Professional Documents
Culture Documents
These specifications were submitted for public comment and reviewed by the NETA
Standards Review Council.
NOTICE
ln no event shall the tnterNational Electrical Testing Association be liable to anyone for special,
collateral, incidental, or consequential damages in connection with or arising out of the use of these
materials.
This document is subjecl to periodic review, and users are cautioned to obtain the latest edition.
Comments and suggestions are invited from all users for consideration by the Association in connection with
such review. Any such suggestions will be fully reviewed by the Association after giving the commenter,
upon request, a reasonable opportuni$ to be heard.
This document should not be confused with federal, state, or municipal specifications or regulations,
insurance requirements, or nationalsafety codes. While the Association recommends reference to or use of
this document by government agencies and others, use of this document is purely voluntary and not binding.
The purpose of these specifications is to assure that alltested electrical equipment and
F systems supplied by either contractor or owner are operational and within applicable standards
and manufacturer's tolerances and that equipment and systems are installed in accordance with
I
I
I
t..
design specifications.
T-
I
The need for acceptance testing of electrical power systems is very clear to those with
I
I
extensive startup and/or operating experience. Shipping and installation damage, field and
factory wiring errors, manufacturing defects, and systems and comppnents not in accordance I
with drawings and specifications are some of the many problems that can be deteoted by
appropriate testing. When these defects are found before startup they can be corrected under
r--
warranty and without the safety hazards and possible equipment and consequential damages of I
I
loss of use/production that can occur if discovered after startup or energizing. ln addition, test
I
t_,
results obtained during acceptance testing are invaluable as base reference data for the
periodic testing that is an essential element of an effective maintenance program. I
i.._
the
It is the intent of this document to list a majority of the field tests available for assessing -.
suitability for service and reliability of the power distribution system. Certain tests have been I'
assigned an "optional" classification. The following considerations were used in determining thd- i'-'
use of the "optional" classification:
i-,
1. Did another test listed provide similar information? L.-
r-
r 2. How did the cost of the test compare to the cost of other tests providing similar i
) inrormarion?
I
3. How commonplace was the test procedure? ls it new technology?
I
i
While acknowledging the above, it is still necessary to make an informed judgment for each r'*:
li
particular system regarding how extensive the testing should be. The approach taken in these l,
specifications is to present a comprehensive series of tests that is appticable to most industrial
and larger commercial systems. The guidance of an experienced testing professional should be f-
t:
^'
sought when making decisions such as how extensive testing should be. ln smaller systems t_
some of the tests can be deleted. ln other cases, a number of the tests indicated as optional
''_
should be performed.
-l l
L
'
The Association encourages comment from users of this document. Please contact the 1
Alan D. Peterson
NETA Technical Chair (
L-
L
ATS - 1999 I
I
CONTENTS
7.3
7.4
7.5
1. Low-Vo1ta9e........... .......44
2. Medium-Voltage, Metal-Enclosed....... ......i......... ...........47
3. High- and Medium-Voltage, Open .................50
2. Oil Switches: Medium-Voltage ..............52
3. Vacuum Switches: Medium Voltage.... .................. 55
4. SFo Switches: Medium-Voltage - Reserved........... ............... 57
ir
lir
5. Cutouts - Reserved............. 57 l-
il
i
7.6 Circuit Breakers.
1. Low-Vo1tage........................... 58 - .
1. lnsulated Case/Molded Case 58 i ,
2. Power ............61 I
Ii
1;
i-l
iiii
l-
I
ATs - 1 999
{
t*
7.19 Surge Arresters .......... 158
1. Low-Voltage Surge Protection Devices...
2. Medium- and High-Voltage Surge Protection Devices ........ 160
7.20 Capacitors and Reac1ors.......................:... . 162
1. Capacitors ........... 162
f;
R
2. Capacitor Control Devices - Reserved............. ... 163
i. 3. Reactors (Shunt & Current Limiting) ...164
1. Dry-Type. .....164
2. Liquid-Fi11ed............ ..... 166
7.21 Outdoor Bus Structures......... ..... 170
7.22 Emergency Systems
1. Engine Generator ................172
"f;
ili 2. Uninterruptible Power Systems ...........174
3. Automatic Transfer Switches ....,.........1TT
7.23rebmetry/PilotWire/Scada.Reserved.........
7.24 Aulomatic Circuit Reclosers and Line Sectionalizers ........ ......... 1g0
1. Automatic Circuit Reclosers, OilA/acuum.......... . 180
2. Automatic Line Sectionalizers, Oi1........... ............ 193
7.25 Fiber-Optic Cables
7.26 Electrostatic/Electromagnetic Field Testing - Reserved........ ..... 1g6
7.27SpecialSystems-Reserved...........................
SYSTEM FUNCTION TESTS................ ............ 1BT
THERMOGRAPHIC SURVEY ........... 1BB
1l
Li
10. TABLES
10.1 systems..........
lnsulation Resistance Tests, ElectricarApparatus and ... 1g0 :_l
10.2 Switchgear Withstand Test Voltages.......... ....:........... .............191 i
10.3 Recommended Dissipation Factor/Power Factor Il
Reactors
of Liquid-Filled Transformers, Regulators, and ........1g2
10.4 Suggested Limits for New lnsulating Liquids l
Equipment
Test Limits for New lnsulating oir Received in New ...... 193
Test Limits for Silicone lnsulating Liquid in New Transioimers....................... 193
Typical Values for Less-Flammable Hydrocarbon lnsutating Liquid ................ 194
10.5 Transformer lnsulation-Resistance, Acceptance Test Voltage ano
Minimum Results.... .._..........r.. .1g2
10.6 Medium-Voltage Cables, Maximum Field Acceptance Test Voltages (kV, dc)........ 1g6
10.7 Molded-Case Circuit Breakers, lnverse Time Trip Test................:.......................... 197
10.8 lnstantaneous Trip Tolerances for Field Testing pf Circuit Breakers ....... 198
10.9 lnstrumentTransformerDielectricTests,Acceptance..............
10.10 Maximum Allowable Vibration Amplitude
10.11 Overpotential Test Voltages for Electrical Apparatus
Other than lnductive Equipment........ ......20
10.12 Bolt Torques for Bus Connections....
US standard, Heat-Treated steel - cadmium or Zinc plated ..........202
Silicon Bronze Fasteners, Torque (Foot pounds).. ....:..... 203
Aluminum Alloy Fasteners, Torque (Foot pounds) ......... 203
Stainless Steel Fasteners, Torque (Foot pounds).. .........2O4
10.13 Reserved ................ . ZOs
10.14 lnsulation Resistance Conversion Factors
for Conversion of Test Temperature to 20oC.... ....... 206
10.15 AC High-Potential Test Voltage for Automatic circuit Rectosers .............207
10.16 AC High-Potential Test Voltage for Automatic Line Sectionalizers. .........2O7
10.17 Metal Enclosed Bus Dielectric Withstand Test Voltages ......... 208
10.18 Thermographic survey, suggested Actions Based on Temperature Rise .............. 20g
) I
I
I
J
l
l
STANDARD SPECIFICATION FORM
I
Y l. GENERAL SGOPE, ACGEPTANCE TESTING SPECIFICATIONS
i.
1.1 This standard covers the suggested field tests and inspections that are available
T
iii to assess the suitability for initial energization of electricat power distribution
.iii
equipment and systems.
R
i:
1.2 The purpose of these specifications is to assure that all tested electrical
t:
equipment and systems are operational and within applicable standards and
'v, manufacturer's tolerances and that the equipment and systems are installed in
I.
i
1.3 The work specified in these specifications may involve hazardous voltages,
i materials, operations, and equipment. These specifications do not purport to
address all of the safety problems associated with their use. lt is the responsibility
i of the user to review all applicable regulatory limitations prior to the use of these
i specifications.
's
*
3 ts
*t
$J
I - --.---l--
F$
F(
!t
t:
ti,
ii 2. APPLICABLE REFERENCES
I
FB
ei
tt:
ti:
2.1 All inspections and field tests shall be in accordance with the latest edition of the
following codes, standards, and specifications except as provided otherwise
il herein.
ii 1. American Society for Testing and Materials - ASTM
I
r.*
li 2.
ii
r
American National Standards lnstitute - ANSI
I
i{S
ASTM D 92-90. Test Method for Flash and Fire Points by Clevetand Open
iii cup
i{
I
I.F ASTM D 445-BB. Test Method for Knematic Viscosity of Transparent and
$
Opaque Liquids
,,i
I ASTM D 664-95 Test Method for Acid Number of Petroleum products by
i P ote nti o m et ri c Titrati o n
il-
il. ASTM D 877-87. Test Method for Dierectric Breakdown voltage of
lnsulating Liquids using Disk Etectroaes
i
I
I
t. ASTM D 923-91. Iesf Method for Sampting Etectrical lnsutating Liquids
D 924-98 (1990). Test Method for A-c Loss chara cteristics and
Relative Permittivity (Dielectric Constant) of Etectrical tnsulating Liquids
^srM
ASTM D 971-91. Iesf Method for lnterfacial Tension of Oil against Water
by the Ring Method
ASTM D 974-95. Test Method for Acid and Base Number by Color-tndicator
ri
li
Titration
s
T,:
il
* ASTM D 1298-85 (199q. Test Method for Density, Relative Density
(pOe.ciftg
Qravity), or API Gravity of Crude Petroteum and Liquid petroleum
l',
I
E
ii
Praducts by Hydrometer Method
i:
E
ASTM D 1500-91. resf Method for ASTM cotorof petroleum products
;
{l
(ASTM Color Sca/e)
t,
t
6
I
:
ASTM D 1524-94 (1990). Test Method for visuat Examination of lJsed
I
:t:
Electrical Insulating oils of petroleum origin in the Fietd
g
I
ii
'J
c.
