaker at the service line entrance on electrogeometric models. This relationship holds good as
Circuit
ion I
Configurat
long as the height is up to about 100 m.
1 circuit㧙1/4 bus㧙1 transformer
ion II The probability of lightning strokes to transmission lines
GIS
Single phase distributed constant circuit, Lossless (Nt) is based on the information above and the actual
line, Surge impedance: 91 : occurrence of 43 lightning strokes per 100 km of transmission
Substation
In closing: same as the GIS line when the height of transmission towers was 25 m, with an
Circuit breaker
In opening: S-type capacitance simulation IKL of 30 to 35 (which more or less corresponds to the
Capacitance simulation
calculation results using the electrogeometric model.)
Transformer - Core-type 16600 pF h IKL [times / 100 km / year]
- Shell-type 5800 pF Nt 43 u u (5)
25 30ᨺ35
Bushing Capacitance simulation: 300 pF
Here, the transmission tower height h is 110 m, the average
Model taking fast transient current characteristics height of UHV transmission towers. As for IKL (Mesh
Surge arrester
into account㧔V10kA= 1550 kV㧕 covering 15 minutes of latitude and longitude: about 25
km×27 km), the lightning stroke density (1 km×1 km) where
UHV designed transmission lines pass through was obtained
Service line
entrance Circuit configuration I : using a lightning positioning and tracking system (LPATS)
Overvoltage at a GIS analyzed with the
circuit breaker at the service line entrance and converted into IKL. In consequence, IKL = 40 was used.
opened
Circuit configuration II :
3.3.2 RANGE OF ASSUMED LIGHTNING STROKE
Overvoltage at a transformer analyzed with LOCATIONS
one transformer in one circuit
Circuit breaker
(Solid line in the figure) With regard to the location of lightning strokes, as referred
at the service line
(CB is 18m away SA) to in Section 3.2, only the top of the first transmission tower is
Open
considered as a lightning stroke location for the overvoltage
analysis since the present study is a basic one focusing mainly
Close (Tr. is 12m away SA)
Transformer
on the effects of lightning stroke waveforms. Severe lightning
stroke overvoltages are generally generated when back-
flashover conditions occur close to the substation, and
therefore the spans including one of the first towers are
assumed as the range of the location of lightning strokes for a
rigorous evaluation, taking the attenuation of surge due to
Figure 3. Circuit configuration of UHV substation subject to lightning surge corona and other factors into account. Also since the surge
overvoltage analysis. current is shunted two ways and back-flashovers will be less
likely in the case of lightning strokes in the middle part of the
and the range of the length of the front duration was divided span, it is appropriate to assume a range within about a quarter
into 50 cases, from 0.1 ȝs to the max. 5.0 ȝs with 0.1 ȝs of the span length on both sides of the transmission tower.
increment. Since the stroke duration has only a small effect on Consequently, the range of the location of assumed lightning
lightning surge overvoltages, it was constant for 70 ȝs. This strokes was set to a total length of 200 m on the both sides of
has been conventionally used in lightning protection design in the first tower for transmission lines designed for UHV.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 1; February 2011 225
RATE
(a) Three-dimensional display
To evaluate the failure rate, the frequency per year of
occurrence of overvoltages generated in the substation 0
equipment (GIS’s and transformers) exceeding the set LIWV is 1
200kA,1.0ȝs : 2622kV
calculated. The frequency of occurrence of individual
overvoltages can be expressed by the frequency of occurrence P 200kA,1.7ȝs : 2137kV 2 Front duration
in equation (6) of lightning stroke current within the range of [ȝs]
3
assumed lightning stroke locations - the condition for generating
overvoltages. The lightning failure rate can be calculated by 4
integrating the frequency of occurrence of overvoltages
exceeding the LIWV assumed in advance, taking the probability 270 240 210 180 150 120 90 60 30 0
of lightning strokes to transmission lines into account.
