You are on page 1of 123

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91

Subrack Power system User Manual

Version V1.0
Revision date August 29, 2012
BOM 31012653

Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.

Copyright © 2012 by Emerson Network Power Co., Ltd.


All rights reserved. The contents in this document are subject to change without notice.

Emerson Network Power Co., Ltd.


Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn
Safety Precautions
To reduce the chance of accident, please read the safety precautions very carefully before operation. The
"Caution, Notice, Warning, Danger" in this book do not represent all the safety points to be observed, and are
only supplement to various safety points. Therefore, the installation and operation personnel must be strictly
trained and master the correct operations and all the safety points before actual operation.
When operating Emerson products, the safety rules in the industry, the general safety points and special safety
instructions specified in this book must be strictly observed.

Electrical Safety
I. Hazardous voltage

Danger
Some components of the power system carry hazardous voltage in operation. Direct contact or indirect contact through
moist objects with these components will result in fatal injury.

Safety rules in the industry must be observed when installing the power system. The installation personnel must
be licensed to operate high voltage and AC power.
In operation, the installation personnel are not allowed to wear conductive objects such as watches, bracelets,
bangles, rings.
When water or moisture is found on the Subrack, turn off the power immediately. In moist environment,
precautions must be taken to keep moisture out of the power system.
"Prohibit" warning label must be attached to the switches and buttons that are not permitted to operate during
installation.

Danger
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance
with the local rules and regulations. Only those who are licensed to operate high voltage and AC power can perform high
voltage operations.

II. Tools

Warning
In high voltage and AC operation, special tools must be used. No common or self-carried tools should be used.

III. Thunderstorm

Danger
Never operate on high voltage, AC, iron tower or mast in the thunderstorm.

In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be
well earthed in time to avoid damage by lightning strikes.
IV. ESD

Notice
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale
ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from
damaging the sensitive components. The other end of the ESD wrist strap must be well earthed.

V. Short circuit

Danger
During operation, never short the positive and negative poles of the DC distribution unit of the system or the non-grounding
pole and the earth. The power system is a constant voltage DC power equipment, short circuit will result in equipment
burning and endanger human safety.

Check carefully the polarity of the cable and connection terminal when performing DC live operations.
As the operation space in the DC distribution unit is very tight, please carefully select the operation space.
Never wear a watch, bracelet, bangle, ring, or other conductive objects during operation.
Insulated tools must be used.
In live operation, keep the arm muscle tense, so that when tool connection is loosened, the free movement of
the human body and tool is reduced to a minimum.

VI. Dangerous energy

Warning

240VA, hazardous energy, keep off, no bridge connection. This converter contains outputs exceed 240VA, when installing
into end system care must be taken that the output and appropriate wire may not be touched.

Battery

Danger
Before any operation on battery, read carefully the safety precautions for battery transportation and the correct battery
connection method.

Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent
battery short circuit and overflow of electrolyte. The overflow of electrolyte will erode the metal objects and PCBs,
thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points:
Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.
Use special insulated tools.
Use eye protection device, and take preventive measures.
Wear rubber gloves and apron to guard against electrolyte overflow.
In battery transportation, the electrode of the battery should always be kept facing upward. Never put the battery
upside down or slanted.
BLVD
The system has battery low voltage disconnection (BLVD) function. BLVD means when the mains fail and
batteries supply power, the monitoring module cuts the load off when the battery voltage drops down to below
43.2V to prevent over-discharge. The BLVD voltage is settable. Refer to 4.2.3 Battery Selection for setting
method.
The factory setting is enabling BLVD, which means that if power outage lasts for a long time or the power system
fails, there might be BLVD. Users should classify the loads and connect the priority loads to BLVD routes. For
vital loads, users can disable BLVD of these loads to insure reliability of the power supply.
The method of disabling BLVD is:
Set “BLVD Enable” item of the monitoring module to “N”. Refer to 4.2.3 错误! 未找到引用源。 for setting
错误!未找到引用源。
method.

Notice
The advantage of enabling BLVD is protecting the batteries from over-discharge when the battery voltage is low. The
disadvantage of enabling BLVD is that when the battery voltage drops down to a certain value, all the loads (including
non-priority loads and priority loads) will be cut off due to battery disconnection.
The advantage of software disabling BLVD is prolonging the power supply of priority loads. The disadvantage is that
software disabling cannot prevent unwanted power failure due to misoperation or power system failure.

Others
I. Sharp object

Warning
When moving equipment by hand, protective gloves should be worn to avoid injury by sharp object.

II. Cable connection

Notice
Please verify the compliance of the cable and cable label with the actual installation prior to cable connection.

III. Binding the signal lines

Notice
The signal lines should be bound separately from heavy current and high voltage lines, with binding interval of at least
150mm.
Contents

Chapter 1 Overview ............................................................................................................................................................ 1

1.1 Model Information ................................................................................................................................................. 1


1.2 Composition And Configuration ............................................................................................................................ 1
1.3 Features ................................................................................................................................................................ 4

Chapter 2 Installation Instruction ......................................................................................................................................... 5

2.1 Safety Regulations ................................................................................................................................................ 5


2.2 Preparation ........................................................................................................................................................... 5
2.3 Mechanical Installation.......................................................................................................................................... 6
2.4 Electrical Installation ............................................................................................................................................. 9
2.4.1 Power System Cabling Method ................................................................................................................. 9
2.4.2 Connecting AC Input Cables ................................................................................................................... 10
2.4.3 Connecting Load Cables ......................................................................................................................... 11
2.4.4 Connecting Battery Cables ...................................................................................................................... 11
2.4.5 Connecting Signal Cables ....................................................................................................................... 12

Chapter 3 Installation Testing............................................................................................................................................ 16

3.1 Installation Check And Startup ............................................................................................................................ 16


3.2 Basic Settings ..................................................................................................................................................... 16
3.3 Alarm Check And System Operation Status Check ............................................................................................ 17
3.4 Final Steps .......................................................................................................................................................... 18

Chapter 4 Use Of Monitoring Module M221S、M221S ..................................................................................................... 19

4.1 Control Keypad And Indicator ............................................................................................................................. 19


4.1.1 Front Panel .............................................................................................................................................. 19
4.1.2 Indicator Function .................................................................................................................................... 19
4.1.3 Control Keypad Function ......................................................................................................................... 19
4.2 LCD Menu Tree .................................................................................................................................................. 20
4.2.1 Status ...................................................................................................................................................... 20
4.2.2 Settings.................................................................................................................................................... 21
4.2.3 Manual ..................................................................................................................................................... 28
4.2.4 ECO ......................................................................................................................................................... 28
4.2.5 Quick Setting ........................................................................................................................................... 28
4.2.6 Controller Setting ..................................................................................................................................... 29
4.3 WEB Interface Operation .................................................................................................................................... 30
4.3.1 Setting Up The Internet Explorer Web Browser ....................................................................................... 30
4.3.2 Logging Into The Controller ..................................................................................................................... 31
4.3.3 Homepage Introduction ........................................................................................................................... 32
4.4 WEB Bootloader Interface Operation .................................................................................................................. 36
4.5 Serial Bootloader Interface Operation ................................................................................................................. 37
Chapter 5 Use Of Monitoring Module M820B.................................................................................................................... 41

5.1 Operation Panel .................................................................................................................................................. 41


5.2 First Screen......................................................................................................................................................... 42
5.3 Default Main Screen ........................................................................................................................................... 42
5.4 Overall Menu Structure ....................................................................................................................................... 43
5.5 Main Menu .......................................................................................................................................................... 43
5.6 Status.................................................................................................................................................................. 44
5.7 Manual ................................................................................................................................................................ 46
5.7.1 Settings.................................................................................................................................................... 47
5.7.2 Power System Setting ............................................................................................................................. 55
5.7.3 Rectifier Setting ....................................................................................................................................... 57
5.7.4 Battery Setting ......................................................................................................................................... 57
5.7.5 Parameter Settings Of BattFuseUnit ....................................................................................................... 59
5.7.6 Parameter Settings Of DC ....................................................................................................................... 59
5.7.7 Parameter Setting Of LVD ....................................................................................................................... 59
5.7.8 AC Parameter Settings ............................................................................................................................ 60
5.7.9 Communication Parameter Settings ........................................................................................................ 60
5.7.10 Controller Parameter Settings ............................................................................................................... 60
5.8 Energy Saving Setting ........................................................................................................................................ 60
5.9 Quick Settings ..................................................................................................................................................... 61
5.10 Access M820B Through Web ........................................................................................................................... 61
5.10.1 Login ...................................................................................................................................................... 62
5.10.2 Homepage Introduction ......................................................................................................................... 63
5.10.3 Device Information ................................................................................................................................. 64
5.10.4 Data Browse, Control And Parameter Setting Of Rectifier..................................................................... 64
5.10.5 Data Browse, Control And Parameter Setting Of Battery ...................................................................... 67
5.10.6 Alarms ................................................................................................................................................... 69
5.10.7 Maintenance .......................................................................................................................................... 70
5.10.8 Configurations ....................................................................................................................................... 78
5.10.9 Query ..................................................................................................................................................... 83
5.11 Access ACU+ Through NMS ............................................................................................................................ 85
5.11.1 NMS Supported By SNMP Agent .......................................................................................................... 85
5.11.2 MIB Installation ...................................................................................................................................... 85
5.11.3 Access ACU+ Through NMS ................................................................................................................. 86
5.11.4 ESR Configure....................................................................................................................................... 87

Chapter 6 Alarm Handling ................................................................................................................................................. 88

6.1 Handling Alarms.................................................................................................................................................. 88


6.2 Handling Rectifier Fault....................................................................................................................................... 89
Appendix 1 Technical And Engineering Data .................................................................................................................... 91

Appendix 2 Installation Instruction Of Battery Rack .......................................................................................................... 95

1. Installation Instruction Of Two-Layer And Four-Layer Battery Rack ..................................................................... 95


2. Installation Instruction Of Three-Layer Battery Rack............................................................................................. 97
3. Fixing The Battery Rack........................................................................................................................................ 98

Appendix 3 Wiring Diagram............................................................................................................................................... 99

Appendix 4 Shematic Diagram ........................................................................................................................................ 107

Appendix 5 Glossary ....................................................................................................................................................... 115


Chapter 1 Overview 1

Chapter 1 Overview

This chapter introduces model description, composition and configuration, and features.
The “power system” in this manual refers to the NetSure NetSure 701 A41, NetSure 501 A41, NetSure 501 A91
series 19 subrack power system.

1.1 Model Information


Take NetSure 501 A41-S1 power system as an example, the model description is given in Figure 1-1.

NetSure 501 A 4 1 S 1

Cabinet configuration
Cabinet type: Subrack
Version
The number of the rectifier in the typical power supply system: 4. If the number ranges between 0 ~ 9,
the character is represented by a number. If the number is larger than 9, the character isrepresented
by a letter, for example, A represents the number 10, B represents the number 11,and so on

Region. A: Asia-Pacific region


Output power of the rectifier. 501: 1740W ~ 2000W. 701: 2900W ~ 5000W

Brand name of the power supply system

Figure 1-1Model information

1.2 Composition And Configuration


System composition
The system consists of power distribution parts, rectifiers and monitoring module. The rectifier model is
R48-1800, R48-2900U or R48-3200 and the model of the monitoring module is M221S, M222S or M820B. The
internal structures of the systems are shown in Figure 1-2 to Figure 1-6.

Figure 1-2 NetSure 501 A41- S1/S2 system structure

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
2 Chapter 1 Overview

Positive terminals

Battery MCB
AC input MCB

Load MCB
Rectifier
Monitoring module
Controller

Dummy panel

Figure 1-3 NetSure 501 A91-S1 system structure

Figure 1-4 NetSure 701 A41 –S2/S4 system structure

Figure 1-5 NetSure 701 A41-S1/S3/S5 system structure

Figure 1-6 NetSure 701 A41-S5 system structure

System configuration
The configurations of the power system are described in Table 1-1.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 1 Overview 3

Table 1-1 Configuration of fixed- configuration system


Item NetSure 501 A41-S1 NetSure 501 A41-S2 NetSure 501 A91-S1 NetSure 701 A41-S1 NetSure 701 A41-S2 NetSure 701 A41-S3 NetSure 701 A41-S4 NetSure 701 A41-S5
Model: Model: Model: Model: Model: Model: Model: Model:
Contorller
M221S/M222S M820B M221S/M222S M221S/M222S M221S/M222S M221S/M222S M820B M221S/M222S
Model: Model: Model: Model: Model: Model: Model: Model:
R48-1800A/R48-2000/ R48-1800A/R48-2000/ R48-1800A/R48-2000 R48-2900U/R48-300 R48-2900U/ R48-2900U/ R48-2900U/ R48-2900U/
R48-2000e R48-2000e /R48-2000e 0e/R48-3200/R48-35 R48-3000e R48-3000e R48-3000e R48-3000e
Standard Standard Standard 00e/R48-4000e R48- 3200 R48- 3200 R48- 3200 R48- 3200
Rectifier configuration:4 pieces configuration:4 pieces configuration:5 Standard R48-3500e R48-3500e R48-3500e R48-3500e
pieces configuration:3 R48-4000e R48-4000e R48-4000e R48-4000e
pieces Standard Standard Standard Standard
configuration:4 configuration:4 configuration:4 configuration:4 个
pieces pieces pieces
AC power L+N+PE/ 220Vac L+N+PE/220Vac 3P+N+PE/380Vac 3P+N+PE/380Vac L+N+PE/380Vac 3P+N+PE/ 220Vac 3P+N+PE/ 380Vac L+N+PE/ 220Vac
distribution
BLVD load route: BLVD load route: BLVD load route: BLVD load route: BLVD load route: BLVD load route: BLVD load route: BLVD load route:
2 × 16A/1P, 2 × 10A/1P, 5 × 63A/1P, 1 × 10A/1P 4 × 63A/1P, 2 × 32A/1P, 2 × 63A/1P 2 × 32A/1P,
MCB 2 × 32A/1PMCB 5 × 32A/1P, MCB 6 × 32A/1P, 2 × 16A/1P 4 × 32A/1P, 2 × 16A/1P
LLVD load route: LLVD load route: 8 × 10A/1P LLVD load route: 2 × 10A/1P MCB 4 × 10A/1P MCB
DC power MCB MCB LLVD load route: MCB LLVD load route:
2 × 63A/1P, 2 × 63A/1P, 4 × 40A/1P
distribution LLVD load route: LLVD load route: LLVD load route:
2 × 32A/1P 2 × 32A/1P MCB 2×63A/1P, 2×63A/1P, 4×
MCB MCB Not configured Not configured 4×32A/1P, 2×100A/1P 32A/1P MCB
2×16A/1P MCB 2×63A/1P,
2×32A/1P MCB
Battery MCB 2 × 63A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P 2 × 125A/1P
AC SPD 1 piece Optional Optional Optional Optional 1 piece Optional 1 piece
DC SPD 1 piece Optional Optional Optional Optional 1 piece Optional 1 piece
Max.size (mm) 483 × 360 × 222 483 × 360 × 222 483 × 360 × 400 483 × 360 × 267 483 × 360 × 267 483 × 360 × 267 483 × 360 × 400 483 × 360 × 267
BLVD contorller Contorller power-off Contorller power-on Contorller power-on Contorller power-on Contorller power-on Contorller power-off Contorller power-on Contorller power-off
mode
Weight ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg ≤ 25kg
Notes:
1. Temperature sensor and connected cables, remote monitoring unit, battery rack.
2. The way of outage for control is cutting off the battery, disconnecting the monitor and storage battery, monitor dropping out and communication broken up.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
4 Chapter 1 Overview

1.3 Features
The rectifier uses the active Power Factor Compensation (PFC) technology, raising the power factor to 0.99.
Wide AC input voltage range: 85V ~ 290V (NetSure 701 A41) or 85Vac ~ 300Vac (NetSure 501 A41 & NetSure
501 A91).
The rectifier uses soft switching technology, raising the system rated efficiency to 91%, and the efficient systems
can be as high as 95%.
Ultra-low radiation. With advanced EMC design, the rectifier meets international standards such as CE and
NEBS. Both the conducted and radiated interference reach Class B.
The rectifier safety design complies with UL, CE and NEBS standards.
High power density.
Rectifiers are hot pluggable. It takes less than 1min to replace a rectifier.
Two over-voltage protection methods are optional: hardware protection and software protection. The latter one
also has two optional modes: lock-out at the first over-voltage and lock-out at the second over-voltage.
Perfect battery management: The management functions include the LLVD (optional), BLVD, temperature
compensation, auto voltage regulation, stepless current limiting, battery capacity calculation and on-line battery
test, etc.
M221S and M222S support historical alarm record up to 200 and historical record up to 1000. And M820B
supports historical alarm record up to 3000 and historical record up to 60000
10 sets of battery test data records.
Network design: Providing multiple communication ports (such as RS232, modem and dry contacts), which
enables flexible networking and remote monitoring. M820B support the USB communication interface.
Perfect lightning protection at AC side and DC side.
Complete fault protection and fault alarm functions.
NetSure 701 A41-S3, NetSure 701 A41-S5 and NetSure 501 A41-S1 adopt the way of outage for control, This
way effectively prevents the storage battery from deeply discharging after system battery protection drops out
and hence prevents the unattended outdoors and indoors server rooms from the damage due to the deep
discharge.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 5

Chapter 2 Installation Instruction

2.1 Safety Regulations


Certain components in this power system have hazardous voltage and current. Always follow the instructions below:
1. Only the adequately trained personnel with satisfactory knowledge of the power system can carry out the
installation. The most recent revision of these safety rules and local safety rules in force shall be adhered to during
the installation.
2. All external circuits that are below 48V and connected to the power system must comply with the requirements of
SELV as defined in IEC 60950.
3. Make sure that the power (mains and battery) to the system is cut off before any operations can be carried out
within the system subrack.
4. The power subracks shall be kept locked and placed in a locked room. The key keeper should be the one
responsible for the power system.
5. The wiring of the power distribution cables should be arranged carefully so that the cables are kept away from the
maintenance personnel.

2.2 Preparation
Unpacking inspection
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done
by representatives of both the user and Emerson Network Power Co., Ltd.To inspect the equipment, you should open
the packing case, take out the packing list and check against the packing list that the equipment is correct and
complete. Make sure that the equipment is delivered intact.

Cables
The cable design should meet relevant industry standards.
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least +70°C temperature
durability. With cable length shorter than 30 meters, the Cross-Sectional Area (CSA) calculation should be based on
2
the current density of 3.5A/mm . The suggested CSA value is no less than the Table 2-1.
Table 2-1 Load cable CSA selection
AC MCB rated current Max. battery current Min. cable CSA Max. cable length
125A 105A 35mm2 50mm2
100A 80A 25mm2 50mm2
63A 50A 16mm2 25mm2

The CSA of DC cable depends on the current flowing through the cable and the allowable voltage drop. To select the
battery cable CSA, see Table 2-2. Select the DC load cable CSA according to the Table 2-3.
Table 2-2 Battery cable CSA selection
Battery MCB rated current Max. battery current Min. cable CSA Max. cable length (volt drop: 0.5V, with max. CSA)
125A 105A 35mm2 6m
63A 50A 16 mm2 5m
Note:
1. The specs are applicable at ambient temperature of 25°C. If the temperature is higher or lower than this, the CSA of the cable
should be increased.
2. The battery cable should reach at least +90°C he at durability. It is recommended to use double-insulated copper-core flame
retardant cable as battery cable

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
6 Chapter 2 Installation Instruction

Table 2-3 DC load cable selection


Load route rated Max. output Min. cable Max. cable length (volt drop: Max. cable length (volt drop:
Max. cable CSA
current current CSA 0.5V, with min. CSA) 0.5V, with max. CSA)
100A 80A 25mm2 14m 50mm2 20m
63A 50A 16mm2 9m 25mm2 14m
32A 25A 10mm2 11m 25mm2 29m
16A 12A 6mm2 14m 25mm2 48m
10A 8A 6mm2 23m 25mm2 98m
Note: The specs are applicable at ambient temperature of 25°C. If the temperature is higher than this, the CSA of the cable should
be increased

To prevent the air switching capacity is too large, the load overload does not work. Recommended the capacity of the
air switching is up to 1.5 ~ 2 times of the load peak.
The CSA of the system grounding cables should be consistent with the largest power distribution cables. The CSA
2
value is no less than 25mm .
AC and DC power distribution interface definition see Table 2-4.
Table 2-4 AC and DC power distribution interface definition
Connector name Connector specifications Wiring instructions
H type terminal, max. cable CSA 35mm2 (Single-phase power input)
AC input MCB AC power line
H type terminal, max. cable CSA 25mm2 (Three -phase power input)
AC power
Connected to the
distribution Grounding
One M8 bolt, OT type wiring terminal, max. cable CSA 35mm2 grounding bar of the
busbar
equipment room
Battery output H type terminal, max. cable CSA 25mm2 (63A and below) Connected to the battery
MCB H type terminal, max. cable CSA 50mm2 (capacity above 63A) port
DC power Negative H type terminal, max. cable CSA 25mm2 (63A and below) Connected to the users load
distribution output MCB H type terminal, max. cable CSA 50mm2 (capacity above 63A) port
Positive Connected to the users load
Terminal subrack terminal:cable CSA ≤ 50mm2
busbar port

2.3 Mechanical Installation

Note
1. The cabinet or rack the subrack power supply system installed in must provide fireproof and electric protection casing, or
install in cement or other difficult to burn, at the same time and other combustible materials to keep enough distance.
2. For the convenience of maintenance, users should maintain a clearance of 800mm at the front of the power supply system.
3. Subrack cannot be installed against the wall, it must leave enough space for heat dissipation.

Installed on battery bracket


1. Fix the subrack power system to the battery bracket through the connectors with M6 bolts, as shown in Figure 2-1.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 7

Subrack
power system

M6 screw
M6 screw
Connector
Connector

Battery
bracket

Figure 2-1 Cabinet and rack installation

Installed in cabient
Insert the subrack power system to the matching cabinet, as shown in Figure 2-2.

Subrack power
system
电源插框

Figure 2-2 Installed in the cabinet system

The engineering graphics of the subrack power system as shown in Figure 2-3 to Figure 2-8.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
8 Chapter 2 Installation Instruction

Figure 2-3 Installation size of NetSure 501 A41 (unit: mm)

445

Figure 2-4 Installation size of NetSure 501 A91 (unit: mm)

Figure 2-5 Installation size of NetSure 701 A41-S1 (unit: mm)

Figure 2-6 Installation size of NetSure 701 A41-S2/S3 (unit: mm)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 9

Figure 2-7 Installation size of NetSure 701 A41- S4 (unit: mm)

265.0

438.5

482.6
Figure 2-8 Installation size of NetSure 701 A41-S5 (unit: mm)

Note
1. Tighten the captive screw of the MFU and DU Panel by the cross head screwdriver when there is no operation.
2. Also tighten the handle of the 501 modules by the cross head screwdriver.
3. Please plug in the new modules or installing a new panel after removing the rectifier module.

2.4 Electrical Installation

2.4.1 Power System Cabling Method

Cabling from the top of the power system


DU unit and MFU unit are available for the system top cover cabling.
For DU unit cabling: Cabling from the cable outlet area and then fixed to the cable-bundling plate and the top edge.
As shown in Figure 2-9.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
10 Chapter 2 Installation Instruction

Cable outlet area

Cable-bundling plate

Cable outlet area

Figure 2-9 Cable entry Illustration of the DU unit

The MFU unit cabling is shown in 2-10.

Figure 2-10 Cable entry Illustration of the MFU unit

Cabling from side of the power system


Use a cross head screwdriver to remove two screws which fix the cabling panel at side of cabling area, then the cable
can be led out from the cabling area, as shown in Figure 2-11.
螺钉

出线板
(出线空间)

Figure 2-11 Side cable cabling Illustration

2.4.2 Connecting AC Input Cables

Danger

1. Switch off all MCBs before the electrical connection.


2. Only the qualified personnel can do the mains cable connection.

Take the NetSure 701 A41 power supply system as an example, the position of the terminals are shown in
Figure 2-12.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 11

Figure 2-12 Illustration of the connection terminal

注意

若用户选用插框的交流输入采用的是端子形式,无过流和短路保护功能,则需要在插框前级配过流和接地保护器件,具
体保护器件规格的选择可以咨询艾默生网络能源有限公司当地的技术支持。

2.4.3 Connecting Load Cables

Connect the negative cable of the load to the upper terminal of load MCB. Connect the positive cable of the load to
the DC positive busbar, as shown in Figure 2-13.