APPLICABLE REFERENCES (cont.)
::
ii; ANSI/IEEE std. 81.2-1991. IEEE Guide for Measurement of lmpedance
E.
and Safety Characteristics of Large, Extended or lnterconnected Grounding
l[ Sysfems (Paft 2)
1i
ANSI/IEEE std.95-1977 (R1991). IEEE Recommended practice for
l Insulation Testing of Large AC Rotating Machinery with High Direct Voltage
i;:.
"i
il
ANSI/IEEE std. 242-19s6 (R1991). IEEE Recommended practice for
lii
11l
Protection and Coardinatio'n of lndustrial and Commercial powerSysfems
I (Buff Book)
I
li IEEE 386-1995. IEEE standard for separable lnsulated connecfors
I
c
t,
I
I
ANSI/IEEE std. 4218-1929. IEEE standard for High-potentiat-Test
Requirements for Excitation sysfems for synchroiou" Machines
I
F
,g
I
I
!
t;
't
I
a
I
I
il
2. APPLICABLE REFERENCES (cont.)
i-l I
lt
ANSI/IEEE std- 446-1ggs. /EEE Recommended practice
a n d sta n d bv powe r svsfems
for Emergency
(orange Book)
fo r t n.d u st i a;, | ;;; ; ; b;;
e rci a t A p p t i catio n s
'stvta' ^plrttcauon
-l
I
.i
fo r Stati o na
LiJi_Acid (,RLA) Bafteries
ry Ap pl icatio n s I
i
6 ATS - 1999
,ffi
ilL)
ll
lr
ti,
3. QUALIFIGATIONS OF TESTING ORGANIZATION AND PERSONNEL
3.2 The testing organization shall utilize technicians who are regularly employed for
testing seruices.
3.3 Each on-site crew leader shall hold a current registered certification in electrical
testing applicable to each type of apparatus to be inspected or tested. The
certification in electrical testing shall be issued by an independent, nationally-
recognized, technician certification agency. The following entities shall qualify as
independent, nationally-recognized, technician certifi cation agencies :
4.1 The owne/s representative shall provide the testing organization with the
following:
4.2 The installing contractor or testing firm shall perform certain preliminary low-
voltage insulation-resistance, continuity, and/or rotation tests prior to and in
addition to tests specified herein.
5. GENERAL
i
I
-..l
5.1 Safety and precautions
tllil
E
3. Presence of external magnetic fields
li
=
.i
{ 4. Accuracy of the current transformer ratio in addition to the accuracy
t,
I of the secondary meter.
I
E
s
I
i:
$ 3. Selection of metering equipment shall be based on a knowledge of the
I
I
waveform of the variable being measured. Digital multimeters may be
I
.F
4. Field test metering used to check power system meter calibration must
I have an accuracy higher than that of the instrument being checked.
i
.t
: 5. Accuracy-of metering in test equipment shall be appropriate for the test
i
being performed but not in excess of two percent of the scale used.
I
:
6. Waveshape and frequency of test equipment output waveforms shalt be
i
appropriate for the test and tested equipment.
tt
:;
1. The testing firm shall have a calibration program which assures that all
:
R
r!
applicable test instruments are maintained within rated accuracy.
;i
2.
H
;
I
The accuracy shatl be directly traceable to the National lnstitute of
h
it Standards and Technology (NIST).
ti
g
il
3. lnstruments shall be calibrated in accordance with the following frequency
il
:!
schedule:
d
I
2. Laboratory instruments: 12 months
r
3. Leased specialty equipment: 12 months where accuracy is
guaranteed by lessor.
ATS - 1999
It
5. GENERAL (cont.)
t 7.
maintained for each test instrument.
be
1. Summary of project.
3. Description of test.
4. Test data.
)
2. Equipment identification. j
3. The testing firm shatl furnish a copy or copies of the complete report to the
owner as required in the acceptance contract.
)
tl
u
#
-ti
t,
2. The study input data shall include the utility company's short-circuit
single- and three-phase contribution, with the )0R ratio, the
resistance and reactance components of each branch impedance,
motor and generator contributions, base quantities selected, and all
ther applicable circuit parameters.
ATS - 1999
I
.i
4. Protective-DeviceCoordinationStudy I
I
\
)
2' The coordil.a-tio1 study shall include atl voltage classes of equipment r..]
i
from the utility's incoming line protective devi-ce down to and I
5. Study Report
)
d 6. POWER SYSTEM STUDIES (cont.)
il
6. lmplementation
I
u
The owner shall engage an independent testing organization for the
$ purpose of inspecting, setting, testing, and calibrating the protective relays,
1
circuit breakers, fuses, and other applicable devicesis recommended in
.5
the power-system study report.
[-
H.
'1
5' Veriff that fuse and/or circuit breaker sizes and types correspond
to
drawings and coordination study as wetl as to the'circuit breaker,s
add ress for m icroprocesso r-comm u n ication packages.
ATS - 1 99e
$t
11. Lubrication
16. Verify that filters are in place and/or vents are clear.
"Optional t"ffi.t
16 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
2. ElectricalTests
5. perform an overpotentiartest
on each bus section, each phase to
.l
ground with phases not under
test grounJ"d,;" accordance with
manufacturer's published data. lr m"anuract,il"r
nas no ]l--l
recommendation for this test, it shail
be in accoroance with rabre
10.2' The test vortage shatt be appried
for' one minute. Refer to
Section 7.1.3.4 before performing test. -"-
a-'1
/
;J
6. Perform insulation-resistance tests
at 1000 vorts dc on ail
wiring. For units with sorid-state .o,,ponunts, contror i I
recommendations. r "v' foilow,"nur"""irrlr,
'v"vy' rr ii
ATS - 1999 17 i
.ffi
llii ll,:
7 INSPECTION AND TEST PROCEDURES
i
2. Perform secondary wiring integrity test. Disconnect
t'-T transformer at secondary terminals and connect secondary
i:
s!
t; 3. Verify secondary voltages.
5
ii
13. Verify operation of switchgear/switchboard heaters.
i
I
ie
il
*Optional
rq
:1
I
g
18 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
puurished data.
lf manufacture/s data is not avaitaore, inveffit"
deviate from simirar bus by more than
;il
varues which I
I
50 percent of the rowest i
value. .)
ou"rpot"ntial tests
should not proceed until insutation-resistance
above minimum values.
revets are raised I
j
Fr
3
:.i 7. INSPECTION AND TEST PROCEDURES
'i
G
7.2 Transformers
i 1. Dry TYPe
:
:l
1. Air-Gooled, 600 Volt and Below - Small
E (167 kVA Single-Phase, 500 kVA Three-Phase, and Smaller)
l;
i1
'ii
,4
1. Visual and Mechanical lnspections
'a
1.
l1
etl
tri
Compare equipment nameplate data with drawings
i
and specifications.
la
,:l
i
ii
t 2. lnspect physical and mechanical condition.
I
i
,Y
4.
I
1- fesutri
- /-
'1 @/en'\9
*Optional ' F-€
I
20 ATS-1999
l
7.2 Transformers(cont.) I
1. Dry-Type (cont.)
1. Air-Cooled, 600 Volt and Below _ Small I
({67 kvA singre-phase, s00 kvA Three-phase,
and smailer)
(cont.)
I
2. ElectricalTests
I
I
1- Perform resistance measurements through ail borted
I
)
7. INSPECTION AND TEST PROCEDURES
3. Test Values
*Optional
22 ATS - 1999
r)
7. INSPECTION AND TEST PROCEDURES
I
7.2 Transformers(cont.)
i
i
600 Volt and Below - Large
--t
(Greater than 162 kvA single-phase and 500
kvA Three-phase) I
I
I
and specifications.
I
i
"Optional
ATS - 1999 23
$
I
T i:
7. INSPEGTION AND TEST PROGEDURES
y
7.2 Transformers(cont.)
&
i' 1. Dry Type (cont.)
t:
i"
2. Air-Gooledi All Above 600 Volt and
E
i. iS :"Xii : ?ili"XHiY;i3 Ifl i, ., n s e an d 50 o kvA r h ree - phase
)
&
n.
(cont.) " "
*
i"
L:
it
2. ElectricalTests
B
ii.!
1. Perform insulation-resistance testswinding-to-winding
$
''i:
and each winding-to-ground with test voltage in
accordance with Table 10.5.
l
!