Current amplitude [kA]
(b) Two-dimensional display
4 OVERVOLTAGE ANALYSIS RESULTS Figure 5. Distribution of overvoltages generated at the terminal of GIS’s
with changes in current amplitude and front duration of lightning stroke
4.1 DISTRIBUTION OF OVERVOLTAGES current waveforms.
GENERATED AT GIS’S
In the Circuit Configuration I, Figures 4 and 5 show
examples of overvoltage waveforms and the distribution of The part where overvoltages generated are negative values
overvoltages in three-dimensional and two-dimensional in Figure 5 is the area where back-flashovers do not occur.
displays, respectively, generated at the GIS terminals and with The boundary area with positive values indicates the boundary
changes in lightning stroke current waveform parameters. As between the presence and absence of back-flashovers. In the
shown in Figure 4, in the case of GIS’s, the maximum value figure, the critical points of back-flashover occurrence are
appears at the spike waveform of wavefront, the peak value almost linear. These critical characteristics can be almost
varying with changes in the front durations of lightning stroke linearly approximated with respect to the current amplitude
current waveforms. and the front duration, suggesting a condition in which the
3000 front steepness is almost constant. However, when the current
tf : 1.0 ȝs amplitude is around 50 kA, back-flashovers do not occur
tf : 2.0 ȝs
tf : 3.0 ȝs because of lack of time to generate back-flashovers resulting
2000 from shorter front duration less than approx. 1 ȝs. While
Voltage [kV]
Voltage [kV]
tail, after lightning stroke current peaks, as a result of front 1000
durations shorter than the time required for back-flashovers to
tf : 1.0 ȝs
occur. It is also thought that the voltage increase due to pre- tf : 2.0 ȝs
0 tf : 3.0 ȝs
discharge has an impact on decreasing the surge suppression
effect of surge arresters [3].
-1000
Under the analysis conditions established in the present 0 2 4 6 8 10
study, the highest overvoltage was 3760 kV, with a current Time [ȝs]
amplitude of 300 kA and a front duration of 0.1 ȝs; a
combination of the highest current amplitude and the shortest Figure 6. Examples of overvoltage waveforms generated at shell-type
transformers with changes in front duration of lightning stroke current with
front duration. amplitude of 200kA. The time 0 is defined as the time of the lightning to a
tower and ac phase voltage is superimposed.
4.2 DISTRIBUTION OF OVERVOLTAGES
GENERATED AT TRANSFORMERS
2000-2500
In the circuit configuration II, overvoltages generated at the 1500-2000
primary terminal of shell-type transformers and core-type 1000-1500
transformers were analyzed and calculated. Figures 6 and 7 500-1000
show examples of lightning stroke overvoltage waveforms 0-500
or below
and the distribution of overvoltages, respectively, generated at 2500 -500-0
the primary terminal of shell-type transformers. As shown in 2000 -1000--500
Figure 6, the maximum value is generated during the 1500
wavefront of overvoltages; however, there is no steep spike as 270 1000
240
500 Voltage [kV]
observed in the case of GIS’s and changes in overvoltages 210
180 0
with changes in the front duration of lightning stroke current 150 -500
waveforms seem small. 120 -1000
90 0
Current amplitude 1
The part where generated overvoltages are negative values in 60
2
[kA] 30 3 Front duration
Figure 7 is the area where back-flashover does not occur and the 0 4 [ȝs]
boundary area to positive values indicates the boundary between
the presence and absence of back-flashovers. These critical (a) Three-dimensional display
characteristics of back-flashover generation are almost identical 0
to those of GIS’s. The characteristics of generated overvoltages 200kA,1.0ȝs : 1741kV
are also the same as those at GIS’s in that the voltage area 1
corresponding to the residual voltage of surge arresters around 2 Front duration
1550 kV is the widest. 200kA,1.7ȝs : 1800kV
[ȝs]
3
The way back-flashovers occur is strongly affected by the
front duration in the case of both transformer and GIS. 4
However, the overvoltage distribution after back-flashovers
occur is different to that of GIS’s. While it would be natural 270 240 210 180 150 120 90 60 30 0
to conclude that the contour line of overvoltages after back-
Current amplitude [kA]
flashovers occur shows a positive correlation between the
current amplitude and the front duration (a straight line (b) Two-dimensional display
from the right bottom to the top left in the figure) - similar Figure 7. Distribution of overvoltages generated at primary terminal of shell-
to critical characteristics of flashover generation - the type transformers with changes in current amplitude and front duration of
contour line of overvoltages at transformers is closer to lightning stroke current waveforms.
being in parallel with the front duration axis than in the
case of GIS’s. Overvoltage waveforms are steep during the the overvoltage is regarded as being determined by the size of
wavefront due to the effect of the front duration of the charge from a lightning surge.
lightning stroke current and the maximum voltage Under the analysis conditions set out in this study, the
appearing at the peak during the wavefront of waveforms. highest overvoltage at shell-type transformers was 2219 kV,
However, if a large capacitance, such as a transformer, is with a current amplitude of 300 kA, and a front duration of
connected to the line, the impedance to steep surge voltage 0.3 ȝs. Compared with voltages generated at GIS’s, changes
is reduced and the influence of the front duration of in voltage are smaller on the whole, and the maximum voltage
lightning stroke current decreases. The generated voltage at is about 59 % of the maximum voltage at GIS’s. Overvoltages
transformers increases as if charging the entire substation, so generated at core-type transformers are shown in Figure 8.