Figure 2-13 Illustration of the load cable connection terminal

2.4.4 Connecting Battery Cables

Note
1. The batteries may have dangerous current. Before connecting the battery cables, the corresponding battery input MCBs or the
battery cell connector must be disconnected to avoid live state of the power system after installation.
2. Be careful not to reverse connect the battery. Otherwise, both the battery and the power system will be damaged!

1. Connect one end of the negative battery cable to the upper terminal of battery MCBs. Connect one end of the
positive battery cable to the DC positive bus bar.
2. Connect copper lugs to the other end of the battery cables. Bind the connecting parts with insulating tape, and put
them beside the battery. Connect the cables to the battery when the DC distribution unit is to be tested. As shown in
Figure 2-14.

Positive terminal

Battery MCB

Figure 2-14 Illustration of the battery connection terminal

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
12 Chapter 2 Installation Instruction

2.4.5 Connecting Signal Cables

There are two user interface board of the power system can optional, respectively the W2453X1 user interface board
and IB2 user interface board. The W2453X1 user interface board is used together with the M221S monitoring unit or
M222S monitoring unit only; and the IB2 user interface board is used together with the M820B monitoring unit only.

W2453X1 user interface board cable connection


Take the NetSure 501 A41 power supply system as an example, the position of the user connector board (W2453X1)
is shown in Figure 2-15.

Figure 2-15 W2453X1 user interface board Illustration

At most two user connector boards are allowed in the power supply system. Standard cabinet is only configured with
one user connector board.
With one user connector board configured, the power supply system provides three external digital signal input
interfaces: DI2, DI3, DI4 (DI1 is used for DC SPD alarm. If no DC SPD is configured in the power supply system, DI1
is available) and four dry contact alarm output interfaces: DO1, DO2, DO3, DO4. With two user connector boards
configured, the power supply system provides additional four dry contact alarm output interfaces: DO5, DO6, DO7,
and DO8.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 13

The functions of the interfaces are shown in Table 2-5.


Table 2-5 nterface functions
Type Default alarm Description
Dry contact 1 AC power failure /
Dry contact 2 DC overvoltage or DC undervoltage Four-level DC voltage alarms
Dry contact 3 Rectifier alarm Except rectifier lost and multi-rectifier alarm
Dry contact 4 Priority LLVD /
Dry contact 5 Non-priority LLVD /
Dry contact 6 / /
Dry contact 7 / /
Dry contact 8 / /

With default settings, when the preceding alarms are generated, the contactors of the corresponding dry contacts
should change their status, that is, the normally-open contactors close, and the normally-closed contactors open. All
the status changes should be verified by a multimeter. After the alarms are removed, the dry contacts should resume.
The default settings of the dry contact alarms can be changed through the controller. The interfaces of the user
connector board are shown in Figure 2-16.

Figure 2-16 W2453X1 user connector board interface

IB2 user interface board


The external input and output signals are all connected to the IB2 user interface board. For the ports on the IB2 user
interface board, see Figure 2-17.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
14 Chapter 2 Installation Instruction

Figure 2-17 IB2 user interface board definition

Note
1. J11 and J12 are temperature sensor ports. They are not used here.
2. J2 is I2C interface, and provides the power.

See Table 2-6 for the dry contact terminal definition.


Table 2-6 Dry contact terminal definition
Name of double-layer port Pin No. Pin name Definition
1 DI1- Digital input 1-
2 DI1+ Digital input 1+
3 DI2- Digital input 2-
J3
4 DI2+ Digital input 2+
5 DI3- Digital input 3-
6 DI3+ Digital input 3+
1 DI4- Digital input 4-
2 DI4+ Digital input 4+
3 DI5- Digital input 5-
J4
4 DI5+ Digital input 5+
5 DI6- Digital input 6-
6 DI6+ Digital input 6+
1 DI7- Digital input 7-
2 DI7+ Digital input 7+
3 DI8- Digital input 8-
J5
4 DI8+ Digital input 8+
5 NA /
6 NA /
1 DO1_NC NC contact of relay 1
2 DO2_NC NC contact of relay 2
3 DO1_COM Common contact of relay 1
J6
4 DO2_COM Common contact of relay 2
5 DO1_NO NO contact of relay 1
6 DO2_NO NO contact of relay 2
1 DO3_NC NC contact of relay 3
J7 2 DO4_NC NC contact of relay 4
3 DO3_COM Common contact of relay 3

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 2 Installation Instruction 15

Name of double-layer port Pin No. Pin name Definition


4 DO4_COM Common contact of relay 4
J7 5 DO3_NO NO contact of relay 3
6 DO4_NO NO contact of relay 4
1 DO5_NC NC contact of relay 5
2 DO6_NC NC contact of relay 6
3 DO5_COM Common contact of relay 5
J8
4 DO6_COM Common contact of relay 6
5 DO5_NO NO contact of relay 5
6 DO6_NO NO contact of relay 6
1 DO7_NC NC contact of relay 7
2 DO8_NC NC contact of relay 8
3 DO7_COM Common contact of relay 7
J9
4 DO8_COM Common contact of relay 8
5 DO7_NO NO contact of relay 7
6 DO8_NO NO contact of relay 8

The definition of dry contact function can be set through controller or WEB browser.
The specifications of the dry contact ports are as follows:
Digital inputs: 8-route, opto-isolation, the alarm and high/low level are definable (high level: 20V ~ 60V, low level: less
than 1V).
Digital output: 8-route, relay isolation, maximum: 30Vdc 1A, 125Vac 0.5A; 60W; minimum: 10uA @ 10Vdc, alarm is
definable.

Connecting Communication Signal Cable


The communication port of the M221S controller is shown in Figure 2-18. The M222S only provides the RS232
communication serial port, whereas the Ethernet port is not provided.

Figure 2-18 M221S controller communication port

The communication port of the M820B controller is shown in Figure 2-19.

Figure 2-19 M820B controller communication port

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
16 Chapter 3 Installation Testing

Chapter 3 Installation Testing

This chapter introduces procedures of installation testing. The corresponding safety rules shall be adhered to in the
test.

3.1 Installation Check And Startup


Before the test, inform the chief manufacturer representative. Only trained electrical engineer can maintain and
operate this equipment. In operation, the installation personnel are not allowed to wear conductive objects such as
watches, bracelets, bangles and rings.
During operation, parts of this equipment carry hazardous voltage. Misoperation can result in severe or fatal injuries
and property damage. Before the test, check the equipment to ensure the proper earthing. Installation check must be
done before testing. Then the batteries can be charged for the first time.
Make sure that the AC input MCBs, battery MCBs and load MCBs are switched off. Make sure that all the devices are
properly installed.

Installation check
OK Comments
Check all the MCBs and cables. Are their models correct?
Check the bus bar connections, input and output cable connection, and connection between the power
system and the system grounding.
Check the if the number and connections of the batteris are correct. Check the polarity of the battery string
with a voltmeter.
Make sure all the cable connections are firm and reliable.

Startup preparations
OK Comments
Make sure that all the MCB are switched off.
Measure the AC input voltage. Make sure the input voltage is within the allowable range. Umin=___V
Check that the communication and alarm cables are connected to the signal transfer board.
Check that the temperature sensor, if any, has been installed.
Check that the battery string circuit is not closed.
Connect the disconnected batteries to the battery string circuit
Switch off unconnected battery MCBs. Check that the battery signal cables are connected to battery
MCBs reliably, not loosened or suspended
Measure with a voltmeter across the connection points of each battery and make sure that the polarity is Umin=___V
right. For a lead-acid battery with 24 cells, the voltmeter should read 2.0-2.1V/cell or 48-51V/battery. If the
voltage of certain cell is lower than 2.0V, that cell must be replaced.
Check with an ohmmeter that there is no short circuit between the positive & negative distribution bus
bars, or between the positive & negative battery poles
(Note: Pull out all modules before the check and restore them after the check)

Startup
OK Comments
Switch on the system AC input MCB. The green LED on the rectifier will be on and the fan will start
running after a certain delay. The monitoring module will show that the power supply voltage is 53.5V.
Check the system voltage and busbar polarity with a voltmeter. The voltage difference between the
measured value and displayed value should be less than ± 0.2V.
Start and stop each rectifier of the system by unplugging and inserting each rectifier. Check their output
voltages.

3.2 Basic Settings


When the system is put into service for the first time, the parameters of monitoring module must be set based on the
actual system configuration, such as battery number, capacity, user’s charge current limit and other functional
requirements. Only after that can the monitoring module display system operation information and control the output.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 3 Installation Testing 17

OK Comments
The system model has been set correctly in factory before delivery, check that the setting agrees with
the actual system:
NetSure 701 A41-S1:48V/SET;Set the battery shunt coefficient for:175A/25mV;
NetSure 701 A41-S2~S5:48V/SET;Set the battery shunt coefficient for:300A/25mV;
NetSure 501 A41-S1:48V/SET;Set the battery shunt coefficient for:175A/25mV;
NetSure 501 A41-S2:48V/SET;Set the battery shunt coefficient for:300A/25mV;
NetSure 501 A91-S1:48V/SET;Set the battery shunt coefficient for:300A/25mV
The DC over-voltage alarm point has been set correctly in factory before delivery, check that the
setting agrees with the actual system:
Set DC over-voltage alarm: 58V
Check that the parameter Setting→Alarm Settings→Alarm mode, check that the mode is set to “High”
The battery string number set at the monitoring module should be the same as the number actually
connected. (By default: 2)
Set the battery capacity according to the actual capacity of the battery connected to the system.
Default: 300Ah
Configure the temperature coefficient according to the battery manufacturer’s requirement. Setting
range: 0-500mV/°C. By default: 72mV/°C. (if no temp erature sensor is installed, do not set this
parameter)
Set the charge current limit according to your needs. Setting range: 0.1~0.25C10. (By default: 0.1C10)
Set the monitoring module according to the voltage suggested by the battery supplier.
Floating Charge (FC) voltage range: 42V ~ Boost Charge (BC) voltage. Default: 53.5V.
BC voltage range: FC voltage ~ 58V. By default: 56.4V.
For batteries that do not need BC, set the BC voltage to FC voltage plus 0.1V
Put through the battery MCBs and connect the batteries

3.3 Alarm Check And System Operation Status Check


Alarm check
Check that all functional units can trigger alarms that can be displayed on the monitoring module.
OK Comments
Pull out one rectifier. The “Rect N Com Failure” alarm should be triggered. Insert the rectifier in. The
alarm should disappear. Repeat the same procedures on other rectifiers.
Remove battery MCB 1. The “Batt1 Failure” alarm should be triggered. Put on the MCB. The alarm
should be cleared. Repeat the same on battery MCB 2.
Switch off a load MCB connected to a load route. The alarm “Load N Failure” should be triggered.
Switch on the MCB, and the alarm should be cleared. Repeat the same on the other load MCBs.
Remove all the battery input MCBs. Keep only one rectifier in operation. Through the monitoring
module, adjust the rectifier FC voltage to make it lower than the alarm point. The alarm “DC Voltage
Low” should be triggered.
Keep the rectifiers in operation. Set through the monitoring module the battery management
parameter to “Manual”. Enter the maintenance menu at the monitoring module. Select “Disconnect”
and confirm it. The battery protection contactor should be open, and the “BLVD” alarm should be
displayed at the monitoring module.
Note: when the preceding alarms are generated, the monitoring module will give alarms after approximately 3s.

System operation status check


There should be no alarms during normal system operation. The system operation status check can be conducted
through the monitoring module.
OK Comments
Check that the system type agrees with the actual system when the system operates
The monitoring module should display the correct AC voltage.
The monitoring module should be able to display the DC voltage. The difference between the
displayed voltage and that measured at the bus bar should be less than 1%.
The monitoring module should display the battery current. The difference between the displayed and
measured battery current should be less than 1%.
Check the number of the rectifier through the monitoring module. The number should be consistent
with the actual number.
Check the voltage, current, current limiting point of rectifiers through the monitoring module. They

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
18 Chapter 3 Installation Testing

OK Comments
should agree with the actual parameters.
For the system configured with temperature sensor, the monitoring module should be able to display
the battery ambient temperature. Hold the probe of the temperature sensor with hand and watch the
monitoring module, which should diplay the change of temperature.

3.4 Final Steps


OK Comments
Disconnect all test equipment from the system and make sure that materials irrelevant to the equipment
have been all removed.
Restore the equipment to its original condition and close the cabinet door.
Check and handover the equipment that the user has purchased.
Note down all the operations taken, including time of the operation and name of the operator.

If any defect is found in this equipment, inform the personnel responsible for the contract.
If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the
repairing center for fault analysis.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 19

Chapter 4 Use Of Monitoring Module M221S、


、M221S

This chapter introduces the front panel and functional keys briefly, and expounds screen contents, access method,
system controlling, information querying and parameter setting.
After the monitoring module is powered on, the language selection screen will pop up, and the monitoring module is
initialized. The default language is Chinese. After the initialization, the first system information page will appear.

4.1 Control Keypad And Indicator

4.1.1 Front Panel

There are backlit LCD display, functional keypad, indicators and positioning pin on the front panel of M500D
monitoring module, as shown in figure 4-1.

Figure 4-1 Front panel of M500D monitoring module

4.1.2 Indicator Function

The function of the indicators is shown in table 4-1.


Table 4-1 Functions of Indicators
Indicator Normal State Fault State Fault Cause
Status (green) On Off If this LED is on, this means the system is operating normally
Observation Alarm The power system has one or more active observation alarms.
Off On
(yellow) Alarm conditions are programmable. Refer to Table 3-3 for defaults
The power system has one or more active major alarms (Major and
Major Alarm (red)* Off On Critical Alarms). Alarm conditions are programmable. Refer to
Table 3-3 for defaults
Note: A Major Alarm initiates an alarm report if alarm report is enabled

4.1.3 Control Keypad Function

The function of the control keypad is shown in table 4-2.


Table 4-2 Function of Keys on the Panel
Key Symbol Key Name Function
ENT Enter Confirm or Execute
▲ Up Move Up Cursor or Select the Previous Screen
▼ Down Move Down Cursor or Select the Next Screen
ESC Escape Escape or Cancel

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
20 Chapter 4 Use Of Monitoring Module M221S、M221S

4.2 LCD Menu Tree


The overall menu structure is shown in Figure 3-5.

09:20:20 ENT MAIN MENU STATUS


Float Status ENT Active Alarm
53.4V 404A Settings Rectifiers
Manual Normal Manual History Alarm
ECO
Quick Settings
08 -11 - 03
Float SETTINGS
53.4V 404A Alarm
Manual Normal Battery
AC
DC
Rectifier
Controller
Communication

MANUAL
Sys Mode: Auto
▼ In Manual

ECO
Disable
CycPeriod: 168h
RectWork: 80%
Rect Limit: 1

System Type:
48V / set
Capacity: 300Ah
LCD Rotation: On

Figure 4-2 Main menu screen

4.2.1 Status

In the screen of MAINMENU, when cursor is at ‘Status’, press ‘ENT’ to go to the status screen:

Status ALARM: 1/2 ALARM: 2/2


Active Alarm ENT Batt Discharge ENT Batt Volt Low
Rectifiers Observation Alarm Critical Alarm
History Alarm Start Time: Start Time:
081104 15:52:53 081104 15:52:55

RECTIFIER 1/3
ID: 02070801232
R48800B00
DC Volt: 53.4V
DC Curr : 0.0A
Curr Limit: 109%
AC Volt: 201V
AC Status: On
DC Status: On
AC Derated : N
Temp Derated : N

ALARM 001 ALARM 002


SPD Fault ENT
DC Volt Low
08- 07 -10 11:35:22 08 - 07-10 11:35:25
08- 07 - 10 12:35:22 08 - 07-10 12:35:25

Figure 4-3 Status screen

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 21

In the status screen, you can move the cursor to ‘Active Alarm’, ‘Rectifiers’, and ‘History Alarm’ respectively and press
‘ENT’ to check the information of active alarm, rectifiers, and history alarm. The rectifier screen shows the information
of first rectifier, if you want see the information of next rectifier, just press ‘ENT’. In screen of ‘Active Alarm’, ‘Alarm
1/2’, ‘1/2’ means there are 2 active alarms and this screen is displaying the first active alarm. The alarm level and
alarm start time are displayed in the screen
In the screen of ‘History Alarm’, the ‘ALARM 001’ means this screen is displaying the first history alarm. The alarm
start time and end time are displayed in the screen.

4.2.2 Settings

In the Main Menu screen, move the cursor to the item of ‘Setting’ and press ‘ENT’ to enter the Setting menus. Before
you access the Setting menu, the system will require you to enter the password first. Method of entering password:
For example, to enter the password of ‘640275’: Press ‘ENT’, and the bit will be highlighted, now you can press ▲ or
▼ continuously to enter the numbers from 0 to 9, or enter the letters from ‘a’ to ‘z’ or from capital letter ‘A’ to ‘Z’. After
entering ‘6’, press ‘ENT’ and the cursor will move to the next bit, and in the same way, press ▲ or ▼ continuously to
enter ‘4’, and you can enter the rest bits ‘0275’ in the same way.

ALARM
Alarm Level
Alarm Control BATTERY
DI Setting Basic
LVD
Charge
AC Test
Over Volt: 280V Temp Comp
Under Volt: 180V
PH Fail: 80V DC
AC Input: N Over Volt2: 58.2V
AC PH: 3-PH Over Volt1: 58.5V
Under V1: 45.0V
Under V2: 45.0V
Amb High: 40C
Amb Low: - 5C
RECTIFIER
Position: Disabl
R -Posi: 1-1
SETTINGS
HVSD: 59.0V
Alarm
Default V: 53.5V
Battery
Walk-in On: N
AC
Walk-in T: 8s
DC
Interval T: 0s
Rectifier
Controller AC OverV On: N
Communication ACCurrLim : 30A

CONTROLLER
Lang: English
Tzone: GMT + 08:00
Date: 2009-03 -23
Time: 22:17:18 COMMUNICATION
System Type: Address: 1
48V/1000A CommMode : RS232
DownloadMode:N Protocol: YDN23
Reset PWD: N BaudRate: 9600
Reset Para: N IP/Subnet/Gate:
Oper1PWD: ****** 10.163.210.91
Oper2PWD: ****** 255.255.255.0
AdminPWD: ****** 10.163.210.1
CallbackTime: 3
PhoneNumber:
86010677
86010808

Figure 4-4 Settings screen

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
22 Chapter 4 Use Of Monitoring Module M221S、M221S

In the Setting menu, there are 7 items that are ‘Alarm’, ‘Rectifier’, ‘LVD’, ‘AC’, ‘DC’, ‘Controller’ and ‘Communication’
respectively.
Move the cursor to ‘Rectifier’ and press ENT, you can configure the following rectifier parameters:
Position: Enable or disable the shelf setting.
R-Posi: rectifier position in shelf.
HVSD: high voltage shut down, rectifier will shut down when its output voltage exceeds this HVSD point.
Default V: rectifier default output voltage.
Walk-in ON: rectifier walk-in function (soft start) is enabled.
Walk-in T: rectifier walk-in time (soft start time).
Interval T: rectifier sequential startup interval.
AC OverV on: rectifier will shutdown when AC input exceeds AC over voltage point.
ACCurrLim: rectifier current limiting value during startup process.
Move the cursor to ‘AC’ and press ENT, you can configure the following AC parameters:
Over Volt: set the over voltage protection point.
Under Volt: set the under voltage protection point.
PH Fail: set the phase failure voltage point.
AC PH: can set the AC input to 3-phase or single phase (‘1-PH’).
Move the cursor to ‘DC’ and press ENT, you can configure the following DC parameters:
Over Volt2: set the over voltage protection point2.
Over Volt1: set the over voltage protection point1.
Under V1: set the DC output under voltage point 1.
Under V2: set the DC output under voltage point 2.
AmbHigh: set the high ambient temperature.
AmbLow: set the low ambient temperature.
Move the cursor to ‘Controller’ and press ENT, you can configure the following controller parameters:
Lang: set the display language of LCD, you can select English or your local language.
Tzone: set the time zone.
Date: set the current date.
Time: set the current time.
System Type: set the system type.
DownloadMode: enter the download mode through serial port.
Reset PWD: Reset the password to default.
Reset Para: Reset parameters to default.
Oper1PWD: set the password of operator 1.
Oper2PWD: set the password of operator 2.
AdminPWD: set the password of administrator.
There are three levels password. Default passwords: 1 for operator1, 2 for operator2, and 640275 for administrator.
Only administrator can transfer to serial and web download mode and reset the password. Operator2 can change the
system type and reset the parameters.
Move the cursor to ‘Alarm’ and press ENT, you can enter the alarm menus:

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 23

Alarm ENT ALARM LEVEL ENT ALARM LEVEL ENT ALARM LEVEL
Alarm Level Alarm Block SPD fault LFuse Alarm
Alarm Control Severity: Severity: Severity:
DI Setting Observation Alarm Major Alarm Critical Alarm
Out Relay: 0 Out Relay: 0 Out Relay: 6

ALARM CONTROL
Alm Voice: Open
Clear: History

DI SETTINGS
DI NO.: 1
Digital1 Alarm
Active: High

Figure 4-5 Alarm screen

Alarm level setting


In the submenu of alarm level setting, move cursor before ‘Alarm Block’, press ‘ENT’, then you can set the alarm
levels of other alarms such as ‘SPD fault’, ‘LFuse Alarm’, ‘Digital3 Alarm’, etc.
In the submenu of alarm level setting, you can set the alarm level of each alarm to observe alarm, major alarm, or
critical alarm. You can also set the output relay number that outputs the alarm signal.
The characteristics of 4 alarm categories are given in the following table:
Table 4-3 characteristics of 4 alarm categories
Red alarm Yellow alarm
indicator of indicator of
Alarm levels Alarm buzzer Alarm report Remark
controller and controller and
system system
CA (critical Alarm report is
On On Yes
alarm) enabled
MA (major Alarm report is
On On Yes
alarm) enabled
OA (observation
On Off No
alarm)
No alarm Off Off Off No

Note:
1. The alarm levels of temperature sensor disconnected alarm and temperature sensor failure alarm, and the
corresponding relay output cannot be set through the LCD. The alarm levels of these two alarms and the
corresponding relay are the same with those of the high temperature alarm setting.
2. If the analog alarm has two levels of alarm thresholds, and if these two alarm thresholds are set to the same value,
then the second level will be cancelled and the first level of the alarm will be displayed in LCD. For example: If the
alarm threshold of ‘high temperature 1’ is set to the same with the threshold of ‘high temperature 2’, and if this
threshold is set to 40 deg C, then when the temperature exceeds 40 deg C, the system will only issue ‘high
temperature 1 alarm’, and will not issue the ‘high temperature 2 alarm’.
In the alarm level setting submenu, you can also set the output relay no. for the corresponding alarm.
Alarm control menu
For the submenu of ‘AlmVoice’ of alarm control menu, you can set it to ‘Open’(audible alarm is enabled) or ‘Close’ (no
audible alarm), and you can also set the time of audible alarm and the time can be ‘3min’, ‘10min’, ‘1h’ and ‘4h’.
For the submenu of ‘Block Alarm’, you can set ‘Y’ or ‘N’ to select whether the alarm should be blocked or not.
For the submenu of ‘Clear’, you can select ‘History’, ‘ECOFail’, ‘Maintain’, ‘ShortTest’, ‘TestFail’ ,’Rect Lost’ ‘Rect
Commb’ and ‘Rect Not respond’ to clear corresponding alarm.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
24 Chapter 4 Use Of Monitoring Module M221S、M221S

DI SETTINGS
All the alarms can be configured with No.1 to No.8 alarm contacts. ‘0’ means no alarm dry contacts. All the alarm dry
contacts provide NC (normally closed) or NO (normally opened) output and the default alarm dry contacts are given in
the following table.
Table 4-4 Default alarm dry contact setting
Dry contact No. Default alarm
Dry contact 1 Mains Failure
Dry contact 2 DC Under Volt or DC Over Volt
Dry contact 3 Rectifier alarm
Dry contact 4 LVD2
Dry contact 5 LVD1
Dry contact 6 None
Dry contact 7 None
Dry contact 8 None