I
t
2. Calculate polarization index.
-l
3. Perform resistance measurements through all bolted
I
l
connections with low-resistance ohmmeter, if
applicable, in accordance with Section7.2.1.2.1 (Visual
l and Mechanical inspection).
i
d
I
*7. Measure the resistance of each winding at each tap
i connection.
t,
E
B. Measure core insulation resistance at 500 volts dc if
core is insulated and if the core ground strap is
.:
i.
!r
i..
removable
!i
!
t;
tl
il
*9. Perform an overpotential test on all high- and low-
I
rrj
I voltage wind ings-to-g rou nd.
ti.
I
.Optional
24 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
E
*Optional
A
i
11
:'
-r
l. INSPECTION AND TEST PROCEDURES
E
7.2 Transformers(cont.)
's
!: 1. Dry Type (cont.)
2. Air-Gooled, All Above 600 Volt and
t'.
i,
"t
9. Typical excitation current test data pattern for a three-
i
.ll legged core transformer is two similar current readings
] and one lower current reading.
I
:J
:.
10. Core insulation resistance values should be
comparable to factory obtained results but not less than
'E
il
I
one megohm at 500 volts dc.
]i
l
i'
I
I
l;
t'
')
i
I
li
.t
$
il
\;
t.l
gts
26 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
7.2 Transformers(Cont.)
? 2. Liquid-Filled
1. Visual and Mechanical lnspection
6. Verify that cooling fans and pumps operate correcfly and that
fan and pump motors have corect overcurrent protbction, if
applicable.
)
.s
'*
x. 7. INSPECTION AND TEST PROCEDURES
i
:;
7.2 Transformers (cont.)
T
!
2. Liquid-Filled (cont.)
lii
t
i4
11. Perform specific inspections and mechanical tests as
I recommended by manufactu rer.
I
R
)'
12, Verify correct equipment grounding.
t"
;;
13. Verify the presence of transformer surge arresters.
R
I
&
2. ElectricalTests
R
published data.
{!
PI
E
: 7. Perfo rm powe r-facto r/d iss ipation-factor tests or hot collar
:. watts-loss tests on bushings in accordance with test
"q:
R
*8. Perform excitation-current tests in accordance with test
>i
,1
t"
N
9. Measure resistance of each high-voltage winding in each no-
T
! load tap-changer position. Measure resistance of each low-
voltage winding in each load tap-changer position, if
applicable.
*Optional
28 ATS-1999
7. INSPECTION AND TEST PROCEDURES
7.2 Transformers(cont.)
2. Liquid-Fiiled (cont.)
12.
T:f:.": g-sgqnte of insutating tiquid in accordance with
ASTM D-923. sampre shail bitested for tne
rorrowing:
1. Dielectricbreakdown vottage:
--.s ASTM D-g7T and/or
ASTM D-1816..
2. Acid neutralization number: ANSI/ASTM D-924.
13.
TgT:.u:_" sample of insulating liquid in accordance with
ASTM D3013 and perform dissolved g",
in
accordance with ANSyTEEE c57.104;r ASTM "n;fyrir-fOCnl
D-i612.
14. Perform tests on ail instrument transformers
in accordance
with Section 7.10.
s
7.2 Transformers(cont.)
1:
..::
:,ll
2. Liquid-Filled (cont.)
3. Test Vatues
e
:i:
il
1. Compare bolted connection resistance to values of similar
connections.
t.
i:'
Jr 2. Bolt-torque levels should be in accordance with Table 14..12
unless otherwise specified by manufacturer.
?
I
I 3. Microhm or millivolt drop values shall not exceed the high
levels of the normal range as indicated in the manufacturer's
h
I published data. lf manufacturer's data is not available,
investigate any values which deviate from similar connections
by more than 50 percent of the lowest value.
any bushing hot collar watts-loss results that exceed the test
equipment manufacturer's published data.
R
*Optional
30 ATS-1999
7. INSPEGTION AND TEST PROCEDURES
7.2 Transformers(cont.)
) 2. Liquid-Filled (cont.)
11. Consult manufacturer if core insulation is less than one
megohm at 500 volts dc.
)
t
!
a
i.
:.
,t
7. INSPECTION AND TEST PROGEDURES
3i
7.3 Gables
i
tt 1. Low-Voltage, Low-Energy - Reserued
F
ll:
ii
2. Low-Voltage, 600 Vott Maximum
B
1. Visual and Mechanical lnspection
.\-r
j:
.i
I
3. lnspect all bolted electrical connections for high resistance
using one of the following methods:
a Table 10.12.
s
g
Sl
&
3. Perform thermographic survey in accordance with
Section 9.
#
t
v
4. lnspect compression-applied connectors for correct cable
match and indentation.
&
ii;
ti
E
5. Verify cable color coding with applicable specifications and
the Nafion al Electrical Code.
I
f
d
E-
*Optional
32 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
2. ElectricalTests
3. Test Values
)
$
-9
1:
2. Verify tightness of accessible bolted electrical
I connections by calibrated torque-wrench method in
"'
accordance with manufacturer's published data or
s Table 10.12.
L
Jj
a
correctly terminated for operation of protective devices.
*Optional
34 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
t
12. When new cables are spliced into existing cables, the
i
I dc high-potentialtest shall be performed on the new
cable prior to splicing in accordance with Section 7.3.2.
After test results are approved for new cable and the
splice is completed, an insulation-resistance test and a
shield-continuity test shall be performed on the length
?
i
of new and existing cable including the splice. After a
i- satisfactory insulation-resistance test, a dc high-
potentialtest shall be performed on the cable utilizing a
s
:!'
t; test voltage acceptable to owner and not exceeding 60
h
a percent of factory test value.
$
I
*
a
s
i:l
v
n
*Optional
36 ATS-1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
7
.i:
7. INSPECTION AND TEST PROCEDURES
;,;
1. Compare cable data with drawings and specifications.
-h
ii
l 2. lnspect exposed sections of cables for physical damage.
i
3. lnspect all bolted electrical connections for high resistance
r)
(
using one of the following methods:
t
.} 1. Use of low-resistance ohmmeter in accordance with
I
: Section 7 .3.4.2 (Electrical Tests).
t
tl
2. Verify tightness of accessible bolted electrical
J connections by calibrated torque-wrench method in
accordance with manufacturer's published data or
il
Table 10.12.
;:
&
3. Perform thermographic survey in accordance with
il Section 9.
ji
4. lnspect compression-applied connectors for correct cable
r
I match and indention.
E
correctly terminated for operation of protective devices.
$
$
9. Visually inspect jacket and insulation condition.
b
2. ElectricalTests
*Optional
ATS- 1999 39
I
TEST PROCEDURES
7. INSPEGTION AND
7.3
r 'v cables (cont.) $ Ut,
i: High-Voltage (cont')
test voltage-does not exceed
7 - lnsure that the maximum
in'ANSI/IEEE
the limits for terminaioit tp"tified
specifications'
Standard 48 or manufacturer's
at least five equal
8. Apply a dc high-potential !"lin
test voltage is reached' No
incrementt''iiirHaxim.um cable'
increment "f"uf"I" the voltage rating 9f 11"
a
Record O" current at each step after
'il"ii "*""ed
with system
constant tt"Uifitition time consistent
charging current'
t-
l!
.itiJti.t"rv intrr"tlo*iesistance on test' a dc !i9h;" '
the cable utilizing, a
potentialtest sniiu'e p"iot*"0
and not exceeding 60
$ test voltage acceptable to owner
i.
percent oi factory test value'
ffi
*Optional
40 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
"Optional
tH -.--
T
l
i' PROCEDURES
'I . INSPECTION AND TEST
2 ["j"?:::::Til":ttlJ:fi3'oo,:il:ffi
and correct cclnnection in
3.lnspectforappropriatebracing'suspension'alignment'and
enclosure ground'
4.lnspectallboltedelectricalconnectionsforhighresistanceusingone
of the following methods:
l,Useoflow-resistance.ohmmeterinaccordancewithSection
7 .4 -2 (Electrical Tests)'
;
. !--r -^-h^^*iane hrr
2.Verifytightnessofaccessibleboltedelectricalconnectionsby
in accordance with
cafinr#iifi;;;;h method
puoritTo data or Table 1 o'12'
i *"nrt"ii'i!tt-
Q)
!:
,'i
f:
3.PerformthermographicsurveyinaccordancewithSection9.
;ical orientation in accordance
with manufacturer's
s
si 6u"b to'iniure adequate cooling'
'dt
6.Examineoutdoorbuswayforremovalof..weep-hole''plugs,if
of joint shield'
F
il
F]
applicable, uiO n" torrect installation
g
il
2. ElectricalTests
and
ft of each busway' pl-?t9+o-phase
1. Measure insulation resistance 10'1'
phase-to-ground *inute' in accordance with Table
t"i"t"
2.Performanoverpotentialtestoneachbusway,phase.to.groundwith
manufacturer's
phases not ;;;; tlst grouno"J, in "."ordante'with test'
no recommendation for this
published d;i;.lirunilt""turer has
witnlaoG ro.rz. w.hgre no dc test value is
it shalt u" in
"."oid"n." useO' The test voltage shall
shown in Table 10.17 ,". u"tu""Jft"tiUe
be aPPlied for one minute'
p
Ii
€
E
* *Optional
$
g
42 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
7.4 Metal-EnclosedBusways(cont.)
t 3' Perform contact-resistance test on each connection point
of
noninsulated busway. on insulated busway, *""rrr" resistance
assembled busway sections and compare values with - of
--
adjacent
phases.
