IDMT Relay Operating TIME CALCULATIONS

Operating TIME= K * Tms =


(I/Is)^t -1

K
K t I=Fault Current
For NI 0.14 0.02 Is=Current Settings
For VI 13.5 1 t=
For EI 80 2 Tms=
For LTI 120 1 (I/IS)=

Operating time in seconds at various TMS


I/Is Operating Time
at TMS 1.00 0.05 0.075 0.1 0.125 0.15 0.175

2 10.02902702 0.501451 0.752177027 1.002903 1.253628 1.504354 1.75508


3 6.3019309272 0.315097 0.47264482 0.630193 0.787741 0.94529 1.102838
4 4.9797561077 0.248988 0.373481708 0.497976 0.62247 0.746963 0.871457
5 4.2797200709 0.213986 0.320979005 0.427972 0.534965 0.641958 0.748951
6 3.8371924541 0.19186 0.287789434 0.383719 0.479649 0.575579 0.671509
7 3.5277424308 0.176387 0.264580682 0.352774 0.440968 0.529161 0.617355
8 3.2967736178 0.164839 0.247258021 0.329677 0.412097 0.494516 0.576935
9 3.1163499624 0.155817 0.233726247 0.311635 0.389544 0.467452 0.545361
10 2.9705986242 0.14853 0.222794897 0.29706 0.371325 0.44559 0.519855
11 2.8497862274 0.142489 0.213733967 0.284979 0.356223 0.427468 0.498713
12 2.7475870184 0.137379 0.206069026 0.274759 0.343448 0.412138 0.480828
13 2.6596971787 0.132985 0.199477288 0.26597 0.332462 0.398955 0.465447
14 2.5830780233 0.129154 0.193730852 0.258308 0.322885 0.387462 0.452039
15 2.515517459 0.125776 0.188663809 0.251552 0.31444 0.377328 0.440216
16 2.4553632258 0.122768 0.184152242 0.245536 0.30692 0.368304 0.429689
17 2.4013539148 0.120068 0.180101544 0.240135 0.300169 0.360203 0.420237
18 2.3525081763 0.117625 0.176438113 0.235251 0.294064 0.352876 0.411689
19 2.3080498993 0.115402 0.173103742 0.230805 0.288506 0.346207 0.403909
20 2.2673563672 0.113368 0.170051728 0.226736 0.28342 0.340103 0.396787
21 2.2299215159 0.111496 0.167244114 0.222992 0.27874 0.334488 0.390236
22 2.1953293693 0.109766 0.164649703 0.219533 0.274416 0.329299 0.384183
23 2.1632344897 0.108162 0.162242587 0.216323 0.270404 0.324485 0.378566
24 2.1333473591 0.106667 0.160001052 0.213335 0.266668 0.320002 0.373336
25 2.1054232901 0.105271 0.157906747 0.210542 0.263178 0.315813 0.368449
26 2.0792539037 0.103963 0.155944043 0.207925 0.259907 0.311888 0.363869
27 2.0546605017 0.102733 0.154099538 0.205466 0.256833 0.308199 0.359566
28 2.0314888563 0.101574 0.152361664 0.203149 0.253936 0.304723 0.355511
29 2.0096050736 0.10048 0.150720381 0.200961 0.251201 0.301441 0.351681
30 1.9888922781 0.099445 0.149166921 0.198889 0.248612 0.298334 0.348056
ALCULATIONS

0.522629

0.14
1200
320
0.02
0.1
3.75

onds at various TMS

0.2 0.225 0.25 0.275

2.005805 2.256531 2.507257 2.757982


1.260386 1.417934 1.575483 1.733031
0.995951 1.120445 1.244939 1.369433
0.855944 0.962937 1.06993 1.176923
0.767438 0.863368 0.959298 1.055228
0.705548 0.793742 0.881936 0.970129
0.659355 0.741774 0.824193 0.906613
0.62327 0.701179 0.779087 0.856996
0.59412 0.668385 0.74265 0.816915
0.569957 0.641202 0.712447 0.783691
0.549517 0.618207 0.686897 0.755586
0.531939 0.598432 0.664924 0.731417
0.516616 0.581193 0.64577 0.710346
0.503103 0.565991 0.628879 0.691767
0.491073 0.552457 0.613841 0.675225
0.480271 0.540305 0.600338 0.660372
0.470502 0.529314 0.588127 0.64694
0.46161 0.519311 0.577012 0.634714
0.453471 0.510155 0.566839 0.623523
0.445984 0.501732 0.55748 0.613228
0.439066 0.493949 0.548832 0.603716
0.432647 0.486728 0.540809 0.594889
0.426669 0.480003 0.533337 0.586671
0.421085 0.47372 0.526356 0.578991
0.415851 0.467832 0.519813 0.571795
0.410932 0.462299 0.513665 0.565032
0.406298 0.457085 0.507872 0.558659
0.401921 0.452161 0.502401 0.552641
0.397778 0.447501 0.497223 0.546945
The inverse time delayed characteristics comply with the following formula (based on IEC60255-3
and IEEE Std C37.112-1996 standard).

�=( �/
((�/��)^�−�)+�)×𝐓𝐌�

Where:
k = Constant, the setting [50/51P4.K]. 13.50
α = Constant, the setting [50/51P4.Alpha]. 1.00
C = Constant, the setting [50/51P4.C].
t = Operation time . 3.186
I = Measured phase current. 0.30
Ip = current threshold setting 0.33
TMS = Time Multiply Setting 0.23

Ip is the current threshold setting; the current setting of the stage 4 overcurrent [50/51P4.I_Set]
is used as the Ip in this relay. If the stage 4 overcurrent protection is used as IDMT overcurrent
protection, the range of the setting [50/51P4.I_Set] is 0.05×In ~ 4×In.

Tp is the time multiplier setting; the multiplier setting of the IDMT overcurrent protection
[50/51P4.TMS] is used as Tp in this relay. If the stage 4 overcurrent protection is used as
IDMT overcurrent protection, the range of the setting [50/51P4.TMS] is 0.05 ~ 100.00.

Some recommended types of IDMT characteristic curves are applied in this relay. It is also can be
programmed according to the demand of the special practical application through the
PCS-Explorer configuration tool auxiliary software.
The setting [50/51P4.Opt_Curve] can be used to select the expected curve.

If the setting [50/51P4.Opt_Curve] is set as “1” to “12”, these settings [50/51P4.K], [50/51P4.Alpha]
and [50/51P4.C] do not need to be set, and this relay will use these values as listed in above table.
above
table.