NOTES :
1. THE FOLLOWING INFORMATION IS OBTAINED FROM THE LINE SCHEDULE :
a. POLE LENGTH AND STRENGTH.
A b. SPECIAL FOUNDATION REQUIREMENTS. A

2550
2250

2700
1350
450
150

800
c. POLE EMBEDMENT DEPTH.

0 d. PHASE CONDUCTOR SIZE.


c c c c c c c e. VARIATIONS TO STANDARD CROSSARM REQUIREMENTS.
f. STAY REQUIREMENTS.
g. DEVIATION ANGLE.
h. ASSESSED EARTHING REQUIREMENTS.
2. THE MAXIMUM LINE DEVIATION ANGLE TO BE CONSTRUCTED ON THIS ARRANGEMENT IS TO BE DETERMINED BY THE LINE DESIGNER.
3. POLE STEPS ARE TO BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF NS126.
4. IN AREAS WHERE THE 11kV NETWORK CANNOT BE WORKED ON USING LIVE LINE TECHNIQUES, UNDERBUILT CIRCUITS SHALL BE INSTALLED
13 WITH A MINIMUM CLEARANCE OF 1200mm. IN AREAS WHERE THE 11kV NETWORK CAN BE WORKED ON USING LIVE LINE TECHNIQUES,
UNDERBUILT CIRCUITS SHALL BE INSTALLED WITH A MINIMUM CLEARANCE OF 2500mm.
12 5. THE LOAD AND DEVIATION ALLOWABLE ON THE EYEBOLT AND EYENUT ASSEMBLY IS TO BE DETERMINED FROM DRG : 520331.

B c 6. POLES SHALL BE DRILLED, SCARFED AND DRESSED ON SITE. DRILLING AND SCARFING TO BE TREATED WITH APPROVED PRESERVATIVES. B
10 10 12 13 15 7. ALL BOLTS PASSING THROUGH TIMBER ARE TO BE COATED WITH GRAPHITE GREASE.
8. A STEEL CROSSARM IS TO BE USED WHEN THE MAXIMUM LOAD OF A TIMBER CROSSARM IS EXCEEDED.
9. TO MAINTAIN THE INTEGRITY OF A COVERED SYSTEM , IT IS ESSENTIAL THAT ALL STRIPPED AND PUNCTURED INSULATION IS
c CONTAINED WITHIN THE APPROPRIATE INSULATING COVER.
c
4 10. CCT CONDUCTOR INSULATION SHALL ONLY BE REMOVED BY THE USE OF AN APPROVED CCT CONDUCTOR STRIPPING TOOL.
c
14
11 c
25 STEPS - POLE (SEE NOTE 3) 517698 H17720 A/R
c
8 9 16 24 LUG - COMPRESSION (TO SUIT CONDUCTOR) 514053 6
12 FUSE - ELEMENT 11kV DROPOUT (FOR USE WITH FUSE HOLDER ONLY)
c 23 3
(REFER TO TS4200)
17 18 LINK - ISOLATING, 12/24kV, OUTDOOR, SINGLE INSULATOR 58750 3
C 22 C
FUSEHOLDER - BASE & CARRIER, 12/24kV EXPULSION DROPOUT, 150MVA, 8kA H84350 3
21 WASHER - CONICAL, M16, STAINLESS STEEL 518082 146308 3
20 WASHER - SQUARE, 50x50x6mm, GALVANISED (18mm HOLE) 518081 H39257 3
19 BOLT & NUT - M16x140mm, HEX., GALVANISED 515466 H37506 3
18 COVER - STRAIN CLAMP 144543 6
24 CLAMP - CONDUCTOR STRAIN, FOR CCT180 176313 6

c 17 CLAMP - CONDUCTOR STRAIN, FOR CCT120 144527 6


0
CLAMP - CONDUCTOR STRAIN, FOR CCT80 144535 6
c

16 INSULATOR - STRAIN ROD 144550 6


200
c

DIRECT
15 LINK - SAG, 70kN (PLP PART No.CTSLEW-070-1) PURCHASE
6
14 BLOCK - GAIN, ALUMINIUM, 100mm 146274 1
23
CIRCUIT CONDUCTORS

c
MINIMUM DISTANCE

13 EYENUT - M20, GALVANISED (SEE NOTE 5) 513951 H38853 3


D D
TO UNDERBUILT
1200 OR 2500

(SEE NOTE 4)

12 WASHER - LIP, M24, GALVANISED 518081 176912 5


11 EYEBOLT - M20x200mm, GALVANISED (SEE NOTE 5) 513653 H37881 2
5 6 7 21 20 19 10 WASHER - CONICAL, M20, STAINLESS STEEL 518082 146316 3
3
22 2 9 WASHER - SQUARE, 75x75x6mm, GALVANISED (22mm HOLE) 518081 H39231 1
8 EYEBOLT - M20, GALVANISED (LENGTH TO SUIT POLE) (SEE NOTE 5) 513653 1
7 WASHER - CONICAL, M12, STAINLESS STEEL 518082 179601 1
1 c
6 WASHER - FLAT, M12, GALVANISED 518081 177982 1
5 BOLT & NUT - M12x180mm, HEX., GALVANISED 515466 46888 1
CROSSARM - 3000x150x100x5mm, RHS, GALVANISED (SEE NOTE 8) 514377 H23787 1
UNDERBUILT CIRCUIT
c

c 4
CROSSARM - 2700x150x100mm, TYPE C, HARDWOOD OR LAMINATED VENEER 514373 H23907 1
CONDUCTOR LOCATION
(SEE NOTE 8)

E 3 SCREW - COACH, M12x90mm, GALVANISED 50443 1 E


25 2 BRACE - CROSSARM, ANGLE, 920mm, GALVANISED 514381 H17283 1
1 POLE - TIMBER (AS REQUIRED) 513988 1
ALL DIMENSIONS IN MILLIMETRES UNLESS NOTED OTHERWISE. DO NOT SCALE. STOCK
ITEM DESCRIPTION DRG. No CODE QTY
DO NOT MANUALLY AMEND

SCALE 1:25
APP’D by: STEPHEN CONNOR
A M E N D M E N T S

NETWORK STANDARD
STANDARD CONSTRUCTION
STOCK CODE CHANGED
DWN: PATRICIA RIOS

DWN: PATRICIA RIOS

DESIGNED PHIL JONES


CAD DRAWING

04/09/2007

27/03/2008

APP’D by: GLENN FORD

11kV THROUGH TERMINATION


NOTE 4 AMENDED.
CHKED: PHIL JONES

CHKED: PHIL JONES

DRAWN PATRICIA RIOS


INITIAL ISSUE

CHECKED PHIL JONES CONSTRUCTION WITH


ON ITEM 22.

DESIGN APPROVED STEPHEN CONNOR


145 NEWCASTLE RD WALLSEND, NSW 2287
DROPOUT FUSES OR ISOLATING LINKS
DATE 05/12/06
F F
DATE:

DATE:

TEL: 4951 9388 FAX: 4951 9389


PRJTRK No. -
2-60CCT
A Business of PROJECT
Enerserve STD DRAWING No
175886 SHEET
01 AMD
2 SIZE
A3
1

2
0

EnergyAustralia NUMBER

1 2 3 4 5 6 7 8 '