S95 Series Step Controls

www.indeecocontrols.com

201 Series 202 Series 204 Series 205 Series

Operation Dead Band Control: Typically used by older


The S95 Series step controls can be used to model step controls. When the input signal is
replace earlier models of M72 Series, S71 Series, within the input range, the stages do not change.
S81 Series and S92 Series step controls. Contact Above the input range, stages are added. Below
the factory for additional information and cross- the input range, stages are removed.
referencing. Common applications are HVAC Proportional Control: The total number of
duct heaters, process air heaters and boilers. stages ON, including the optional vernier stage,
Features include status leds and diagnostics. is linear with respect to the input range. For
A test mode will cycle the selected stages, testing example, a 5.0VDC signal to a 0-10VDC input
the load wiring, contactors and stage operation. will result in half of the stages being ON. The
A vernier control is available, which results vernier control operates 0-100% between stages.
in more precise control than is possible with a Progressive Switching: Even wear on stages is
standard step control. A separate power controller achieved by turning ON stages 1 to 10 in order,
provides proportional control (0-100% load), in then starting over with stage 1. When removing
between the switching of step control stages. stages, the first stage ON is the first stage OFF.
Two different control modes and switching Linear Switching: Stage 1 is the first stage to
schemes can be selected, per the following: be turned ON and the last stage turned OFF.
For example: 1,2,3,4,5 ON then 5,4,3,2,1 OFF.

Specifications
UL Recognized: File E52105 Guide XAPX2 Stage Outputs: Pilot-duty triacs
Storage Temp: 0° to 186°F Stage Ratings: 120/240VAC, 90VA max
Operating Temp: 0°F to 167°F Stage Terminal Block: 12-22 AWG, copper only
Line Voltage: 120/240VAC +/-10%, 12VA max Stage Quick Connects: 0.25” x 0.032” male
Frequency: 47 to 63 Hertz Selectable Time Delay: 5 seconds - 10 minutes
Input Impedance: 250Ω (mA), 33KΩ (VDC) Vernier Output: 12VDC pulse, 0.5 VA max.
Input Wire Range: 18-22 AWG, copper only Slaves Allowed: 1 per 10 stage master
Input Quick Connects: 0.25” x 0.032” male Slave Cable: 30” ribbon-cable, supplied with unit
Catalog and Part Numbers: 201 & 204 Series

2 0 1-S95 - M10 - 2 E
Mounting & Series Type Terminals Input Code
201 = metal plate M = master 2 = terminal A = 2200 ohm
204 = NEMA 1 enclosure S = slave blocks C = 135 ohm
E = 4-20mA
Typically used for new products Stages L = 0-10VDC
and to replace earlier models of 05 = 5 stages V = adjustable VDC
M72, S71, S81 and S92 Series. 10 = 10 stages blank = slave
Note: Standard masters have 4 field-selectable inputs: A, C, E and L ( S input code).
The input code determines the switch position before shipment from the factory.

Catalog and Part Numbers: 202 Series

202-S95-M10 - 2 S - I
Mounting & Series Type & Stages Terminals Control
Six snap-in nylon standoffs. M = master 2 = terminal blocks I = fixed for
Typically used in INDEECO S = slave 1 = QC (obsolete) linear and
electric duct heaters and proportional,
process air heaters. 05 = 5 stages Input Code regardless of dip
10 = 10 stages S = (see note) switch setting.
Note: Masters have selectable inputs: A (2200 ohm), C (135 ohm), E (4-20mA), L (0-10VDC)
Slaves do not have an input nor control code.

Catalog and Part Numbers: 205 Series

2 0 5 - S 9 5 - M 1 0 - 2A - 21
Mounting & Series Type Terminals Temperature Range
NEMA 1 enclosure with M = master 2 = terminal 21 = 0-100 F
setpoint adjuster in lid. blocks 41 = 50-150 F
Stages 43 = 50-180 F
Requires 310 Series 05 = 5 stages Input Code 47 = 100-210 F
thermistor sensor. 10 = 10 stages A = 2200 ohms 51 = 120-250 F
55 = 150-250 F

INDEECO CONTROLS phone: 636-349-9400


546 Axminister Drive fax: 636-326-0009
Fenton, MO 63026-2904 www.indeecocontrols.com
Setup and Diagnostics WARNING: Remove 120/240 VAC power to the
step control and stages before changing any settings.
Changes take effect when power is restored.
1) Turn on 1 of 4 inputs. Set remaining inputs to OFF.
2) Select DEADBAND or PROPORTIONAL control.
3) Select PROGRESSIVE or LINEAR switching.
4) Select the VERNIER control mode if the optional
power controller is used, otherwise set to OFF.
5) Select the time delay between stages (see table).
6) Select the number of stages by adding up the total.
For example, 10 stages would be −2− and −8−.
7) Potentiometer RA3 is used for 2200 ohm inputs only.
The span can be adjusted from +/− 200 ohm (fully
clockwise) to +/− 20 ohms (fully counter-clockwise).
Delay in Switch Set To: Delay in
Seconds Delay 1 Delay 2 Delay 3 Minutes
5 No No No 1
10 Yes No No 2
15 No Yes No 3
20 Yes Yes No 4
30 No No Yes 5
40 Yes No Yes 7
50 No Yes Yes 9
60 Yes Yes Yes (1 sec)

