Zamil Air Conditioners (ZAC), a sector business of Zamil Industrial, is the largest supplier of air conditioners in the Middle East. It manufactures
and markets a whole range of air conditioners from room air conditioners to packaged units to large capacity chillers for residential, commercial
and industrial applications. Zamil Air Conditioners was founded in 1974 as one of the first air conditioning companies to be established in Saudi
Arabia and today is a leading international manufacturer of air conditioning systems & service solutions and is Number One in the Middle East.
ZAC’s operations are structured into four companies supporting seven in-house brands and twelve products and service units as well as a
number of international brands under the OEM Sales. The seven in-house brands are Zamil Air Conditioners, Classic, Zamil, Cooline, CoolCare,
Climatech and Geoclima.
The four companies are:
1. Zamil Air Conditioners & Home Appliances Co. (L.L.C.), supporting Zamil, Classic, Cooline, GE and OEM brands for consumers.
2. Zamil Central Air Conditioners Co. (L.L.C.), supporting Zamil Air Conditioners, Cooline and Climatech for commercial and industrial customers.
3. Zamil Air Conditioning and Refrigeration Services Co. (L.L.C.), providing electromechanical engineering, construction and project management
services, HVAC Operation & Maintenance, Retrofit Services, Spare Parts, Fire Protection, Controls, Electrical Services, Coils, Ducting and Coating.
4. Geoclima srl is an independent business supporting other three companies for their requirements of Chillers and Double Skin AHU’s.
The first three Companies- direct their business operations from the First and Second Industrial Cities in Dammam, Saudi Arabia and have a
product design center in Austria.
GEOCLIMA has its engineering and production departments located at Monfalcone, Italy.
All the four companies, while operating independently, supplement each other’s activities in a way that makes synergy work at its best and
achieves ZAC’s goals of maximizing customer value and satisfaction.

OEM Sales - Private Labeling


Zamil Air Conditioners produces branded air conditioners under OEM agreements for several leading international brands. Such relationships are
testimony to the excellence of ZAC’s engineering and production processes. Most of the units produced under the private labeling agreements
are for window and mini-split systems. However, ZAC is expanding its OEM offerings to include residential and light commercial units. Some of
the OEM brands manufactured at Zamil Air Conditioners are: Supra, Sanyo and Blue Star.

Joint Venture
Middle East Air Conditioners - Joint Venture with General Electric.
Zamil Air Conditioners partners with GE Appliances - Europe since 1997, in a joint venture called Middle East Air Conditioners (MEAC), for
manufacturing and marketing of GE branded air conditioners.
MEAC was awarded the license to manufacture Window, Mini Splits and Ducted Split types under the brand names GE, Hotpoint and RCA. Today,
MEAC enjoys extensive coverage in Saudi Arabia, GCC and the African market. In an ever-changing market, MEAC continually strives to acquire
new technologies and stylish integrated design with optimum performance and reliability that bring greater value to customers.

Factories and Production


Zamil Air Conditioners has two prime manufacturing plants in Dammam, Saudi Arabia and a production facility in Italy operated by GEOCLIMA and
a product design center in Austria. ZAC can produce up to 900,000 room air conditioners, 300,000 mini-split systems and 65,000 central air-
conditioning systems per annum and supplies air conditioning products to over 55 countries across the world - the major markets being GCC,
Middle East, North Africa, Europe and Asia.

Quality & Product Certificates


The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2008 certification.
ZAC’s products are certified with:
1. CE (Council of European Community).
2. UL (Underwriters Laboratory).
3. Eurovent (Certified Performance).
4. ISO 9001-2008 (International Organization for Standardization).
5. AHRI (Air-Conditioning, Heating and Refrigeration Institute).
Other awards include the prestigious Engineering Excellence Award of General Electric and the inaugural Prince Mohammed bin Fahd Al Saud
Award for Factory Safety.

Our Products & Service Units


In addition to consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners manufactures a host of
residential, commercial and industrial air conditioners. This broad product range extends from the concealed units up to 5 TR, the ducted splits
up to 30 TR, the packaged units up to 100 TR, the single and double skin air handling units up to 138,316 CFM, the water chillers up to 590 TR
and the centrifugal chillers up to 5,000 TR cooling capacity.
Our products and services include, in addition to Maintenance, Retrofit & Operations (MRO), complete integrate suite of solutions like:
• Zamil Projects: Providing EPC for electromechanical works for Industrial, Utility and Oil & Gas customers.
• Zamil Controls: Design, assembly, integration and commissioning of low current & low voltage systems.
• Zamil Fire Protection: Design, integration and commissioning of active fire protection systems.
• Zamil Electrical: Design, integration and commissioning of lv/mv (low voltage/middle voltage) systems.
• Coil & Coating: Coil replacement, anti-corrosion coating, water proofing & reflective coating and passive fire protection solutions.
• Zamil Ducting: Facilities designs and manufactures high quality duct systems and other HVAC industry related products, utilizing state of the
art automated duct lines, Plasma Cutting, CNC Turret punch press and other specific machinery through two duct factories located in Saudi
Arabia western province (Yanbu) and Eastern province (Dammam).
INDEX