Table 3-5 lists the alarms that you can scroll through in the ALARM SETTINGS/ALARM LEVEL menu, and also
shows their factory default ‘Alarm Level’ and ‘Mapped Output Relay’ settings.
Table 4-5 Controller Alarms and Factory Default Settings
Default mapped
Alarm name Alarm description Condition Default alarm level
output relay
Alarm Block Alarm Block Alarms are blocked by the LCU+ Observation
Batt Battery middle voltage out of the range of ( bus
Batt Imbalance Major
Imbalance voltage /2) ± 0.6
SavePowerF Into and out of save power status for 5 times in one
SavePowerFault Major
ault hour
Save Power Save Power Function System is in save power status Observation
AC High AC Voltage High Input phase voltage higher than AC High point Observation
AC Low AC Voltage Low Input phase voltage lower than AC Low point Observation
AC PH Fail AC Phase Fail Input phase fails Observation
Ambient/ Battery temperature higher than
Temp High2 Temperature High 2 Major
Temperature High 2
Ambient/ Battery temperature higher than normal
Temp High1 Temperature High1 Major
operation range
Ambient/ Battery temperature lower than normal
Temp Low Temperature Low Observation
operation range
Batt Over
Battery Over Charge The charging current over the maximum value Observation
Chg
DC Volt System output voltage much higher than float
DC Voltage High+ Critical 2
High+ charge voltage
System output voltage higher than float charge
DC Volt High DC Voltage High Critical 2
voltage
System output voltage slightly lower than float
DC Volt Low DC Voltage Low Critical 2
charge voltage
System output voltage is much lower than float
DC Volt Low- DC Voltage Low- Critical 2
charge voltage
Rect HVSD Rectifier HVSD Rectifier HVSD circuit activated Major 3
The difference between rectifier output current and
Rect average output current larger than 8A (+/-4A), and
Rectifier LoadShare Observation 3
LoadShare the load of the rectifier greater than 10% of its
capacity
The output power of at least one rectifier is derated
Rect Derated Rectifier Derated Observation 3
because of AC undervoltage or overtemperature
Rect Fan
Rectifier Fan Fails Fan of at least one rectifier fails Major 3
Fails
AC input voltage out of the range of 85Vac to
Rect Protect Rectifier Protect Observation 3
295Vac results in at least one rectifier protected

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 25

Default mapped
Alarm name Alarm description Condition Default alarm level
output relay
Serious load sharing alarm (the output current of the
Rect Failure Rectifier Failure rectifier is lower than 1A, and the average load is Critical 3
greater than 10% of the total rectifier capacity)
Rect Rectifier High temperature protection activated in at least one
Major 3
TempHigh Temperature High rectifier
Rect AC Fail Rectifier AC Fail AC input voltage lower than 80Vac Major 3
Rect Comm Rectifier
Rectifier(s) unable to communicate with LCU+ Major 3
Fail Communication Fail
MultiRect
Multi rectifier Alarm Two or more rectifiers have alarms Critical
Alarm
System System has not been maintained within preset
System Maintain None
Maintain maintenance time
Rect Lost Rectifier Lost Rectifier reduction detected Critical
Rect
Rectifier OverLoad Total load current greater than the High Load value Observation
OverLoad
Mains
Mains Failure AC input voltage lower than 80Vac Major 1
Failure
LVD2 LVD2 LVD contactor 2 open due to low battery voltage Critical 4
LVD1 LVD1 LVD contactor 1 open due to low battery voltage Critical 5
Battery discharge test failure (battery voltage is
Batt Test Fail Battery Test Fail Observation
lower than setting value before test time is reached)
The difference between bus voltage and the set
DC Volt Fail DC Voltage Fail Observation
output voltage larger than the set value
Curr The total output current not equal to the sum of the
Current Imbalance Observation
Imbalance battery current and the load current
Batt
Battery Discharge Batteries are discharging Observation
Discharge
Batt Test Battery Test The batteries are testing None
Boost
Boost Charge The batteries are in boost charge state None
Charge
Manual
Manual Mode The system is in manual mode Observation
Mode
SelfDetect
SelfDetect Fail LCU+ detects error in hardware self test Observation
Fail
After battery disconnection/ connection signal is
LVD2Ctrl Fail LVD2 Control Fail sent out, the feedback signal of the contactor is Critical
false
BattFuse
Battery Fuse Fail Battery fuse(s) or circuit breaker(s) open Critical
Fail
LoadFuse
Load Fuse Fail Distribution (load) fuse(s) or circuit breaker(s) open Critical
Fail
Digital4 Digital4 User programmable Major
Digital3 Digital3 User programmable Major
Digital2 Digital2 User programmable Major
Digital1 Digital1 User programmable Major
SPD SPD SPD signal interrupted Major

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
26 Chapter 4 Use Of Monitoring Module M221S、M221S

Move the cursor to ‘Battery’ to set the battery parameters:

Sys Mode: Auto Float: 51.8V


BattFuse : 2 Boost: 57.6V
Capacity: 600Ah Limit: 0.100C
Bat. Shunt: Y Over: 0.300C
Shunt Coeff Auto Boost:
-Current: 500A - Enable
-Volt: 25mV -Current: 0.060C
- Capacity: 80.0%
Const Boost:
- Curr: 0.01C
- Time: 180min
LVD1: Enbl Cyc Boost:
ENT LVD2: Enbl - Enable
BATTERY LVD1 Volt: 44.0V - Period: 2400h
Basic LVD2 Volt: 43.2V -Time: 720min
LVD Boost Limit Time:
Charge 1080min
Test
Temp Comp

Center Temp: 25C


Coeff : 72mV / C End Test
Temp1: N - Volt: 45.2V
Temp2: N - Time: 300min
- Capacity: 0.70C
Batt T H2: 50C
Cyc Test: Disabl
Batt T H1: 50C
Cyc Test Time:
Batt T L1: 0C
01 - 01 00:00
04 - 01 00:00
07 - 01 00:00
10 - 01 00:00
Short Test:
- Enable: No
- Alarm 10A
- Period: 1h
- Time: 1min
ConCurr Test:
- Enable: No
- Current: 9999A

Figure 4-6 Battery screen

Move cursor to ‘Basic’, you can configure the following parameters:


Sys Mode: set the system mode from ‘Auto’ to ‘Manual’ or from ‘Manual’ to ‘Auto’.
Method of changing ‘Auto’ to ‘Manual’:
As shown in screen of ‘Basic’, in the item of ‘Sys Mode’, press ‘ENT’ to highlight ‘Auto’, and then press ▲ or ▼ to
change it into ‘Manual’, and then press ‘ENT’ again to validate the change.
BattFuse: set the number of battery fuses.
Capacity: Set the battery capacities.
Bat. Shunt: set if battery shunt is configured.
Shunt Coeff: set current and voltage coefficients.
Move cursor to ‘LVD’, you can configure the following parameters:
LVD1: Enable or disable LVD1.
LVD2: Enable or disable LVD2.
LVD1 Volt: set the voltage point at which the LVD1 contactor disconnects.
LVD2 Volt: set the voltage point at which the LVD2 contactor disconnects.
Move cursor to ‘Charge’, you can configure the following parameters:
Float: set the float charging voltage.
Boost: set the boost charging voltage.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 27

Limit: set the charging current limit. This is the maximum charging current that should be allowed into the battery at
any time, as regards to the nominal capacity of the battery. For example, a value of 0.150C10 means that the
charging current is limited to 15% of the battery’s nominal capacity.
Over: set the over boost charging current. This is the charging current, as regards to the nominal capacity of the
battery, at which an over current alarm will be initiated if this current is reached. For example, a value of 0.300C10
means that when the charging current reaches 30% of the battery’s nominal capacity, an alarm will be extended.
AutoBoost: An Automatic Boost is started when one of the following conditions is reached.
-Enable: Use this submenu to enable or disable auto boost charging.
-Curr: This is the battery discharge current, as regards to the nominal capacity of the battery, above which an
Automatic Boost is started, when the Automatic Boost function is enabled. For example, a value of 0.060C10 means
that an Automatic Boost is started if the battery current is greater than 6% of the battery’s nominal capacity.
-Cap: This is the remaining battery capacity under which (less than) an Automatic Boost is started when the
Automatic Boost function is enabled.
CycBoost
-Enable: Use this submenu to enable or disable cyclic boost charging.
-Period: Use this submenu to set cyclic boost charging period. This is the interval, in hours, between the boost
cycles.
-Time: Use this submenu to set cyclic boost charging time. This is the duration of each cycle for the Cyclic Boost
when this function is enabled.
Const Boost
-Curr: Use this submenu to set constant boost charging current.
-Time: Use this submenu to set constant boost charging time.
BoostLimitTime: Use this submenu to set boost charging time limit beyond which boost charge will be stopped.
Move cursor to ‘Test’, you can configure the following parameters:
End Test: A Battery Test is interrupted when one of the following conditions is reached.
-Volt: This is the ‘end of test voltage level’ for each battery test.
-Time: This is the maximum duration, in minutes, for each battery test.
-Cap: This is the remaining battery capacity, as regards to the nominal capacity of the battery, at which a Battery Test
will be interrupted. For example, a value of 0.700C10 means that when the charging current reaches 70% of the
battery’s nominal capacity, the battery test is interrupted.
Cyc Test: Displays whether the time (on specific dates) battery test function is enabled (Y) or not (N). During a Timed
Battery Test, the output voltage of the rectifiers is reduced so that the batteries power the load. If the batteries fail, the
rectifiers power the load.
Short Test: A short test is a short duration battery discharge test used to verify that parallel batteries are discharging
equally. If the discharge current difference between the two batteries exceeds a preset level (default is 10 A), a Short
Test Fault alarm is generated.
-Enable: Displays whether the short (at specific intervals) battery test function is enabled (Y) or not (N).
-Alarm: Displays the battery current difference at which an alarm will be extended.
-Time: Displays the interval, in hours, between short battery tests.
-Duration: Displays the duration, in minutes, of each short battery test.
ConCurr Test: A Constant Current test is a battery discharge test done at constant current. The controller will
automatically adjust the rectifiers to maintain the battery discharge current at the preset value.
-Enable: Displays whether the constant current battery test function is enabled (Y) or not (N).
-Current: Displays the stable test current.
Move cursor to ‘TEMP COMP’, you can configure the following parameters:
Center Temp: Displays the temperature, in °C, at which the syst em operates at normal voltage levels.
Temp 1: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None)
in position No. 1, and if there is one, whether it is used for battery or ambient temperature measurements.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
28 Chapter 4 Use Of Monitoring Module M221S、M221S

Temp 2: Displays whether a temperature probe on MB is installed and enabled (Battery or Ambient) or not (None)
in position No. 2, and if there is one, whether it is used for battery or ambient temperature measurements.
Coeff: Displays the temperature compensation slope or rate of change per °C above or below the normal operat ion
level selected in the second line. This value is expressed in millivolt per °C per string (mV/°C/str). For example, for a
rate of change of 72mV/°C/str in a 24-cell, 48 V nom inal, battery string, the rate of change is 3 mV per cell.

4.2.3 Manual

In the Main Menu, move the cursor to ‘Manual’ and press ENT to enter Manual control menu:
Change to 'Manual' from 'Auto'
MAIN MENU MANUAL MANUAL
Status ENT Sys Mode: Auto Start: Float
Settings ▼ In Manual LVD1: Reconn
Manual LVD2: Reconn
ECO RectTrim : 53.5V
Quick Settings RectLimit : 121%

Figure 4-7 Manual screen

In the manual screen, you can perform the following manual control operations:
Start: To start float or boost charging or battery test.
LVD1: To reconnect or disconnect LVD1 contactor.
LVD2: To reconnect or disconnect LVD2 contactor.
RectTrim: To adjust the rectifier output voltage.
RectLimit: To adjust the rectifier current limiting point.

4.2.4 ECO

In the Main Menu, move the cursor to ‘ECO’ and press ENT to enter ECO menu:

MAIN MENU ECO


Status ENT Disable
Settings Cyc Period: 168h
Manual
Rect Work: 80%
ECO
Quick Settings Rect Limit: 1

Figure 4-8 ECO screen

The following parameters can be configured:


ECO: To disable or enable ECO function.
Cyc Period: Rectifier redundancy cycle.
Rect Work: Optimum operating load point of rectifier.
Rect Limit: In ECO mode, the minimum number of rectifiers required.

4.2.5 Quick Setting

In the Main Menu, move the cursor to ‘Quick Setting’ and press ENT to enter Quick Setting menu:

MAIN MENU
ENT System Type:
Status 48V / 1000A
Settings Capacity: 300Ah
Manual LCD Rotation: On
ECO
Quick Settings

Figure 4-9 Quick Settings screen

In the Quick Setting screen, you set the system type and system capacity, as well as the parameters (current, voltage)
of load shunts and battery shunts.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 29

4.2.6 Controller Setting

Table 3-7 summarizes all the settings of the controller.


Table 4-6 Controller Settings
Available Settings
Components Name Default setting Unit
Low limit High limit
Alarm DI alarm mode High / low High /
HVSD point 56 59 59 V
Default voltage 48 58 53.5
Restart time upon over voltage 0 300 300 s
Soft-start time with load 8 128 8 s
Soft-start with load enabled Enabled/Disabled Disabled /
Rectifier Startup upon AC over voltage Enabled/Disabled Disabled /
System ECO enabled Enabled/Disabled Disabled /
Sequencial start interval 0 10 0 s
Input current limiting 1 50 30
Rectifier slot setting enabled Enabled/Disabled Disabled /
Rectifier slot setting 1 30 1-1/2-2… /
Number of fuses 0 5 2
Nominal capacity 20 5000 600 Ah
Shunt Yes / No
Basic battery According to system
Shunt current 1 2000 A
parameters type
Shunt voltage 1 500 25 mV
Temperature 1 None/Battery/Ambient Disabled /
Temperature 2 None/Battery/Ambient Disabled /
Float charging voltage 42 58 53.5 V
Battery Boost charging voltage 42 58 56.4 V
charge Charging current limiting 0.1 0.25 0.1 C10
parameters Auto boost charging enabled Yes / No Yes /
Constant charging current 0.002 0.02 0.01 C10
Constant current charging time 5 1440 180 Min
To boost charging current 0.04 0.08 0.06 C10
Battery To boost charging capacity 10 99 80 %
charge Scheduled boost charging enabled Yes / No Yes /
Battery

parameters Boost charging protection time 60 2880 1080 H


Scheduled boost charging cycle 2 8760 2400 h
Scheduled boost charging time 30 2880 720 Min
Battery test end time 5 1440 300 Min
Battery test end voltage 43.1 57.9 45.2 Min
Battery test end capacity 0 1 0.7 C10
Scheduled test enabled Yes No /
Battery test Constant current test enabled Yes / No No /
parameters Constant battery test current 1 9999 9999 A
Short test enabled Yes / No No /
Short test alarm point 1 100 10 A
Short test cycle 24 8760 720 h
Short test time 1 60 5 min
Temperature compensation central
10 40 25 deg.C
point
Battery temp
Battery compensation coefficient 0 500 72 mv/deg.C
compensation
Battery over temperature point 10 100 50 deg.C
coefficient
Battery high temperature point 10 100 50 deg.C
Battery low temperature point -40 10 0 deg.C
Over voltage 1 40 60 58.5 V
Under voltage 1 40 60 45 V
DC unit Under voltage 2 40 60 45 V
High ambient temperature 10 100 40 deg.C
Low ambient temperature -40 10 -5 deg.C

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
30 Chapter 4 Use Of Monitoring Module M221S、M221S

Available Settings
Components Name Default setting Unit
Low limit High limit
Load shunt Yes / No No /
LVD1 Enabled Disabled / Enabled Disabled /
Disabled
LVD2 enabled Disabled /
LVD /Enabled
LVD1 voltage 40 60 43.2 V
LVD2 voltage 40 60 43.2 V
Over voltage alarm point 0 500(866) 280(485) V
AC unit Under voltage alarm point 0 500(866) 180(304) V
Phase failure alarm point 0 500(866) 80(255) %
IP address 0-255 192.168.1.2 /
Subnet code 0-255 255.255.255.0 /
Default gateway 0-255 192.168.1.1 /
Local address 1 255 1 /
Port type RS232/Modem/ETH RS232 /
Communication Baud rate 1200/2400/4800/9600 9600
parameters Protocol YDN23/EEM/RSOC/SOCTPE YDN23 /
Alarm call-back enabled Yes / No No /
Call back times 0 10 3
Call back number 1
Call back number 2
Call back number 3
Language English / Chinese English
Display time zone GMT+08:00
System date
System time
Restore default configurations Yes / No No
Controller
Set rotating screens Horizontal/Vertical Horizontal
parameters
48V/set, 48V/1000A,
48V/500A, 48V/300A,
System type 48V/100A, 24V/set, 48V/set
24V/1000A, 24V/500A,
24V/300A and 24V/100A

4.3 WEB Interface Operation


Through the WEB Interface, a remote user can:
View real-time operating information.
Send control commands.
Set programmable parameters.
Set which new alarms are displayed in a pop-up WEB window.
Download and upload configuration files.

4.3.1 Setting Up The Internet Explorer Web Browser

Procedure

Note
This procedure needs to be performed only when the controller is connected to an Internet and the User has set that
the access to the Internet needs to be made through proxy. If the controller is connected Internet and the user
computer is connected to the Internet, the user cannot disable the proxy, otherwise he will have no access to the
controller.

1. Launch Internet Explorer.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 31

2. Select Internet Options from the Tools menu. The ‘Internet Options’ window opens. In the ‘Internet Options’
window, select the Connections tab.

Figure 4-10 Internet options window

3. Click on the LAN Settings... button. The following window opens. In the LAN Settings window, uncheck the proxy
box and click OK.

Figure 4-11 LAN settings window

4.3.2 Logging Into The Controller

Procedure
In Internet Explorer, enter the IP address programmed into the controller and press ENTER. The following WEB
Interface window opens. Enter a valid User Name and Password, and then click OK. By default, there are two ‘User
Name’ and ‘Password’ combinations, one is ‘admin’ and ‘640275’, the other is ‘operator’ and ‘1’. The username of
‘admin’ has the highest authority and the username ‘operator’ has no authority for uploading and downloading
configuration files.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
32 Chapter 4 Use Of Monitoring Module M221S、M221S

Figure 4-12 Access to controller

4.3.3 Homepage Introduction

After entering a valid User Name and Password, and clicking OK; the homepage window opens.
The homepage window is divided into three areas: System Information, Parameter Settings and Control Functions,
and Upload/Download Files.

Figure 4-13 Homepage window

System information
At the top of homepage, System Information is displayed, such as System Voltage, System Load, MA/CA Number,
OA Number, Battery Mode, Site Name, HW Version, and SW Version.

Parameter and control function


You can set the following parameters and control functions:
Battery Temp Comp: To disable or enable the battery temperature compensation function.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 33

Battery Test: To disable or enable the periodical battery test function. This setting has no effect on the short
test.
Current Limitation: To disable or enable the battery charging current limitation function.
Boost Charge: To disable or enable the periodical battery boost charging function. This setting has no effect on
auto boost charging.
LVD1 Level, LVD2 Level: To set the low voltage disconnection point.
Under Voltage Level 1, Under Voltage Level 2: To set the under voltage point.
System Volt: To set the system voltage.
Boost Volt: To set the battery boost charging voltage.
NMS1 IP, NMS2 IP: To set the IP address of SNMP
Remote1 IP, Remote2 IP: To set the IP address of EEM protocol.
TCP IP address: To set the IP address of TCP IP protocol.

Upload/download files
1. Procedure
1) To upload a configuration file, click the Upload button. The following window opens. Click the Save button.

Figure 4-14 Uploading the configuration file

2) The following window opens. Navigate to where you want the file to be saved. Click the Save button.

Figure 4-15 Save as window

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
34 Chapter 4 Use Of Monitoring Module M221S、M221S

After the upload is completed, the system will pop up a window to prompt the user that the upload is successful:

Figure 4-16 Upload successful

3) Users can also upload up to 80 active alarms or history alarms.


4) To download a file, click the Browse button. Navigate to and select the configuration file to be downloaded:

Figure 4-17 Selecting the configuration file

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 35

Then click Open:

Figure 4-18 Access to the homepage

Then click Download button, the system will pop up a window requiring you to confirm:

Figure 4-19 Confirmation window

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
36 Chapter 4 Use Of Monitoring Module M221S、M221S

Click OK, the system will prompt you that the download is successful:

Figure 4-20 Download successful

In the above screen, you can click ‘Back to the Homepage’ to return to the Homepage.
Administrator can click ‘Go to Firmware Download Mode’ to enter Bootloader download interface.

4.4 WEB Bootloader Interface Operation


Below is the web download webpage. In this webpage administrator can update the firmware. Please ensure that the
file name of the firmware is M221S.bin.

Figure 4-21 WEB webpage

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 37

4.5 Serial Bootloader Interface Operation


Serial COM PORT can be used to download and upload files through the following procedure:
1. Connect Serial line to the computer and LCU+. Connect the DB9 terminal to computer, while connect the RJ45
terminal to the port assigned with ‘IOIO’ on LCU+.
2. Open the software of HyperTerminal on the computer, set the parameters according to the following method, here
we use COM1, however, other COM PORT is optional dependent on your computer.

Figure 4-22 Choose the COM port

Figure 4-23 Set the parameters of COM port

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
38 Chapter 4 Use Of Monitoring Module M221S、M221S

Figure 4-24 Main menu of download/upload

Here we can see there are 4 options, choose ‘1’ to download the application program, choose ‘2’ to download the
configuration data, choose ‘3’ to upload the data configuration file, choose ‘4’ to execute the application program.
1. Method of downloading the application program:
1) Press ‘1’ on the keyboard, enter the surface of download;
2) Choose Transfer->Send File…, select the .bin file you want to download;

Figure 4-25 Choose the file

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 4 Use Of Monitoring Module M221S、M221S 39

Pay attention that the protocol is Ymodem

Figure 4-26 Choose Ymodem as protocol

3) Press ‘Send’, ‘.bin’ file is transmitted from computer to LCU+;

Figure 4-27 The process of downloading file

4) After the file downloading is completed successfully, the following interface pops up:

Figure 4-28 Downloading file successfully

2. Method of downloading the configuration data: Similar to the download of application program, will not be
introduced here;
3. Method of uploading the data configuration file:
1) Press ‘3’ on the keyboard, enter the interface of uploading files:

Figure 4-29 Uploading the file

2) Choose Transfer->Receive File… to select the position in which you save the file

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
40 Chapter 4 Use Of Monitoring Module M221S、M221S

Figure 4-30 Select the position in which you save the file

Pay attention that the protocol is Ymodem.

Figure 4-31 Choose Ymodem as protocol

3) Press Receive, the file is transmitted from LCU+ to computer.

Figure 4-32 The process of uploading file

4) After the file downloading is completed successfully, the following interface pops up.

Figure 4-33 Uploading file successfully

You can also press "4" on the keyboard to execute the application.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 41

Chapter 5 Use Of Monitoring Module M820B

This chapter introduces the front panel and functional keys briefly, and expounds screen contents, access method,
system controlling, information querying, parameter setting, access M820B through web and NMS, and parameter
setting guidance.

5.1 Operation Panel


M820B Panel is illustrated in Figure 5-1:

Figure 5-1 M820B panel

Functions of LED indicators are illustrated in Table 5-1.


Table 5-1 Functions of LED indicators
LED Normal status Abnormal status Cause
Run Indicator (green) On Off No power supply
Protection Indicator (yellow) Off On The power system has at least an observation alarm
The power system has at least a major alarm or critical
Alarm Indicator (red) Off On
alarm

The M820B controller has two kinds of LCD: One is a 128 × 64 dot-matrix LCD unit that can display 4 rows of text
and the other is 128 × 128 dot-matrix LCD that can display 8 rows of text. It has 4 functional keys. Its interface is
easy-to-use and supports multi-language display. The panel of the controller is easy-to-remove. The functions of
these 4 keys are shown in Table 5-2.
Table 5-2 Functions of M820B keys
Keys Name of Keys Functions
Press this key to back to previous menu or
ESC Return Key
cancel a setting of a parameter .
Press this key to go to next menu or highlight Press ESC and ENT together to reset ACU+
ENT Enter Key editable area for parameter setting, validate
the change made to a parameter setting.

▲ Up These two arrow keys can be used to change


the value of a parameter: Press ▲or▼ to
Press ▲ or ▼ to scroll through the menus.
move the cursor to the parameter to be
▼ Down changed and change the value of a parameter

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
42 Chapter 5 Use Of Monitoring Module M820B

5.2 First Screen

Advanced Control
Unit Plus
V2.01
Starting...