The POWER led is ON when 120/240VAC power is


applied to the control. The ERROR led is ON when the
input or stage switches are set incorrectly or jumper JP1
is set for test mode (see Operation). When JP1 is set to
control mode, the step control functions normally. The
SMI led is OFF when the input signal is below the input
range and ON when above the input range. It flashes
when the input signal is within the selected input range.
Individual STAGE leds (not shown) are ON when the
triac output is energized.

Units with the V input code have an adjustable VDC


input range. Attach a DC voltmeter to TP1 (-) and TP3
(+). Adjust RA1 to the upper VDC range. Move the
meter from TP3 (+) to TP2 (+). Adjust RA2 to the
lower VDC range. The HIGH input range must be at
least 2.0VDC greater than the LOW input range.
Physical Dimensions: 201 Series mounting holes match older S71 & M72 Series.
201 Series 202 Series 204/205 Series
metal mounting plate nylon standoffs NEMA 1 enclosure

Wiring Diagram: Outputs Wiring Diagrams: Inputs

INDEECO CONTROLS phone: 636-349-9400


546 Axminister Drive fax: 636-326-0009
Fenton, MO 63026-2904 www.indeecocontrols.com
M&S Series Power Controllers

Operation:
The M&S Series can be used to replace earlier models of H&J Series and
D&E Series power controllers. Contact the factory for additional informa-
tion and cross-referencing.
M&S Series power controllers are solid-state, zero-cross fired, proportional
devices. Line voltage is switched 0-100% linearly, with respect to the input
range. A 4 second time-base controls power to the load. For example, a
5VDC signal to a 0-10VDC input will cycle the output full on for 2.0 seconds
and full off for 2.0 seconds. Line voltage is used to power the electronics.
An external transformer is not required.
Features of these controllers include an LED to indicate when the output
should be on. Also, the output will be shut off if the input signal is discon-
nected or the input is shorted.
Masters can operate alone or can drive numerous slaves to control mul-
tiple loads. Slaves can be driven from other controllers with a pulsing-DC
type output (see specifications).

Catalog and Part Numbers:

101-M3-480-50- E- W
Mounting Type AC Voltage Max Current Input Code Gasket Kit
101 - through M = master 120 = 120VAC 50 = 50 amps A = 2200 ohm W = included
panel S = slave 208 = 208VAC 70 = 70 amps C = 135 ohm blank = none
240 = 240VAC D = 609VDC
AC Phase 277 = 277VAC E = 4-20 mA
1 = 1 phase 480 = 480VAC L = 0-10VDC
3 = phase 600 = 600VAC blank = slave

Note: Input boards can be changed in the field to reconfigure the power controller.
Some models, i.e. 440VAC, have a separate 120VAC transformer for the electronics.
Contact the factory for other catalog and part numbers not shown above.

Specifications
Storage Temp: -400 to 1900 F Load Current: 0.5A to Max Current rating
Operating Temp: -400 F to 1320 F Load Wire Range: 2-18 AWG, copper only
UL Recognized: File E52105 Guide XAPX2 Input Impedance: 250Ω (mA), 47KΩ (VDC)
Isolation: 2500Vrms input to output Input Wire Range: 16-22 AWG, copper only
Isolation: 2500Vrms output to heatsink Slave Input: 3.0-12VDC, 270KΩ impedance
Line Voltage: +/- 10% of AC Voltage rating UL Type 4X with option “W” gaskets.
Frequency: 47 to 63 Hertz, sinewave only Panel gasket and screws shipped loose.

85-2222-83-2
Physical
Dimensions

Wiring Diagrams
1 phase and 3 phase units

Wiring Diagrams
120VAC Electronic Input Board Specifications
Input Code Full Off Full On Board Part #
Transformer
A = 220 ohms 2150 ohms 2250 ohms 110-B50-M-A
C = 135 ohms 20 ohms 120 ohms 100-B50M-C
D = 6-9 VDC 6.5 VDC 8.5 VDC 110-B50M-D
E = 4-20mA 5.6mA 18.4 mA 100-B50M-E
L = 0-10VDC 1.0 VDC 9.0 VDC 110-B50M-L
S = slave < 3.0 VDC >3.0 VDC 110-B50S

85-2222-83-2