3. Test Values
manufacturer's
3. Confirm correct application of
recommended lubricants'
and required area
4- Verify appropriate anchorage
clearances'
grounding'
5. Verify appropriate equipment
44 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
2. ElectricalTests
D 4 :""f,"j[#]*iilT#tT:f[:"j;ffi"jg?,a,, bo,ted
PROCEDURES
t. INSPECTION AND TEST
'1
! 7.5
r 'v Switches (cont') $'rr'
.!
:i
i: Air bwitches (cont').(cont')
1. Low-Voltage
t-
I
.s i:
3. Test Values
values of
.3
i 1. Compare bolted connection resistance to
similar connections'
:l
!; 2.Bolt-torquelevelsshouldbeinaccordancewithTable
ed by manufactu rer'
;i:
1 0. 1 ;;;'i;ss oir'erwise specifi
3|:
3.Microhmormillivoltdropvaluesshallnotexceedthe
as indicated in the
high levels of the no.t*tt range
#;;;i;rei! puurirn"o 0.i". lf manufacturer's data
va.lues which devlat9
is not available' inu"=iig"t" any
l
than 50 percent of
from similar connectionl- ny mot"
;
values which
5' lnvestigate any contact resistance
deviatefromadjacenfpobsorsimilarswitchesby C
more than 25 Percent'
that deviate from
s
a 6. lnvestigate fuse-resistance values
s
FJ oiner by more than 15 percent'
d
"..ft
b
g
$1
;!
E
R
;i
li -
*Optional
46 ATS-1999
7. INSPECTION AND TEST PROCEDURES
t with Section 9.
p
::
i
.nl. INSPEGTION AND TEST PROCEDURES
.ri 12.Verifycorrectphase-barriermaterialsandinstallation.
ii
i:
l3.Compareswitchbladeclearanceswithindustry
i: standards.
t
14.lnspectallindicatingandcontroldevicesforcorrect
oPeration.
2. ElectricalTests
pole'
"_! 1. Perform insulation-resistance tests on each
i: pfl""u-to-phase and phase-to-g rou nd with switch
Test
closed and across each open pole for one minute'
s JJtag";hall be in accordance with manufacturer's
'li published data orTable 10.1.
&
switch
!i 2. Perform an overpotentialtest on each pole with
poles
iil closed. Test eaih pole-to-ground with all other
,,
iest voitage snitl ue in accordance with
;;;;J
ii"nut"Arrer's published data or Table 10'2'
bolted
3. Perform resistance measurements through 4l
with low-resistance ohmmeter' if
(Visual
apfticaOte, in accordance with Section 7'5'1'2'1
"onn"ttions
and Mechanical lnsPection).
"Optional
48 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
)
5. Minimum insuration resistance shail
be in accordance
wit h m a n u fa ct u re r's p u b is h e
r d o t" o
r-r"tL*i"ti. r .
"
6' rnvestigate fuse resistance varues
that deviate from
each other by more than 1S percent.
ATS - 1 999
s
-4
----"-
lG
T,.
t
t'
1. Visual and Mechanical lnspection
data with drawings
+
.'
i,
1. Compare equipment nameplate
I and sPecifications'
with industry
3 4. Verify that grounding is in accordance
standards ind project specifications'
i:
i
,b
F
! 5.lnspectallboltedelectricalconnectionsforhigh
methods:
I
b
t"ti"i"n"" using one of the following
1- Use of low-resistance ohmmeter in accordance
i!
!l with Section 7.5.1.3'2 (Electrical Tests)'
3
;;ih;d il acc'ordance with manufacturer's
10' 12'
!
l Published data or Table
of motor
7. Verify correct operation and adjustment
s
interlocks, if
J"i"t"i ii;it-r;',t;h;; and melhanical
,Bl
a "applicable.
$
::l
& 8. Verify correct blade alignment, blade
p"l,"tflll:^,^.
a
i;;;i ini"ii'"pter operation' and mechanical
"t"
"top.,if aPPlicable'
operation,
"Optional
50 ATS - 1999
7. INSPEGTION AND TEST PROCEDURES
3. Test Values
*Optional
ATS- 1999 51
s'
$
4. Performallmechanicaloperationandcontactalignmenttests
fn'Ootn tne switch and its operating mechanism'
and contact'
5. Check each fuse holder for adequate support
*Optional
52 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
1. perform a contact
resistance test.
2. perform resistance
measurements through a[ borted
con nections with row-resistan ce
m metEri #
9rr
accordance with section z.i.i.1(Visuar fr-prcao te, in
and Mechanicar
lnspection).
lSffi f .3,'iTji.;';Hii'il"',[:i:X',?::::li:ffi:[,,H,n"
referenced standard.
l.CompareboltedconnectionresistancetoValuesofsimilar
connections'
2.Bolt-torquelevelsshouldbeinaccordancewithTablelo.l2
unless otherwise specified by manufacturer'
3.Microhmormillivoltdropvaluessha.llnotexceedthehigh
in the manufacturer's
levels of the normar r"ni" "r indic.atgd.
data is not available,
brUfirn"O data. lf manuiacturer's similar connections
inu.r-tig"i" any v"tu"s *ni"n deviate from
the lowest value'
UV *oL than 50 percent of
4.lnsulatingliquidtestresultsshallbeinaccordancewithTable
10.4.
5.Controlwiringinsulationresistanceshouldbeaminimumof
two megohms'
C
"Optional
s4 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
2. lnspectphysicalandmechanicalcondition.
ATS - 1 999
.:s
.F
Ig
INSPECTION AND TEST PROCEDURES
2. ElectricalTests
T
t"
*
1. perform resistance measurements through allbolted electrical
connections with a low-resistance ohmmeter, if applicable'
?
:i,
see section 7.5.3.1 (Visual and Mechanical lnspection).
E
T
2. Perform a contact-resistance test'
i
*Optional
56 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
I
ij
9. INSPECTION AND TEST PROCEDURES
ii
.i 1. Perform a contact-resistance test'
at 1000 volts dc
2.
L' Perform an insulation-resistance test
with
ito* por"-t*poi" ano from each pole-to-ground
of each
breaker closed and across open contacts
Phase
*Optional
58 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
:,]
7.6 Gircuit Breakers (cont.)
1. Low-Voltage (cont.)
a
1. lnsulated Case/Molded Gase (cont')
i
t 3. Test Values
1$
t
1. compare botted connection resistance to values of
.&
similar connections.
s
t
2. Bolt-torque levels should be in accordance with Table
1
:id lo.l2unlessotherwisespecifiedbymanufacturer
'16
{j
t"
r
3. Microhm or millivolt drop values shall not exceed the
highlevelsofthenormalrangeasindicatedinthe
manufacturecs published data. lf manufacture/s data
1l
is not available, investigate any values which deviate
from similar connections by more than 50 percent of
the lowest value.
s{
!l
il
I
E
*Optional
60 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
4. lnspect.anchorage.,alignment,.andgrounding.lnspect
arc chutes. rnspect moving and statLnary
contacts for
condition, w€ar, and alignment.
"Optional
ATS-1999 61
PROCEDURES
it. INSPECTION AND TEST
*I
a
li
'1
7.6 Gircuit Breakers (cont') . .
1. Low-Voltage (cont')
2. Power (cont')
$
i:,
2. ElectricalTests
v'
3.Performaninsulation-resistancetestatl000voltsdc
ito* pofot*pote anO from each pole-to-ground with
of each
breaker closed and across open contacts
3
l:
t phase.
ii(
*4.Performinsulation-resistancetestsatl000voltsdcon
]i
allcontrol*iiing Do not perform the test on wiring
connected to sotiO state components'
g
in accordance
"!
{:
* 5. Make adjustments for the final settings
with the coordination study supplied by owner' C
i primary current
i)
6. Determine minimum pickup current by
injection.
current injection.
B
I
s
g. Determine ground-fault pickup and delay
by primary
current iniection'
t
by primary
10. Determine instantaneous pickup value
i\.
I
6
current injection'
t
F
5
v
*11. Verify the calibration of all functions of the trip
unit by
means of secondary injection'
"Optional
62 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
ATS - 1999
7. INSPECTION AND TEST PROCEDURES
B.lnspectallboltedelectricalconnectionsforhigh
resistance using one of the following methods:
l.Useoflow-resistanceohmmeterinaccordance
with Secti on 7 -6.2.1.2 (Electrical Tests)'
2.Verifytightnessofaccessibleboltedelectrical
connections by calibrated torque-wrench .
method in accordance with manufacturer's
published data orTable 10.12'
*Optional
64 ATS-1999
7. INSPECTION AND TEST PROCEDURES
2. ElectricalTests
3. Test Values
*Optional
66 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
I
ATS - 1 999
PROCEDURES
7. INSPECTION AND TEST
'
comply with Table
$
5. lnsulating-liquid test results should G
10.4.
B
I
should be in
J
6. Circuit breaker insulation resistance
:
accordance with Table 10'1'
i
should be a
7. Controlwiring insulation resistance
minimum of two megohms'
resu lts and tank
Dissipatio n-facto r/powe r-factor test
.i
B.
