Air Conditioner Maintenance

Guidance
Air Conditioner Description

The DC series air conditioner is a cooling product developed


for cabinet which is supplied DC power. The internal cycle air
path absorbs the hot air from the upside, and discharges the
cold air from the downside of the air conditioner. The external
cycle air path absorbs the external cold air from the downside,
and discharges the hot air from the upside after heat exchange.
Technical Parameters
EC08 air conditioner
Input Power w 220V
Cooling Capacity @ L35/L35 w 800
Power consumption @ L35/L35 w 390
Input current @ L35/L35 A 2.02
Refrigerant R134a
Working temperature range ℃ -15~55
Noise level dB(A) 63
Dimensions
mm 750 430 195
(height*width*depth)
Protection from dust, water
IP55
and wind driven rain
Internal airflow CMH 135
Commonly Used Spare Parts

Commonly used spare parts


Name Model
Controller ENVICOOL EC03U17
Inlet fan ADDA AD1248HB-F91GP
Outlet fan AVC BN17569B48M
Compressor
Sensor ENVICOOL NTC0001
Membrane keyboards ENVICCOL EC03-008
Prepared tools

Phillips screwdriver:
Remove the panel screws
Temperature tester:
Test the temperature

Small screwdriver:
Inspect &
maintain control lines
Clamp Multi-meter:
Test electronic
control components,
test voltage and current.

Needle nose pliers:


Wiring, test electronic control

Oblique mouth clamp:


Cut & strip wire

Adjustable wrench:
Fasten, remove fan & motor
System introduce

Inlet fan

Main
controller

Outlet fan

Heater

Compressor
ec08 Menu List
LCD screen Inlet fan Check

STEP1:Observe LCD Input power


OFF OFF
screen and inlet fan Main controller
ON OFF Inlet fan

STEP2:Check active Refer to common alarm analysis


alarm and alarm log

Cooling

Compressor Outlet fan Current Others Check


Around0.3A Tp≈Tin Main controller
OFF OFF
STEP3:Selftest and Te≈Tout
test the system current OFF ON
Around0.6A Tp≈Tin Compressor controller
Te≈Tout

ON OFF ----- Te≥30℃ Outlet fan

Tin-Tp≤4℃ Refrigerant, compressor,


ON ON -----
filter, inlet fan, outlet fan
Above2.2 Refrigerant, compressor,
ON ON -------
filter, inlet fan, outlet fan
Common alarm analysis
Check or
Alarm Possible Cause
Maintenance

The AC failure Check AC alarm menu

High temperature(HT) Alarm Inlet is failure Repalce inlet fan

Wrong set point Check AC set point

Input power is overtop ac220v+15% Check input power


Over Voltage alarm
Controller is failure Replace controller

Input power is lower than 220-15% Check input power


Under Voltage alarm
Controller is failure Replace controller
The inlet /outlet /coil /discharge
Replace sensor
Sensor Fault alarm temperature sensor fault
AC controller is failure Replace controller
Common alarm analysis
Check or
Alarm Possible Cause
Maintenance
The outlet fan is failure Replace outlet fan
High Pressure(HP) Alarm
The filter screen is dirty Clean the filter screen

Compressor failure Replace air conditioner

Compressor failure alarm System have no refrigerant(R134a) Replace air conditioner

Inlet or coil temperature sensor fault Replace sensor

The inlet fan is failure Replace inlet fan


Frost alarm
System have no refrigerant Replace air conditioner
Fault Feedback Form
Fault Feedback Form
Date Model
Adress SN

Fault
Description

Alarm Menu
Active Alarm Alarm Log
Alarm1 Tp S
Alarm2 Te S
Alarm3 HP
Alarm4 Comp
Alarm5 Frost
Alarm6 DC OV
…… DC UV
…… …..
…..
Sensor Value
Tin1 Te
Tin2 Tp
Tout Cond
….. Vdc
Current Test

System Compressor
Inlet Fan Outlet Fan
What did you test and judgment?

Do you think the possible reasons?


Others