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 1; February 2011 227
Since the capacitance of transformers is larger, the influence 5 EVALUATION OF LIGHTNING FAILURE
of the front duration becomes smaller than on shell-type RATE OF SUBSTATION
transformers. Accordingly, the maximum overvoltage is
comparatively lower and the overvoltage characteristics with 5.1 FAILURE RATE OF GIS’S
changes in current waveforms are flatter. The highest
Based on the overvoltages at GIS’s with back-flashovers
overvoltage at core-type transformers was 2070 kV, with a
analyzed in the previous section, overvoltages exceeding the
current amplitude of 300 kA, and a front duration of 0.6 μs.
LIWV are defined as insulation failures here. The frequency
While the highest overvoltage at GIS’s appeared with the
of occurrence of overvoltages is obtained by calculating
shortest front duration of lightning stroke current, the highest
equation (6). The failure rates of GIS’s are obtained by
overvoltage at transformers of both types appeared in
calculating the frequency of occurrence of overvoltages
conditions other than the shortest lightning stroke current
exceeding the specified LIWV and integrating them, which
front duration.
are expressed in the per year per route (line). The results of
As described above, the characteristics of overvoltages the calculation of the failure rate of GIS’s are shown in Table
shows that neither the increased current amplitude nor the 3. Figure 9 shows the relationship between the failure rate of
shorter front duration of lightning stroke current necessarily GIS’s and the LIWV. In the UHV field-test equipment, the
lead to a simple increase in overvoltages. So as far as test voltage for GIS’s is set to 2250 kV [16] and the failure
lightning stroke current conditions in studies of lightning rate is very low at 8.41×10-6 [times/route /year]. (Hence the
failure rates are concerned, it will be necessary to carry out frequency of failure (MTBF: Mean Time Between Failure) is
statistical evaluations of front durations of lightning stroke about once in 119000 years per route.) If the LIWV is reduced
current, taking into account their correlation with current to 2100 kV, 1950 kV, and 1800 kV, with the lightning
amplitudes. impulse withstand voltage level specified by IEC [4] as a
guide, the failure rate is increased to 2.5, 6.5 and 18.9 times,
respectively, from the baseline of the failure rate with the LIWV
2000-2500 at 2250 kV; however, the failure rate remains at 1.59×10-4
1500-2000 [times/route/year] even if the LIWV is reduced to 1800 kV.
1000-1500
While this is limited to the failure due to back-flashover, the
frequency of occurrence is about once in 6290 years per route.
500-1000
Evaluating the failure rate conventionally, based only on the
0-500
or below
frequency of occurrence of the assumed lightning stroke current
-500-0
2500 amplitude of 200 kA (the cumulative frequency of occurrence of
-1000--500
2000 0.3 % of the current amplitude exceeding 200 kA), would mean
1500 that failures occur once in about 700 to 1000 years [9]. The
270 1000 failure rate mentioned above is considerably lower than this. In
240 500
210 Voltage [kV] the case of an LIWV set to 2250 kV, the evaluation based on the
180 0
150 -500 frequency of occurrence of generated overvoltages resulting in
120 -1000 MTBF of 119000 [year, route/time] is significantly different
90
Current amplitude
60 0 from the conventional evaluation based only on the frequency of
[kA] 1
30 2 occurrence with the current amplitude resulting in MTBF of 700
0 3
4 Front duration to 1000 [year, route/time]. This is an significant difference from
[μs]
the point of view of reliability to promote electrical insulation
(a) Three-dimensional display rationalization.