Contents Page

Model decoding ......................................................................................................................................... 3

Indoor unit features ................................................................................................................................... 4

Standard specifications ............................................................................................................................. 4

Outdoor unit features ................................................................................................................................ 5

ECM motors .............................................................................................................................................. 6

Microprocessor controlled thermostat ........................................................................................................ 6

Physical data ............................................................................................................................................ 7

Cooling capacities ..................................................................................................................................... 8

ECM motor air flow chart ........................................................................................................................... 9

Dimensions, indoor units ......................................................................................................................... 10

Dimensions, outdoor units ...................................................................................................................11-13

Typical schematic wiring diagram ........................................................................................................... 14

Installation, operation & maintenance .................................................................................................. 15-16

Electrical ................................................................................................................................................. 17

System design ........................................................................................................................................ 17

Servicing instructions .............................................................................................................................. 18

CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS.


THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

1
FEATURES
HYBRID DESIGN BETWEEN MINI SPLITS AND CENTRAL UNITS

INDOOR UNIT:
SASO CERTIFIED
*
COMPACT DESIGN WITH LOW PROFILE
*
HEIGHT RANGES FROM 9.6" TO 14.5"
*
UNITS ARE FOR DUCTED APPLICATIONS
*
QUIET PULSE FREE OPERATION
*
DRAW THRU AIRFLOW CONFIGURATION
*
ELECTRONICALLY COMMUTATED MOTOR (ECM)
*
REAR RETURN AIR FILTER
*
EASY MAINTENANCE AND INSTALLATION
*
G-90 GALVANIZED HEAVY GAUGE PANELS
* INDOOR UNIT - 'DYA' SERIES
DIGITAL MICRO PROCESSOR CONTROL
*
WIRED LCD DISPLAY THERMOSTAT
*

OUTDOOR UNIT:
SASO CERTIFIED
*
G-90 GALVANIZED HEAVY GAUGE PANELS
*
PAINT: ELECTROSTATIC POWDER COAT
*
COOL GRAY COLOR
HIGH EFFICIENCY TROPICAL DESIGN
*
POWERFUL COMPRESSOR
*
230 VOLT CONTROL
*
EXTERNAL SERVICE VALVES WITH GAUGE PORTS
*
LOW & HIGH PRESSURE SWITCHES
*
OPTIONAL COPPER OR COATED ALUMINUM FINS
*
COIL GUARD PROTECTION
*
SIDE AIR DISCHARGE
*
OUTDOOR UNIT - 'KYA' SERIES
(MODELS: KYA018 - KYA024)

2
MODEL DECODING
INDOOR UNIT
1, 2 & 3 4&5 6 7 8 9 10 11 12
BASIC COOLING CAPACITY MODE ELECTRICAL ACCESSORIES EVAPORATOR COIL FILTER OPTION*
(SERIES) (x 1000 BTUH) SUPPLY (V-Ph-Hz) COIL CONNECTION
DYA 18 C : COOL ONLY C : 230-1-60 N : STANDARD D : ALUMINUM FIN R : RH SIDE N : STANDARD B : R-410A
DUCTED SPLIT (FACING AIR
FAN COIL UNIT 24 H : HEAT PUMP M: FOR MATCHING S : SS DRAIN PAN E :COATED DISCHARGE)
(R-410A) WITH 'M' VOLTAGE ALUMINUM FIN
30 OUTDOOR UNIT V : VFC
KYA060 ONLY. F : COPPER FIN
36 INDOOR UNIT A:S & V
POWER SUPPLY A : ALUMINUM FIN
48 REMAIN 230-1-60. WITH RESISTEC

60 B : COPPER FIN
WITH RESISTEC

OUTDOOR UNIT (MODELS: KYA018 & KYA024)


1, 2 & 3 4, 5 & 6 7 8 9 10 11 12 13
BASIC NOMINAL MODE ELECTRICAL COMPRESSOR TYPE CONDENSER CONDENSER ACCESSORIES OPTION*
(SERIES) COOLING SUPPLY MOTOR COIL
CAPACITY (V-Ph-Hz)
(MBH)
KYA 018 C : COOL ONLY C : 230-1-60 R : RECIPROCATING N : STANDARD B :COATED N : STANDARD B : R-410A
CONDENSING ALUMINUM FIN
UNIT 024 H : HEAT PUMP
(R-410A)

OUTDOOR UNIT (MODELS: KYA030 - KYA060)


1, 2 & 3 4, 5 & 6 7 8 9 10 11 12 13
BASIC NOMINAL MODE ELECTRICAL COMPRESSOR TYPE CONDENSER CONDENSER ACCESSORIES OPTION*
(SERIES) COOLING SUPPLY MOTOR COIL
CAPACITY (V-Ph-Hz)
(MBH)
KYA 030 C : COOL ONLY C : 230-1-60 S : SCROLL N : STANDARD A : ALUMINUM FIN N : STANDARD UNIT B : R-410A
CONDENSING
UNIT 036 H : HEAT PUMP **
M : 380/400-3-60 B :COATED F : STANDARD UNIT
(R-410A) (4 WIRE) ALUMINUM FIN WITH FILTER DRIER
048 & SIGHT GLASS
C : COPPER FIN (LOOSE ITEMS)
060
M: ALUMINUM FIN M: METALLIC GUARD
WITH
RESISTEC V : VFC***

A: F & M
N : COPPER FIN
WITH B: F & V
RESISTEC
C: M & V

D : F, M & V

* This digit is required for identification in the decoding for R-410A unit.
** Applicable for KYA060 model only.
*** VFC for Run indicator only.
NOTE: At 400V-3Ph-60Hz power supply, voltage variation will be -10% & +5%.

