Specifications
UL Recognized: File E52105 Guide XAPX2 Stage Outputs: Pilot-duty triacs
Storage Temp: 0° to 186°F Stage Ratings: 120/240VAC, 90VA max
Operating Temp: 0°F to 167°F Stage Terminal Block: 12-22 AWG, copper only
Line Voltage: 120/240VAC +/-10%, 12VA max Stage Quick Connects: 0.25” x 0.032” male
Frequency: 47 to 63 Hertz Selectable Time Delay: 5 seconds - 10 minutes
Input Impedance: 250Ω (mA), 33KΩ (VDC) Vernier Output: 12VDC pulse, 0.5 VA max.
Input Wire Range: 18-22 AWG, copper only Slaves Allowed: 1 per 10 stage master
Input Quick Connects: 0.25” x 0.032” male Slave Cable: 30” ribbon-cable, supplied with unit
Catalog and Part Numbers: 201 & 204 Series
2 0 1-S95 - M10 - 2 E
Mounting & Series Type Terminals Input Code
201 = metal plate M = master 2 = terminal A = 2200 ohm
204 = NEMA 1 enclosure S = slave blocks C = 135 ohm
E = 4-20mA
Typically used for new products Stages L = 0-10VDC
and to replace earlier models of 05 = 5 stages V = adjustable VDC
M72, S71, S81 and S92 Series. 10 = 10 stages blank = slave
Note: Standard masters have 4 field-selectable inputs: A, C, E and L ( S input code).
The input code determines the switch position before shipment from the factory.
202-S95-M10 - 2 S - I
Mounting & Series Type & Stages Terminals Control
Six snap-in nylon standoffs. M = master 2 = terminal blocks I = fixed for
Typically used in INDEECO S = slave 1 = QC (obsolete) linear and
electric duct heaters and proportional,
process air heaters. 05 = 5 stages Input Code regardless of dip
10 = 10 stages S = (see note) switch setting.
Note: Masters have selectable inputs: A (2200 ohm), C (135 ohm), E (4-20mA), L (0-10VDC)
Slaves do not have an input nor control code.
2 0 5 - S 9 5 - M 1 0 - 2A - 21
Mounting & Series Type Terminals Temperature Range
NEMA 1 enclosure with M = master 2 = terminal 21 = 0-100 F
setpoint adjuster in lid. blocks 41 = 50-150 F
Stages 43 = 50-180 F
Requires 310 Series 05 = 5 stages Input Code 47 = 100-210 F
thermistor sensor. 10 = 10 stages A = 2200 ohms 51 = 120-250 F
55 = 150-250 F
Operation:
The M&S Series can be used to replace earlier models of H&J Series and
D&E Series power controllers. Contact the factory for additional informa-
tion and cross-referencing.
M&S Series power controllers are solid-state, zero-cross fired, proportional
devices. Line voltage is switched 0-100% linearly, with respect to the input
range. A 4 second time-base controls power to the load. For example, a
5VDC signal to a 0-10VDC input will cycle the output full on for 2.0 seconds
and full off for 2.0 seconds. Line voltage is used to power the electronics.
An external transformer is not required.
Features of these controllers include an LED to indicate when the output
should be on. Also, the output will be shut off if the input signal is discon-
nected or the input is shorted.
Masters can operate alone or can drive numerous slaves to control mul-
tiple loads. Slaves can be driven from other controllers with a pulsing-DC
type output (see specifications).
101-M3-480-50- E- W
Mounting Type AC Voltage Max Current Input Code Gasket Kit
101 - through M = master 120 = 120VAC 50 = 50 amps A = 2200 ohm W = included
panel S = slave 208 = 208VAC 70 = 70 amps C = 135 ohm blank = none
240 = 240VAC D = 609VDC
AC Phase 277 = 277VAC E = 4-20 mA
1 = 1 phase 480 = 480VAC L = 0-10VDC
3 = phase 600 = 600VAC blank = slave
Note: Input boards can be changed in the field to reconfigure the power controller.
Some models, i.e. 440VAC, have a separate 120VAC transformer for the electronics.
Contact the factory for other catalog and part numbers not shown above.
Specifications
Storage Temp: -400 to 1900 F Load Current: 0.5A to Max Current rating
Operating Temp: -400 F to 1320 F Load Wire Range: 2-18 AWG, copper only
UL Recognized: File E52105 Guide XAPX2 Input Impedance: 250Ω (mA), 47KΩ (VDC)
Isolation: 2500Vrms input to output Input Wire Range: 16-22 AWG, copper only
Isolation: 2500Vrms output to heatsink Slave Input: 3.0-12VDC, 270KΩ impedance
Line Voltage: +/- 10% of AC Voltage rating UL Type 4X with option “W” gaskets.
Frequency: 47 to 63 Hertz, sinewave only Panel gasket and screws shipped loose.
85-2222-83-2
Physical
Dimensions
Wiring Diagrams
1 phase and 3 phase units
Wiring Diagrams
120VAC Electronic Input Board Specifications
Input Code Full Off Full On Board Part #
Transformer
A = 220 ohms 2150 ohms 2250 ohms 110-B50-M-A
C = 135 ohms 20 ohms 120 ohms 100-B50M-C
D = 6-9 VDC 6.5 VDC 8.5 VDC 110-B50M-D
E = 4-20mA 5.6mA 18.4 mA 100-B50M-E
L = 0-10VDC 1.0 VDC 9.0 VDC 110-B50M-L
S = slave < 3.0 VDC >3.0 VDC 110-B50S
85-2222-83-2