-t ilJ; fi;;* shall bJcompared to manufacturer's
l
p,iurisGo oata. tn tn" of.manufacturer's
I "'bt"n"" shall be made to
[tniittt"O data, the comparison
fr
q
similar breakers.
k
#
capacitance test
9. Dissipatio n-f actor/power-facto r and
ft otrii":inould be within ten percent of nameplate
fi!n
g rating for bushings.
test
$ 10. The insulation shall withstand the overpotential
w voltage aPPlied.
coils shall conform to
F
s: 11. Minimum pickup for trip and close
E manutacture/s Publish"d
.
m
*'l
*Optional
5
70 ATS-1999
'sJelpaJq Jeltulls ol apeu.I aq
lleqs uosueduoc
aql Elep porlstlqnd s,JoJnlceJnuer! Jo acussqe
aql ul .Elep peqsrlqnd s,JaJnlceJnueu ol paredtuoc
oq lp q s sll n seJ lsal JolceJ-:eanod7.ro1ce;-uonedrssrq '6
'palldde ebelon
;enuqodrano eql puBlsr{lrl lleqs.raionr"lr; iq1 'o
t"16T
1o e'e1 da u eu a Lrl r;it"r:J; #lJ#l,:;"?:
r'tr}lm ecuepJocoe ut aq lleLls luatuace;dsrp '9
1ce1uo3 {
'L'0t elqBl
qlt^^ acuepJocce
u! oq plnoqs acuelstseJ uollelnsut JaIeeJq 'v
llncrlc
ro son e^ or acu
I Blsr sar u or lca; ;:15111; :?#JlH5 .L
senlBn lsel .t
('1uoc) runncel .t
('1uoc) a6e1ol-urnlpary .Z
0
llncrl3
(1uoc) sraleorg g.L
'pasols lalPsrq
aql ql!/v\ eseqd qceo pue uedo laleaJq eq1 t111m elod
qcBa uo slsol Jolcel-lo/v\od7.to1ce;-uoqedtsslp tulo$ad'6*
'9
-e1od'a1od-o1-a;od s1sa1 ocuelslsol-uollelnsul ullo#ad
l:)
$
t.
'ocl^ep
e4pelord qcea Jo uolleledo [q Jaleelq ynclp dp1 'v ri
'sl!oc
asolc pue du1 uo slsal e6e1on dnpld unullultu I'ulolad 'Z*
:'i
7
ii
i,
*-
ff:
Tt
i'l INSPECTION AND TEST PROCEDURES
"t
I
.-g
i
*-
t
!,
*
!1
tj:
b
(
t
a
"Optional
74 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
*Optional
k
i: 1. Use of low-resistance ohmmeter in accordance
with Secti on 7 .6.2.4.2 (Electrical Tests).
c
i.
iil 2. Verify tightness of accessible bolted electrical
connections by calibrated torque-wrench
E
method in accordance with manufacturer's
t
jj published data or Table 10.12.
a
€
"Optional
76 ATS-1999
7. INSPECTION AND TEST PROCEDURES
1. perform a contact
resistance test.
3. Perform insulation_resistance
tests pole{o_pole, pole_
to-ground, and across open poles
minimum. I -" rvrvv at 2500 volts
*4.
Perform insuration-resista nce tests
o n_ at contror wiring
at 1000 volts dc. For units;ith
,"lid-state components,
vv'|,,p',
follow ma n ufactu r"r'r ru.omiilro"ii"rr.v
"5. t*. g iss ipatio n -facto r/powe
l" Tgbushings.
and r- - -r v'r-fa
's cto r tests o n b reake r
*6.
ferfolm overpotentialtest in accordance
'vv with
rv'r'l
manufacturer,s instructions.
*7.
minimum pick-up votrage test
:":i::* on trip and crose i I
8. Verifytrip,close,trip-free,andantipumpfunctions.
o Trip circuit breaker by operation
of each
'qvrr protective
Pr\,(suLlve
dgViCg.
ATS- 1999 77
t
;
b
3. Test Values.
l.Compareboltedconnectionresistancetovaluesof
t'! similar connections'
rF
.ii 2.Bolt-torquelevelsshouldbeinaccordancewithTable
* t o.tiuntess otherwise specified by manufacturer.
the
3. Microhm or millivolt drop values shall not exceed
indicated in the
f ighl"u"f. of the normal range as
minutacturer's published daia. lf manufacturer's data
deviate
i. noiavailable,'investigate any values which
percent of
i;;;;i*ilai "onne"tionls
ny more than 50
the towest value.
H
:l:.
'i:
4. Compare time-travel data with manufacturer's
published data.
I
l:i
ti
5. Controlwiring insulation resistance should be a
minimum of two megohms. @r
T
be in
6. Circuit breaker insulation resistance should
accordance with Table 10'1'
sh all be
7. Dissipatio n-facto r/p owe r-factor test resu lts
compared to manufacturer's published data' ln'the
anience of manufacturer's published data' the
comp"titon shall be made to similar breakers'
-t
test
Dissipation-factor/power-factor and capacitance
!
li B.
iesutis should be within ten percent of nameplate
R
:r
rating for bushings.
,u
test
9. The insulation shall withstand the overpotential
voltage aPPlied.
conform to
10. Minimum pickup for trip and close coils shall
manufacturer's Published data'
*Optional
78 ATS-1999
7. INSPECTION AND TEST PROCEDURES
3. Slow-close
fre.ak_er
and check for binding,
friction, contact alig n m ent, pen etration, a-nd
overtravel. Check that all phares make
contact
stmuttaneously.
)
$
t
i7- INSPECTION AND TEST PROCEDURES
l
t3 1. Use of low-resistance ohmmeter in accordance
with Section 7.6.3.1.2 (Electrical Tests)'
,E
e
t;l
*.
2.Verifytightnessofaccessibleboltedelectrical
connections by calibrated torque-wrench
'b
ElectricalTests
2.Removeasampleofinsulatingliquidinaccordance
with ASTM D-923. Sample shall hre tested for the
i
$_ following:
/:,
1. Dielectric breakdown voltage: ASTM D-877
u
$
I
*4. lnterfacialtension: ANSI/ASTM D-971 or
2
ANSI/ASTM D-2285
*Optional
80 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
.l?
7.6 Circuit Breakers (cont.)
3. High Voltage (cont.)
i.
1. Oil (cont.)
::
jil
3. Microhmormillivoltdropvaluesshallnotexceedthe
iiighl"u"rt of the normal range as indicated in the
!:,
t
+
minutacturer's published data. lf manufacture/s data
E
ir not available, investigate any values which deviate
from similar connectionls ny more than 50 percent of
il',
5. lnsulatingliquidtestresultsshouldbeinaccordance
!i
with Table 10.4.
i
.i:
R
))
;:
d
t
h
!1
:)
?
g
B
*Optional
I
j
5
82 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
ATS - 1 999
;1:-:if;r
?
A lnsulatingliquidtestresultsshouldbeinaccordance
with Table 10.4.
lfl
.$
j,t
puor.l'r'"odata.lntheabsenceofmanufacturer's
shall be made to
brUiitn"O data, the comparison
similar breakers.
test
9. Dissi patio n-factor/powe r-factor and capacitance
iesutis should be within ten percent of nameplate
rating for bushings.
a
Ilt
s
10. Theinsulationshallwithstandtheoverpotentialtest
voltage aPPlied.
conform to
li
6 11. Minimum pickup for trip and close coils shall
manufacturer's Published data'
ft
ei
;j
t
5
!1
5
I
a
H
*Optional
3
E
82 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
,
7. Inspect hydraulic systenr in accordance with
manufacturer's published data.
T {--t
r-
7. INSPECTION AND TEST PROCEDURES
2.Verifytightnessofaccessibleboltedelectrical
con nections by calibrated torque-wrench
method in accordance with manufacturer's
Published data or Table 10'12'
"Optional
84 ATS-1999
7. INSPECTION AND TEST PROCEDURES
1. perform a contact
resistance test.
2' perform resistance
measurements through a, borted
connections with tow_resistance
ohmmetEr, if
appricabre, in accordance
*i*,-s"rti"r'i.E.g.z.
and Mechanical lnspection). - --,.y.. .\
, 1 (visuar
3' performinsuration-resistancetestspore-to-pore,pore_
to-ground, and across open poles
ai is-,d60 votts
minimum. ,
"Optional
86 ATS-1999
7. INSPECTION AND TEST PROCEDURES
l.Useoflow-resistanceohmmeterinaccordance
withSection7.6.4.1.2(ElectricalTests).
2.Verifytightnessofaccessibleboltedelectrical
connections by calibrated torque-wrench
method in accbrdance with manufacturer's
Published data or Table 10'12'
14.Recordas-foundandasleftcounteroperations.
and
15. Check spring charging motor starts counter
"o*f"*witiopeEtionscounter'ifapplicable' (
*Optional
88 ATS-1999
7. INSPECTION AND TEST PROCEDURES
1. perform a contact
resistance test.
