Professional Documents
Culture Documents
Abstract. Very fast electromagnetic transients (VFT) in air distance between the disconnector contacts, the contacts
insulated substations (AIS) and gas insulated substations (GIS) geometry, the pressure and characteristics of the SF6 gas
caused by switching operation of disconnectors are investigated. (GIS) as well as relative atmospheric conditions (AIS) at the
Results obtained from very extensive field tests and from digital moment of striking.
simulations as well as a comparison between field tests and
Every strike causes high-frequency currents tending to equalize
calculation results of VFT in AIS and GIS due to disconnector
switching are presented. Field tests of disconnector switching in 220 potentials at the contacts. When the current is interrupted, the
kV air insulated substations Grabovica and Kakanj as well as test voltages at the source side and the loading side will oscillate
circuit of 110 kV GIS section are performed. Digital simulation of independently. The source side will follow the power frequency
VFT for different models of power network are performed using while the loading side will remain at the trapped voltage. As
EMTP-ATP [1]. soon as the voltage between the disconnector contacts exceeds
the dielectric strength of the SF6 gas or the air, at that distance
Key words: electromagnetic compatibility (EMC), very fast between the contacts the restrike will occur, and so on.
transients (VFT), disconnector switching, air insulated substation Successive strikes occuring during the closing and opening
(AIS), gas insulated substation (GIS)
operations of the off-loaded busbar by the disconnector in AIS
are shown in Fig. 1 a and b, and in GIS are shown in Fig. 2 a and
I. INTRODUCTION b, respectively.
When the disconnector is closing, the first strike will occur at the
Switching operation in power stations and substations, high- maximum value of the source voltages. Its values can be positive
voltage faults and lightning cause high level of high frequency or negative. As the time passes a series of successive strikes will
overvoltages that can be coupled with low voltage secondary keep occuring at reduced amplitudes, until the contacts touch.
circuits and electronic equipment unless they are suitable The highest transient overvoltage therefore occurs during the
protected. The function of high-voltage disconnectors is to initial pre-arc, Fig 1 a and 2 a, respectively.
provide electrical isolation of one part of the switchgear. When the disconnector is opening, restrikes occur because of the
Disconnector's standards define that they are able to open or very small initial clearance between the disconnector contacts.
close a circuit if either a neglibile current (≤0.5 A) is switched At the transient beginning, the intervals between particular
or if no significant change occurs in the voltage between the strikes are of the order of a millisecond, while just before the last
disconnector contacts. These values of currents include the strike occures, the interval can reach about one half of cycle at
capacitive charging currents of high-voltage busbars, bushings, power frequency, Fig. 1 b and 2 b, respectively.
connectors, very short lenghts of cables and the current of
voltage transformers. Contacts of disconnector are moving
slowly during opening and closing operation. That causes
numerous strikes and restrikes between the contacts. When
contacts are closed, the capacitive charging current flowing
through the contacts ranges from 0.017⋅10-3 to 1.1⋅10-3 Aeff/m for
voltage levels 72.5-500 kV in AIS [2] and from 0.3 to 1 Aeff in
GIS [3], depending on the rated voltage and lenght of high-
voltage busbar which is being switched. Strikes and restrikes
occur as soon as the dielectric strength of the air (AIS) or SF6
gas under pressure (GIS) between the disconnector contacts is
exceeded by overvoltages. The overvoltage is defined by a)
Fig. 3 Very fast transient overvoltage at the load side during the AIS
disconnector closing [4]
a)
Fig. 4 Very fast transient overvoltage at the load side during the GIS
disconnector closing [3]
VT
100
[kV ]
50
-50
-100
-150
divider
Fig. 9. Waveshape of simulated overvoltage surge [7]