3
INDOOR UNIT FEATURES
COMPACT DIMENSIONS
Low height units are ideal to fit into tight spaces. Maximum height of unit ranges from 9.6" to 14.5" (24cm to 37cm).
EASY INSTALLATION WITH FLARE NUT CONNECTIONS
No need for complicated brazing for connecting the refrigerant piping.
EASY MAINTENANCE / ONE SIDE ACCESS
Filters can be easily removed by lifting/sliding. Piping and controls are on one side for easy access.
DIGITAL & MICROPROCESSOR CONTROL WITH LCD DISPLAY THERMOSTAT
Programmable wired thermostat loaded with all required functions and features for safe, energy efficient & smooth operation.
QUIET, PULSE FREE AIR SUPPLY
Centrifugal fans that are statically and dynamically balanced, handle upto 0.5" w.g. (125pa) external static pressure allowing
you to keep the unit away from your comfort zone.
MATCHED WITH RELIABLE CONDENSING UNITS
For optimum performance in cooling and heat pump applications.

Quiet Operation Dedicated Thermostat Compact Dimensions High Cooling Capacity Easy Installation

STANDARD SPECIFICATIONS
ENVIRONMENT FRIENDLY UNITS
These units are developed as environment friendly units that use refrigerant R-410A, which has ZERO OZONE DEPLE-
TION POTENTIAL (ODP = 0) and therefore conform to the International protocol regulations concerning refrigerant gases.
Polyol Ester lubricants are used with R-410A.
UNIT CONSTRUCTION
These ducted indoor fan coil unit consists of a coil, motor/blower assembly, filter and a drain pan securely mounted on
heavy gauge galvanized steel housing. Steel sheet panels are zinc coated and galvanized by the hot dip process of lock-
forming quality conforming to ASTM A 653 commercial weight G-90. This unit is designed for those concealed overhead
installations which require supply ductwork. A 1.5" duct collar is provided into the front panel for supply air duct connection.
Return air is from the rear side.
Access to the blower assembly is provided through the removable bottom panel from where the complete fan/motor deck
can be removed for servicing. The panels are insulated with 5/16" thick polyethylene acoustic and thermal insulation.
BLOWER ASSEMBLY
The direct drive blower motor assembly is easily accessible for complete servicing after removal of fan deck from the unit.
The blower wheels are large in diameter and are of the forward curved design, statically and dynamically balanced for quiet
and smooth performance.
MOTORS
Motors are ECM type with an ultra high efficiency programmable brush-less DC Motors.
COILS
All cooling coils are of corrugated fin & tube type, constructed of enhanced copper tubes and mechanically bonded to
aluminum fins. As an option to aluminum fins, coated aluminum fins or corrugated copper fins may be provided. Tube
support sheets are of galvanized steel, formed to provide structural strength. Coils are provided with the orifice type
refrigerant metering device on all models (except DYA18/DYA24 models). This provides for ease of serviceability.
DRAIN PAN
The condensate drain pan is fabricated of 18 gauge galvanized steel. The drain pan is powder coat painted and the outer
surface is thermally insulated. Since water never touches the metal pan, then possibility of corrosion is eliminated.
FILTER
Polypropylene filters are provided as standard.

4
OUTDOOR UNIT FEATURES
A. GENERAL
The Zamil side discharge condensing units incorporate the latest innovative technology to provide quiet, reliable perfor-
mance. The wrap-around coil not only adds to the aesthetical appeal, it also gives optimum heat transfer efficiency.
The access panels provide access to the compressor and to the electrical control box. Removal of top panel gives access
to fan motor and coil.
These condensing units can be combined with a wide variety of evaporator coils and blower packages to provide quiet and
dependable comfort.
These units are available as standard cool only models.