2. perform resistance
measurements through a, borted
connections wiilr low-resistance
onmmJLr, it
appricabre, in accordance wi*r
seciion 7.b.+.r.1 (Visue
and Mechanical lnspection).
7. Dissipation-factor/power-factortest resultsshall be
comparedtomanufacturer'spublisheddata.lnthe
absence of manufacturer's published. data, the
comparison shall be made to similar breakers'
8. Dissipation-factor/power-factorandcapacitancetest
resulis should be within ten peicent of nameplate
rating for bushings.
10. Minimum pickup for trip and close coils shall conform to
manufacturer's published data.
"Optional
e0 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
5. lnspect all bolted electrical connections for high resistance using one
of the following methods:
2. Electrical Tests
':I
'tl
,*
7;
,,]
il
4. Trip circuit switcher by operation of each protective device.
i
i
S. Verify correct operation of electrical shunt trip of interrupters.
E
"6. perform insulation-resistance tests pole-to-pole, pole-to-ground, and
R across open poles at 15,000 volts minimum'
I
j 1
T
:;
a
B. Perform an overpotentialtest in accordance with manufacturer's
4 published data.
*-
{
!l
i
ti:
3. Test Values
3
i
1. Compare bolted connection resistances to values of similar
connections.
i
&
3. Microhm or millivolt drop values shall not eiceed the high levels of
the normal range as indicated in the manufacturer's published data.
lf manufactureis data is not available, investigate any values which
deviate from adjacent poles or similar switchers by more than 50
percent of the lowest value.
*Optional
s2 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
i0 "*trurn" ,
L f
nlgegt network protector fuse covers, fuses, and btown fuse
indicators for damage.
ATS - 1999
Tr. 1l
INSPECTION AND TEST PROCEDURES
4
i..
$
16.
i7. perform a leak test on submersible enclosure in accordance with
3
jI
manufacture/s Published data'
'T
'i
2. ElectricalTests
*5. Measuretheresistanceofeachprotectorpowerfuse.
6. Measureminimumpickupvoltageofmotorcontrolrelay.
*v. Verifythatthemotorcanchargetheclosingmechanismatthe
minimum voltage specified by the manufacturer'
$
Verify that the
Measure minimum pickup voltage of the trip actuator.
i.
g 8.
actuator resets correctlY.
R
with section
2
9. calibrate the network protector relays in accordance
7.9.
"Optional
94 ATS-1999
7. INSPECTION AND TEST PROCEDURES
5. terify the protector will open when the source feeder breaker
is opened.
3. Test Values
1.lnsulationresistanceoftheprotectorcomponentsshouldbein
accordance with Table 10.1 .
t$ fi:ffi,#ring
insulation resistance should be a minimum of two I
3. Microhm or millivolt drop values shall not exceed the high levels of
the normal range as indicated in the manufactur"r'. prblished data.
lf manufacturer's data is not available, investigate ariy ualues which
;
deviate from similar connections by more tnai SO peicent of
lowest value.
the ;
ATS - 1 999
T
!' I. INSPECTION AND TEST PROCEDURES
t
't 7.g Protective RelaYs
s,
1. Visual and Mechanical lnspection
1.
e
:l
i
)i
compare equipment nameptate data with drawings and
specifications.
E
4i
i:
Z. lnspect relays and cases for physical damage. Remove shipping
restraint material.
i
i;
2. ElectricalTests
relays.
i
t
.t
2. lnspect targets and indicators.
f
,
$
1. Determine pickup and dropout of electromechanical targets'
*Optional
96 ATS- 1999
7. INSPECTION AND TEST PROCEDURES
2. Determine instantaneous
contacts.
2. 21 Distance Relay
ATS - 1999 97
..$
l:
T
t'
0l
1' Determine droPout voltage'
B
2. Determine time delaY'
il
4 point on the
3. Determine the time delay at a second
s timing curve for inverse time relays'
l:"\.
J:]
it
I
2. Determine closing zone'
E
j
l 3. Determine offset'
*Optional
98 ATS- 1999
I
,
i
,,.-
I
I
7. INSPECTION AND TEST PROCEDURES
it.
';
INSPECTTON AND TEST PROCEDURES
.i,
g{
2. Determine time delay.
*Optional
1' impedance to
,?i$ttT:?:maximum sround causins
5. Determine overcurrent
unit pickup.
6. Determine overcurrent
unit time delay at two points
the time curent curve. on
't
i
7. INSPECTION AND TEST PROGEDURES
24. 87 Differential
3. Determine sloPe.
*6.Plotoperatingcharacteristicsforeachrestraint.
*Optional
Verify that each of the relay contacts performs its intended function in the
control scheme including breaker trip tests, ctose inhibit tests, 86 lockout
tests, and alarm functions.
4. System Tests
5. Test Values
i@
.11
'.1 i
i
ii
:t,
' 4. INSPECTION AND TEST PROCEDURES
i:
i
t:,
1. compare equipment nameplate data with drawings and
specifications.
F
z
7..
2. lnspect physical and mechanicalcondition'
:'. ,_.t- ..
7. INSPECTION AND TEST PROCEDURES
l
"Optional
Tz.
I
INSPECTION AND TEST PROCEDURES
?
7 1A lnstrumentTransformers (cont')
I 6,
t 4. ElectricalTests-coupling-capacitanceVoltageTransformers
?
J 1. Perform all tests from 7.10.3 Voltage Transformers.
*
'E
5. Test Values
5
connections.
unless
2. Bolt-torque levels should be in accordance with Table 10-12
otherwise specified by manufacturer'
of
3. Microhm or millivolt drop values shall not exceed the high levels
iil;;;;"1 range as indicated in the manufacturer's published data'
lf manr-rfactureis data is not available, investigate any values which
deviate from similar connections by more than 50 percent of
the
lowest value.
€
*Optional
7.11 Metering
& 1. Visual and Mechanical lnspection
ElectricalTests
i7.
7.12 Regulating APParatus
:
1. Voltage $
1. SteP-Voltage Regulators
.E
il
L
1. Visual and Mechanical lnspection
*Optional
5. Performpower-factor/dissipation-factortests(orhot
coilar watts-ross test) on bushings and in accordance
i(0
I
with test equipment manufactur6/s pubrished
data.
6. Measu.re winding-resistance of source windings
in the
neutral position. Measure resistance of ail tap"s
on toao
windings.
I
*1
3. lf regulator has a separate tap-changer compartment,
s"m-pt" insulating liquid in the main tank in accordance
with ASTM D3613 and perform dissolved gas analysis
in accordance with ANSI/IEEE C57 JA4 or ASTM
D3612.
€
*Optional
1{0 ATS-1999
i-t..-1
;:1';-':: :: -'; 1''-
7. INSPECTTON AND TEST PROCEDURES
3. Test Values
b
{
5
".i
e
i"l
g.Turns-ratiotestresultsshouldmaintainanormal
deviation between each voltage step and should not
l:j
t)
]i
:..
i
E
*Optional
112 ATS-1999
l'- .
7. TNSPECTION AND TEST PROCEDURES
3. lnspect all bolted electricat connections for high resistance using one
of the following methods:
2. Electrical Tests
q
I.
t!
R
x
t
R
&
FJ
w
F (
E
"Optional
I
170 ATS- 1999
7- INSPECTION AND TEST PROCEDURES
T'
'i:
7. INSPECTION AND TEST PROCEDURES
4
*Optional
172 ATS-1999
7. INSPECTION AND TEST PROCEDURES
1- porarization
index varues shat be in accordance
ANS!/|EEE Standard 43. with
3. performance_tests
shail conform to manufacturer,s pubrished
data and ANSI/NFPA Standard -
1ib.
-
173
i
!
;i
! 2. lnspect physical, and mechanical condition.
iF.
T
it
3. Check for correct anchorage, required area clearances, and
t alignment.
l
4. Verify that fuse sizes and types correspond to drawings.
t
t-. 5. Test all electrical and mechanical interlock systems for correct
I
,i operation and sequencing.
?
!
6. lnspect all bolted electrical connections for high resistance
{:
I using one of the following methods:
fl
it
1. Use of tow-resistance ohmmeter in accordance with
$ Section 7 .22.2.2 (Electrical Tests).
$
I
I 2. Verify tightness of accessible bolted electrical
E connections by calibrated torque-wrench method in
accordance with manufacturer's published data or
Table 10.12.
4
*Optional
1- perform resistance
measurements through ail borted
connections with row-resistance ohmme6r,
if appricabre, in
accordance with section 7 .22.2.1 (visuar
ano trrtecn;;i.;i'
lnspection).
l.Compareboltedconnectionresistancetovaluesofsimilar
connections'
accordan ce with Table 10'12
2. Bolt-torque levels should be in
unrutt dGrwise specified by manufacturer'
3.Microhmormillivoltdropvaluesshallnotexceedthehigh
tevets of the normat r*[;;; in the manufacturer's
inoicateo
punGn"odata.rtmanuiacturer'Sdataisnotavailable' ns
i nvestig ate any
deviate f rom si mi lar conneclio
ue;;i;h
-val
UV moi" than 60 percent
of the lowest value'
{76 ATS-1999
7. INSPECTION AND TEST PROCEDURES
2. ElectricalTests
ATS - 1 999
$
!
