Professional Documents
Culture Documents
Abstract--This paper deals with the application of controlled breakdown strength under overvoltages with front time in the
switching technique for limitation of switching overvoltages range 50-500 µs, which is typical for SOVs. Therefore, all the
(SOVs) and transient currents on the 400 kV transmission line equipment designed for operating voltages above 300 kV
with capacitive voltage transformers installed at both ends.
should be tested under laboratory simulated switching surges
Switching off unloaded transmission line and line reclosing was
analysed by using EMTP-RV software. The simulation results [3].
show that the controlled switching significantly reduces SOVs, The most used techniques for reducing SOVs are the
current transients and energy stress of station surge arresters. installation of circuit breakers equipped with closing resistors,
controlled switching and application of surge arresters [4-6].
Keywords: controlled switching, EMTP-RV, switching In recent years, several large utilities have experienced
overvoltages, 400 kV transmission line. problems with the long term mechanical reliability of closing
resistor mechanisms (especially in older circuit breakers) with
I. INTRODUCTION adverse impact on the overall system reliability and have
+
420kVRMSLL /_0 -1ms| 10| 0
Uniform a 5000ms | 50000ms| 0
+
+
C5 -1ms| 10| 0 C4 BUS8 BUS11 BUS20 420kVRMSLL /_0
5000ms | 50000ms| 0
1uF 5.52nF 420kVRMSLL /_-120 AC1
+
?v
5.52nF C3
ZnO +
BUS17 420kVRMSLL /_120
ZnO +
660000 ?vi>e
672000 ?vi>e
ZnO1
Capacitance LINE DATA LINE DATA LINE DATA LINE DATA ZnO2
capacitive voltage model in: velesevac_tumbri_37_86_rv.pun model in:km_85_rv.pun model in:km_68_rv.pun
model in: km_39_rv.pun capacitive voltage
of 400 kV
transformer 4400 pF Surge arrester Surge arrester transformer 4400 pF
substation
current transformer 680 pF Ur=330 kV Ur=336 kV current transformer 680 pF
disconnector 200 pF model in: abb_330.pun 400 kV T RANSMISSION LINE model in: abb_336.pun disconnector 200 pF
ZnO
support insulators 2x120 pF Data function
ZnO support insulators 2x120 pF
Data function
abb_336.dat
TABLE II
NONLINEAR U-I CHARACTERISTICS OF SURGE ARRESTERS
Ur=330 kV Ur=336 kV
(beginning of (end of the
I (A)
the line) line)
U (kV)
100 593 604
500 627 639
1000 644 656
2000 667 679
Fig. 2. Conductor arrangement at tower and average heights above the ground 3000 684 696
1,8 X: 67
Y: 311
250
2%
1,6
Emax (kJ)
U
200
1,4 150
U U U 100
A B C
2,6
2,4
U U U
AB AC BC
2,2
0 30 60 90 120 150 180 210 240
l (km)
Fig. 4. U2% phase-to-phase SOV profiles along the transmission line length
(uncontrolled energization)
10
(ms)
8
t
4
0 50 100 150 200 250 300 350 400 450 500
Broj simulacije
Fig. 9. Closing time of a circuit breaker contacts for 500 switching operations
Emax (J)
1,2
2%
25
U
1,1
20
U U U
A B C
1
0 30 60 90 120 150 180 210 240
l (km) 15
Fig. 10. U2% phase-to-ground SOV profiles along the transmission line length
0 100 200 300 400 500
(controlled energization)
Broj simulacije
Fig. 14. Energy stress of station surge arresters at the end of transmission line
(controlled energization)
2,5
1,9
U U U
AB AC BC
1,8
0 30 60 90 120 150 180 210 240
l (km)
Fig. 11. U2% phase-to-phase SOV profiles along the transmission line length
(controlled energization)
U2% (p.u.)
2
-415.5 A -513.7 A -528.2 A
energization 1,8
1,6
IV. SINGLE-PHASE AUTORECLOSURE OF TRANSMISSION LINE 1,4
1,2 U U U
A. Uncontrolled single-phase autoreclosure A B C
1
In the case of the transmission line with a capacitive voltage 0 30 60 90
120 150 180 210 240
transformers connected at both ends, no leakage path exists for l (km)
the trapped charge. Fig. 16 shows voltages at substation 2 (end Fig. 18. U2% phase-to-ground SOV profiles along the transmission line length
(uncontrolled reclosing)
of transmission line) in case of uncontrolled reclosing in phase 3,8
A from the substation 1 (beginning of the line). After 3,6
switching off phase A at t=20 ms a trapped charge of positive
3,4
polarity remains on the line. Contact closing occurs at voltage
3,2
peak on the source side of the opposite polarity to the trapped
U2% (p.u.)
charge (t=350 ms). This represents the most severe case of 3 U U U
AB AC BC
uncontrolled autoreclosure. 2,8
Phase A Phase B Phase C 2,6
2,4
2,2
2
0 30 60 90
120 150 180 210 240
l (km)
Fig. 19. U2% phase-to-phase SOV profiles along the transmission line length
(uncontrolled reclosing)
1000 Faza A Faza B Faza C
800
(kJ)
600
Fig. 16. Voltages at the end of transmission line in case of uncontrolled
reclosing in phase A from the beginning of the line
max
400
E