英语

English

The first screen is the language-selecting screen. User can select between English and the user’s local language in
the screen by pressing ▲and▼, and press ENT to enter the default main screen after selecting the language. If no
key has been pressed for 30 seconds, user will enter the default screen directly.

5.3 Default Main Screen

18:15:10 2010-07-02
▼ ▼
Float Float
53.5V 20A 53.5V 20A
▼ ▼
Auto Alarm Auto Alarm

The first row of the default main screen displays the date and time alternatively (For example, it displays “18:15:10”,
after a while it displays “2010-07-02”, and then displays “18:15:10”, and it repeats this cycle continuously). The rest
information is dependent on the configuration information such as the equipment Type, signal ID and display
location).
In the default main screen:
Press ▼, the following screen will appear.

Rect Number 5
Sys Cap Used
0.0%
TotalBattCurr
10A

Press ENT + ▲ + ▼ together to change the contrast of LCD.


Press ▲ and ▼ and ESC together to log out (The password will be invalid).
Press ENT and ESC together to reset ACU+.
Press ENT to enter main menu.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 43

5.4 Overall Menu Structure


The overall menu structure is shown in the following figure.
NGC-HF Level1 Level2 Level3
Dev Name M820D Time/Date MAIN MENU STATUS
Serial No. Float Status Active Alarm
BATTERY
##.#V ###A Settings Power System Batt1
031000500115 Rectifier
Auto Alarm Energy Saving Batt2
SW Rev: Battery SMDU Batt1
Rect Num: ## Manual
2.01 DC SMDU Batt2
SysCap Used: Quick Settings
AC EIB Batt1
##.#% History Alarm ......
TotalBattCurr:
##A Site Inventory
CurrLmt: ##.#%
MANUAL ALL DC: On/Off
RECTIFIER ......
Man / Auto Set
Rect Group
Power System Rect1 AC Control
Rectifier ON
Rect2 DC Control
Battery Group ......
...... OFF
LVD
RECTIFIER High Voltage Limit: ##
SETTINGS
Rect Group Low Voltage Limit: ##
Alarm Setting Position ......
Power System
Rectifier BATTERY Rect 1 ###
Battery Basic Rect 1 ###
BatteryFuseUnit Charge Data Rect 2 ###
DC Test Data Rect 2 ###
...... ......
LVD
AC LVD
Communication AC Fail Enb
Controller LVD Temp Enb
LVD 1
LVD 2
SMDU
...... LVD1

ECO Mode
ECO Mode Enabled
Enabled Best Point
0.0%
EngySave Point
45%
Fluct Range
10%
Quick Settings Cyc Period
Auto / Manual 168 hour
ECO Mode Set Rect Drying Tim
FC / BC Voltage 120 min
FC / BC Change SwitchOff Delay
Temp Compens 5 min
Work Mode Set

Figure 5-2 ACU+ Overall Menu Structure

5.5 Main Menu

Dev Name M820D ESC 09:20:20 ENT MAIN MENU


Serial No. Float Status
53.4V 20A Settings
031000500115
Auto Alarm Energy Saving
SW Rev: 2.01 Manual
Quick Settings

Figure 5-3 Main Menu

Main Menu includes running information, settings, energy saving, manual control and quick settings.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
44 Chapter 5 Use Of Monitoring Module M820B

5.6 Status
In the main menu, move cursor to “Status”, press ENT to show the status menu as shown in the following figure.

MAIN MENU ENT Status


Status Active Alarm
Settings Power System
Energy Saving Rectifier
Manual Battery
Quick Settings DC
AC
EIB
SMDU Unit
History Alarm
Site Inventory

Figure 5-4 Status Menu

In the screen of MAINMENU, when cursor is at “Status”, press “ENT” to go to the status screen, and when cursor is at
“Active Alarm”, press “ENT” to show the following screen to check Active Alarm information.

Status ENT Active Alarm


Active Alarm Observation: 1
Power System Major: 0
Rectifier Critical: 0
Battery
DC
AC
EIB
SMDU Unit
History Alarm
Site Inventory

Figure 5-5 Active Alarm Information

The Active Alarm screen shows the information of the alarms, and the number of the alarms in different alarm levels
(Observation, Major and Critical) are displayed, and alarm start time are displayed in the screen. If you want to see
the information of other unit, move cursor to this unit and just press “ENT”. Using the same method, you can browse
all the information listed in the following table.
Table 5-3 Device Information
No. Status Information Description
Active Alarm
1 Observation: Number of observation alarms
2 Major: Number of major alarms
3 Critical: Number of critical alarms
Power System
1 System Voltage System output voltage
2 System Load System output current
3 Mtn Time Run
4 Alarm Status Whether or not the system is in alarming status
5 Power Split Whether this system is master or slave in a power split system
6 SPD Surge protection device
Rectifier
Rect 1 (001)
1 DC Voltage Rectifier output voltage
2 DC Current Rectifier output current
3 Current Limit Current limit value
4 Temperature Rectifier internal temperature
5 DC Status Whether the DC is on or off
6 Derated by AC Rectifier output power is derated according to input voltage
7 Derated by Temp Rectifier output power is derated according to temperature
8 Walk-in Func Rectifier soft start function
9 Rect Position

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 45

No. Status Information Description


10 Rect Phase Whether the rectifier is on Phase A, or Phase B or Phase C?
11 Rectifier SN Rectifier series number
12 Running Time Rectifier operating time
13 AC Voltage Rectifier input AC voltage
Rect 2 (002): The information of Rect 2 (002) is similar to Rect 1 (001), so is the information of other rectifiers in the system.
Battery
Battery 1
1 Batt Current Battery current
2 Batt Voltage Battery voltage
3 Batt Cap (Ah) Battery capacity and the unit is Ah
4 Batt Cap (%) Battery capacity and the unit is %
Battery 2, SMDU/Batt3 and SMDU/Batt4: The information of these batteries is similar to that of Battery 1.
DC
1 DC Voltage DC output voltage
AC
Rect1 AC
1 Phase A Voltage The line-to-neutral voltage of Phase A of rectifier 1
2 Phase B Voltage The line-to-neutral voltage of Phase B of rectifier 1
3 Phase C Voltage The line-to-neutral voltage of Phase C of rectifier 1
OB AC Unit: The information of OB AC Unit is similar to that of Rect AC.
EIB
1 Bad Battery Blo Bad battery block
2 Load 1 Current Current of load 1
3 Load 2 Current Current of load 2
4 Load 3 Current Current of load 3
5 Voltage 1 Voltage of load 1
6 Voltage 2 Voltage of load 2
7 Voltage 3 Voltage of load 3
History Alarm
1 Observation: Number of observation alarms
2 Major: Number of major alarms
3 Critical: Number of critical alarms
Site Inventory
Rectifier 1
1 Device Name Name of the device
2 Product Ver Product version number
3 SW Version Software version number
4 Serial Number Serial number of the device
The screens give user the information about what devices are available and the device information. The information of SM DU,
Controller and IB1 board are similar to the rectifier information that includes the device name, product version, software version
and serial number

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
46 Chapter 5 Use Of Monitoring Module M820B

For some devices, there are more than one menu levels, and you need to press ENT more than one time to browse
its information. Take “Rectifier” for example.

Status ENT Rectifier ENT DC Voltage


Active Alarm Rect 1 (001) 53.8 V
Power System Rect 2 (002) DC Current
Rectifier 8.5 A
Battery Curr Limit
DC 60 %
AC Temperature
EIB 30 deg C
SMDU Unit DC Status
History Alarm Off
Site Inventory Derated by AC
Normal
Derated by Temp
Normal
Walk -in Func
Disabled
Rect Position
1
Rect Phase
A
Rectifier SN
010700213
Running Time
200 h
AC Voltage
224 V

Figure 5-6 Rectifier Information

5.7 Manual

MAIN MENU Manual


ENT Select User ENT
Status Man / Auto Set
Settings admin Power System
Energy Saving Enter Password Rectifier
Manual Batt Group
*
Quick Settings LVD

Figure 5-7 Manual Operations

In the Main Menu, move the cursor to the position of “Manual”, and press ENT, the system will require you to select
user first and then enter password. To enter the password: Move the cursor to the character “*”. Press ENT to
highlight the character “*” and then press ▲ and ▼ to change value of this character. After entering the password,
press ENT to show the “Manual” operation menus.

Manual ENT Auto/Man State


Man / Auto Set Auto
Power System
Rectifier
Batt Group
LVD

Figure 5-8 Manual / Auto Control Status

In the screen as shown in Figure 3-8, you can set the system from “Auto” control to “Manual” control. Setting method:
When the cursor is beside the “Auto”, press ENT to highlight the characters of “Auto”, and then press ▲ and ▼ to
change the “Auto” to “Manual”. After the system is set to “Manual” control, you can set the system manually.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 47

Move the cursor to “Power System”, and press ENT, following screen will show up.

Manual ENT Clr Run Time


Man / Auto Set Yes
Power System
Rectifier
Batt Group
LVD

Figure 5-9 Set the Power System Manually

If you set “Clr Run Time” to “Yes”, the system running time record will be cleared.
Move the cursor to “Rectifier”, and press ENT, following screen will show up.

Manual ENT Rectifier ENT Rect Trim


Man / Auto Set All Rect Ctrl 54.0 V
Power System Rect1(001) Current Limit
Rectifier Rect2(002) 60 %
Batt Group DC On / Off Ctrl
LVD Switch on All
LEDs Control
Stop Twinkle
Fan Speed Ctrl
Auto Speed
Confirm Posi/PH
Yes
Clear Rect Lose
Clear
Reset Oscill
Clear
Clear Comm Fail
Yes

Figure 5-10 Set the Rectifier Manually

Move the cursor to “Batt Group”, and press ENT, following screen will show up.

Manual ENT BC / FC Control


Man / Auto Set Float Charge
Power System BT Start/Stop
Rectifier Stop
Batt Group Reset Capacity
LVD Yes
Clear BadBatt A
Yes
Clear Abcur Alm
Yes
Clear Imcur Alm
Yes
Figure 5-11 Set Battery Group Manually

Move the cursor to “LVD”, and press ENT, following screen will show up.

Manual ENT LVD1 Control


Man / Auto Set Connected
Power System LVD2 Control
Rectifier Connected
Batt Group
LVD

Figure 5-12 Set LVD Manually

5.7.1 Settings

In the submenu of “Settings”, you can set the parameters of alarm, power system, rectifier, battery, DC distribution,
LVD, AC, communication and controller.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
48 Chapter 5 Use Of Monitoring Module M820B

Alarm Setting
Move cursor to “Alarm Setting”, press ENT to show the following screen.

MAIN MENU Settings Alarm Settings


ENT Select User ENT Alarm Setting ENT Alarm Severity
Status
Settings admin Power System Alarm Relay
Energy Saving Rectifier Alarm Param
Enter Password
Manual Battery
*
Quick Settings BatteryFuseUnit
DC
LVD
AC
Communication
Controller
Figure 5-13 Alarm Setting

Alarm severity setting


Move the cursor to the “Alarm Severity”, press ENT to pop up the following screen.

Alarm Settings Alarm Severity Self Detect Fail


ENT
Alarm Severity ENT Power System Observation
Alarm Relay Rect Group CAN Comm Fail
Alarm Param Rectifier Critical
Battery Group Alarm Blocked
Battery Observation
SMDU Battery …… .
EIB Battery
SM Batt
Ldu Battery
OBBattery Fus
SMDU Batt Fus
DC
DC Fuse Unit
SMDU DC Fuse
LVD
SMDU LVD
LargeDU LVD
......

Figure 5-14 Alarm Severity Setting of Power System

In this menu, you can set the severity levels of the alarms of power system, rectifier group, rectifier, battery group,
battery, SM DU battery fuse, OB battery fuse, DC distribution, DC fuse, LVD, AC, IB, EIB and converter. Move cursor
to “Power System”, and press ENT, the power system alarm severity setting screen will pop up.
In the screen as shown in Figure 3-14, the alarms of power system are displayed, such as “Self Detect Fail”, “CAN
Comm Fail”, “Alarm Blocked”, etc. The default alarm severities of the alarm are also displayed, such as “Critical” and
“Observation”. Method of change alarm severity: With the alarm of “Self Detect Fail” as an example, move the cursor
to the alarm severity of “Observation”, press ENT to highlight the “Observation”, and then press ▲and▼ to change
the severity from “Observation” to “Critical” or “Major” or “No Alarm”. You can also change the severity of other alarms
such as “CAN Comm Fail” and “Alarm Blocked” using the same method. In Figure 3-20, move the cursor to “Rect
Group”, you can set the severity levels of the alarms of rectifier group. The ACU+ has 4 alarm severity levels as
shown in the following table.
Table 5-4 Characteristics of 4 alarm categories
Red alarm indicator Yellow alarm indicator
Alarm Alarm call
Alarm levels of controller and of controller and Remark
buzzer back
system system
CA (critical alarm) On On Yes Alarm call back is enabled
MA (major alarm) On On Yes Alarm call back is enabled
OA (observation alarm) On Off No
No alarm Off Off Off No

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 49

The alarm list and the default alarm severity levels of the ACU+ is shown in the following table:
Table 5-5 List of Alarms and Alarm Severity Levels of ACU+
Default Alarm
No. Alarm Name Alarm Description
Severity
Alarms of power system
1 Self Detect Fail System self detection failure Observation
2 CAN Comm Fail CAN bus communication failure. Critical
3 Alarm Blocked Alarm is blocked Observation
4 Maintenance Alrm Maintenance alarm No Alarm
5 Config Error 1 Configuration error 1 Observation
6 Config Error 2 Configuration error 2 Observation
7 Imbalance Curr Current sharing imbalance Critical
8 Over Load DC power system overload Observation
9 SPD Surge protection device tripped Critical
10 EStop/EShutdown Emergency stop or emergency shutdown Critical
11 Temp 1 Not Used Temp 1 sensor is not used Observation
12 Temp 2 Not Used Observation
13 Temp 3 Not Used Observation
14 Temp 4 Not Used Observation
15 Temp 5 Not Used Observation
16 Temp 6 Not Used Observation
17 Temp 7 Not Used Observation
18 T1 Sensor Fault Temperature sensor 1 failure conditon Observation
19 T2 Sensor Fault Temperature sensor 2 has fault Observation
20 T3 Sensor Fault Temperature sensor 3 has fault Observation
21 T4 Sensor Fault Temperature sensor 4 has fault Observation
22 T5 Sensor Fault Temperature sensor 5 has fault Observation
23 T6 Sensor Fault Temperature sensor 6 has fault Observation
24 T7 Sensor Fault Temperature sensor 7 has fault Observation
25 Temp1 High2 Temperature 1 exceeds high temperature threshold 2 Major
26 Temp2 High2 Temperature 2 exceeds high temperature threshold 2 Major
27 …….. …….. Major
31 Temp7 High2 Temperature 7 exceeds high temperature threshold 2 Major
32 Temp1 High1 Temperature 1 exceeds high temperature threshold 1 Major
33 Temp2 High1 Temperature 2 exceeds high temperature threshold 1 Major
34 …….. …….. Major
38 Temp7 High1 Temperature 7 exceeds high temperature threshold 1 Major
39 Temp1 Low Temperature 1 low Observation
40 Temp2 Low Temperature 2 low Observation
41 …….. …….. Observation
45 Temp7 Low Temperature 7 low Observation
46 DHCP Failure DHCP function enabled, but cannot acquire IP address Observation
Alarms of Rect Group
1 Multi-rect Fail More than one rectifier failure detected Critical
2 Rectifier Lost Rectifier cannot be detected by the controller Critical
3 Redund Active Rectifier redundancy is enabled Observation
4 Rect No Resp Rectifier communication failure Major
Indicates rectifier redundancy condition has changed
5 Redund Oscill Observation
status more than 5 times due to load change
Alarms of Rectifier
1 AC Failure Rectifier AC power fails Major
2 Rect Temp High Rectifier temperature high Major
3 Rect Fault Rectifier fault Major
4 Over Voltage Rectifier over voltage Major
5 Rect Protected Rectifier is protected Major
6 Fan Failure Rectifier fan fails Major
7 Current Limit Rectifier is in current limiting status Major
8 Comm Fail Rectifier communication fails Major
9 Derated Rectifier output power is derated Observation

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
50 Chapter 5 Use Of Monitoring Module M820B

Default Alarm
No. Alarm Name Alarm Description
Severity
10 SharingCurr Alm Rectifier has current sharing alarm Observation
11 U-Volt Protect Under voltage protection Major
Alarms of Batt Group
1 Short Test Battery short time test Observation
2 Boost For Test Boost charge test Observation
3 Manual Test Manual battery discharge test Observation
4 Plan Test Planned battery test Observation
Switch off AC power to perform the battery discharging
5 AC Fail Test Observation
test
6 Manual Boost Manually start the boost charging Observation
7 Auto BC Automatic boost charging Observation
8 Cyclic Boost Cyclic boost charging Observation
In slave mode, the slave unit starts boost charging with
9 Master Boost Observation
the master unit
In slave mode, the slave unit starts the test with the
10 Master Test Observation
master unit
11 Dis Curr Im Rectifier distribution current alarm Observation
12 Abnorm Batt Curr Battery current is abnormal Observation
13 Temp Comp Activ Temperature compensation is started Observation
14 Batt Curr Lmt Battery current limit Observation
15 Bad Battery Battery block fails Observation
16 Battery Dischar Battery discharging Observation
Alarms of Battery
1 Exceed Curr Lmt Current limit point is exceeded Observation
2 Over Current Battery over current Observation
3 Low Capacity Battery low capacity Observation
Alarms of SMDU Battery
1 Exceed Curr Lmt Current limit point is exceeded Observation
2 Over Current Battery over current Observation
3 Low Capacity Battery low capacity Observation
Alarms of EIB Battery
1 Exceed Curr Lmt Current limit point is exceeded Observation
2 Over Current Battery over current Observation
3 Low Capacity Battery low capacity Observation
Alarms of SM Batt
1 Over Curr Lmt Current limit point is exceeded Observation
2 Ov Batt Current Battery over current Observation
3 Battery Leakage Battery has leakage Observation
4 Low Acid Level Battery electrolytic level is low Observation
5 Batt disconnec Battery is disconnected Observation
6 Batt high temp Battery temperature is high Observation
7 Batt low temp Battery temperature is low Observation
8 Cell volt diff Cell voltage is diffierent Observation
9 SM unit fail SM Unit failure Observation
10 T Sensor Fault Temperature sensor fails Observation
11 Low Capacity Battery low capacity Observation
12 Battery No Resp Battery has no response Observation
13 Battery Temp no No battery temperature Observation
Alarms of Ldu Battery
1 Exceed Curr Lmt Current limit point is exceeded Observation
2 Low Capacity Battery low capacity Observation
3 Fuse Failure Battery fuse fails Critical
4 Over Volt Battery over voltage Observation
5 Under Volt Battery under voltage Observation
6 Over Curr Battery over current Observation
7 No Response Battery has no response Observation
Alarms of OBBattery Fus
1 Fuse1 Alarm Battery fuse 1 alarm Critical

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 51

Default Alarm
No. Alarm Name Alarm Description
Severity
2 Fuse2 Alarm Battery fuse 2 alarm Critical
3 Fuse3 Alarm Battery fuse 3 alarm Critical
4 Fuse4 Alarm Battery fuse 4 alarm Critical
Alarms of SMDUBattery Fus
1 Batt Fuse 1 Alm Battery fuse 1 alarm Critical
2 Batt Fuse 2 Alm Battery fuse 2 alarm Critical
3 Batt Fuse 3 Alm Battery fuse 3 alarm Critical
4 Batt Fuse 4 Alm Battery fuse 4 alarm Critical
Alarms of DC
1 Over Voltage1 DC over voltage 1 Critical
2 Over Voltage2 DC over voltage 2 Critical
3 Under Voltage1 DC under voltage 1 Critical
4 Under Voltage2 DC under voltage 2 Critical
Alarms of DC Fuse Unit
1 Fuse1 Alarm Fuse 1 alarm Critical
2 Fuse2 Alarm Fuse 2 alarm Critical
3 …….. …….. Critical
10 Fuse10 Alarm Fuse 10 alarm Critical
Alarms of SMDU DC Fuse
1 DC Fuse1 Alarm Critical
2 DC Fuse2 Alarm Critical
3 …….. Critical
16 DC Fuse16 Alarm Critical
Alarms of LVD
1 LVD1 Disconnect LVD1 contactor disconnected Critical
2 LVD2 Disconnect LVD2 contactor disconnected Critical
3 LVD1 Failure LVD1 contactor fails Critical
4 LVD2 Failure LVD2 contactor fails Critical
Alarms of SMDU LVD
1 LVD1 Disconnect LVD1 contactor disconnected Critical
2 LVD2 Disconnect LVD2 contactor disconnected Critical
3 LVD1 Failure LVD1 contactor fails Critical
4 LVD2 Failure LVD2 contactor fails Critical
Alarms of LargDU LVD
1 LVD1 Disconnect LVD1 contactor disconnected Critical
2 LVD2 Disconnect LVD2 contactor disconnected Critical
Alarms of AC
1 L-AB OverVolt1 Line A-to-Line B over voltage 1 Observation
2 L-AB OverVolt2 Line A-to-Line B over voltage 2 Observation
3 L-AB UnderVolt1 Line A-to-Line B under voltage 1 Observation
4 L-AB UnderVolt2 Line A-to-Line B under voltage 2 Observation
5 L-BC OverVolt1 Line B-to-Line C over voltage 1 Observation
6 L-BC OverVolt2 Line B-to-Line C over voltage 2 Observation
7 L-BC UnderVolt1 Line B-to-Line C under voltage 1 Observation
8 L-BC UnderVolt2 Line B-to-Line C under voltage 2 Observation
9 L-CA OverVolt1 Line C-to-Line A over voltage 1 Observation
10 L-CA OverVolt2 Line C-to-Line A over voltage 2 Observation
11 L-CA UnderVolt1 Line C-to-Line A under voltage 1 Observation
12 L-CA UnderVolt2 Line C-to-Line A under voltage 2 Observation
13 PH-A OverVolt1 Phase A over voltage 1 Observation
14 PH-A OverVolt2 Phase A over voltage 2 Observation
15 PH-A UnderVolt1 Phase A under voltage 1 Observation
16 PH-A UnderVolt2 Phase A under voltage 2 Observation
17 PH-B OverVolt1 Phase B over voltage 1 Observation
18 PH-B OverVolt2 Phase B over voltage 2 Observation
19 PH-B UnderVolt1 Phase B under voltage 1 Observation
20 PH-B UnderVolt2 Phase B under voltage 2 Observation
21 PH-C OverVolt1 Phase C over voltage 1 Observation

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
52 Chapter 5 Use Of Monitoring Module M820B