Low Noise Level Powerful R-410A Compressor High Energy Efficiency Ratio

B. UNIT ENCLOSURE
All panels are of heavy gauge (G-90) galvanized steel sheet and completely weatherized for outdoor installation. Steel
sheet panels are zinc coated and galvanized by the hot dip process of lock-forming quality conforming to ASTM A 653
commercial weight G-90, followed by baked on electrostatic polyester dry powder coat.
C. COMPRESSOR
R-410A compressors are fully hermetic type and are provided with all the standard controls necessary for proper and safe
operation. These compressors have improved internal pressure relief valve which provides high pressure protection to the
refrigerant system and rubber vibration isolators for quiet and efficient operation.
D. AIR COOLED CONDENSER
1. The condenser coils are of the enhanced fin & tube type, constructed of enhanced copper tubes and mechanically
bonded to aluminum fins. As an option to aluminum fins, coated aluminum fins or corrugated copper fins may be
provided. Tube support sheets are of galvanized steel, formed to provide structural strength. Tubes are circuited to
ensure minimum pressure drop and maximum heat transfer. Each coil is completely dehydrated, charged and sealed at
the factory upon completion of pressure tests.
2. The fans are propeller type and direct-driven, front discharge & provided with fan guards.
3. Units are equipped with totally enclosed fan motors for greater reliability and dependable performance for many years.
Inherent thermal protection is automatic reset type.
4. For heat pump version units, fixed orifice expansion device is inherent within the condensing units on KYA030 - KYA060
(except KYA018 & KYA024 models where capillary is provided).
E. SERVICE VALVES
Both suction and liquid service valves are brass, back seating type with flare connections. Valves are externally located so
refrigerant tube connections can be made quickly and easily. Each valve has a gauge pressure port for ease of checking
refrigerant operating pressures.
F. LOW PRESSURE SWITCH
Auto reset SPST switch activated by refrigerant pressure - locks out the compressor, if the refrigerant pressure falls below
50 PSIG. Also provides additional protection against evaporator freeze up due to loss of indoor airflow.
G. HIGH PRESSURE SWITCH
Auto reset SPST switch activated by refrigerant pressure - locks out the compressor, if the refrigerant pressure rises above
650 PSIG. Also provides additional protection against compressor damage due to loss of outdoor airflow.

5
ELECTRONICALLY COMMUTATED MOTOR (ECM)
The ECM (Electronically Commutated Motor) is an ultra high efficiency programmable brush-less DC motor utilizing a
permanent magnet motor and a built-in inverter. DC motors are significantly more energy efficient than AC motors and
much easier to control.
1. Significant energy savings (67% average compared to PSC motors).
2. Unique factory preset air volume capability (+/- 5%).
3. Pressure independent fan operation.
4. Field adjustable fan air volume controller.

MICROPROCESSOR CONTROLLED THERMOSTAT


FEATURES BENEFITS
Wired remote controller with Liquid Crystal Display (LCD) Unit operation controlled remotely with a large LCD display.
with Touch screen

FAN/HEAT/AUTO/COOL/DRY mode of operation 5 modes of operation with automatic shift between COOL & HEAT when on AUTO.

Modulating fan speed with 10 steps along with AUTO mode Cover the whole range of CFM/capacity requirements.

SLEEP mode To raise/lower temperature setting by a maximum of 20F during night time for
added comfort and energy.

Auto Restart Thermostat settings are preserved in the memory in case of power interruption
and will be retrieved to operate the unit accordingly when power is restored.

Real Time Clock Display the day and time in AM/PM format.

7 Day Programmable Timer To select up to 7 days in advance when to start and when to stop operation.

De-icing To avoid freezing of indoor coil during COOL cycle.

Electronic Defrost cycle Prevent freezing of outdoor coil during HEAT cycle.

Child Lock To restrict the number of persons tampering with the control.

Room Temperature Display Both room & set point temperatures can be displayed in either 0C or 0F.

ON/OFF status LED indicator To inform on the status of operation.

6
PHYSICAL DATA
INDOOR UNIT DYA 18 DYA 24 DYA 30 DYA 36 DYA 48 DYA 60
MODEL
OUTDOOR UNIT KYA 018 KYA 024 KYA 030 KYA 036 KYA 048 KYA 060
PERFORMANCE
Gross cooling capacity, BTUh/kW 19381/5.678 23913/7.06 28835/8.44 34600/10.08 48130/14.02 55720/16.23
Rated cooling capacity, BTUh/kW 19000/5.56 23700/6.94 28200/8.26 33000/9.66 46000/13.47 53000/15.52
Actual total unit power input, Kw 1.6 1.94 2.276 2.797 3.711 4.52
Rated total unit power input, Kw 1.62 2.008 2.4 2.82 3.767 4.57
Actual EER 12.06 12.3 12.51 12.114 12.7 12.01
Rated EER 11.67 11.8 12.15 11.7 12.2 11.6
Heating capacity, BTUH/Kw 15893/4.65 19893/5.80 25298/7.36 27250/7.95 43060/12.54 49360/14.37
Total unit power input, Kw 1.56 2.06 2.16 3.0 3.5 4.0
Evaporator airflow, CFM 700 800 970 1200 1590 1800
Sound pressure level, dBA (high/medium/low) 36/34/33 42/36/35 44/41/37 45/42/37 45/43/38 46/44/38
INDOOR UNIT
Power supply (V-Ph-Hz) 230-1-60
Face area, ft2 2.2 2.67 4.37 4.37 4.37 4.37
Evaporator coil Tube dia, inch 3/8 3/8 3/8 3/8 3/8 3/8
No. of rows/FPI 3/14 4/14 4/14 4/14 4/14 5/14
Suction - Liquid line, inch 5/8 - 3/8 5/8 - 3/8 3/4 - 3/8 7/8 -1/2 7/8 -1/2 7/8 -1/2
Weight, Kg. 40 40 65 65 65 73
Minimum circuit ampacity, Amps 1.5 1.5 3.3 3.3 4.5 4.5
Maximum fuse size, Amps 15 15 15 15 15 15
OUTDOOR UNIT
Compressor 230-1-60 6/43 9.4/54 13.8/80 15.7/77 24.3/137 30.1/144
RLA/LRA 380/400-3-60 N.A. N.A. N.A. N.A. N.A. 10.7/64
Outdoor unit 230-1-60 8.96/20 16.9/25 18.08/30 21.28/35 33.5/55 40.2/70
MCA/MOCP
380/400-3-60 N.A. N.A. N.A. N.A. N.A. 16.57/45
Condenser airflow, CFM 2200 2200 2200 4600 4800 4800