*Optional
3. Test Values
4
5
n
is
t
7.24 Automatic Gircuit Reclosers and Line Sectionalizers
*:!: 1. Automatic Gircuit Reclosers, Oil/Vacuum €)
i
N
"t
1. Visual and Mechanical lnspection
ii
f
lt 1. Compare equipment nameplate data with drawings and
specifications.
s
ii
:l
I
2. lnspect physical and mechanical condition'
3
?
t
3. lnspect anchorage, alignment, and grounding'
I
4. perform all mechanical operation and contact alignment tests
ir onboththerecloseranditsoperatingmechanismin
accordance with manufacturer's published data'
.t
'i,
ti
i 5. lnspect all bolted electrical connections for high resistance
using one of the following methods:
-}.
a
i 1. Use of low-resistance ohmmeter in accordance with
Section 7 .24 -1.2 (Electrical Tests)'
q,
11
*;
& 2.Verifytightnessof.accessibleboltedelectrical6ii),
wa'
by calibrated torque-wrench method in
& "onn-ect'rns
accordalgewithmanufacturer'spublisheddataor
i Table 10.12.
3.Performthermographicsurveyinaccordancewith
Section 9.
ElectricalTests
@
*Optional
-1
i1 7.
T.24AutomaticcircuitReclosersandLinesectionalizers(cont.)
(cont') Q)
1. eutom"irc Circuit Reclosers' Oil/Vacuum
t
ll
j:
3
3. Test Values
i,
f.
l.Compareboltedconnectionresistancetovaluesofsimilar
n\ connections'
b
2.Bolt-torquelevelsshouldbeinaccordancewithTablelo.l2
unt"si othenruise specified by manufacturer'
3.Microhmormillivoltdropvaluesshallnotexceedthehigh
in the manufacturer's
levels of the normal r*b" ". indicated
not available'
punfitneO data' lf manuiacture.r's.data ]1
from similar connections
investigate any valuer *t'ri"r'r deviate
nV tot"" than 5O percent of the
lowest value'
be a minimum of
#
@
6. :t":;r",wiring insuration resistance shourd
F
l'
two megohms.
Dissi pation-factor/power-facto
test results and tank loss
r
l 7. published data'
index should not exceed the manufacture/s the
iffi; ot-manutacturer's published data'
;;;#"n"niun""
shall be made to similar reclosers'
il
!1
I
3
$
ri
I
tI
A
*Optional
I
g
182 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
3. perform thermographic
survey in accordance with
Section 9.
:!ii''
'
{:
7. INSPECTION AND TEST PROCEDURES
3.Removeasampleinsulatingliquid.inaccordancewithASTM
Dg23.Sampleshallbetestedforthefollowing:
4.Performanoverpotentialtestoneachpole-to-groundand
Pole-to-Pole. @
6.Testsectionalizercountingfunctionblapplicationof
simulatedfaultcurrent(greaterthanl60percentof
continuous current rating)'
positions'
7. Test sectionalizer lockout function for all counting
184 ATS-1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
ATS - 1999
I
i
1]
7. INSPECTION AND TEST PROCEDURES
damage'
Z. lnspect cable and connections for physical and mechanical
2. ElectricalTests
3. Test Values
for
1. The opticaltime domain reflectometer signal should be analyzed
by viewing the
excessive connection, splice, or cable backscatter
reflected Power/distance graPh'
Losses
Z. Attenuation loss measurement shall be expressed in dB/km.
no local
shall be within the manufacturer's recommendations when
site specifications are available.
*Optional
8.1 General
2. lmplementation
2' )/erify the correct operation of all interlock safety devices for
rv'q',-o,
fail-safr
functions in addition to design function.
3- Y".rirv the correct operation of ail sensing devices, ararms, and
indicating devices.
it
!
I
i
4
9. THERMOGRAPHIC SURVEY
'i.
$i
L
9.1 Visual and Mechanical lnsPection
F
i
t
l.lnspectphysical,electrical,andmechanicalcondition.
utilize
2. Remove all necessary covers prior to thermographicinspectigl'
h
:"
'" liililbii"ie caution, safety devices, and personal protective
equiPment.
*
current-carrying devices'
Equipment to be inspected shall include all
+
l:.
I 9.2
:
1. Description of equipment to be tested'
i
I
2. DiscrePanctes.
and the reference
3. Temperature difference between the area of concern
i
area.
I
a 4. Probable cause of temperature difference'
t
@
areas and/or
ii 5. Areas inspected. ldentify inaccessible and/or unobservable
equipment.
u
s
FI
6. ldentify load conditions at time of inspection'
E
l+
i!
i-
i.
i
;l
&
ii
;
s
F
lr
&
i
i
E
F
"Optional
N
F
188 ATS- 1999
9. THERMOGRAPHIC SURVEY
1999 189
TABLE 1O'1
Recommended Minimum
Minimum Test Voltage, dc lnsulation Resistance
Maximum Rating of in Megohrns
F-..!-*anl in Vnlfc in Volts
YurH.
500 25
250
1,000 100
600
2,500 1,000
5,000
2,500 2,000
8,000
2,500 5,000
15,000
5,000 20,000
?5 000
15,000 100,000
35,000
15.000 100,000
46,000
@
15,000 100,000
69,000
R
i1
F
tii
s
s
H
F
B.
E
G
lxl
g ATS - 1999
TABLE 10.2
4.76 14
Metal-Clad Switchgear 8.25 27
150 27 27
270 45
38.0 60
Station-Type Cubicle 37
Switchgear 38.0 60
72.5 120
4.76 14
20
8.25 1S
Metal Enclosed lnterrupter 27
15.0 27
Switchgear 37
15.5 37 52
25.8 45
38.0 60
L.
t:
l'i
I]
TABLE 10.3
0.5o/o
New Power Transformers and Reactors
1.OYo
New Distribution Transformers and Regulators
1.0%
Remanufactured Power Transformers and Reactors
1.5%
hemanufactured Distribution Transformers and Regulators
B
*jj
&
$
t;
..&
B
fi
il
a
R
s
L
ti
6
s
!':
j'i
B
v
#
g
F1
u
gi 6
I
g
H
E
TABLE 10.4
Test Limits for New rnsurating oir
Received in New Equipment
kV minimum
Test
Dielectric breakdowh,
uletectric breakdown,
kV minimum @ 0.04" gap
I nsrna Method
D877
D1816
m
Mineral Oill
30
Above 69 kV
through 230 kV
30
345 kV Class
and Above
3n
utetectric breakdown, 20 30 30
kV minimum @ 0.08" gap D1816
tllreffactat tension 40 48 60
MN/rn minimum D971
Neutralization numb6r, 35 35 40
mg KOH/g ryaximum D974
Water content, ppm 0.03 0.03 0.03
maximum D'1533 25 2A
Power factor al2S"C, o/o
10
D924 0.15 0.10 0.05
Powerfactorat 100"C, % D924 1.50 1.00
Color 0.30
D1500 10 1.0 0.5
Visualcondition D1524
ffi
Bright & Ctear Bright & Clear Bright & Clear
Test
ASTM Methorl
Dielectric breakdown, kV minimum ___,Acqeptable, Values
D877
Visual 30
D2129 clear, free of
Water content, ppm maximum
D1533
Dissipation factor, % max. 50
25.C @ D924
Viscosity, cSt @ 25.C 0.1
D445
Fire point, "C, minimum 47.5 - 52 5
D92
Neutrarization nur*a 340
mg KOH/g max.
D974
0.01
(Gurde rorAcceptance orsiticone
-
tl"n'"?o?11;j,t;:t?"ti:1ees) tnsutating Fruid and ,,
?o
D1816
34.5 kV Class ano setow
D1816 25
Above 34.5 kV Glass
Dielectric breakdown' 30
D1816
kV minimum 0.04" gaP Desirable
D1816 40
34.5 kV Class and Below
n{R{6 50
Ahove 34.5 kV Class
Dielectric breakdown' 60
D1816
kV minimum 0'08" gap Desirable
DB77 30
Dielectric breaKoown' Kv Clear
D1524
Visual 25
D15338
y'ater content' 0.1
np?4
Dissipation factor, ?o maxlmull @ f9i- D924 1.0
D92 300
Fire Point, ("C) minimum D92 270-294
Flash Point ("C) I Yplcar 0.03
D974 or D664
D971 38
€
ffia tension, mNtry rninimt
in
Less Ftammabte Hydrocarbon Fluid
(R19g5) (Guide for Acceptance and Maintenanceof
1EEEC57.121_1gBB
Transformerg,Table 2'
TABLE 10.5
GE
lR:r/kVA
=
lR Minimum recommended one minute insuration
rrrvsrerrvrr resistance
rsorotcrrluE'
Q = COnStant
f= Phase-to-phase voltage for delta connected windings;
connected windings. 'v-' phase{o-neutral
t'r'sev-rv-l voltage for star
kVA = Rated kVA of traniformer
Oil-filled C = 1.5
Dry-type C = 30
0
:
)
TABLE 10.6
Medium-Voltage Cables €
5KV 1 00% 25
5kv 133% 25
Elastomeric:
IOOYo 55
Butyl and Oil Base
-----15kV
ffinv f33% 65
lOgYo BO
25 KV
CKV 1 00% 25
5kv 133% 25
Elastomeric: EPR
BAV f00% 35
BKV 133% 45
t 55
i 15 kV 1OO"/o
J
15 kV 133% 65
..] -------z5kv 1 00% 80
25kV T33% 100
zgkv 1 00% 85
35 kV 1 00% 100
5kv 1 00% 25
5kv 133% 25
8kv 1 00% 3b
Polyethylene
akv 1 33% 45
T'KV TO0% 55
T5 KV 733% 65
25 kV 1 00% 80
25 kV 133% 100
t
e
t1 35 KV 1 00% fo0
H
196
'"-ffi
ATS - 1999
TABLE 10.7
t 226400
401-600
300 350
450
601-800
500
801-1000
600
1001 - 1200 70a
1201-1600
775
1601-2000
800
2001-2500
850
2501-5000
900
6000
1000
Derived from Table 5-3, NEMA Standard
AB 4_1996.