Default Alarm
No. Alarm Name Alarm Description
Severity
22 PH-C OverVolt2 Phase C over voltage 2 Observation
23 PH-C UnderVolt1 Phase C under voltage 1 Observation
24 PH-C UnderVolt2 Phase C under voltage 2 Observation
25 Mains Failure AC mains power fails Critical
Alarms of OB AC Unit
1 PH-A OverVolt1 Phase A over voltage 1 Observation
2 PH-A OverVolt2 Phase A over voltage 2 Observation
3 PH-A UnderVolt1 Phase A under voltage 1 Observation
4 PH-A UnderVolt2 Phase A under voltage 2 Observation
5 PH-B OverVolt1 Phase B over voltage 1 Observation
6 PH-B OverVolt2 Phase B over voltage 2 Observation
7 PH-B UnderVolt1 Phase B under voltage 1 Observation
8 PH-B UnderVolt2 Phase B under voltage 2 Observation
9 PH-C OverVolt1 Phase C over voltage 1 Observation
10 PH-C OverVolt2 Phase C over voltage 2 Observation
11 PH-C UnderVolt1 Phase C under voltage 1 Observation
12 PH-C UnderVolt2 Phase C under voltage 2 Observation
13 Mains Failure AC mains power fails Critical
14 SevereMainsFail AC mains voltage is too low Critical
Alarms of SMAC
1 Supervision Fa Supervision failure Observation
2 High L-Volt AB Line A-Line B voltage high Observation
3 Vhigh L-Volt AB Line A-Line B voltage very high Major
4 Low L-Volt AB Line A-Line B voltage low Observation
5 VLow L-Volt AB Line A-Line B voltage very low Major
6 High L-Volt BC Line B-Line C voltage high Observation
7 VHigh L-Volt BC Line B-Line C voltage very high Major
8 Low L-Volt BC Line B-Line C voltage low Observation
9 VLow L-Volt BC Line B-Line C voltage very low Major
10 High L-Volt CA Line C-Line A voltage high Observation
11 Vhigh L-Volt CA Line C-Line A voltage very high Major
12 Low L-Volt CA Line C-Line A voltage low Observation
13 VLow L-Volt CA Line C-Line A voltage very low Major
14 High Ph-Volt A Phase A voltage high Observation
15 VHigh Ph-Volt A Phase A voltage very high Major
16 Low Ph-Volt A Phase A voltage low Observation
17 VLow Ph-Volt A Phase A voltage very low Major
18 High Ph-Volt B Phase B voltage high Observation
19 VHigh Ph-Volt B Phase B voltage very high Major
20 Low Ph-Volt B Phase B voltage low Observation
21 VLow Ph-Volt B Phase B voltage very low Major
22 High Ph-Volt C Phase C voltage high Observation
23 VHigh Ph-Volt C Phase C voltage very high Major
24 Low Ph-Volt C Phase C voltage low Observation
25 VLow Ph-Volt C Phase C voltage very low Major
26 Mains Failure Mains power outage Critical
27 Severe Mains Fai Severe mains power outage Critical
28 High Frequency AC power frequency is high Major
29 Low Frequency AC power frequency is low Major
30 High Temp High temperature Observation
31 Low Temperature Low temperature Observation
32 A High Current Phase A high current Observation
33 B High Current Phase B high current Observation
34 C High Current Phase C high current Observation
Alarms of IB
1 IB Failure Critical
2 DI1 Alarm Digital input 1 alarm Critical
3 DI2 Alarm Digital input 2 alarm Critical

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 53

Default Alarm
No. Alarm Name Alarm Description
Severity
4 …….. …….. Critical
9 DI8 Alarm Digital input 8 alarm Critical
Alarms of EIB
1 EIB Failure EIB board fails Critical
2 Bad Batt Block Battery block fails Observation
Alarms of SMDU Unit
1 Under Voltage Observation
2 Over Voltage Observation
3 Comm Interrupt Rectifier communication failure Major
Alarms of Converter
1 Converter Fail Major
Alarms of SMIO 1
1 SMIO Fail SM IO fails Observation
Alarms of SMIO Unit 2—SMIO Unit 8
1 Hi-AI 1 Alarm Analog input 1 high alarm Observation
2 Low-AI 1 Alarm Analog input 1 low alarm Observation
3 Hi-AI 2 Alarm Analog input 1 high alarm Observation
4 Low-AI 2 Alarm Analog input 1 low alarm Observation
5 Hi-AI 3 Alarm Analog input 1 high alarm Observation
6 Low-AI 3 Alarm Analog input 1 low alarm Observation
7 Hi-AI 4 Alarm Analog input 1 high alarm Observation
8 Low-AI 4 Alarm Analog input 1 low alarm Observation
9 Hi-AI 5 Alarm Analog input 1 high alarm Observation
10 Low-AI 5 Alarm Analog input 1 low alarm Observation
11 Hi-Freq IN Alm High frequency input alarm Observation
12 Low-Freq IN Alm Low frequency input alarm Observation
13 SMIO Fail SM IO failure Observation
Alarms of ACD Group
1 Mains Failure Mains power outage Major
Alarms of AC Distri
1 Mains 1 Fail Mains 1 failure Major
2 Mains 2 Fail Mains 2 failure Major
3 Mains 3 Fail Mains 3 failure Major
4 M1 Uab/a Fail Mains 1 Uab/a failure Major
5 M1 Ubc/b Fail Mains 1 Ubc/b failure Major
6 M1 Uca/c Fail Mains 1 Uca/c failure Major
7 M2 Uab/a Fail Mains 2 Uab/a failure Major
8 M2 Ubc/b Fail Mains 2 Ubc/b failure Major
9 M2 Uca/c Fail Mains 2 Uca/c failure Major
10 M3 Uab/a Fail Mains 3 Uab/a failure Major
11 M3 Ubc/b Fail Mains 3 Ubc/b failure Major
12 M3 Uca/c Fail Mains 3 Uca/c failure Major
13 Over Frequency Major
14 Under Frequency Major
15 M1 Uab/a OverV M1 Uab/a Over Voltage Major
16 M1 Ubc/b OverV M1 Ubc/b Over Voltage Major
17 M1 Uca/c OverV M1 Uca/c Over Voltage Major
18 M2 Uab/a OverV M2 Uab/a Over Voltage Major
19 M2 Ubc/b OverV M2 Ubc/b Over Voltage Major
20 M2 Uca/c OverV M2 Uca/c Over Voltage Major
21 M3 Uab/a OverV M3 Uab/a Over Voltage Major
22 M3 Ubc/b OverV M3 Ubc/b Over Voltage Major
23 M3 Uca/c OverV M3 Uca/c Over Voltage Major
24 M1 Uab/a UnderV M1 Uab/a Under Voltage Major
25 M1 Ubc/b UnderV M1 Ubc/b Under Voltage Major
26 M1 Uca/c UnderV M1 Uca/c Under Voltage Major
27 M2 Uab/a UnderV M2 Uab/a Under Voltage Major
28 M2 Ubc/b UnderV M2 Ubc/b Under Voltage Major

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
54 Chapter 5 Use Of Monitoring Module M820B

Default Alarm
No. Alarm Name Alarm Description
Severity
29 M2 Uca/c UnderV M2 Uca/c Under Voltage Major
30 M3 Uab/a UnderV M3 Uab/a Under Voltage Major
31 M3 Ubc/b UnderV M3 Ubc/b Under Voltage Major
32 M3 Uca/c UnderV M3 Uca/c Under Voltage Major
33 In-MCCB Trip Input MCCB trips Critical
34 Out-MCCB Trip Output MCCB trips Critical
35 SPD Trip SPD trips Critical
36 No Response No response Critical
Alarms of DC Distri
1 DC Over VOlt DC over voltage Critical
2 DC Under Volt DC under voltage Critical
3 Output1 Discon Output 1 disconnection Critical
. . . .
. . . .
. . . .
66 Output 64 Discon Output 64 disconnection Critical
67 No Response No response Critical
68 T1 Over Temp T1 over temperature Critical
69 T2 Over Temp T2 over temperature Critical
70 T3 Over Temp T3 over temperature Critical
71 T1 Under Temp T1 Under temperature Critical
72 T2 Under Temp T2 Under temperature Critical
73 T3 Under Temp T3 Under temperature Critical
74 T1 sensor fail Temperature 1 sensor failure Observation
75 T2 sensor fail Temperature 2 sensor failure Observation
76 T3 sensor fail Temperature 3 sensor failure Observation
Alarms of Diesel Group
1 Diesel Test Observation
2 Test Failure Diesel test fails Major
3
Alarms of Diesel Genrat
1 Low DC Voltage DC voltage is low Major
2 Supervision Fai Supervision Failure Observation
3 Generator Fail Generator failure Critical
4 Genrtor Cnected Generator is connected Observation
5 Low Fuel Level Fuel level is low Major
6 High Water Temp Water temperature is high Major
7 Low Oil Press Oil pressure is low Major
Alarms of RectifierGrou
1 Rects No Resp Rectifiers have no response Major
2 Rectifier Lost Rectifier is lost Critical
3 Comm failure Rectifier communication failure Critical
4 Mains Failure Mains power outage Critical
Alarms of Group2Rectifi
1 AC Failure AC input power failure Major
2 Rect Temp High Rectifier temperature is high Major
3 Rect Fault Rectifier has fault Major
4 Over VOltage Rectifier has over voltage Major
5 Rect Protected Rectifier is under protection Observation
6 Fan Failure Fan fails Major
7 Current limit Rectifier output current is limited None
8 Comm failure Rectifier communication failure Major
9 Derated Rectifier power is derated Observation
10 SharingCurr Alm Current sharing alarm Observation
11 U-Volt Protect Rectifier is in under voltage protection status Major
Alarms of Group3Rectifi and Group4Rectifi are the same with Group2Rectifi.
Alarms of SMDUP Unit
1 Comm Interrupt Communication fails Major

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 55

The Default Alarm Severity of all the alarms in the above table can be changed.

Alarm relay setting


Move the cursor to “Alarm Relay” and press ENT, following screen pop up.

Alarm Settings Alarm Severity Self Detect Fail


ENT
Alarm Severity ENT Power System None
Alarm Relay Rect Group CAN Comm Fail
Alarm Param Rectifier None
Battery Group Alarm Blocked
Battery None
SMDU Battery …… .
EIB Battery
SM Batt
Ldu Battery
OBBattery Fus
SMDU Batt Fus
DC
DC Fuse Unit
SMDU DC Fuse
LVD
SMDU LVD
LargeDU LVD
......

Figure 5-15 Alarm Relay Setting

In the screen of Alarm Relay Setting, move cursor to Power System and press ENT to highlight the “Power System”,
and press ENT again to display the alarms of the power system, such as Self Detect Fail, CAN Comm Fail, Alarm
Blocked, etc, as well as the alarm relay number. In the screen, the alarm relay number is displayed as “None”, and
you can configure it to the relay number from “Relay 1” to “Relay 13”. For example, if you want to set the alarm relay
number for the “Self Detect Fail” alarm, move the cursor to “None”, press ENT to highlight “None”, and press ▲ or ▼
continuously to enter the numbers from 0 to 10, this means you can set any of the alarm relays (1 through 10) for the
alarm of “Self Detect Fail”. You can set the alarm relay for other alarms in the same way.

Alarm parameter setting


Move the cursor to “Alarm Param” and press ENT, following screen shows up.

Alarm Settings Alarm Voice


ENT
Alarm Severity On
Alarm Relay Block Alarm
Alarm Param Normal
Clear His Alarm
Yes

Figure 5-16 Alarm Parameter Setting

For the menu of “Alarm Voice”, you can set the alarm voice to “Off” to turn off the buzzer.
For the menu of “Clear His Alarm”, you can set it from “Yes” to “No”, which means do not clear the history alarm.

5.7.2 Power System Setting

In the Setting screen, move cursor to “Power System”, press ENT to show the Power System Setting screen. In the
Power System Setting screen, you can set the general parameters (“General”), Power Split parameters and
temperature parameters (“Temp Para”). Move cursor to “General”, press ENT, general parameter setting screen will
show up.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
56 Chapter 5 Use Of Monitoring Module M820B

MAIN MENU Settings ENT Power System ENT Auto / Man State
Status ENT Select User ENT Alarm Setting General Auto
Settings admin Power System Power Split To AUto Delay
Energy Saving Rectifier Temp Para 0h
Enter Password
Manual Battery Work Mode
*
Quick Settings BatteryFuseUnit Alone
DC Mtn Cycle Time
LVD …… 360 days
AC
Communication
Controller
Figure 5-17 General Parameter Settings of Power System

The general parameter settings of power system are: Auto / Man State, Mtn Time Delay, Mtn Cycle Time, etc. Method
of changing the parameter settings: With “Mtn Time Delay” as an example, move cursor beside “3” that is in “30 days”,
press ENT to highlight the character of “3”, now you can press ▲ or ▼ continuously to enter the numbers from 0 to 9
to change the number “3” to other numbers, after the changing, press ENT to validate the change. Then, move cursor
beside “0” that is in “30 days”, press ENT to highlight the character of “0”, and now you can press ▲ or ▼
continuously to enter the numbers from 0 to 9 to change the number “0” to other numbers. After the changing, press
ENT to validate the change.
You can use the same method to change all the other parameters listed in following tables.
Table 5-6 Parameter Settings of Power System
No. Parameter Name Parameter Description Default Setting Setting Range
General Parameter Settings
1 Auto / Man State Auto / manual control Auto Auto / manual
2 To Auto Delay Delay of transfering to auto mode 0h
Master, Slave,
3 Work Mode Alone
Alone
4 Mtn Cycle Time Cycle time of maintenance 360 days
5 Over Load Point 70%
6 Imb Protect Current sharing imbalance Enabled Disable / enable
7 Relay Report Way Relay report way Fixed Fixed / user defined
If the alarm is blocked, the alarm information
8 Alarm Blocked Normal Normal / blocked
will not be reported under EEM protocol.
9 SMDUSampChange SMDU sampler can be changed Can CAN/RS485
10 Lower Consump ??????? Disabled Disable / enable
11 P Peak Shaving Peak power limit Disabled Disable / enable
Maximum power consumption limit (MPCL)
12 MPCL CtlHister 2.00kW
hysteresis
13 MPCL BatDisco Should the battery be disconnected? Disabled Disable / enable
14 MPCL DieselCtl Whether to turn on the diesel generator? Disabled Disable / enable
Power Split Parameter Settings (Only valid for Slave system)
1 Slave Curr Lmt Current limit of slave units 60%
2 Delta Volt 0.5V
3 Proportion Coeff 30.0
4 Integral Time 60s
Temp Para Settings
Options are “disable”, “environment” and
1 Temp1 enable “battery”, which means whether this Disabled Disable / enable
temperature sensor detects ambient
2 Temp2 enable Same with above Disabled Disable / enable
3 Temp3 enable Same with above Disabled Disable / enable
Temperature 1 higher than high temperature
4 Temp1 High1 50 deg.C
threshold 1
Temperature 2 higher than high temperature
5 Temp2 High1 50 deg.C
threshold 1
Temperature 3 higher than high temperature
6 Temp3 High1 50 deg.C
threshold 1
7 Temp1 Low Temperature 1 low 0 deg.C

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 57

No. Parameter Name Parameter Description Default Setting Setting Range


8 Temp2 Low Temperature 2 low 0 deg.C
9 Temp3 Low Temperature 3 low 0 deg.C

5.7.3 Rectifier Setting

Move cursor to “Rectifier” and press ENT, the rectifier setting screen pops up, then move cursor to “All Rect Set”,
following screen pops up.

Settings Rectifier Hi Volt Limit


ENT ENT
Alarm Setting All Rect Set 59.0 V
Power System Rect1(001) DCOverVRestart
Rectifier
Rect2(002) Disable
Battery
OverVRestart
BatteryFuseUnit
DC 300 s
……
LVD
AC
Communication
Controller
Figure 5-18 Rectifier Parameter Setting

In the middle screen of Figure 3-18, there are 3 items: “All Rect Set”, “Rect1(001)” and “Rect2(002)”. For “All Rect
Set”, the parameter setting will be effective for all the rectifiers. For “Rect1(001)”, the parameter setting is only
effectively for rectifier 1 (001). From the screen, you can see that there are only 2 rectifiers working. If there are 5
rectifiers working, the screen will show all the rectifiers from Rect1(001) to Rect5(005).
User can configure all the rectifier parameters listed in the following table.
Table 5-7 List of Rectifier Parameter Settings
No. Parameter Name Parameter Description Default Setting Setting Range
Parameter Settings of All Rect Set
1 Hi Volt Limit High voltage limit 59.0V
2 DCOverVRestart Restart after DC over voltage Disabled Disable / enable
3 OverVRestartT Time after over voltage restart 300s
4 Start Interval Start interval 0s
5 Walk-in Enable Rectifier Walk-in enabled Disabled Disable / enable
6 Turn-on ACOverV AC over voltage turn-on No
7 ECO Mode Operating in energy saving mode Disabled Disable / enable
8 InputCurrLimit Input current limit 30.0A
9 Full Capacity E Operate at full power Degraded Degraded / full power
10 HVSD Enable Hight voltage shutdown enabled Disabled Disable / enable
Rect1 Parameter Settings
1 Rect Position Rectifier position 1
2 Rect Phase Rectifier phase A

The contents of settings of rect1 (001) are same with those of rect2(002).

5.7.4 Battery Setting

Move cursor to “Battery”, press ENT to show the battery setting screen, you can configure all the battery parameters
listed in the following table.
Table 5-8 List of Battery Parameter Settings
No. Parameter Name Parameter Description Default Setting Setting Range
Basic Battery Parameter Settings
1 Batt Type No. Type of battery string 1 1-10
2 BattShunt Numbe Number of battery shunts 2 0,1,2
Battery voltage measurement for NA
3 BattVoltForNA No No, Yes
customer

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
58 Chapter 5 Use Of Monitoring Module M820B

No. Parameter Name Parameter Description Default Setting Setting Range


Whether to disconnect the LVD
contactor or regulate the battery
4 Action on VHBT Disabled Disable / enable
voltage, when battery over
temperature happens
5 Low Cap Point Low capacity threshold 75%
6 CurrLmtEnb Current limit enabled Yes Yes, No
Settings of Charge Para
1 FC Voltage Float charging voltage 53.5V
2 BC Voltage Boost charging voltage 56.4V
3 Batt Curr Lmt Battery charging current limit 0.10C10
4 Over Current Battery over voltage 0.30C10
Automatic boost charging test is
5 Auto BC Enabled Yes Yes / No
enabled
Current for transferring boost
6 To BC Current 0.060C10
charging
Capacity for transferring boost
7 To BC Capacity 80.0%
charging
8 Stable BC Curr Stable boost charging current 0.010
9 Stable BC delay Stable boost charging delay 100 min
10 BC ProtectTime Boost charging protection time 1000 min
11 CycBC Enabled Cyclic boost charging enabled Yes Yes / No
12 Cyc/BC Interval Cyclic boost charging interval 100 days
13 Cyc/BC Duration Cyclic boost charging duration 720min
Settings of Test Para
1 Test Volt Test voltage 45.0V
2 Test End Volt End of test voltage 45.2V
3 Test End Time Test time 100 min
4 Test End Cap End of test capacity 70.0%
5 Record Threshold 0.100V
6 AC Fail Test Enb Disable
7 Planned Test Num 0
8 ConstCurrT Enb Constant current charge is enabled Disabled Disable / enable
9 ShortTestEnable Battery short test is enabled Disabled Disable / enable
10 Lowest Capa for Lowest capacity for the test 99%
Parameter Settings of Temp Comp
1 TempComp Center Temperature compensation center 25.0 deg.C
Temperature compensation
2 TempComp Coeff 72.0 mV/deg.C
coefficient
Temp1, Temp2,
Number of temperature inputs used Temp3, Temp4,
3 Temp No. for TC None
for temperature compensation Temp5, Temp6,
Temp7, None
Parameter Settings of Capa Cacu
1 Capacity Coef Capacity coefficient 96%
2 Time 0.1C10 10.00h
3 Time 0.2C10 4.90h
4 Time 0.3C10 3.00h
5 Time 0.4C10 2.00h
6 Time 0.5C10 1.40h
7 Time 0.6C10 1.20h
8 Time 0.7C10 1.10h
9 Time 0.8C10 0.90h
10 Time 0.9C10 0.70h
11 Time 1.0C10 0.50h
Battery 1
Whether the battery participates the
1 Manage Enable Yes Yes, No
battery management
2 Rated Capacity Rated battery capacity 300Ah

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 59

No. Parameter Name Parameter Description Default Setting Setting Range


3 Shunt Current Battery shunt current 500.0A
4 Shunt Voltage Battery shunt voltage 75.0mV

The parameter settings of Battery 2 and SMDU Battery are the same with those of Battery 1.

5.7.5 Parameter Settings Of BattFuseUnit

Move the cursor to “BattFuseUnit” in the setting screen to configure all the parameters of DC distribution unit listed in
the following table.
Table 5-9 Parameter Settings of BattFuseUnit
No. Parameter Name Parameter Description Default Setting Setting Range
1 BattFuse Number Number of battery fuses 2 1, 2

5.7.6 Parameter Settings Of DC

Move the cursor to “DC” in the setting screen to configure all the parameters of DC distribution unit listed in the
following table.
Table 5-10 Parameter Settings of DC Distribution
No. Parameter Name Parameter Description Default Setting Setting Range
1 Over Voltage 1 DC over voltage 1 55.7V
2 Over Voltage 2 DC over voltage 2 58.5V
3 Under Voltage 1 DC Under Voltage 1 45.0V
4 Under Voltage 2 DC Under Voltage 2 42.0V
5 Shunt Current 500.0A
6 Shunt Voltage 75.0mV
Whether the load shunt is connected
7 Load Exist Yes Yes, No
in the system

5.7.7 Parameter Setting Of LVD

Move cursor to “LVD” in the setting screen, press ENT to set the LVD parameters listed in the following table.
Table 5-11 Parameter Setting of LVD
No. Parameter Name Parameter Description Default Setting Setting Range
Parameter Settings of LVD Group
1 ACFailRequired Disable Enable/disable
Parameter Settings of LVDUnit
1 LVD1 Enabled LVD1 is enabled Enable Enable/disable
LVD1 is enabled according to
2 LVD1 Mode Voltage Voltage/Time
voltage or time
3 LVD1 Voltage LVD1 voltage 43.2V
4 LVD1 Reconn Volt LVD1 reconnection voltage 52.5V
5 LVD1 Reconn Delay LVD1 reconnection delay time 2min
6 LVD1 Time 300min
7 LVD1 Dependency None
8 LVD2 Enabled LVD2 is enabled Enabled Enable/disable
Whether the LVD2 is activated
9 LVD2 Mode Voltage Voltage/Time
according to voltage or time
10 LVD2 Voltage 43.2V
11 LVD2 Reconn Volt LVD2 reconnection voltage 52.5V
12 LVD2 Reconn Delay LVD2 reconnection delay 2min
13 LVD2 Time 300min
14 LVD2 Dependency None
15 LVD Type Type of LVD contactor Bistable Bistable/monostable

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
60 Chapter 5 Use Of Monitoring Module M820B

5.7.8 AC Parameter Settings

Move cursor to “AC” in the setting screen, press ENT to set the AC parameters listed in the following table.
Table 5-12 AC Parameter Setting
No. Parameter Name Parameter Description Default Setting Setting Range
Rect AC Parameter Settings
1 Nominal PH-Volt Nominal line-to-neutral voltage 220V
2 Volt Threshold1 Voltage threshold 1 20.0%
3 Volt Threshold Voltage threshold 25.0%
OB AC Unit Parameter Settings
1 Nominal PH-Volt Nominal line-to-neutral voltage 220V
2 Volt Threshold1 Voltage threshold 1 20.0%
3 Volt Threshold Voltage threshold 25.0%
None, Three-Phase,
4 AC Type AC input type None
Single-Phase

5.7.9 Communication Parameter Settings

Move cursor to “Communication” in the setting screen, press ENT to set the communication parameters listed in the
following table.
Table 5-13 Communication Parameter Setting
No. Parameter Name Parameter Description Default Setting Setting Range
1 DH CP Close Close, open
2 IP Address 10.163.210.205
3 Subnet Mask 255.255.254.0
4 Default Gateway 10.163.210.205

5.7.10 Controller Parameter Settings

Move cursor to “Controller” in the setting screen, press ENT to set the controller parameters listed in the following
table.
Table 5-14 Controller Parameter Setting
No. Parameter Name Parameter Description Default Setting Setting Range
1 Language Language used in LCD display English English/Chinese
2 Time Zone GMT+00:00
3 Date 2009-01-19
4 Time 11:10:20
5 Keypad Voice On On/Off
6 LCD Rotation 90 deg 0, 90, 180, 270
7 Reload Config Yes Yes/No
8 Download Config Yes Yes/No
9 Auto Config Yes Yes/No

5.8 Energy Saving Setting


Move cursor to “Energy Saving” in the setting screen, press ENT to set the Energy Saving parameters listed in the
following table.
Table 5-15 Rect Standby Parameter Setting
No. Parameter Name Parameter Description Default Setting Setting Range
1 ECO Mode Disabled Disable/Enable

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 61

5.9 Quick Settings


Move cursor to “Quick Settings” in the setting screen, press ENT to set the parameters listed in the following table.
Table 5-16 Quick Settings
No. Parameter Name Parameter Description Default Setting Setting Range
Parameter settings of Auto/Manual
1 Auto/Man State Auto or manual control status Auto Auto/Manual
Parameter settings of ECO Mode Set
1 ECO Mode Disable Disable/Enable
Parameter settings of FC/BC Voltage
1 FC Voltage 53.5V
2 BC Voltage 56.4V
Parameter settings of FC/BC Change
Automatic boost charging test is
1 Auto BC Enabled Yes Yes/No
enabled
Current for transferring boost
2 To BC Current 0.060C10
charging
Capacity for transferring boost
3 To BC Capacity 80.0%
charging
4 Stable BC Curr Stable boost charging current 0.010
5 Stable BC delay Stable boost charging delay 100min
6 BC ProtectTime Boost charging protection time 1000min
7 CycBC Enabled Cyclic boost charging enabled Yes Yes/No
8 Cyc/BC Interval Cyclic boost charging interval 100 days
9 Cyc/BC Duration Cyclic boost charging duration 720min
Parameter settings of Temp Compens
1 TempComp Center Temperature compensation center 25.0 deg.C
Temperature compensation
2 TempComp Coeff 72.0 mV/deg.C
coefficient
Temp1, Temp2,
Number of temperature inputs used Temp3, Temp4,
3 Temp No. for TC None
for temperature compensation Temp5, Temp6,
Temp7, None
Parameter settings of Work Mode Set
1 Work Mode Alone Master, Slave, Alone

5.10 Access M820B Through Web


Web is a remote user interface, user can
Browser the detail status of each equipment such as rectifiers, batteries, and AC unit
Send control command and set parameters to equipment
View the active alarms that can be auto popped up if a new alarm comes.
Query historical alarms, historical signal data and logs(battery test, diesel test, user control, system)
Change system parameters, such as IP address, time, SNMP and EEM protocol settings, user information
Change equipment name, signal name and alarm level
Download/upload configuration files, and update application software and local language package.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
62 Chapter 5 Use Of Monitoring Module M820B

5.10.1 Login

To log in ACU+, double-click the icon of IE to run the software, click the menus of Tools→Internet Options and then
click the button “Connections” to pop up the following screen.