A high assumed failure rate with the conventional method is
0
200kA,1.0μs: 1592kV mainly due to not taking into consideration the frequency of
1 occurrence of the front duration of the assumed lightning
stroke current. In the present analysis, the overvoltage of 2622
200kA,1.7μs: 1616kV 2 Front duration kV is generated by the conventionally assumed lightning
[μs]
stroke current waveforms with a current amplitude of 200 kA
3
and a front duration of 1.0 μs. Figure 10 shows the
4
overvoltage distribution overlaid with the density distribution
of occurrence of lightning stroke current. The failure rate
conventionally used was evaluated using only the current
270 240 210 180 150 120 90 60 30 0
amplitude, regardless of the front duration. Consequently,
Current amplitude [kA]
overvoltages generated under the condition of 200 kA or
(b) Two-dimensional display higher are assumed to result in failure in all cases as shown by
the hatched area surrounded by a light red line in Figure 10a.
Figure 8. Distribution of overvoltages generated at primary terminal of core-
type transformers with changes in current amplitude and front duration of
On the other hand, in the case of evaluation using overvoltages,
lightning stroke current waveforms. these overvoltages depend on the influence of the current
228 S. Okabe, and J. Takami: Occurrence Probability of Lightning Failure Rates at Substations in Consideration of Lightning Stroke
Table 3. Calculation of the lightning failure rate of GIS’s. amplitude and the front duration. Therefore, the evaluation of
overvoltages exceeding 2622 kV with a front duration of 1.0 ȝs
Failure rate Relative failure rate using the conventional assumed lightning stroke current
LIWV [times/route/year] compared with LIWV of waveform results in the hatched area surrounded by a light red
(MTBF [year]) 2250kV
line in Figure 10b. The area surrounded by a light red line in
1550 1.48×10-3 (676) 176 Figure 10b is determined by overvoltages with a front duration
1675 -4
5.14×10 (1950) 61.1 of 1.0 ȝs. The light red line here is the 2622 kV contour line.
This area is small and, further, is far from the area where the
1800 1.59×10-4 (6290) 18.9
-5
probability of occurrence of lightning stroke current is high and
1950 5.44×10 (18400) 6.47
therefore the frequency of occurrence is low. The higher the
2100 2.13×10-5 (46900) 2.53 current amplitude, the longer the front duration becomes.
2250 -6
8.41×10 (119000) 1.00 Therefore, in the area of large currents such as the one with a
2400 3.13×10-6 (319000) 0.30 current amplitude of 200 kA, there is a large gap between an
evaluation with one parameter shown in Figure 10a, and an
[u10-3] evaluation with two parameters shown in Figure 10b.
The evaluation of the failure rate with overvoltages is more
1.5
essential, and the front duration has a large impact on
[circuits/route/year]
Table 4. Calculation of the lightning failure rate of shell-type transformers. 6 RELIABILITY WITH ASSUMED
LIGHTNING STROKE CURRENT
Failure rate Relative failure rate
LIWV [times/route/year] compared with LIWV of WAVEFORM
(MTBF [year]) 1950kV The study has clarified that the front duration of lightning
1550 -4
5.64×10 (1770) 7.11 stroke current has a significant impact on overvoltages and
1675 3.99×10-4 (2510) 5.02
that the effect of the front duration is not simple. It is therefore
more essential, and more appropriate, for the reliability to be
1800 2.50×10-4 (4000) 3.15
evaluated by generated overvoltages rather than by the
1950 7.94×10-5 (12600) 1.00 frequency of occurrence of lightning stroke current
2100 8.43×10-6 (119000) 0.11 waveforms This section, therefore, evaluates the reliability
2250 0.00 () 0.00 ensured in the context of the assumed lightning stroke current
2400 0.00 () 0.00
based on the generated overvoltage level. With regard to the
assumed lightning stroke current waveforms, a comparison is made
between a waveform with 200 kA and 1 / 70 ȝs in the study of
[u10-4]
0
6.0
Shell-type transformers
[circuits/route/year]
4.0 2
200kA,1.7ȝs Front duration
3 [ȝs]
2.0 4
the test voltage for the UHV field-test equipment (hereinafter core-type transformers, while the overvoltage generated by the
referred to as the conventional waveform), and a waveform with proposed waveform is low at 1616 kV, the lightning failure rate
200 kA and 1.7 / 70 ȝs, as proposed in [2] (hereinafter referred was 2.50×10-4 [times/route/year] (MTBF: 4000 [year,
to as the proposed waveform). It should be noted that the study route/time]), which is shown by the area surrounded by a blue
of reliability in this study was done under specific analysis line in Figure 13, accidentally just the same as that of shell-type
conditions. In addition, for the actual test voltages, LIWV, it is transformers, because generated overvoltages were generally
necessary to consider not only the back-flashover analysis lower. The overvoltage generated by the conventional waveform
results but also the impact of direct lightning strokes on phase is 1592kV and the failure rate, the area surrounded by a light red
conductors with shielding failures [18] and overvoltages in line in Figure 13, is estimated as about same as that calculated by
other lightning surge time areas, such as disconnector surges. the proposed waveform.