Condenser Fan HP - RPM (Qty.) 1/8 - 900 1/8 - 900 1/8 - 900 1/8 - 900(2) 1/8 - 900(2) 1/8 - 900(2)
motor FLA (each) 0.83 0.83 0.83 0.83 0.83 0.83
Condenser coil Tube dia, inch 7mm 7mm 3/8 3/8 3/8 3/8
No. of rows/FPI 3/16 4/14 3/14 2/14 2/14 2/14
Refrigerant (R-410A) charge, oz. - Cool 96 101 201 353 260 310
Refrigerant (R-410A) charge, oz. - Heat pump 92 115 188 364 265 292
Suction - Liquid line, inch 5/8 - 3/8 5/8 - 3/8 3/4 - 3/8 7/8 -1/2 7/8 - 1/2 7/8 - 1/2
Dimensions, mm (width x depth x height) 1005x402x830 1005x402x830 967x392x829 1177x516x1282 1297x516x1282 1297x516x1282
Weight, Kg. (cool models) 70 74 85 132 145 145
Weight, Kg. (heat pump models) 73 78 90 138 150 150

NOTE: 1. Cooling capacities & power input data @ 80.60F (270C) DB/66.20F (190C) WB indoor & 950F (350C) ambient temperatures (SASO std.).
2. Heating capacities & power input data @ 680F (200C) DB/590F (150C) WB indoor & 44.60F (70C) outdoor temperatures. At outdoor
temperature less than -20C, other source of heating must be used.
3. Sound pressure level @ 9 feet distance and 0.15 ESP.
4. Pipe sizes are for runs up to 25 feet (7.6 meters) to indoor unit.

7
COOLING CAPACITIES
MODEL NUMBER (INDOOR UNIT/OUTDOOR UNIT)
DYA18/ KYA018 DYA24/ KYA024 DYA30/ KYA030 DYA36/ KYA036 DYA48/ KYA048 DYA60/ KYA060
CONDENSER EVAPORATOR AIRFLOW, CFM/DR
ENTERING AIR 710/0.128 800/0.128 950/0.135 1200/0.095 1600/0.086 1800/0.080
TEMP. (0F)
EVAPORATOR ENTERING AIR, WBE (0F)
62 66.2 72 62 66.2 72 62 66.2 72 62 66.2 72 62 66.2 72 62 66.2 72

TC 19.35 21.50 24.73 23.25 25.83 28.16 29.18 31.71 34.25 34.38 37.37 39.98 48.26 52.46 56.66 55.11 59.90 63.49

85 SC 18.86 17.46 15.71 20.97 19.78 18.59 24.96 23.54 22.13 30.62 28.89 26.87 42.96 40.53 37.29 48.83 45.64 41.98

kW 1.43 1.48 1.57 1.78 1.87 1.97 2.03 2.13 2.24 2.38 2.51 2.66 3.14 3.34 3.57 3.90 4.15 4.44

TC 17.64 19.38 22.29 21.77 23.92 26.31 26.24 28.83 31.42 31.83 34.60 37.37 43.80 48.13 52.94 50.71 55.72 60.01

95 SC 17.47 16.48 14.83 19.78 18.66 17.35 23.54 22.21 20.88 29.45 27.78 25.28 40.16 37.53 34.15 45.59 42.61 39.20

kW 1.52 1.60 1.70 1.85 1.95 2.07 2.16 2.27 2.38 2.65 2.79 2.96 3.52 3.71 3.97 4.31 4.51 4.83

TC 16.21 17.25 19.83 20.03 22.01 24.21 24.40 26.52 28.65 29.29 31.83 33.42 41.18 44.28 48.71 48.19 51.82 55.29

105 SC 15.80 15.49 13.94 18.40 17.35 16.31 21.19 19.99 18.79 26.80 25.28 22.75 37.00 34.90 32.11 42.86 40.05 37.25

kW 1.64 1.71 1.81 2.00 2.09 2.21 2.26 2.38 2.50 2.94 3.12 3.31 4.02 4.23 4.53 4.75 5.05 5.38