Figure 5-19 LAN Setting (Step 1)

In the screen as shown in Figure 4-1, click the button “LAN Settings” to pop up the following screen.

Figure 5-20 LAN Setting (Step 2)

In the above screen, uncheck the proxy screen and click OK to finish the LAN setting. Then input the IP address and
press ENT, the following Web interface pops up requiring user to enter username and password.
Note that the user only needs to do the above settings when the ACU+ is connected to an intranet and the user has
set that the access to the intranet needs to be made through proxy. If the ACU+ is connected Internet and the user
computer is connected to the intranet, the user cannot disable the proxy, and otherwise, the user will have no access
to the ACU+.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 63

Figure 5-21 Log in ACU+

In the above screen, enter the username and password to log in ACU+, and the homepage screen as shown in
Figure 4-4 pops up.

5.10.2 Homepage Introduction

The homepage screen is shown in Figure 4-4.

Figure 5-22 ACU+ Homepage

In the main page, the system voltage, load current, management mode and battery management status are displayed
at the top.
The “Device Information”, “Quick Settings”, “Query”, “Maintenance” and “Configuration” are displayed in the left side.
Click each kind of menu and the contents will be displayed in the right side.
The alarm bar is located at the bottom of the screen.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
64 Chapter 5 Use Of Monitoring Module M820B

5.10.3 Device Information

As shown in Figure 4-4, the menu “Device Information” has the sub-menus of equipment groups such as “Power
System”, “RectifierGroup”, “BatteryGroup”, “DC”, “AC Group”, and “LVD Group”. User can check the sample data of
the equipment, set the equipment parameter and control the equipment by operating these sub-menus.
Every equipment has 3 signals that are data acquisition signals (sampled values), control signal and setting signal.
The following part introduces the device information operation with rectifier and battery as examples.

5.10.4 Data Browse, Control And Parameter Setting Of Rectifier

Rectifier group
In the screen as shown in Figure 4-5, click “RectifierGroup”, following screen pops up.

Figure 5-23 Rectifier Screen 1

The signals in the screen as shown in Figure 4-6 are all the actually sampled values such as “Total current”, “Rectifier
Number” and so on. In the screen, click the button “Control”, following screen pops up.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 65

Figure 5-24 Rectifier Screen 2

The signals in the screen as shown in Figure 4-6 are all the values used to control the rectifier. For example, in “Fan
full speed control”, user can select “Full Speed” and click “Set” to make the rectifier fan run at full speed. The control
command is effective for all the rectifiers. Pay attention that the “Control” button is only active when the ACU+ is in
manual status. Therefore, before implementing the “Control” operation, you have to set the “Auto/Man State” of the
ACU+ System to “Man” status.
Click the button “Setting”, following screen pops up.

Figure 5-25 Rectifier Screen 3

The screen as shown in Figure 4-7 lists all the values that can be set. For example, user can select “Disabled” for the
value of “Walk-in enabled” in the box of “Set value”, and then click the button “Set” to make the setting effective. After
the setting, the walk-in function of all the rectifiers is disabled.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
66 Chapter 5 Use Of Monitoring Module M820B

Single rectifier
Click the submenu “Rectifier1” of “RectifierGroup”, following screen pops up as shown in Figure 4-8.

Figure 5-26 Sampled Values of Single Rectifier

The screen as shown in Figure 4-8 shows the sample value of “Rectifier1”, similar to the operation of “RectifierGroup”,
user can click the button “Control” to view the values of rectifier 1 that can be controlled, as shown in Figure 4-9.

Figure 5-27 Control Screen of Rectifier 1

In the screen as shown in Figure 4-9, user can control the rectifier 1. For example, user can set the AC input of
rectifier 1 to “on”.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 67

5.10.5 Data Browse, Control And Parameter Setting Of Battery

Click the icon in the left of “Battery Group”, all the sampled values of the battery group are displayed as shown in
Figure 4-10.

Figure 5-28 Battery Screen (Sampled Value of Battery)

In Figure 4-10, the battery voltage is the total battery string voltage. The battery current is the total battery current.
Similar to browse the control values of the rectifier, click the button “Control” to view the control signals of the battery
as shown in Figure 4-11.

Figure 5-29 Control the Battery Group

In the screen as shown in Figure 4-11, user can control the battery. For example, in the “Set value” box of
“Boost/Float charge control”, user can set the “Float Charge” to “Boost Charge”, and click the button “Set” to make
the setting become effective. Click the “Setting” button to view setting signals of the battery as shown in Figure 4-12.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
68 Chapter 5 Use Of Monitoring Module M820B

Figure 5-30 Setting Values of Battery Group

In the screen as shown in Figure 4-12, user can set the battery parameters. For example, in the “Set value” box of
“Very High Temperature Limit”, user can set the “temperature limit” from “36.00” to “38.00”, and click the button “set”
to make the setting become effective.
Click the submenu of “Battery1”, the following screen pops up.

Figure 5-31 Sampled Values of Battery 1

The screen as shown in Figure 4-13 displays the sampled values of battery 1. In this screen, if you click “Control”,
nothing will be displayed because it is not allowed to control the single battery or set the values of the single battery.
Click “Setting”, following screen pops up.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 69

Figure 5-32 Setting Signals of Battery 1

Figure 4-14 shows the settable signals of battery 1 and user can set these signal values. For example, user can
select whether to enable this string of battery to participate the battery management and whether the shunt coefficient
of this battery can be set.

5.10.6 Alarms

The lower part on the right side of the page shows the active alarms of the DC power system.

When browsing the signals, click the icon “ ▼ ” to collapse more alarm signal information and you can recover the
display of alarm list by clicking “ ▼ ” again.
The active alarms are displayed as shown in Figure 4-15.

Figure 5-33 Alarm Screen

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
70 Chapter 5 Use Of Monitoring Module M820B

Figure 4-15 shows all the default alarms in the current active alarm page. Click “Observation Alarm” button to display
the alarms that are in the category of “Observation Alarm”.

Figure 5-34 Only Display Minor Alarms

Using the same method, click “Major Alarm” to display all the major alarms, in the same way, click “Critical Alarm” to
display all the critical alarms. All the minor alarms are displayed in yellow color and all the major alarms are displayed
in red colors and all the critical alarms are displayed in red color.

5.10.7 Maintenance

Click the icon in the left of “Maintenance”, and then click the sub-menu of “Network configuration”, following screen
pops up.

Figure 5-35 Network configuration

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 71

In the screen as shown in Figure 4-17, user can configure the network parameters of ACU+, such as ACU+ IP
address, default gateway and Mask. After modifying the network parameters, click “Save Parameter” to validate the
change made to the parameters.
Click the sub-menu of “HLMS Settings”, following screen pops up.

Figure 5-36 HLMS Setting

Click the sub-menu of “NMS Configure”, following screen pops up.

Figure 5-37 NMS Configuration

In the screen as shown in Figure 4-19, user can configure the NMS IP, authority and trap level. User can also add
new NMS, modify NMS information and delete the selected NMS through the interface as shown in Figure 4-19. User
can also set the trap level.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
72 Chapter 5 Use Of Monitoring Module M820B

Click the sub-menu of “ESR Configure”, following screen pops up.

Figure 5-38 ESR Configuration

In the screen as shown in Figure 4-20, user can configure the phone number and protocol for communication.
Click “Edit PowerSplit” submenu, and the following screen shows up.

Figure 5-39 PowerSplit Configurations

In this screen, user can set the PowerSplit mode and Digital input signals. There are some setting parameters, such
as delta voltage and proportional coefficient in Menu Power System/Setting for slave system in PowerSplit mode
(Refer to 6.3 Power Split Parameters). Note these setting parameters shall be set by expert only, user do not need
to set them.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 73

Click “User Information” submenu, the following screen shows up.

Figure 5-40 Configure User Information

In the screen as shown in Figure 4-22, user can add a user, and the method is as follows.
1. Enter the user name in the box at the right side of “User name”;
2. Select authority of the user;
3. Select the user type;
4. Configure the password for the user;
5. Finally, click “Add” button to add the user.
The method to delete a user is as follows:
(1) Select the user to be deleted in the user list;
(2) Click “Delete user” to delete the user.
The method to modify a user is as follows:
(1) Select the user to be deleted in the user list;
(2) Modify the user information;
(3) Click “Modify the user” to validate the modified user information.
Any user who visits user interfaces of the ACU+, such as LCD, Web interface, Console, shall be assigned with one of
the following 5 security levels/user groups.
Table 5-17 User Security Levels
Privilege Level User Group User authority
Level A Browser All users can browse power information without any writing permission.
Level B Operator The operator needs to write one password for control power system
The engineer needs to write one password to get the following access: browsing,
control, modifying parameter, downloading configuration file, but except updating
Level C Engineer
application an OS and modifying, adding, deleting user information (user name, user
level, password).
The administrator needs to write one password to get full access that include updating
Level D Administrator application an OS and modifying, adding, deleting user information (user name, user
level, password)
Level E Hardware An H/W switch is set that makes no writing of any kind possible to the product

Click the sub-menu of “Time synchronization” to calibrate the clock as shown in the screen below.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
74 Chapter 5 Use Of Monitoring Module M820B

Figure 5-41 Time Setting Screen

After changing the time, click “Setting” to validate the new time.
Click the submenu of “Clear Data” to clear the history alarm, history data, control log, battery test log and system
operation log.
Select the data to be deleted, click “Clear” to clear the corresponding data.

Figure 5-42 Clear Data

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 75

Click “Restore Default Configurations” submenu to restore the default configurations and restart the controller.

Figure 5-43 Restore Default Configurations

Click “Restore Default” and click “OK”, the default configuration files will overwrite the existing configuration files and
all the system parameters will be restored to default values.
Then, click “Restart Controller” button to restart the controller to make the default settings become effective.
Note: If the user uses the function of restoring default configurations, the ACU+ will lose its original configurations and
existing parameter settings.
Click “Download” submenu to upgrade the application programs, upload the current configuration package and
language package.
You need to shut down the controller first.

Figure 5-44 Download File: Shutdown the Controller

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
76 Chapter 5 Use Of Monitoring Module M820B

Click “Shutdown Controller”, the following interface shows up.

Figure 5-45 Download file

Click “Browse….” button to file the folder where the file will be downloaded. Select the file to be downloaded and then
click “Download”.
You can download configuration file package, application file package and language file package through ACU+, but
the suffix of the file must be “tar” or “tar.gz”. You can also download the file of “MonitoringSolution.cfg” through ACU+.
You cannot download other files through ACU+ except the above files.
You can upload configuration file package and language package through ACU+. In the screen of Figure 4-26, select
‘Configuration File Package” or “Language Package”, click “Upload” to save the configuration file package or
language package into the computer.
Click “Start Controller” to restart the controller so as to validate the updated application program.
Click the “Get Parameter Settings” submenu, you can save the parameter settings into the computer and then
download the file to other controllers (refer to “Download” menu), so that the other controllers can have the same
parameters.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 77

Figure 5-46 Restore Default Configurations

Click “Acquire” button to save the file of SettingParam.run.


Click the “Site Inventory” submenu, you can check the software version, hardware version and serial number
information of the intelligent devices (such as rectifier, SMDU and IB board) connected to the ACU+.

Figure 5-47 Restore Default Configurations

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
78 Chapter 5 Use Of Monitoring Module M820B

5.10.8 Configurations

Click the “Configuration” menu and then select the submenu of “Auto Configuration” to configure the controller
automatically.

Figure 5-48 Automatic Configuration

The auto configuration function can detect the intelligent equipment (such as SMDU, IB and EIB) connected to ACU+
and complete relevant configuration.
Click the menu of “Site Information Modification” to change the site name as shown below.

Figure 5-49 Modify Site Name

After entering the site name, site location or site description, click “Set” to modify the site information.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 79

Click the menu of “Equipment Information Modification” to change the name of the device as shown below.

Figure 5-50 Modify Equipment Name

Equipment device has two device names: One is the “Device name” and another is the “Device abbr name”. The
“Device name” is displayed in WEB and the “Device abbr name” is displayed in LCD.
Enter the new device name in the column of “New device name”, and select what type of device name will be
changed (whether to change the “Device name” or the “Device abbr name”), and finally click “Set”.
Click the menu of “Signal Information Modifcation” to modify the signal names as shown below.

Figure 5-51 Change Information Name

Similar to equipment name, each signal has two signal names: Long signal name and short signal name. The long
signal name is displayed in WEB and the short signal name is displayed in LCD.
For example: You can use following procedures to change the “System Name” to “Bus Voltage”.
1. Select the equipment to which this signal belongs: Power system;

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
80 Chapter 5 Use Of Monitoring Module M820B

2. Select the signal type to which the signal belongs: Acquisition signal
3. Enter new signal name: Bus voltage
4. Select the type of signal name to be changed: Long signal name or short signal name
5. Click “Set” button
For alarm signal, you can also change the alarm level for this alarm signal here.

Figure 5-52 Change Signal Name

In the second step in above procedures, select “Alarm Signal”, then the alarm signal name and alarm level are
displayed. Select “New alarm level” and click “Set” to change the alarm level of this alarm signal.
Click the “Configuration of Alarm Suppressing” menu to modify the shielding relationship of the alarm signal as shown
below.

Figure 5-53 Alarm Shielding Configuration: Select Standard Equipment

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 81

Alarm shielding means: If Alarm A shields Alarm B, when Alarm A happens, Alarm B will not be reported even if the
conditions of alarm B are met. For example, AC failure alarm will shield AC low voltage alarm. When AC failure
happens, the alarm conditions for both AC failure alarm and AC low voltage alarm are met, and both alarms should
be reported. However, since the AC failure alarm shields the AC low voltage alarm, only AC failure alarm is displayed
in the alarm list.
First, select the device to which the alarm signal belongs, all the alarm signals of this device will be displayed.
Find the alarm signal to be modified, click “Modify” button, and then set the alarm shield expression, as shown in the
Figure below.

Figure 5-54 Alarm Shield Configurations: Select the signal number

After selecting the number of signals in the alarm shield expression (for example, select 2), following screen shows
up.

Figure 5-55 Alarm shield configuration: Select alarm shield expression

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
82 Chapter 5 Use Of Monitoring Module M820B

In this screen, user can select the signals in the alarm shield expression and enter the logic relationship before the
alarm signal (Logic AND &, Logic OR |, Logic NO !).
Click “Configuration of PLC” menu to configure the PLC functions of ACU+, as shown below.

Figure 5-56 PLC Configurations

Click “Configuration of Alarm Relay” menu to configure the relevant relays of the alarm signal, as shown in the
following figure.

Figure 5-57 Alarm Relay Configurations

Select the standard device first, the screen will display all the alarm signals of this device, as well as the related relay
number for each alarm signal. If you need to modify the relay number, click “Modify” button behind the relay number.
“NA” means there is no related relay number.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 83

5.10.9 Query

Click “Query Data” menu, then select “History Alarm” submenu to query the history alarm information.

Figure 5-58 Screen for History Alarm Query

In Figure 4-40, select device (for example, select “Power System”, and the default is “All Devices”), enter the start
time and end time, and then click “Query” to query the data within this time slot.
Click “History Data” to pop up the following screen.

Figure 5-59 Query History Data

In Figure 4-41, select the device to be queried, and the default selection is “All Devices”.
Enter the start time and end time (for example, from December 18, 2007 to December 18, 2008), all the log in this
time slot will be displayed as shown in the above screen.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
84 Chapter 5 Use Of Monitoring Module M820B

Click “ControlSystem Log” to pop up the following screen.

Figure 5-60 Query Control and System Log

In Figure 4-42, first select the type of log to be queried: Control log or system log.
Enter the start time and end time (for example, from December 18, 2007 to December 18, 2008), all the log in this
time slot will be displayed as shown in the above screen.
You can save the queried log on your computer: Click “Download”, and select the path to save the query results.
Click “Battery Test Log” button to pop up the following screen.

Figure 5-61 Query Battery Test Data

In Figure 4-43, first enter the latest battery test times; click “Query” to query all the battery test results.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 85

5.11 Access ACU+ Through NMS


ACU+ has SNMP agent function. User can use NMS to do following operations:
Query the operation status and input/output signals of the device connected to ACU+;
Set the operation parameters of the device connected to ACU+;
Browse the active alarms.
When ACU+ generates alarms, SNMP agent can notify the preset NMS through TRAP automatically.

5.11.1 NMS Supported By SNMP Agent

The SNMP agent of ACU+ supports SNMPv2c.


All the NMS that supports SNMPv2c can be used to access ACU+. The NMS includes HP OpenView, IBM NetView,
Novell ManageWise, SunNet Manager and so on. SNMP is a technology used for network management. The
technology is based on implementing an information base called MIB (Managed Information Base). This MIB contains
parameters that are interesting from a management perspective. All LAN connected equipment that support SNMP
shall also support a default MIB called MIB-II.
The SNMP Agent responds to requests received via the SNMP protocol and also actively sends traps to a specified
manager when certain MIB values change state. This is used to actively inform a manager when an alarm situation is
recognized.

5.11.2 MIB Installation

MIB installation
The ACU+ MIB is located in the installation CD delivered together with ACU+, and file name is acu-power.mib.
Use the MIB loading function of NMS to load the MIB database, refer to the corresponding NMS user manual for the
detailed loading method.

Contents of MIB
This MIB is suitable for the firmware version 1.10 of ACU+. The MIB will change with the upgrading of ACU+ firmware.
The contents of MIB supported by ACU+ SNMP agent, and the OID are listed in Table 5-1. For the details, please
refer to the file of acu-power.mib.
Table 5-18 Contents of ACU+ MIB
Ident Group ACU+ ident group
IdentManufacturer The name of the equipment manufacturer R
IdentModel The manufacturers model designation of the power system R
IdentControllerFirmwareVersion The firmware (software) version of the controller R
IdentName The name of the power plant. This object should be set by the administrator. R/W
System Group ACU+ system value group
Status of the complete plant (highest alarm). One of
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
SystemStatus (5) major - MA R
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled
SystemVoltage System voltage, stored as mV R
SystemCurrent System current, stored as mA R
systemUsedCapacity Used capacity, stored as % of the total capacity R

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
86 Chapter 5 Use Of Monitoring Module M820B

The status of communication with the Power System


(1) Unknown
PsStatusCommunication
(2) normal
(3)interrupt indicates some errors occurred between Power System and agent
The status of battery modes,
(1) Unknown
(2) FloatCharging
(3) ShortTest
(4) BoostChargingForTest
(5) ManualTesting
(6) PlanTesting
PsStatusBatteryMode
(7) ACFailTesting
(8) ACFail
(9) ManualBoostCharging
(10) AutoBoostCharging
(11) CyclicBoostCharging
(12) MasterBoostCharging
(13) MasterBatteryTesting
SM series group Power system battery group
PsSMACNumber The number of SM AC module R
PsSMBATNumber The number of SM BAT module R
PsSMIONumber The number of SM IO module R
PsInput group Power system input group
PsInputLineAVoltage The AC line A voltage, stored as mV R
PsInputLineBVoltage The AC line B voltage, stored as mV R
PsInputLineCVoltage The AC line C voltage, stored as mV R
PsTemperature Group Power system temperature group
PsTemperature1 The first route temperature, stored as 0.001 Celsius degree R
PsTemperature2 The second route temperature, stored as 0.001 Celsius degree R
Alarm trap Group ACU+ alarm trap Group
alarmLastTrapNo The sequence number of last submitted alarm trap R
AlarmTrapTable Table holding information about the submitted alarm traps. alarmTrapEntry is the
R
(alarmTrapEntry) entry (conceptual row) in the alarmTrapTable
AlarmTrapNo The unique sequence number of this alarm trap R
Date and time when event occured (local time), including timezone if supported
AlarmTime R
by controller
The type of alarm change. One of
AlarmStatusChange (1) activated R
(2) deactivated
The severity of the alarm. One of
(1) warning - O1, lowest level of alarm severity
AlarmSeverity (2) minor - A3 R
(3) major - A2
(4) critical - A1, highest level of alarm severity
AlarmDescription Free-text description of alarm R
AlarmType Alarm type, i.e. an integer specifying the type of alarm
Traps Alarm traps info
The SNMP agent can send the active alarms to the specified NMSs and the user
can define the lowest severity of the NMS accepted alarms.

In Table 5-1, R means OID is read-only (GET), and R/W means OID can be read and modified (GET/SET).

5.11.3 Access ACU+ Through NMS

The following part introduces how to access ACU+ with HP OpenView as an example.

Apply Administrative Authority


In order to use NMS to manage the devices connected to ACU+, the administrative authority needs to be applied for
the NMS, that is, add the NMS information to the access list of SNMP agent.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 5 Use Of Monitoring Module M820B 87

Add NMS through Web browser


Refer to “4.4 System Menu” for the method of adding NMS.

5.11.4 ESR Configure

The EEM protocol is used for communication between the Main Computer and the ACU+. The Main Computer is the
computer superior to the ACU+ (the client of the ACU+). On this page, all parameters needed for communication with
a main EEM computer are to be set.
User information configuaration.
On this page, users, their authority and password are configured.
Time synchronization.
On this page, the system time and date are to be set.
Automatic time synchronization from time servers can also be configured.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
88 Chapter 6 Alarm Handling

Chapter 6 Alarm Handling

This chapter describes the handling of alarms, as well as the preventive maintenance of the system during system
daily operation.
The maintenance personnel must have adequate knowledge about the power system.

Note
1. The maintenance must be conducted under the guidance of related safety regulations.
2. Only the trained personnel with adequate knowledge about the power system can maintain the inner part of the subrack.