With regard to GIS’s, according to Figure 10b the overvoltage As for a UHV transmission system, making the front duration
generated by the conventional waveform is 2622 kV and the of the assumed lightning stroke current 1.7 ȝs instead of 1.0 ȝs
frequency of occurrence of overvoltages exceeding this is 2.27×10- is considered appropriate, based on the properties of lightning
6
%. Therefore, when LIWV is set to 2622kV generated from the current [2]. It was found from this study that lightning failures
conventional waveform, calculating the failure rate by integration continue to be basically zero, as seen in changes in the required
using equation (6), 5.45×10-7 [times/route/year] (MTBF: 1.83×106 reliability with a revised front duration.
[year, route/time]) is obtained. This failure rate is shown by the area
surrounded by a light red line in Figure 10b. On the other hand, the
overvoltage generated by the proposed waveform is 2137 kV and 7 CONCLUSIONS
the frequency of occurrence of overvoltages exceeding this is
The frequency of occurrence of lightning stroke current
6.80×10-5 % with a lightning failure rate of 1.64×10-5
waveforms was formulated from the lightning stroke current
[times/route/year] (MTBF: 61000 [year, route/time]), which is
waveform parameter characteristics based on observed
shown by the area surrounded by a blue line in Figure 10b. In
lightning data, and an evaluation of the failure rate of UHV
comparing the contour lines of both cases, in the case of the
substations was attempted in terms of the probability of
proposed waveform as shown in Figure 10b, generated
occurrence of lightning overvoltages exceeding the lightning
overvoltages are lower than with the conventional waveform, and
impulse withstand voltage (LIWV). The results of this study
the probability distribution of occurrence based on the proposed
are summarized below.
waveform extends to the range where the probability of occurrence
is higher and the frequency of occurrence of overvoltages with the 1) Based on the lightning stroke current waveform
proposed waveform is as high 30 times as that with the parameter characteristics obtained from observed lightning
conventional waveform. This means that the reliability from the data, the probability (density) distribution of occurrence of
point of view of lightning protection design decreases. However, lightning stroke current waveforms with the correlation
the absolute value of the frequency of occurrence is extremely between the current amplitude and the front duration taken
small compared to the assumed failure rate of 1.0×10-3 to 1.5×10-3 into account was formulated.
[times/route/year] (MTBF: about 700 to 1000 [year, route/time]) - 2) Using, as parameters, lightning stroke current
an evaluation value with a cumulative frequency of 0.3 % which waveforms with the correlation between the current amplitude
exceeds the conventionally assumed value of 200 kA, based only and the front duration taken into account, overvoltage analysis
on the current amplitude distribution frequency. Therefore, the was conducted in 5000 cases each for GIS’s, shell-type
lightning stroke waveform proposed in [2] maintains a high transformers and core-type transformers, respectively. With
reliability from the engineering point of view, namely, in the regard to GIS’s, overvoltages generated during back-flashover
evaluation the failure rate is basically zero. are suppressed by surge arresters. In general, however, the
Similarly, with regard to shell-type transformers, according to higher the current amplitude and the shorter the front duration,
Figure 7, the overvoltage generated by the conventional the higher the overvoltage generated. Conversely, when the
waveform under the present analysis conditions, is 1741 kV, and front duration was shorter than about 0.5 ȝs, overvoltages
the frequency of occurrence of overvoltages exceeding this is decreased. This is regarded as being caused by delayed back-
1.29×10-3 % and the failure rate is 3.10×10-4 [times/route/year] flashover and the decreased surge suppression by surge
(MTBF: 3230 [year, route/time]). The overvoltage generated by arresters of the voltage increases caused by pre-discharge.
the proposed waveform was 1800 kV and the frequency of With transformers on the other hand, overvoltages during
occurrence of overvoltages exceeding this was 1.04×10-3 % with back-flashover were less dependent on the front duration, and
a lightning failure rate of 2.50×10-4 [times/route/year] (MTBF: generated overvoltages were lower than those at GIS’s, due to
4000 [year, route/time]). These failure rates correspond to the the their large capacitance.