TC 14.44 15.20 17.48 17.11 18.80 20.30 23.31 25.06 26.81 26.36 28.65 30.37 36.67 40.29 43.92 43.86 47.67 51.01

115 SC 14.85 14.56 13.10 17.84 16.83 15.65 19.92 18.79 17.29 24.12 22.75 20.25 34.73 32.46 30.19 40.71 38.05 35.77

kW 1.70 1.79 1.90 2.09 2.20 2.33 2.65 2.76 2.90 3.29 3.50 3.74 4.63 4.82 5.16 5.41 5.76 6.16
8

TC 13.11 13.38 15.38 14.82 15.60 16.85 19.60 21.30 23.01 24.19 25.73 27.02 33.28 36.98 39.57 40.08 44.04 46.24

125 SC 13.38 13.12 11.81 16.84 16.51 15.52 17.93 16.91 15.22 22.86 21.57 18.98 32.81 31.25 29.06 38.67 35.81 32.23

kW 1.86 1.93 2.07 2.23 2.38 2.52 2.78 2.93 3.10 3.94 4.15 4.38 5.14 5.47 5.83 6.09 6.41 6.89

LEGEND:
TC – Total Capacity (1000 Btuh) Gross
SC – Sensible Heat Capacity (1000 Btuh)
kW – Total unit power input
DR – Wet Bulb depression ratio
DBE – Dry Bulb Temp. (0F) of Air Entering Coil
WBE – Wet Bulb Temp. (0F) of Air Entering Coil
DBL – Dry Bulb Temp. (0F) of Air Leaving Coil
WBL – Wet Bulb Temp. (0F) of Air Leaving Coil

NOTES:
1. Capacities above are based on DBE = 80.60F. For higher or lower DBE, add following Correction Factor = 1.08 x CFM (1 – DR) (DBE – 80.6).
2. To calculate leaving conditions, follow this procedure: DBL = DBE – (Sensible Capacity (Btuh) / 1.08 x CFM); WBL = DBL – [DR (DBE – WBE)].

MULTIPLIERS FOR LOWER CFM


% of rated airflow 100% 95% 90% 85% 80% 75% 70% 60%
TC 1 0.98 0.96 0.93 0.91 0.89 0.87 0.83
SC 1 0.965 0.93 0.90 0.87 0.845 0.82 0.78
kW 1 0.992 0.985 0.97 0.965 0.96 0.94 0.93
ECM AIR FLOW CHART
CFM Range
Model No. Factory Set
Minimum Maximum

DYA18 700 400 750


DYA24 800 510 850
DYA30 1000 650 1100
DYA36 1200 900 1250
DYA48 1600 1275 1600
DYA60 1800 1550 1900

NOTE: Values include losses for dry coil and filters.

DYA18 WITH 1/4 HP ECM DYA24 WITH 1/4 HP ECM


0.30 0.30

0.25 0.25
ESP (IN.W.G)

ESP (IN.W.G)
0.20 0.20

0.15 0.15

0.10 0.10

0.05 0.05

0.00 0.00
400 460 525 590 655 705 750 510 575 640 700 765 805 850

CFM CFM

DYA30 WITH 1/3 HP ECM DYA36 WITH 1/3 HP ECM


0.50 0.50

0.40 0.40
ESP (IN.W.G)

ESP (IN.W.G)

0.30 0.30

0.20 0.20

0.10 0.10

0.00 0.00
650 700 750 800 850 880 920 960 1005 1055 1100 900 935 970 1000 1050 1080 1125 1160 1200 1225 1250

CFM CFM

DYA48 WITH 1/2 HP ECM DYA60 WITH 1/2 HP ECM


0.50 0.50

0.40 0.40
ESP (IN.W.G)

ESP (IN.W.G)

0.30 0.30

0.20 0.20

0.10 0.10

0.00 0.00
1275 1305 1340 1375 1400 1445 1470 1500 1540 1570 1600 1550 1590 1625 1665 1695 1730 1755 1785 1825 1865 1900

CFM CFM

9
DIMENSIONS - INDOOR UNITS
DYA18 - DYA60
D
4 A 3/4" NPT(14TPI)
DRAIN TUBE
I 5 H

2
E
B

25 (1.00")
7

END VIEW 6 TOP VIEW END VIEW

89 (3.50")
F 3
G
C

FRONT VIEW

1. Blower & motor assembly


2. Evaporator coil
3. Control box
4. Filter rack
5. Unit mounting brackets (4 Nos.)
6. Duct connection
7. Power entry hole (1-1/8" dia.)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

DIMENSIONS
MODEL
A B C D E F G H I
DYA 18 904 (35.6) 610 (24) 244 (9.6) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1)
DYA 24 904 (35.6) 610 (24) 305 (12) 960 (37.8) 521 (20.5) 769 (30.3) 183 (7.2) 841 (33.1) 206 (8.1)
DYA 30 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 851 (33.5) 234 (9.2) 1155 (45.5) 292 (11.5)
DYA 36 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 851 (33.5) 234 (9.2) 1155 (45.5) 292 (11.5)
DYA 48 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5)
DYA 60 1194 (47) 762 (30) 368 (14.5) 1245 (49) 625 (24.6) 894 (35.2) 266 (10.5) 1155 (45.5) 292 (11.5)

10
DIMENSIONS - OUTDOOR UNITS
KYA018 & KYA024

AIR IN

Model A (mm) B (mm) C (mm) D (mm) E (mm)


D

C
KYA018 1005 830 402 436 628
KYA024 1005 830 402 436 628

AIR OUT 19 mm x 14mm MOUNTING SLOT 4 NOS.