6.1 Handling Alarms


The monitoring module alarms are classified in four types: critical alarm, major alarm, observation and no alarm.
Critical alarm, major alarm: these two types of alarms have strong impacts on the system performance. Whenever
these alarms are generated, users are supposed to handle them immediately. The alarm indicators will be on and
audible indication will be given.
Observation: when this type of alarm is raised, the system maintains normal output for a while. If the alarm occurs
during watch time, it should be handled immediately. If the alarm occurs during non- watch- time, handle it during
watch time. The alarm indicators will be on when observation alarm occurs.
No alarm: if alarms are set as ‘no alarm’ by the users, when these alarms occur, no visible or audible indication will be
generated and the system works normally.
The handling methods of normal alarms are given in Table 6-1.
Table 6-1 System setting parameter description
No. Alarm Handling method
If the failure does not last long, the battery will power the load. If the cause is unknown or the failure lasts
1 Mains Failure too long, a diesel generator is needed. Before using the generator power to supply the power system, it
is suggested to run the generator five minutes to minimize the impact on the power system
Check if the AC over-voltage value is too low. If yes, change the value.
A mild over-voltage does not affect the system operation. However, the rectifier will stop operation when
2 AC Voltage High
the mains voltage is more than 530V. If the mains voltage is above the AC over-voltage value, the mains
grid should be improved
Check if the AC Under- voltage point is too high. If yes, change the value.
When the mains voltage is lower than 304V, the output power of the rectifiers will be derated. And if
3 AC Voltage Low
lower than 260V, the rectifiers will stop working. If the mains voltage is under the AC under-voltage value,
the mains grid should be improved
4 SPD failure Check the SPD condition. If the SPD is damaged, replace it
Check the DC over-vlotage value through the controller. If the set value is inappropriate, correct it.
Otherwise, find out the rectifier that has caused the alarm:
1. Ensure that the batteries can operate normally.
5 DC Volt High 2. Switch off the AC input of all rectifiers.
3. Power on the rectifiers one by one.
4. If the over-voltage protection is triggered when a certain rectifier is powered on, that rectifier is the
faulty one. Replace it
1. Check if the alarm is caused by mains failure, if yes, disconnect some loads to prolong the operation of
the whole system.
2. Check the DC under-voltage value set through the controller. If the set value is inappropriate, correct
it.
6 DC Volt Low
3. Check if any rectifier is inoperative, or has no output current. If yes, replace it.
4. Check if the total load current exceeds the total rectifier current during float charge. If yes, disconnect
some loads or add more rectifiers to make the total rectifier current bigger than 120% of the total load
current with one redundant rectifier
Load Fuse Alarm, Check if the corresponding MCB is switched off. If the MCB is open, find out the fault and remove it.
7
Batt Fuse Alarm Otherwise, the alarm circuit is faulty. Please contact Emerson

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Chapter 6 Alarm Handling 89

No. Alarm Handling method


1. Check if there is mains failure, and the battery voltage is lower than the value of ‘LVD2’.
8 LVD2
2. Check whether the battery is disconnected from the system manually
The rectifier with the fault indicator (red) on is faulty.
9 Rect Failure
Power off the rectifier, and then power it on after a while. If the alarm persists, replace the rectifier
Check if the mains voltage is above 530V or under 260V. If the mains voltage is under the AC
10 Rect Protect
under-voltage value or above the AC over-voltage value, the mains grid should be improved
Pull out the rectifier to check if the fan is obstructed. If yes, clean it and push the rectifier back. If the fan
11 Rect Fan Fails
is not obstructed or if the fault persists after cleaning, replace the fan
Check if the communication cable is connected properly between rectifier and controller. If yes, restart
12 Rect Not Respond
the rectifier. If the alarm persists, replace the rectifier
1. Check if the battery compartment temperature is too high. If yes, cool down the battery compartment.
13 Batt Over Temp
2. Check if there is battery internal fault. If yes, replace the faulty battery

6.2 Handling Rectifier Fault


The indicator description, fan and handling methods of all the rectifiers on the system are the same, take R48-1800A
and R48-3200 as an example.

Handling indicator fault


The symptoms of usual rectifier faults include: Run indicator (green) off, Protection indicator (yellow) on, Protection
indicator blink, Fault indicator (red) on and Fault indicator blink, as shown in Figure 6-1.

Run indicator
Protection indicator Run indicator
Fault indicator Protection indicator
R48-3200 Fault indicator
R48-1800

Figure 6-1 Rectifier indicator

The indicators are shown in Table 6-2.


Table 6-2 Indicator fault description
Monitoring module
Symptom Causes Handling method
alarms
Run indicator No input/output voltage Make sure there is input/output voltage
No alarm
off (green) Assistant power source of the rectifier fails Replace the recitifier
Run indicator The monitoing module performs operations
No alarm No actions need to be taken
blinks(green) upon the rectifier
Rect Protect AC input voltage abnormal Make sure the AC input voltage is normal
Fan blocked Remove the object that blocks the fan
Ventilation path blocked at the inlet or vent Remove the object at the inlet or vent
Rect Protect
Ambient temperature too high or the inlet too Decrease the ambient temperature or remove
close to a heat source the heat source
Protection Check whether the rectifier communication is
indicator on normal. If not, check whether the
(yellow) Load share Alarm Current sharing imbalance communication cable is in normal connection.
If the communication is normal while the
protection indicator is on, replace the rectifier
Power factor compensation internal under
Rect Protect Replace the rectifier
voltage or over voltage

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
90 Chapter 6 Alarm Handling

Monitoring module
Symptom Causes Handling method
alarms
Protection
Check whether the communication cable is in
indicator Rect Not Respond Rectifier communication interrupted
normal connection
blinks(yellow)
Reset the rectifier. If the protection is triggered
Rect HVSD Rectifier over-voltage
again, replace the rectifier
Two or more recitifiers have the same ID
Rect Failure Contact Emerson for maintenance
number
Fault indictor
Check whether the rectifier communication is
on (red)
Serious current sharing imbalance, normal. If not, check whether the
Rect Failure 501 series modle: current imbalance > ± 3%; communication cable is in normal connection.
701 series modle: current imbalance > ± 5% If the communication is normal while the
protection indicator is on, replace the rectifier
Fault indicator
Rect Fan Fails Fan fault Replace the fan
blinks (red)

Replacing rectifier fan


If the rectifier fan is faulty and does not work, it should be replaced. Take the R48-1800 rectifiers as an example, the
replacement procedures are as follows:
1. Use a cross screwdriver to remove the 3 screws from the fixing holes and pull out the front panel.
2. Unplug the power cable of the fan and remove the fan. Install a new fan.
3. Plug the fan power cable. Put the front panel back and fasten it with the 3 screws, as shown in Figure 6-2.

Fixing screw of the fan


Fan

Front panel Fixing screw


of the panel

.
Figure 6-2 Disassembling the front panel

Replacing rectifier
Except replacing the fan, it is recommended not to repair any other part of the module. When faulty, the module
should be replaced, not repaired. See the following procedures to replace the rectifier.
1. Take a new rectifier and check it for any damage from transport.
2. Loosen the fixing screw of the handle of the R48-1800A rectifier with a Phillips screwdriver. Pull out the faulty
rectifier from the rack by grabbing its handle.
Be careful with the rectifier just pulled out from the system, as it could be very hot due to long-term operation. Do not
let it slip away and get damaged.
3. By holding the rectifier handle, push the new rectifier into the slot just vacated and make sure the connection is
good. After a brief delay, the rectifier run indicator will turn on and the fan will start running.
4. Check whether the new rectifier works normally. You should make sure that:
1) The monitoring module recognizes the new rectifier.
2) The new rectifier shares current with other rectifiers.
3) When this new rectifier is pulled out, there is a corresponding alarm and the monitoring module displays the alarm.
If the new rectifier passes all the above tests, the replacement is a success.
5. Push the handle back into the front panel to fix the rectifier with the positioning pin. Fix the fixing screw of the
handle of the R48-1800 rectifier with a Phillips screwdriver.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 1 Technical And Engineering Data 91

Appendix 1 Technical And Engineering Data

Table 1 Technical data


Parameter
Parameter Description
category
Operating temperature -5°C ~ +40°C
Storage temperature -40°C ~ +70°C
Relative humidity 5%RH ~ 95%RH
Environmental
Altitude ≤ 2,000m (derating is necessary above 2,000m)
Polution level Level 2
Others No conductive dust or erosive gases. No possibility of explosion
NetSure 701 A41-S3/S5, NetSure 501 A41-S1/S2:L+N+
AC input system PE/220Vac.
Others: 3P + N + PE/ 380Vac
AC input type TN-C, TN-S, TN-C-S, TT
NetSure 701 A41:85 Vac~290Vac;
Input voltage range
NetSure 501 A41, NetSure 501 A91:85Vac~300Vac
AC input Input AC voltage frequency 45Hz ~ 65Hz
NetSure 701 A41-S1≤25A; NetSure 701 A41-S2/S4≤45A;
NetSure 701 A41-S3≤90A;NetSure 701 A41-S5≤90A;
Max input current
NetSure 501 A91-S1≤37A;NetSure 501 A41-S2≤50A;
NetSure 501 A41-S1≤50A
Power factor ≥ 0.99
Over-voltage level Level II
Standard output DC voltage -48Vdc
Rated output DC voltage -53.5Vdc
Output DC voltage -42.3Vdc ~ -57.6Vdc
NetSure 701 A41 ≤ 275A, load current ≤ 225A, battery charge
current ≤ 50A
NetSure 501 A41≤150A, load current≤ 120A, battery charge
Maximum output current
current ≤ 30A
DC output NetSure 501 A91≤275A, load current≤ 225A, battery charge
current ≤ 50A
Voltage set-point accuracy ≤ 1%
R48-1800A/R48-2000≥89%;
Efficiency R48-2000e/R48-3200e/R48-3500e≥94.5%;
R48-2900U≥90%; R48-4000e≥90%
Noise (peak-peak) ≤ 200mV (0 ~ 20MHz)
Weighted noise ≤ 2mV (300 ~ 3400Hz)
AC input over-voltage alarm point Default: 280 ± 5Vac, cofigurable through monitoring module
AC input over-voltage alarm recovery Default: 270 ± 5Vac, 10Vac lower than the AC input over-voltage
point alarm point
AC input under-voltage alarm point Default: 180 ± 5Vac, configurable through monitoring module
AC input under-voltage alarm recovery Default: 190 ± 5Vac, 10Vac higher than the AC input under-voltage
point alarm point
AC input alarm NetSure 501 A41, NetSure 501 A91: 305 ± 5Vac by default,
and protection cofigurable through monitoring module
AC input over-voltage protection point
NetSure 701 A41: 295 ± 5Vac by default, cofigurable through
monitoring module
NetSure 501 A41, NetSure 501 A91: 295 ± 5Vac by default, 10Vac
AC input over-voltage protection lower than the AC input over-voltage alarm point
recovery point NetSure 701 A41: 285 ± 5Vac by default, 10Vac lower than the AC
input over-voltage alarm point

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
92 Appendix 1 Technical And Engineering Data

Parameter
Parameter Description
category
AC input under-voltage protection point Default: 80 ± 5Vac, configurable through monitoring module
AC input alarm
AC input under-voltage protection Default: 95 ± 5Vac, 10Vac higher than the AC input under-voltage
and protection
recovery point alarm point
DC output over-voltage alarm point Default: -58.0 ± 0.2Vdc, configurable through monitoring module
DC output alarm Default: -57.5 ± 0.2Vdc, 0.5Vdc lower than the over-voltage alarm
DC output over-voltage recovery point
and protection point
DC output under-voltage alarm point Default: -45.0 ± 0.2Vdc, configurable through monitoring module
Default: -45.5 ± 0.2Vdc, 0.5Vdc higher than the under-voltage alarm
DC output under-voltage recovery point
point
DC output alarm
DC output over-voltage proteciton point Default: -59.0 ± 0.2Vdc, configurable through monitoring module
and protection
LLVD Default: -44.0 ± 0.2Vdc, configurable through monitoring module
BLVD Default: -43.2 ± 0.2Vdc, configurable through monitoring module
The rectifiers can work in parallel and share the current. The
Current sharing
unbalanceness is better than ± 5%
R48-1800A、R48-2000、R48-2000e:
176Vac input, The rectifier outputs max.power: 100%
85Vac input, The rectifier outputs max. power: 40%
80Vac input, The rectifier low pressure power off
R48-3200、R48-2900U、R48-3500e、R48-3000e:
176Vac input, The rectifier outputs 100% power
120Vac input, The rectifier outputs 50% power
Derate by input (at 45°C)
85Vac input, The rectifier outputs 18.75% power
80Vac input, The rectifier low pressure power off
R48-4000e:
207Vac input, The rectifier outputs 100% power
120Vac input, The rectifier outputs 2200W power
85Vac input, The rectifier outputs 1500W power
80Vac input, The rectifier low pressure power off
Output voltage can rise slowly upon rectifier start up. The rise time
Output delay
is configurable
Fan speed adjustable Rectifier fan speed can be set to half or full speed
Rectifier The rectifier provides over-voltage hardware and software
protection. The hardware protection point is 59.5V ± 0.5V, and it
requires manual resetting to restore operation. The software
protection point is between 56V and 59V (0.5V above output
voltage, 59V by default), and can be set through the monitoring
module
There are two software protection modes, which can be selected
through the software at the host:
1. Lock out at the first over-voltage
Once the output voltage reaches protection point, the rectifier will
Over-voltage protection shut off and hold that state. It requires manual resetting to restore
the operation
2. Lock out at the second over-voltage
When the output voltage reaches the software protection point, the
rectifier will shutdown, and restart automatically after 5 seconds. If
the over-voltage happens again within a set time (default: 5min.
Configurable through monitoring module), the rectifier will shut off
and hold that state. It requires manual resetting to restore the
operation
Manual resetting: Resetting can be done manually through the
monitoring module, or by removing the rectifier from system

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 1 Technical And Engineering Data 93

Parameter
Parameter Description
category

R48-1800A:
Temperature below 45°C, outputs full power
Temperature above 45°C, there will be linear deratin g, that is:
At 55°C, output power is 1,600W
At 65°C, output power is 1,500W
At 75°C, output power is 800W
At 80°C, output power is 0
R48-2000、R48-2000e:
Starts at -40°C; Temperature below 45°C, outputs fu ll power
Temperature above 45°C, there will be linear deratin g, that is:
At 55°C, output power is 1,750W
At 65°C, output power is 1,600W
At 70°C, output power is 800W
At 75°C, output power is 0
R48-3000e:
At the ambient temperature of:
Below 45°C, outputs full power: 3,000W
Above 45°C, there will be linear derating, that is:
At 55°C, output power ≥ 2,400W
At 60°C, output power ≥ 1,500W
At 65°C, output power: 0
R48-3200:
Starts at -40°C; Temperature below 45°C, outputs po wer is 3200W.
Rectifier Temperature derating Temperature above 45°C, there will be linear deratin g, that is:
At 65°C, output power is 2,320W
At 70°C, output power is 1,450W
At 75°C, output power is 0
R48-2900U:
Starts at -40°C; Temperature below 45°C, outputs po wer is 2900W.
Temperature above 45°C, there will be linear deratin g, that is:
At 55°C, output power is 2,320W
At 60°C, output power is 1,450W
At 65°C, output power is 0
R48-3500e:
Starts at -40°C; Temperature below 45°C, outputs po wer is 3500W.
Temperature above 45°C, there will be linear deratin g, that is:
At 50°C, output power is 3200W;
At 55°C, output power is 2900W;
At 65°C, output power is 2320W;
At 70°C, output power is 1450W.
At 75°C, output power is 0
R48-4000e:
Starts at -40°C; Temperature below 50°C, outputs po wer is 4000W.
Temperature above 45°C, there will be linear deratin g, that is:
At 55°C, output power is 3500W;
At 65°C, output power is 3000W;
At 75°C, output power is 2400W

Conducted emission
Class A EN55022
Radiated emission
Voltage fluctuation and flash Class A EN61000-3-11
Immunity to EFT Level 4 EN/IEC 61000-4-4
EMC
Immunity to ESD Level 3 EN/IEC 61000-4-2
Immunity to surges Level 4 EN/IEC 61000-4-5
Immunity to radiation Level 2 EN/IEC 61000-4-3
Immunity to conduction Level 2 EN/IEC 61000-4-6

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
94 Appendix 1 Technical And Engineering Data

Parameter
Parameter Description
category
The AC input side can withstand five times of simulated lightning
voltage of 5Kv at 10/700µs, for the positive and negative polarities
Lightning respectively. It can withstand five times of simulated lightning surge
protection At AC side current of 20Ka at 8/20µs, for the positive and negative polarities
features respectively. The test interval is not smaller than 1 minute. It can
also withstand one event of simulated lightning surge current of
40Ka at 8/20µs
Safety regulation IEC60950-1:2001
Acoustic noise ≤ 60db (A) (When the ambient temperature is lower than25℃)
At temperature of 15°C ~ 35°C and relative humidity n ot bigger than
90%RH, apply a test voltage of 500Vdc. The insulation resistances
Insulation resistance
between AC circuit and earth, DC circuit and earth, and AC and DC
circuits are all not less than 10MΩ
(Remove the SPD, monitoring module and rectifiers from the system
before the test.) AC loop to DC loop can withstand 50Hz.
Others
DC circuit to earth: 50Hz, 2,500Vac; or 3535Vdc;
AC to DC circuits: 50Hz, 1,000Vac; or 1414Vdc;
Insulation strength
Assistant circuit (not directly connected to the host circuit): 50Hz,
500Vac
For all the three tests above, there should be no breakdown or
flashover within 1min, with leakage current not bigger than 10Ma;
MTBF > 200,000hr
ROHS Compliant with R5 requirement
NetSure 501 A41-S1/S2: 483 × 360 × 223
Maximum dimensions NetSure 501 A91-S1: 483 × 360 × 445
of the subracks NetSure 701 A41-S1/S2/S3/S5: 483 × 360 × 267
NetSure 701 A41-S4: 483 × 360 × 400.5
Dimensions
Monitoring module
(mm)(W×D×H) 85 × 85 × 287
M501D/ M500D
R48-1800A, R48-2000, R48-2000e: 87.9× 85.3× 272
Rectifier R48-3000e, R48-3200, R48-2900U, R48-3500e: 132.3 × 88× 294
Mechanical
R48-4000e:132.3 × 88 × 294
Subrack (without
rectifiers and ≤ 25
monitoring module)
Weight (kg) Monitoring module
< 0.8
M501D/M500D
R48-1800A, R48-2000, R48-2000e ≤ 2.0
Rectifier
R48-3200, R48-2900U, R48-3200, R48-3500e, R48-4000e ≤ 3.5

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 2 Installation Instruction Of Battery Rack 95

Appendix 2 Installation Instruction Of Battery Rack

1. Installation Instruction Of Two-Layer And Four-Layer Battery Rack

Packing list

Accessory 1 Accessory 2 Accessory 3 Accessory 4 Accessory 5

Figure 1 Accessory

Table 2 Packing list of the battery rack


Battery rack
Two-layer battery rack Four-layer battery rack
Accessory
Accessory 1 2 4
Accessory 2 8 14
Accessory 3 2 4
Accessory 4 2 2
Accessory 5 0 2
Expansion bolt 4 pieces 4 pieces
Fastener 1 set 1 set

Installation procedures
1. Installation procedures of two-layer battery rack
1) Install accessory 1 and accessory 2 according to Figure 2 (a).
2) Install accessory 3 according to Figure 2 (b).

Accessory 1

Accessory 3

Accessory 2

(a) (b)

Figure 2 Installation procedure of accessory 1 ~ accessory 3

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
96 Appendix 2 Installation Instruction Of Battery Rack

3) Install accessory 2 and accessory 4 according to Figure 3.

Accessory 4
Accessory 2

Figure 3 Installation procedure of accessory 2 and accessory 4

2. Installation procedures of four-layer battery rack


1) Install accessory 1, accessory 2 and accessory 3 according to Figure 2 (a) and Figure 2 (b).
2) Install accessory 5 according to Figure 4 (a).
3) Install accessory 2 and accessory 4 according to Figure 4 (b).

Accessory 4
Accessory 2

(a) (b)

Figure 4 Installation procedure of accessory 2, accessory 4 and accessory 5

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 2 Installation Instruction Of Battery Rack 97

2. Installation Instruction Of Three-Layer Battery Rack

Packing list

Accessory 1 Accessory 2 Accessory 3 Accessory 4

Figure 5 Accessory

Table 3 Packing list of the battery rack


Accessory Accessory number
Accessory 1 2
Accessory 2 6
Accessory 3 3
Accessory 4 2
Expansion bolt 4 pieces
Fastener 1 set

Installation procedures
1. Install accessory 1 and accessory 2 according to Figure 6 (a).
2. Install accessory 3 according to Figure 6 (b).

Accessory 2

Accessory 1 Accessory 3

(a) (b)

Figure 6 Installation procedure of accessory 1 ~ accessory 3

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
98 Appendix 2 Installation Instruction Of Battery Rack

3. Install accessory 2 and accessory 4 according to Figure 7.

Accessory 2
Accessory 4

Figure 7 Installation procedure of accessory 2 and accessory 4

3. Fixing The Battery Rack

1. Fix the battery rack to the ground according to the installation dimensions shown in Figure 8. The fixing bolts are
accessories.

575

600 480

600
Figure 8 Installation dimensions (unit: mm)

2. Fix the subrack power system onto the top of the battery rack. Refer to 2.3 Mechanical Installation.

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 99

Appendix 3 Wiring Diagram

DU power unit Rear view


17
DU

0V

To MFU positive expansion busbar

W81+W82
7-29 8-QF18

1 8-QF17 1
2 2

Three-phase AC input

PL 1
B QFA

L1 L2 L3 N
TO MFU unit PL busbar 1 3 5 7

25-N/26-N/27-N/228-N/29-N
Controller motherboard switch 7
M221S Front view MFU door connected ground 2 4 6 8

21-N/22-N/23-N/24-N
9-BUS+-2 W80 W80 9-BUS+-1W80

22-L/25-L/28-L
23-L/26-L/29-L
21-L/24-L/27-L
W80 X7-2
8-NPL-QFD

X6-1 X5-1
13-J8-1

13-J8-3
13-J8-5
13-J8-2

8-PL-QFD
13-J7-1

W80 W80 W80


8-PL-1

11-2
11-1
W02
W01 W01W01
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 1
User interface board 1 13
Module subrack Rear view
24-CAN+
24-CAN-

W2453X1
13-J8-8

8-QFB1-1
8-QFB2-1
13-J8-7
13-J8-4

13-J7-2

8-PL-1

9-BUS+-1
13-J8-6

8-B--1
10-1
10-2

6
Shelf 1
TO MFU unit PL busbar To the positive busbar of the MFU
W2453X1

4- 4+ 2- 2+ DO4 DO2
3- 3+ 1- 1+ DO3 DO1
24 23 22 21
W80 W80 H4 H3 H2 H1
X3-2
W80 W80 W80 W80 W80 W01 W01 W01 W01
W80 L L L L

W02 W02 W02 W02


N N N N
X3-1
PE PE PE PE

J3
P W04 P W04 P W04 P W04 7-4 7-2
MFU DC power
8 12 W05
Rear top view

J4
wiring diagram
MFU
9
J6 1
2 3
1
2 3
1
2 3
1
2 3

5 4 5
6
4 5
6
4 5
6
4 5
6
BUS+
TO the user PE
0V 1 8 12
J8 J7
protective
earth
1 2 W80
2 1 7-35/7-47/7-49/7-50 W80
3 9-2 5-3 W07 2 X5-1/X6-1 W80
4 29
H9
28
H8
27
H7
26
H6
25
H5

L
W01 L
W01 L
W01 L
W01 L
W01
W80+W81+W82 To the positive Busbar N
W02 N
W02 N
W02 N
W02 N
W02
7-29 P
PE
W04 P
PE
W04 P
PE
W04 P
PE
W04 P
PE
W04
1 1 1 1
QFD16

QFD1
QFD3

QFD2

W80
2 2 2 2 1
2 3
1
2 3
1
2 3
1
2 3
1
2 3
7-28
7-30

4 5 4 5 4 5 4 5 4 5

PL 6 6 6 6 6

TO DU unit PL bar 12
KM2
W80 1 1
QFB1

W80
QFB2
7-39
7-41

7-31 PL
W80 10
7-46 1 RB 2 2
1 2
W05
15-J7 2 2 1
1 8-B-
7-22
7-20
7-44

To the Negative Busbar


W80 W80

Figure 9 NetSure 501 A91-S1 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 100

18
M34C3C1

W06
DCSPD

13-J3-1+
15

13-J3-1-
J2 J1 M2433X2

12-1 1 7-39
12-2 2
1
8-PL-1 2 7-41
3 J3 J1 J2 J4
J5 J6 J7
PE v+ v-

8-PL-2
5-2

9-2
W06 W06 W06
Controller motherboard switch 7
M221S Front view
9-BUS+-1 W80
W80 W80
X6-1 X5-1 W80 W80 W80 W80 W80 W80

9-BUS+-1
13-J8-1

13-J8-3
13-J8-5
13-J8-2

13-J7-1

18-J1-2
18-J1-1
8-PL-1
X7-2

11-2
11-1
User interface board 1 13
W2453X1

W2453X1

4- 4+ 2- 2+ DO4 DO2
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49

3- 3+ 1- 1+ DO3 DO1
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
Single-phase AC input(SPD)
24-CAN+
24-CAN-