areas surrounded by a light red line and a blue line in Figure 12, 3) As a result of the trial calculation of the lightning failure
respectively. Unlike the case of GIS’s, the required reliability of rate of GIS’s, in the case where a test voltage of 2250 kV for
the proposed waveform is to some extent better than that of the the UHV field-test equipment is set as the LIWV, the failure
conventional waveform and the failure rate is reduced by about rate is 8.41×10-6 [times/route/year] (MTBF: 119000 [year,
20%. In either case, the reliability conventionally assumed with route/time]) under the analysis conditions of the present study.
only the current amplitude (assumed failure rate MTBF: about If the LIWV is reduced to 2100 kV, 1950 kV, and 1800 kV,
700 to 1000 [year, route/time]) is adequately ensured. As for the the failure rate is increased to 2.5, 6.5 and 18.9 times,
IEEE Transactions on Dielectrics and Electrical Insulation Vol. 18, No. 1; February 2011 231
respectively, from the baseline with the LIWV at 2250 kV; REFERENCES
however, the failure rate remains at 1.59×10-4 [1] J. Takami, and S. Okabe, “Observational Results of Lightning Current on
[times/route/year] (MTBF 6290 [year, route/time]) even if the Transmission Towers”, IEEE Trans. Power Delivery, Vol. 22, pp. 547-556,
2007.
LIWV is reduced to 1800 kV.
[2] S. Okabe, and J. Takami, “Evaluation of Improved Lightning Stroke Current
4) As a result of the trial calculation of the lightning failure Waveform Using Advanced Statistical Method”, IEEE Trans. Power Delivery,
rate of transformers under the conditions of the present study, Vol. 24, pp. 2197-2205, 2009.
[3] J. Takami, S. Okabe, and E. Zaima, “Evaluation of Lightning Surge
in the case of the calculation for shell-type transformers, if the Overvoltages at Substations Using Assumed Lightning Stroke Current
LIWV is set to 2250 kV, no overvoltages in excess occur, Waveforms Based on Observations”, IEEE Trans. Power Delivery, Vol. 25, pp.
resulting in a zero failure rate. The failure rate at the test 2958-2969, 2010.
voltage of 1950 kV of the UHV field-test equipment was [4] IEC 60071-1-2006, “Insulation co-ordination, Part 1: Definitions, principles and
rules”.
7.94×10-5 [times/route/year] (MTBF: 12600 [year,
[5] IEC 60071-2-1996, “Insulation co-ordination, Part 2: Applications guide”.
route/time]), and 3.99×10-4 [times/route/year] (MTBF: 2500 [6] IEEE Std 1313-1-1996, “IEEE Standard for Insulation Coordination-
[year, route/time]) even when the LIWV was reduced to 1675 Definitions, Principles, and Rules”.
kV. Since overvoltages generated at core-type transformers [7] IEEE Std 1313-2-1999, “IEEE Guide for Application of Insulation
are lower than those at shell-type transformers, the failure rate Coordination”.
[8] The Japanese Electrotechnical Committee, Standard for Test Voltage, JEC-
is about half that of shell-type transformers. 0102-1994, 1994 (in Japanese).
5) From the point of view of reliability, in the evaluation [9] Sub-committee for Power Stations and Substations, Lightning Protection
Design Committee, “Guide to Lightning Protection Design of Power Stations,
of the assumed lightning stroke current waveforms used for
Substations and Underground Transmission Lines”, CRIEPI Rep., No. T40,
the lightning protection design, the assumed lightning stroke 1995 (in Japanese).
current waveform with 200 kA and 1.7 / 70 ȝs proposed in [10] K. Berger, R. B. Anderson, and H. Kroeninger, “Parameters of Lightning
[2] ensures a lightning failure rate reliability for GIS’s at Flashes”, CIGRE, Electra, No. 41, pp. 23-27, 1975.
[11] R. B. Anderson, and A. J. Eriksson, “Lightning Parameters for Engineering
1.64× 10-5 [times/route/year] (MTBF: 61000 [year,
Application”, CIGRE, Electra, No. 69, pp. 65-102, 1980.
route/time]) or less, and a lightning failure rate reliability for [12] A. J. Eriksson, H. J. Geldenhuys, and G. W. Bourn, “Fifteen Years Data of
transformers - both shell-type and core-type - of 2.50×10-4 Lightning Measurements on a 60 Meter Mast”, Trans. S. African Inst. Elec.
