You are on page 1of 13

Aspen Flare System Analyzer V8.

8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility

Scenario Data
Name System Header Header Header Header Header Tailpipe Tailpipe Tailpipe
Back Pres. Mach No. Vap. Vel. Liq. Vel. Rho V2 Noise Mach No. Vap. Vel. Liq. Vel.
(bar) (m/s) (m/s) (kg/m/s2) (dB) (m/s) (m/s)
Default Scenario 0.5000 100.0 0.5000
Source 1 Only 0.5000 100.0 0.5000
Source 2 Only 0.5000 100.0 0.5000

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 1 of 2


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility

Scenario Data
Name Tailpipe Tailpipe
Rho V2 Noise
(kg/m/s2) (dB)
Default Scenario 100.0
Source 1 Only 100.0
Source 2 Only 100.0

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 2 of 2


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility

Messages:Problem
No. Message

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 1 of 1


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility

Messages:Basis
No. Message

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 1 of 1


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility

Messages:Solver
No. Message

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 1 of 1


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility

Messages:Sizer
No. Message

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 1 of 1


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility

Messages:Loop
No. Message

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 1 of 1


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Mass Molar Rated Mass Static Pressure Noise Static Source
Flow Flow Flow Drop (dB) Back Pressure
(kg/hr) (kgmole/hr) (kg/hr) (bar) (bar)
Stack 100000.0 4000.00 110625.3 0.01329 54.9
Header 3 100000.0 4000.00 110625.3 0.00658 51.6
Tail Pipe 1 0.0 0.00 0.0 0.00000 0.0 1.05734
Tail Pipe 2 100000.0 4000.00 110625.3 0.17877 83.7 1.16605

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 1 of 6


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Upstream Upstream Upstream Upstream Upstream Upstream
Static Pressure Temperature Velocity Mach No. Rho V2 Enthalpy Flow
(bar) (C) (m/s) (kg/m/s2) (kJ/hr)
Stack 1.04679 24.99 43.409 0.125 1999 4.507e+007
Header 3 1.05337 24.99 43.136 0.125 1987 4.507e+007
Tail Pipe 1 1.05734 25.00 0.000 0.000 0 9.840e-005
Tail Pipe 2 1.16605 24.99 162.768 0.470 31331 4.507e+007

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 2 of 6


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Downstream Downstream Downstream Downstream Downstream Downstream
Static Pressure Temperature Velocity Mach No. Rho V2 Enthalpy Flow
(bar) (C) (m/s) (kg/m/s2) (kJ/hr)
Stack 1.03350 25.00 43.970 0.127 2025 4.507e+007
Header 3 1.04679 25.00 43.409 0.125 1999 4.507e+007
Tail Pipe 1 1.05734 24.99 0.000 0.000 0 9.840e-005
Tail Pipe 2 0.98727 25.00 192.408 0.555 37036 4.507e+007

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 3 of 6


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Flow Static Pipe Static Pipe Static Pipe Pipe Friction
Regime Friction Loss Accel. Loss Elevation Loss Fittings Loss Factor
(bar) (bar) (bar) (bar)
Stack Single Phase/Single Phase 0.00000 0.01135
Header 3 Single Phase/Single Phase 0.00000 0.01135
Tail Pipe 1 Single Phase/Single Phase 0.00000 0.00000 0.00000 0.00000 0.00000
Tail Pipe 2 Single Phase/Single Phase 0.00000 0.01235

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 4 of 6


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Reynolds Duty Overall External External Internal
Number (kJ/hr) HTC Convective HTC Radiative HTC HTC
(W/m2/C) (W/m2/C) (W/m2/C) (W/m2/C)
Stack 3968992 0.000e+000
Header 3 3968868 0.000e+000
Tail Pipe 1 0 0.000e+000
Tail Pipe 2 8170476 0.000e+000

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 5 of 6


Printed At 2/5/2018 11:45:07 PM
Aspen Flare System Analyzer V8.8 - aspenONE
Version 34.0.0.109
User Name : PUSTEK
Job Code : PGDD
Project : Pipa Gas Duri-Dumai
Description : Flare network in Dumai receiving facility
Scenario : Source 2 Only

Pressure/Flow Summary(Velocities Based Upon Nominal Flows)


Name Wall External Equivalent Physical
Temperature Temperature Length Length
(C) (C) (m) (m)
Stack 100.00 100.000
Header 3 50.00 50.000
Tail Pipe 1 25.00 25.000
Tail Pipe 2 25.00 25.000

D:\000. Process\Project\9 - Duri-Dumai Pipeline\Calculation - Sizing\Flaring Flowrate\Aspen Flare\5 - rated.fnwx Page 6 of 6


Printed At 2/5/2018 11:45:07 PM

You might also like