TOP VIEW

FRONT VIEW END VIEW

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

11
DIMENSIONS - OUTDOOR UNITS
KYA030

AIR IN

15(0.59)
20 (0.79)

435(17.16)
392 (15.43)
AIR IN

70(2.76)

DETAIL- A
AIR OUT SEE DETAIL -A
(TYPICAL AT FOUR PLACES)
133 (5.25) 698(27.5)

TOP VIEW

967 (38.1)

POWER & CONTROL


WIRE ENTRY

ACCESS PANEL
829 (32.62)

9.5 (3 8") FLARE


TYPE CONN.
82 (3.25) 63(2.5)

16(0.63)

533(21)
152 (6.0)

19 (3 4") FLARE
19(0.75) TYPE CONN.
89 (3.5)
FRONT VIEW END VIEW

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

12
DIMENSIONS - OUTDOOR UNITS
KYA036, KYA048 & KYA060
D
AIR IN

C
E

AIR IN AIR IN

AIR OUT

A
TOP VIEW
TOP VIEW

CONTROL BOX ACCESS PANEL


B

ACCESS PANEL 7
8" CONTROL WIRE ENTRY
5
8" POWER WIRE ENTRY
38 [1.5"]

1
2" LIQUID CONN.)
F
G
7
8" SUCTION CONN.)

FRONT VIEW END VIEW


FRONT VIEW END VIEW
MODEL NUMBER A B C D E F G
KYA036 1177 (46.32) 1244 (48.97) 516 (20.32) 713 (28.07) 549 (21.6) 282 (11.11) 102 (4)

KYA048 - KYA060 1297 (51.04) 1244 (48.97) 516 (20.32) 783 (30.83) 549 (21.6) 299 (11.78) 102 (4)

NOTE: All dimensions are in mm (dimensions in brackets are in inches).

13
TYPICAL SCHEMATIC WIRING DIAGRAM
LEGEND
ATB AUXILIARY TERMINAL BLOCK
COM COMMON
ECB ELECTRONIC CONTROL BOARD
ECM ELECTRONICALLY COMMUTATED MOTOR
GND LUG GROUND
L1 LINE 1
L2 LINE 2 OR NEUTRAL
_ _ _ FIELD WIRING

FACTORY WIRING

NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE.
2. MOTORS ARE THERMALLY PROTECTED.
3. USE COPPER CONDUCTOR WIRES ONLY.
4. REFER TO INTERCONNECTING WIRING DIAGRAM
BEFORE INSTALLATION

INTERCONNECTING DETAILS BETWEEN INDOOR & OUTDOOR UNIT


NOTE: Route wires according to diagram below & ignore all other terminal connection on outdoor unit. Also route outdoor coil sensor wire from indoor
to outdoor sensor holder for heat pump units.
ATB 1 6 8 T3A/N 37A

INDOOR UNIT
DYA SERIES
ATB
1 6
INDOOR UNIT OUTDOOR UNIT
DYA SERIES KYA SERIES
ATB 1 5 6 8

T3A 37A
OUTDOOR UNIT
KYA SERIES
36A

CAP
35A
COMP
1 5 6 ATB FM

NOTE:
T3A IS T1 ON 1PH CONDENSER UNITS

COOL MODELS HEAT PUMP MODELS

14
INSTALLATION - INDOOR UNIT
The complete shipment should be inspected for damage. Any damage, visible or concealed, should be reported immedi-
ately to the delivery man or driver and noted on the shipping invoice.

Place unit in position and make sure that unit is level. This is important to assure proper drainage and operation. Slots
provided in the mounting brackets should be used for installing the units.
Be sure that foreign material is not allowed to fall into or collect in the drain pan. Special care must be taken to prevent
paint, plaster, insulation or other foreign material from being deposited on the motor or blower wheels.

MAINTENANCE
COIL: Coil may be cleaned by removing case and brushing between fins with a stiff wire brush. Brushing should be
followed by cleaning with vacuum cleaner. The coil may also be cleaned by using a high pressure air, if compressed air
source is available. It should be pointed out that if air filters are used and periodically cleaned, the coils will not be clogged
up prematurely.

DRAIN PIPE: Drain pipe should be checked before summer operation of unit is begun. If it is clogged, steps should be
taken to clear the debris so that condensate will flow out easily. A standard pipe cleaner for 1/2" ID pipe may be used.
Periodic checks of the drain pipe should be taken during summer operation, as there is a possibility of it becoming clogged
with dirt.

FILTER CLEANING: Remove access panel, slide filter out of filter rack, and clean as follows:
Tap filter on solid surface to dislodge heavy particles. Wash under stream of water. Set filter on end with slots in frame
down, which allows it to drain. Filters should dry thoroughly before reuse.

REPLACEMENT PARTS: When writing for replacement parts, refer to model number and serial number on the name plate
of the unit.