[times/route/year] (MTBF: 4000 [year, route/time]) or less. Engrs., Vol. 80, No. 1, pp. 98-103, 1989.
The assumed lightning failure rate, based only on a current [13] Alternative Transients Program (ATP) Rule Book. OR: Canadian / American
EMTP User Group, 1987.
amplitude of 200 kA, for setting the test voltage of UHV [14] N. Nagaoka, “A Flashover Model Using a Nonlinear Inductance”, Trans. IEE
field-test equipment, is 1.0×10-3 to 1.5×10-3 [times Japan, Vol. 111-B, No. 5, pp. 529-534, 1991 (in Japanese).
/route/year] (MTBF: about 700 to 1000 [year, route/time]). [15] A. Ametani, and T. Kawamura, “A Method of a Lightning Surge Analysis
Comparing the failure rates, the assumed lightning stroke Recommended in Japan Using EMTP”, IEEE Trans. Power Delivery, Vol. 20,
pp. 867-875, 2005.
waveform proposed has adequate required reliability with a [16] T. Watanabe, Y. Yamagata, and E. Zaima, “Insulation Coordination for UHV
basically zero failure rate. System”, CIGRE Paper, No. 33-101, 1998 Session.
The probability distribution of occurrence of lightning [17] S.Okabe, S.Yuasa, M.Koto, and E.Zaima, “Evaluation of lightning surge
waveform for LIWV reduction of substation equipment”, 13th Intern. Symps.
stroke current waveforms formulated in the present study High Voltage Eng. (ISH), P.05.66, 2003.
would be useful not only for the lightning protection design of [18] J. Takami, S. Okabe, and E. Zaima, “Study of Lightning Surge Overvoltages at
substation equipment and for countermeasures against Substations Due to Direct Lightning Strokes to Phase Conductors”, IEEE Trans.
lightning damage to power transmission lines and structures, Power Delivery, Vol. 25, pp. 425-433, 2010.
[19] S. Taniguchi, T. Tsuboi, S. Okabe, Y. Nagaraki, J. Takami, and H. Ota,
but also for analyzing phenomena dependent on the current “Improved Method of Calculating Lightning Stroke Rate to Large-sized
amplitude and the front duration of lightning stroke current. Transmission Lines Based on an Electric geometry model”, IEEE Trans.
The authors would expect it to be widely used. While the Dielectr. Electr. Insul., Vol. 17, pp. 53-62, 2010.
lightning failure rate was evaluated on a trial calculation basis
using statistical methods, overvoltage analysis could be Shigemitsu Okabe (M’98) received the B.Eng., M.Eng. and
conducted in the future using a combination of all possible Dr. degrees in electrical engineering from the University of
parameters, such as transmission towers struck by lightning Tokyo in 1981, 1983 and 1986, respectively. He has been with
and the ac phases on phase conductors, and applying the Tokyo Electric Power Company since 1986, and presently is a
group manager of the High Voltage & Insulation Group at the
method of calculating lightning stroke rate to transmission R & D center. He was a visiting scientist at the Technical
lines [19]. Those should increase estimation accuracy of University of Munich in 1992. He has been a guest professor
overvoltages and reliability. at the Doshisha University since 2005, at the Nagoya
University since 2006, and a visiting lecturer at the Tokyo University. He works as a
While the relationship between GIS’s and transformers and secretary/member at several WG/MT in CIGRE and IEC. He is an Associate Editor of
the LIWV was referred to in the present study, for the actual the IEEE Transactions on Dielectrics and Electrical Insulation.
test voltages, LIWV, it is necessary to consider not only the
back-flashover analysis results but also the impact of direct Jun Takami (M’06) received the B.Eng., M.Eng. and Dr.
degrees in electrical engineering from Doshisha
lightning strokes on phase conductors with shielding failures University, Kyoto in 1995, 1997 and 2010, respectively.
[18] and overvoltages in other lightning surge time areas, such He joined Tokyo Electric Power Company in 1997 and at
as disconnector surges. In addition, it should be noted that the present is a member of the High Voltage & Insulation
study of reliability in this paper was done under specific Group at R & D center in Tokyo Electric Power
Company. His main research interest is the insulation
analysis conditions. design of power systems. He is a member of CIGRE.