NOTES :
1. THE FOLLOWING INFORMATION IS OBTAINED FROM THE LINE SCHEDULE :
a. POLE LENGTH AND STRENGTH.
A b. SPECIAL FOUNDATION REQUIREMENTS. A
2550
2250
2700
1350
450
150
800
c. POLE EMBEDMENT DEPTH.
B c 6. POLES SHALL BE DRILLED, SCARFED AND DRESSED ON SITE. DRILLING AND SCARFING TO BE TREATED WITH APPROVED PRESERVATIVES. B
10 10 12 13 15 7. ALL BOLTS PASSING THROUGH TIMBER ARE TO BE COATED WITH GRAPHITE GREASE.
8. A STEEL CROSSARM IS TO BE USED WHEN THE MAXIMUM LOAD OF A TIMBER CROSSARM IS EXCEEDED.
9. TO MAINTAIN THE INTEGRITY OF A COVERED SYSTEM , IT IS ESSENTIAL THAT ALL STRIPPED AND PUNCTURED INSULATION IS
c CONTAINED WITHIN THE APPROPRIATE INSULATING COVER.
c
4 10. CCT CONDUCTOR INSULATION SHALL ONLY BE REMOVED BY THE USE OF AN APPROVED CCT CONDUCTOR STRIPPING TOOL.
c
14
11 c
25 STEPS - POLE (SEE NOTE 3) 517698 H17720 A/R
c
8 9 16 24 LUG - COMPRESSION (TO SUIT CONDUCTOR) 514053 6
12 FUSE - ELEMENT 11kV DROPOUT (FOR USE WITH FUSE HOLDER ONLY)
c 23 3
(REFER TO TS4200)
17 18 LINK - ISOLATING, 12/24kV, OUTDOOR, SINGLE INSULATOR 58750 3
C 22 C
FUSEHOLDER - BASE & CARRIER, 12/24kV EXPULSION DROPOUT, 150MVA, 8kA H84350 3
21 WASHER - CONICAL, M16, STAINLESS STEEL 518082 146308 3
20 WASHER - SQUARE, 50x50x6mm, GALVANISED (18mm HOLE) 518081 H39257 3
19 BOLT & NUT - M16x140mm, HEX., GALVANISED 515466 H37506 3
18 COVER - STRAIN CLAMP 144543 6
24 CLAMP - CONDUCTOR STRAIN, FOR CCT180 176313 6
DIRECT
15 LINK - SAG, 70kN (PLP PART No.CTSLEW-070-1) PURCHASE
6
14 BLOCK - GAIN, ALUMINIUM, 100mm 146274 1
23
CIRCUIT CONDUCTORS
c
MINIMUM DISTANCE
(SEE NOTE 4)
c 4
CROSSARM - 2700x150x100mm, TYPE C, HARDWOOD OR LAMINATED VENEER 514373 H23907 1
CONDUCTOR LOCATION
(SEE NOTE 8)
SCALE 1:25
APP’D by: STEPHEN CONNOR
A M E N D M E N T S
NETWORK STANDARD
STANDARD CONSTRUCTION
STOCK CODE CHANGED
DWN: PATRICIA RIOS
04/09/2007
27/03/2008
DATE:
2
0
EnergyAustralia NUMBER
1 2 3 4 5 6 7 8 '