15
INSTALLATION & START-UP INSTRUCTIONS - OUTDOOR UNIT
SAFETY CONSIDERATIONS
Improper installation, service, maintenance or use can cause explosion, fire, electrical shock or other conditions which may
cause personal injury or property damage. Check with your nearest Zamil dealer/sales office for information or assistance.
Warning: Before installation or servicing the system, always turn off main power supply. Electrical shock can cause
personal injury or death.

INSTALLATION
STEP-1:
Check equipment and job site
Unpack unit and move to final location taking care not to damage the unit. Remove screws holding the unit to wooden
pallet and remove wooden pallet.

STEP- 2:
Location of unit
Place the unit with minimum clearance as shown in figure below to enable space for installation, service and optimum
performance of the unit. Be sure that the discharge air from the condenser is not restricted. Double the clearance when
multiple units are installed at one location. Units may be installed using mounting pads on the floor, concrete slabs, steel
frames with adequate strength.

203mm (8") FOR KYA018, 024 & 030


AIR IN
254mm (10") FOR KYA036 AND ABOVE
254mm (10") FOR KYA036 AND ABOVE
203mm (8") FOR KYA018, 024 & 030

AIR IN

610mm (24") CLEARANCE MINIMUM

AIR OUT
914mm (36") CLEARANCE MINIMUM

STEP-3:
Piping connections
Outdoor units should be connected to indoor units using field-supplied piping of refrigerant grade and correct size. The
liquid and suction line diameters can be determined from the physical data table. For piping requirements beyond 25 ft
(7.62 m), obtain information from your nearest Zamil dealer/sales office.
If either refrigerant piping or indoor coil is exposed to atmospheric conditions, it must be dehydrated to 500 microns to
eliminate moisture contamination in the system.
It is advisable to size piping according to recommended ASHRAE methods. Install piping according to refrigeration
standard practice. Run refrigerant pipes as directly as possible, avoiding unnecessary turns and bends. Install refrigerant
pipes carefully to prevent damaging the suction pipe insulation and vibration transmission to the structure.

Outdoor unit connected to factory matched indoor unit


Outdoor unit contains correct system refrigerant charge for operation with matched indoor unit as given on cooling capacity
table and when connected with up to 25 ft (7.62 m) of field-supplied piping. Check refrigerant charge for maximum efficiency.

16
ELECTRICAL
STEP 1: INSTALLATION
A) Please ensure regular power supply to the unit is as per unit nameplate (Volts/Ph/Hz) requirements.
Caution: Operation of the unit on improper power supply like generators will result in damage to the unit.
Note: Use copper wires of proper rating for all field wiring.
Warning: Before servicing or installation of the unit, always TURN OFF all power to the unit. There may be more than one
disconnect switch. Ensure all of them are turned off. Electrical shock can cause personal injury or death.

B) Ground & power wires


Connect power wires to terminal block per wiring diagram.
Connect ground wire to the ground lug inside the control box.

C) Wiring
1. All wiring must comply with the "National Electric Code" and local electrical standards.
2. The power supply, voltage, frequency and phase must coincide with the unit nameplate.
3. Power wiring to the equipment must be adequately sized for maximum ampacity as shown on unit name plate; but not
less than 14 gauge (2.5 mm2) for lower amps.
4. For control wiring, use approved thermostat wire [minimum 18 gauge (0.75 mm2)], color coded wires. Never use tele-
phone wire for this purpose.
5. Power supply should be checked to be certain that supply voltage agrees with equipment nameplate. Serious damage
to compressors and motors can occur, if improper voltage is applied.
6. Install adequate branch disconnect switch as per NEC size requirements to handle unit starting current. Locate dis-
connect switch within sight and readily accessible from the unit.

STEP 2: START-UP
1. Energize crankcase heater for a minimum of 12 hours prior to the system start-up. To energize crankcase heater only,
set thermostat to "off" position and close electrical disconnect switch to the outdoor unit.
2. Fully open liquid/suction service valves.
3. Close electrical disconnect switch to energize the system.
4. Set room thermostat to desired temperature.

SYSTEM DESIGN
THE CONDENSING UNIT SYSTEM HAS BEEN DESIGNED BASED ON THE FOLLOWING:
• Intended for outdoor installation with free air intake and discharge.
• Minimum outdoor operating air temperature during cooling without low ambient operation option is 55 F (12.7 C).
0 0

• For reliable operation, unit should be level on horizontal plane.


• For interconnecting refrigerant pipe lengths greater than 25 feet (7.6 meters), check with your local Zamil sales office.
• Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of
connector provided.

17
SERVICING INSTRUCTIONS

r
moto
&
ers
b low
for CM
ss 95
cce
A

CM
30

Blower deck holding bolt


50
CM

CM
50
Blower deck

Bottom panel

NOTES:
1. Required indoor unit access clearances are shown as hatched area.
2. Free sevice access should be available from the bottom of the unit for removing & servicing the blower/motor deck.
3. Servicing instructions:
a) Remove the bottom panel.
b) Support the blower deck while unscrewing the 4 blower deck holding bolts and bring down the blower deck.

18