User interface board 1

8-QFB2-2
8-QFB3-2
8-QFB4-2
8-QFB1-2

9-BUS+-1
8-PL-1
13-J8-8

10-1
10-2
13-J8-4

13-J8-7
13-J7-2
13-J8-6

3 2 1
W06 15-J4-1

J3
QFA2 SPD1 QFA
X10-2 W03
W80 W80 W06 15-J4-2 X10-1 W03
W80 12

3-4
1-4
X3-2
L N

J4
W80 W80 LO NO
W80 J6 1 3 N 1 3
W80
1 8 12
J8 J7 2 4 PE L
2 4

2-N
W03

1-2
W80 W03
3-2 2-N
W03
MFU DC power
8 W03 W03
wiring diagram MFU Rear top view Conneted earthing terminal

21-N/24-N
21-L/24-L

23-N
22-N
22-L
23-L
5 9
PE BUS+ W01 W02
TO the user protective 0V
earth
1 2
W06 15-J5 W06 15-J6 7-47/7-49/7-50 W80
2 3 9-2 Module subrack Rear view
5-3 W07 1 12-1 W84
2-PE W03 6 TO MFU unit PL busbar To the positive busbar of the MFU
To the positive Busbar Shelf 1

W80 W80 24 23 22 21

7-27 7-29 H4 H3 H2 H1

L
W01 L
W01 L
W01 L
W01
1 1 1 1 1 1 W02 W 02 W02 W02
QFD6

QFD5

QFD4

QFD3

QFD2

QFD1

11
N N N N
X3-1
PE PE PE PE
2 2 KM1
W80 2 2 2 2
P W04 P W04 P W04 P W04 7-4 7-2
W80
W05
7-45
7-43

PL NPL
2 3 2 3 2 3 2 3
1 1 1 1
W80
18-J2-3 2 1
4 5 4 5 4 5 4 5
7-26
7-24

6 6 6 6

7-31 NPL
7-46
W80 7-35 1 12 W84
KM2 W80
9-BUS+-1

W06 1 1
18-J2-1

W80
QFB1
QFB2
18-J2-2

15-J7 2
PL 10 2 2
RB
2 1

1 8-B-
2 1
7-22
7-20

To the Negative Busbar


W80

Figure 10 NetSure 501 A41-S1 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 101

W80

8-NPL-QFD
X12-2 Door connected ground

8-QFB1-1

8-PL-QFD
W80 W80
Controller motherboard switch
W80

11-1
11-2
7
M820B

51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99
52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100

12-1
12-2
8-QFB2-1
W80 W80 User interface board 1
9-BUS+-2 W80 9-BUS+-1 W80
W80 X9
X6-1 X5-1
W80

J6 J7 J8 J9
13-J2-1
13-J2-4
13-J2-3

8-PL-1
13
IB2

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 Single-phase AC input
24-CAN+
24-CAN-

J3 J4 J5
8-PL-1
13-J2-2

9-BUS+-1
8-B--1
10-1
10-2
1
QFA
W80 W80
X3-2
W80 W80 W80 J2 L N
W80 4 3 J11 J12 1 3
2 1
MFU DC power
8 W80
wiring diagram
MFU Rear top view 2 4
5 9
PE BUS+
0V
至用户保护地 1
2

21-N/24-N
21-L/24-L
2 1 7-35/7-47/7-49/7-50 W80
3 9-2 5-3 W07

22-L

23-N
23-L

22-N
2 X5-1/X6-1 W80
4 3 W01 W02

To the positive Busbar Module subrack


Rear top view
W82+W81+W80 W82+W81+W80
6
7-59 7-60 S helf 1
TO MFU unit PL busbar To the positive busbar of the MFU

1 1 1 1
QFD4

QFD3
QFD2
QFD1

24 23 22 21
1 1 1 1 11 H4 H3 H2 H1
QFD8

QFD7
QFD6
QFD5

KM1
2 2 2 2 W01 W01 W01 W01
2 2 2 2 W80 W80 L L L L

NPL
7-79
7-81

W02 W02 W02 W02


N N N N
X3-1
PL P
PE
W04 P
PE
W04 P
PE
W04 P
PE
W04 7-4 7-2
2 1 W80 W05
7-56
7-55

W80 7-31 NPL 1


2 3
1
2 3
1
2 3
1
2 3

4 5 4 5 4 5 4 5
W80 7-46 6 6 6 6

1 12
W80 KM2 W80 1 1
QFB2

QFB1

2
7-80

7-82

PL 10 2 2
RB
1 2
1 8-B-
2 1
7-22
7-20
7-44

To the Negative Busbar


W80 W80

Figure 11 NetSure 501 A41-S2 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 102

Three-phases AC input

1
QFA

L1 L2 L3 N
1 3 5 7

MFU Door connected ground


Front view
7
Controller motherboard switch
M221S 2 4 6 8

21-N/22-N/23-N
X7-2
9-BUS+-2 W80 W80 9-BUS+-1 W80
W80

21-L
22-L
23-L
X6-1 X5-1 W80
13-J8-1

W02
13-J8-3
13-J8-5
13-J8-2

13-J7-1
W80 W80 W80W80

8-NPL-QFD

8-PL-QFD
W01 W01 W01

12-2
12-1
11-2
11-1
8-PL-1
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
13
W2453X1
Module subrack
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 6 TO MFU unit PL busbar To the positive busbar of the MFU
Shelf 1
24-CAN+

4- 4+ 2- 2+ DO4 DO2
W2453X1
24-CAN-

8-QFB1-1

3- 3+ 1- 1+ DO3 DO1
13-J8-8

23 22 21
13-J8-7
13-J8-4

13-J7-2

8-PL-1
8-QFB2-1

9-BUS+-1
8-B--1
13-J8-6

10-1
10-2
H3 H2 H1

1 1 1
-48V
W80W80
X3-2 W80 W80 7-2 X3-1
W80 W80

J3
W80
W80 10 10 10
0V 7-4 W05
12 W04 W04 W04

J4
PE PE PE
J6 W02 W02 W02
N N N
MFU DC power 8 1 8 12 W01 W01 W01
wiring diagram
MFU Rear top view J8 J7
L L L

W80
5 9
PE BUS+
TO the user protective 0V
earth 1
2
2 1 7-35/7-47/7-49/7-50 W80
4 3 9-2 5-3 W07 2 X5-1/X6-1 W80
3
To the positive Busbar
W80+W81+W82 W80+W81+W82
7-29 7-27
11
1 1 1 1 1
QFD5

QFD4

QFD2

QFD1
QFD3

KM1
W80 W80
7-45
7-43

2 2 2 2 2
PL NPL W80
2 1
7-28
7-30

W80 7-31
W80
NPL
7-46
1
12
KM2 W80 1 1
QFB2

QFB1

W80
7-39
7-41

2
PL 10 2 2
RB
1 2

1 8-B-
2 1
7-22
7-20
7-44

To the Negative Busbar


W80 W80

Figure 12 NetSure 701 A41-S1 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 103

MFU Door connected ground


Controller motherboard switch
Front view
7
M221 S

9-BUS+-2 W80 W80 9-BUS+-1 W80


W80 X7-2
X6-1 X5-1

8-NPL-QFD
13-J8-1

13-J8-3
13-J8-5
13-J8-2

13-J7-1
W80

8-PL-QFD
W80 W80

8-PL-1

11-2
11-1
Three-phases AC input

1
QFA
User interface board 1
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 13
W2453X1
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 L1 L2 L3 N
1 3 5 7
24-CAN+
24-CAN-

W2453X1

4- 4+ 2- 2+ DO4 DO2
13-J8-8
13-J8-4
13-J8-6
13-J8-7
13-J7-2

8-QFB1-1

9-BUS+-1
8-QFB2-1
10-1

8-PL-1
10-2

8-B--1

3- 3+ 1- 1+ DO3 DO1
W80 W80 2 4 6 8

21-N/22-N/23-N/24-N
X3-2
W80 W80 W80 W80 W80

J4 J3

21-L/24/L
W80
12

22-L
23-L
J6
MFU DC power
wiring diagram 8 Rear top view 1 8 12 W01 W01W01 W02
MFU 5 9 J8 J7
PE BUS+ W80
TO the user protective 0V Module subrack
earth 1
2 6
Shelf 1
TO MFU unit PL busbar To the positive busbar of the MFU
2 1 7-35/7-47/7-49/7-50 W80
4 3 9-2 5-3 W07 24 23 22 21
H4 H3 H2 H1
2 X5-1/X6-1 W80 1 1 1 1
-48V
3
W80+W81+W82
7-29 7-2 X3-1
1 1 1 1 To the positive Busbar
QFD12

QFD2

QFD1
QFD3

10 10 10 10
0V 7-4 W05
2 2 2 2 W04 W04 W04 W04
PE PE PE PE
PL W02 W02 W02 W02
N N N N
W80 L W01 L W01 L W01 L W01
7-28
W80 7-31 7-30
W80 7-46
1 12
W80 KM2 W80 1 1
QFB2

QFB1
7-41

2
7-39

PL 10 2 2
RB
1 2

1 8-B-
2 1
7-22
7-20
7-44

To the Negative Busbar


W80 W80

Figure 13 NetSure 701 A41-S2 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 104

18
M34C3C1

J2 J1
12-1 1 7-39 W06
DCSPD

13-J3-1+
13-J3-1-
W84 12-2 1 15

8-PL-1
2
2 7-41 W84 M2433X2
3

J3 J1 J2 J4
J5 J6 J7
PE v+ v-

8-PL-2
5-2

9-2
W06 W06 W06
User interface board 1 13
W2453X1

W2453X1

4- 4+ 2- 2+ DO4 DO2
3- 3+ 1- 1+ DO3 DO1
Controller motherboard switch Door connected ground
7
M221S Front view

J4 J3
W06 15-J4-1
9-BUS+-2 W80 W80 9-BUS+-1 W80 W06 15-J4-2 Single-phase AC input
W80
X6-1 X5-1
X7-2
W84 W84 W80W80
12
13-J8-1

J6
13-J8-3
13-J8-5
13-J8-2

13-J7-1

8-NPL-QFD

18-J1-2
18-J1-1
8-PL-QFD

11-2
11-1
W80 3 2 1
QFA2 SPD1 QFA

8-PL-1
1 8 12 W03
X10-1 W03
J8 J7

3-4
1-4
LO NO L N
W80 1 3 N 1 3
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
PE
L
2 4 2 4
24-CAN+
24-CAN-

2-N
13-J8-8

8-PL-1
13-J8-7

8-QFB2-1

8-QFB1-1
13-J8-4
13-J8-6

9-BUS+-1
13-J7-2

W03

1-2
10-1
10-2

W03
5-4 3-2 2-N
X10-2 W03W03 W03
W80 W80 W80
X3-2

21-N/24-N
W80

21-L/24-L
W80 W80
W80

23-N
22-N
22-L
23-L
W01 W02
MFU DC power
8
wiring diagram
MFU Rear top view
Module subrack
5 9
BUS+ 6 TO MFU unit PL busbar To the positive busbar of the MFU
PE 0V
Shelf 1
TO the user protective
24 23 22 21
earth 1 H4 H3 H2 H1

2 1 1 1 1
-48V
15-J6 2 W06 15-J6 1 7-35/7-47/7-49/7-50
W06 W80
4 3 9-2 5-3 W07 2 X5-1/X6-1 W80 7-2 X3-1
2-PE W03 3
12-1
W84 To the positive Busbar 10 10 10 10
0V 7-4 W05
W80 W80 W04 W04 W04 W04
PE PE PE PE
7-29 7-27 W02 W02 W02 W02
N N N N
1 1 1 1 1 1 1 1
QFD12

QFD11
QFD10

QFD9

QFD8

QFD2

QFD1
QFD3

11 L W01 L W01 L W01 L W01


2 2 2 2 KM1 W80 2 2 2 2
W80
7-45
7-43

PL NPL
W80
W84 18-J2-3 2 1
7-28
7-30

W80 7-31
NPL
W80 7-46 W84
1 W84 12 W84
9-BUS+-3

W06 15-J7 KM2


18-J2-2

1 1
18-J2-1

QFB2

QFB1

2
PL 10 2 2
RB
1 2

1 8-B- 2 1
7-22
7-20

To the Negative Busbar W80

Figure 14 NetSure 701 A41-S3 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 105

DU 配电单元 后视图 17
DU
0V

至 MFU 正极扩展排

W81+W82
7-60

1 1 1 1 1 1

8-QF8

8-QF7

8-QF6

8-QF5

8-QF4

8-QF3
2 2 2 2 2 2

PL NPL

Controller motherboard switch7 W80


Front view MFU Door connected ground

8-NPL-QFD
M820B
X12

8-PL-QFD
8-QFB1-1
TO MFU unit PL busbar To the positive busbar of the MFU
W80 W80 W80

11-1
11-2
Three-phases AC input
51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95 97 99 1
QFA
52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100
L1 L2 L3 N

12-1
12-1
8-QFB2-1

User interface board 1 1 3 5 7


W80 W80
W80
9-BUS+-2 W80 9-BUS+-1 W80 2 4 6 8

J6 J7 J8 J9
X9
X4-2 X5-1 W80 13
13-J2-1
13-J2-4

21-L/24-L
8-PL-1
IB2
13-J2-3

21-N
22-N
23-N
24-N
22-L
23-L
W01 W01 W01 W02
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49

J3 J4 J5
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
24-CAN+
24-CAN-

9-BUS+-1
8-PL-1
13-J2-2

8-B--1
10-1
10-2

Module subrack
6
W80W80 J2 Shelf 1
TO MFU unit PL busbar To the positive busbar of the MFU
X3-2 W80W80
4 3 J11 J12 24 23 22 21
2 1 H4 H3 H2 H1
W80 1 1 1 1
W80 -48V
W80
MFU DC power 8 7-2 X3-1
wiring diagram MFU Rear top view
5 9
PE BUS+ 10 10 10 10
0V 7-4 W05
TO the user protective 0V W04 PE
W04
PE
W04 PE
W04
PE
earth
1 W02 W02 W02 W02
2 N N N N
2 1 7-35/7-47/7-49/7-50 W80 W01 L W01 W01 L W01
L
4 3 9-2 5-3 W07 2 X5-1/X6-1 W80
L

3
W80 W80
7-59 至模块正极排 7-60
1 1 1 1 1 1
QFD18

QFD11
QFD10
QFD9

QFD1
QFD2

11 至 DU单元 NPL排
KM1
2 2 2 2 2 2
W80 W80
7-79
7-81

PL NPL
W80
2 1
7-56
7-55

至 DU单元 PL 排

NPL

W80 7-31 W80


12
KM2 W80
7-46 1 1 1
QFB2

QFB1

W80
7-80

7-82

10 2 2
2 RB
1 2
PL
1 8-B-
2 1
7-22
7-20
7-44

至模块负极排
W80 W80

Figure 15 NetSure 701 A41-S4 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 3 Wiring Diagram 106

18
M34C3C1

J2 J1
12-1 1 7-39 DCSPD
W06

13-J3-1+
13-J3-1-
W84 12-2 1 15

8-PL-1
2
2 7-41 W84 M2433X2
3

J3 J1 J2 J4
J5 J6 J7
PE v+ v-

8-PL-2
9-2
5-2
W06 W06
W06
User interface board 1 13
W2453X1

4- 4+ 2- 2+ DO4 DO2
W2453X1

3- 3+ 1- 1+ DO3 DO1
Controller motherboard switch 7
M221S Front view 门接地

J4 J3
W06 15-J4-1
9-BUS+-2 W80 9-BUS+-1 W80 W06 15-J4-2
W80
X6-1 X5-1
W80 W84 W84 W80 W80
12 单相交流输入带防雷
J6
13-J8-1

13-J8-3

X7-2
13-J8-5
13-J8-2

13-J7-1

18-J1-2
18-J1-1
8-NPL-QFD

11-2
11-1
W80

8-PL-QFD
3 2 1

8-PL-1
1 8 12 QFA2
W03 SPD1 QFA

J8 J7 X10-1 W03

3-4
1-4
LO NO L N
W80 1 3 N 1 3
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
PE L
24-CAN+
24-CAN-

2 4 2 4
13-J8-8
13-J8-4

13-J8-7

8-PL-1
13-J7-2

9-BUS+-1
8-QFB2-1

8-QFB1-1
13-J8-6

2-N
10-1
10-2

1-2
W03 W03
X10-2 5-4 3-2 2-N
W80 W80 W03 W03 W03
W80
X3-2

21-N/24-N
W80

21-L/24-L
W80 W80

22-N
23-N
25-N
W80

22-L
25-L
23-L
MFU DC power W07 W01 W02W07
8
wiring diagram
MFU Rear top view
9 Module subrack
5
PE BUS+ 6 TO MFU unit PL busbar To the positive busbar of the MFU
TO the user protective 0V Shelf 1

earth
1 24
H4
23
H3
22
H2
21
H1 -48V 25
H5
2 W08
W06 15-J6 1 1 1 1 1

W06 15-J6 2 1 7-35/7-47/7-49/7-50 W80


4 3 9-2 5-3 W07 2 X5-1/X6-1 W80 7-2 X3-1
2-PEW03 3
To the positive Busbar
12-1
W84 10 10 10 10 0V W08 10 7-4 W05
W80 W80 W04 W04 W04 W04
PE PE PE W04
7-29 7-27 PE PE
W02 W02 W02 W02 W02
1 1 1 1 1 1 1 1 N N N N N
QFD10

QFD8

QFD7

QFD6

QFD2

QFD1
QFD9

QFD3

11 L W01 L W01 L W01 L W01 L W01


2 2 2 2 W80 KM1 W80 2 2 2 2
7-45
7-43

PL NPL
W80
W84 18-J2-3 2 1
7-28
7-30

W80 7-31 NPL


W80 7-46
1 W84
W84
9-BUS+-1

12
15-J7 W84
18-J2-1

KM2
18-J2-2

W06 1 1
QFB2

QFB1

2
10 2 2
PL
RB
1 2

1 B- 2 1
7-22
7-20

To the Negative Busbar


W80

Figure 16 NetSure 701 A41-S5 wiring diagram

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 107

Appendix 4 Shematic Diagram

User interface
PD1 board
W2453X1

User-defined ST1 MB
AC Output Temperature Sensor Controller QFD1
No M221S or
Class C SPD Lo ST2
QFA2 M222S
SPD1 Temperature Sensor NPL
Optional QFD6
H1 KMD1

LLVD Contactor
Mains Input QFD7
H2
QFA1
N PL
W34C3C1
QFD10
L
PD2
H3
PE

KMD2 BLVD Contactor


H4

RS1

H5 QFB1
Battery 1
QFB2
Battery 2 Positive Busbar
CAN

DC SPD
SPD2
M2433X2

AC Distribution Unit -48V DC Distribution Unit 1


0V

Figure 17 Schematic diagram of NetSure 501 A91

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 108

用户接口板
PD1
用户交流输出 W2453X1
User-defined
AC Output
ST1 MB
温度传感器
Temperature Sensor
监控单元 QFD1
No M221S or
C 级防雷器
Lo ST2
Class C SPD M222S
SPD1 QFA2 温度传感器 NPL 非重要负载
选配 Temperature Sensor
Optional QFD4
H1 KMD1

负载下电接触器
市电输入 LLVD Contactor
Mains Input QFD5
H2
QFA1 重要负载
N W34C3C1 PL
QFD6
L
PE H3

KMD2 电池下电接触器
BLVD Contactor
H4

RS1

CAN 电池组 1
QFB1
Battery 1
电池组 2 正排
QFB2 Positive Busbar
Battery 2

直流防雷
DC SPD
SPD2
M2433X2

交流配电单元
-48V
直流配电单元 1
AC Distribution Unit DC Distribution Unit 1
0V

Figure 18 Schematic diagram of NetSure 501 A41(1)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 109

User interface

PD1
board
M A4 C5U3 1

ST1 MB
Temperature Sensor Contoller QFD1
M820B
ST2
Tem perature Sensor NPL
Op tional
QFD4
H1 KMD1

LLVD Contactor
Mains Input QFD5
H2
QFA1 PL
N
QFD8
L
H3

PE
KMD2 BLVD Contactor
H4

RS1

CAN
QFB1 Battery 1

QFB2 Battery 2 Positive Busbar

AC Distribution Unit DC Distribution Unit 1

Figure 19 Schematic diagram of NetSure 501 A41(2)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 110

User interface
PD1 board
W2453X1

ST1 MB
Temperature Sensor
Controller
QFD1
M221S or
ST2
M222S
选配 NPL
Temperature Sensor
Optional QFD4
H1 KMD1

LLVD Contactor
Mains Input
H2
QFA1 QFD5
N PL
W
V H3
U

PE
KMD2
BLVD Contactor
CAN

RS1

QFB1
Battery 1
QFB2 Positive Busbar
Battery 2

AC Distribution Unit DC Distribution Unit 1

Figure 20 Schematic diagram of NetSure 701 A41(1)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 111

User interface

PD1 board
W2453X1

ST1 MB
Temperature Sensor Controller
M221S or
ST2
M222S
Temperature Sensor
Optional

H1

Mains Input QFD1


H2
QFA1
N PL
QFD12
W
V H3
U

PE
KMD2
H4 BLVD Contactor

RS1

CAN
QFB1
Battery 1
QFB2 Positive Busbar
Battery 2

AC Distribution Unit DC Distribution Unit 1

Figure 21 Schematic diagram of NetSure 701 A41(2)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 112

User interface
board
PD1
W2453X1
User-defined
AC Output
ST1 MB
Temperature Sensor Controller
QFD1
No M221S or
Class C SPD Lo ST2
QFA2 M222S
SPD1 Temperature Sensor NPL
Optional QFD8
H1 KMD1

LLVD Contactor
Mains Input QFD9
H2
QFA1
N PL
W34C3C1
QFD12
L
PD2
H3
PE

KMD2
BLVD Contactor
H4

RS1

CAN
QFB1
Battery 1
QFB2
Battery 2 Positive Busbar

DC SPD SPD2

M2433X2

AC Distribution Unit -48V DC Distribution Unit 1


0V

Figure 22 Schematic diagram of NetSure 701 A41(3)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 113

User interface
PD1 board
MA4C5U31

ST1 MB
Temperature Sensor Controller QFD11
QFD1
M820B
ST2
Temperature Sensor NPL NPL
Optional
QFD4 QFD14
H1 KMD1

LLVD Contactor
Mains Input QFD5
H2 QFD15
QFA1
N PL
PL
QFD10
W QFD18
V H3
U

PE
KMD2 BLVD Contactor
H4

RS1

CAN QFB1
Battery 1
QFB2 Positive Busbar Positive Busbar
Battery 2

AC Distribution Unit DC Distribution Unit 2


DC Distribution Unit 1

Figure 23 Schematic diagram of NetSure 701 A41(4)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 4 Shematic Diagram 114

User interface
PD1 board
W2453X1

User-defined ST1 MB
AC Output Temperature Sensor Controller QFD1
No M221S or
Class C SPD Lo ST2
QFA2 M222S
SPD1 Temperature Sensor NPL
Optional QFD6
H1 KMD1

LLVD Contactor
Mains Input QFD7
H2
QFA1
N PL
W34C3C1
QFD10
L
PD2
H3
PE

KMD2 BLVD Contactor


H4

RS1

H5 QFB1
Battery 1
QFB2
Battery 2 Positive Busbar
CAN

DC SPD
SPD2
M2433X2

AC Distribution Unit -48V DC Distribution Unit 1


0V

Figure 24 Schematic diagram of NetSure 701 A41(5)

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual
Appendix 5 Glossary 115

Appendix 5 Glossary

Abbreviation Full word


Amb.Temp Ambient Temperature
Batt Battery
BC Boost Charging
BLVD Battery Lower Voltage Disconnection
Cap Capacity
CommMode Communication Mode
CurrLimit Current Limit
CycBC Cyclic Boost Charging
Con Alarm Voice Control Alarm Voice
Hist Alarm Historical alarm
HVSD High Voltage Shutdown
InitParam Initialize Parameters
InitPWD Initialize Password
LLVD Load Low Voltage Disconnection
LVD Low Voltage Disconnection
MCB Miniature Circuit Breaker
Ph-A Phase A
PWD Password
Rect Rectifier
Shunt coeff Shunt Coefficient
SM Supervision module (monitoring module)
SPD Surge Protection Device
SW Version Software Version
Sys System
Temp Temperature
Temp Comp Temperature Compensation
Volt Voltage

NetSure 701 A41, NetSure 501 A41, NetSure 501 A91 Subrack Power system User Manual

You might also like