t
Trip times mav be substantially longer
for integrally-fused circuit breakers if tested
links (shorting bars). with the fuses replaced by solid
i' l
i,
TABLE 10.8
ffi ofManufacturers
Published TriP Range
Tolerance of Settin
+4A%
Adjustable
-30o/o
€
TABLE 10.9
tl
ll
1l
TABLE 10.10
€'
€
Tabte 10.11
overpotential rest voltages for
Electrical Apparatus other
than tnductive Equipment
Nominal -
System (Line) lnsulation Maximum
AC Factory Maximum
Vottage{ (kW Class Field Apptied
Test (kV) Field Apptier
A(} Taef lLrn
1.2 1.2
uv r est IKV
10
6.0 8.5
2.4 2.5 15
9.0 12.7
4.8 5.0 19
11.4 16.1
8.3 8.7 26 15.6
22.1
14.4 15.0 34
20.4 2B.B
18.0 18.0 40 24.0 -33.9
25.O 25.0 50
30.0 4)t
34.5 35.0 70 42.0 59.4
46.0 46.0 95 57.O -
80.6
69.0 69.0 140 84.O 118.8
.l
rj i-.,
'.',.,'.-ii
5L-------
e
B
- TABLE 10.12
$
US Standard
Bolt Torques for Bus Gonnections
Plated
Heat-Treated Steel 'Cadmium or Zinc
Head Marking
C O s s
133K 150K
hlinimum Tenstte (r.D.1., 64K
Torque (F, rot Pounds)
Bolt Diameter
in lnches
8.0 8.4
4.0 5.6
114
15.2 17.6
7.2 11.2
Stto
27.2 29.6
n.a 20.0
3/8
44.O 48.0
19.2 32.0
7116
68.0 73.6
29.6 48.0
112
96.0 105.6 @
42.4 70.4
9/16
133.6 144.0
59.2 96.0
5/B
224.O 236.8
96.0 160.0
314
352.0 378.4
152.0 241.6
7lB
528.0 571.2
225.6 372.8
1.0
TABLE 10.12 (CONT.)
1
Bronze alloy bolts shall have a minimum tensile strength of 70,000 pounds per
square inch.
)
Torque (Foot Pounds)
ATS - 1999
Table 10.11
overpotentiat rest voltages for
ElectricalApparatus other than
tnductive Equipment
Nominal-
System (Line) lnsulation AC Factory
Mailmum--- Maxtmum
Voltage{ (kvl Glass Field Apptied Field Apptied
_Igst (kv) AG Test (kV) DG Test (kVt
1.2 1.2 10
6.0 8.5
2.4 2.5 15
9.0 12.7
4.8 5.0 19
11.4 16.1
8.3 8.7 26
14.4
15.6 ,*
15.0 34 20.4 28.8
18.0 18.0 40 24.0 33.9
25.0 25.0 50 30.0 42.4
34.s 35.0
46.0 46.0
70 42.0 r*
95 57.0 80.6 I
lnsulation Resistance e
Gonversion Factors
Temperature Multiplier
Apparatus Containing Apparatus Containing
oG oF lmmersed Oil lnsulations Solid lnsulations
32 o.25 0.40
0
41 0.36 0.45
5
50 0.50 0.50
10
59 0.75 0.75
15
1.00 1.00
20 6B
77 1.40 1.30
25
1.98 1.60
30 B6
2.80 2.O5
35 95
3.95 2.50
40 104
5.60 3.25
45 113
7.85 4.00
F 50 122
*ji 11-20 5.20
55 131
E
140 15.85 6.40
60
149 22.40 8.70
n
! 65
,
31.75 10.00
70 158
167 44.70 13.00
75
!
I 176 63.50 16.00
J
80
TABLE 10.15
ffi
70 103
Derived from
vault, and submersibte Automaticlrri
s""t , alizers of AC systems).
I
:l
t
ii
li
j
:
x
t.
i
I
TABLE 10.17
@
MetalEnclosedBusDielectricWithstandTestVoltages
37 52,0
ffiratorLeads 24.5
29.5 45
34.5 60
*$
15.5 37 52.0
$ lsolated Phase 45
25.8
for Other than Generator Leads 60
* 35.0
ij
0.635 1.6 2.3
!
4.76 14 20.0
Nonsegregated Phase
I
15.0 27 37.0
i
25.8 45 63.0
i
38.0 60
i
15.5 37 52.O
I
i, 25,8 45 63.0
t
Segregated Phase
38.0 60
I
(
I'i
lij
d 0.3 1.6 2.3
0.8 2.7 3.9
DC Bus Duct
i;
'& 1.2 3.4 4.8
1.6 4.0 5.7
F
i
3.2 6.6 9.3
Thermographic Survey
Suggested Actions Based on Temperature Rise
TESTTNG ASSOCratro^r
To
The lnterNational Electrical resting Asso..ciation
(NETA) is an accredited standards developer
for the American National standards lnstitute
:: IANSI)and defin." tru ,t"ndards by which
electrical equipment is deemed safe and reliabte. ruErn certifieJ iectnicians conduct the
a
that ensure this equipment meets the association's tests
stringent *p*in.riions. NETA 6id
.? source of specifications, procedure.s., testing, and requirJmentl,-noi leading
onlv ro, commisr-ioiing n"*
equipment but for testing the reliability and -performance
;.
':.
of existing equipment.
'5
,, Certification
certification of competency is particularly important in
the determination of the equipment's service'abiliiyis
t"
electrical testing industry. lnherent in
'i the prereqrLite t,at individuals performing
the tests be capable of conducting the tests in a
sar" manner and with complete knowledge
the hazards involved' They must also evaluate the of
test data ano ma[e a judgmental opinion
the continued serviceability, deterioration, or nonr"rio"**t on
a nationally-recognized certification agency, provides
in! ri""inc equipment. NETA,
"t of four levels of competency
recognition
' ,:s
within the electrical testing industry.
s$t
&
w
r,ffi
The NETA Affitiate
"Technical Affiliate to the Electrical Testig-and
Maintenance Industry,,
It is the intention of NETA, in establishing the Affiliate
crassification, to provide interaction
between NETA and those people who re'quire
electrical testing. This classification
applies to those individuals who have an interest"r 9p""iV
i'iin"iL.trical testinglndustry.
This classification willtypically be chosen by engineers,
electrical contracting personnel,
project manasers, erectricians, prant ensinJers,il;;h;Li;ffi;;il;;;,h;r,
rv s'vr rae' qr ru \Jtr r.' who wish to
participate and learn about the electricaitesting
;il;.try.
Benefits of being a NETA Affitiate:
. Access ernerge ncy consultation
.' Attend NEVLqraining seminars
Attend Annuarrechnicar conference at reduced
rate
at reau"eiioii
-*'
. Receive
. PurchaseNlllWor[d technicartjourr"t---
NETA publication" ui ruirred rate
. Serye on TechnicatWorking Comniiees-''
. Be an active pafticipant in developind,TrvSr standards
First Time Affiliates onlv:
NETA Electricat Accepta'nce or Maintenance
Testing specifications included in Affiliate fee.
ri
'* _^3{:fftoa|{'.,Ei:,#x"3ii,.jJf l;xS"t#,q",
Po PpI6sZ:J!q^SJop.e Sireet, ii,ro"#ii"on, Co 8046s
i phone: 303.692.8441 .
F;iiao,.osiz.shi'-"
{e
:!
{.
E-mail : neta@ netaworld.org . W"U,-***. neiaworld.org
n
rt'tllfllt'llillrlllrtlll'llltlllrt'rfartrrirrtirllrrrrtlrtrrlrrlrlrrlrrrlrttatrtriirrrrrr
t
i
I N ETA Affiliate Appt ication
Nameffitle
Firm
Address
City/State/Zip
t-
,r Phone
J
I
L
I
li
1 year$75
"j"
&
I
i Affiliate fee enclosed: Check # or Visa
i
m
Mastercard Amex
$r
tI Credit Card Number
i
Expiration Date
I
First time Affiliates:
*
F Please send Acceptance Specifications OR
H
E
Maintenance Specifications
I hereby agree to abide by the ByLaws of theAssociafib n and not to
my Affiliate sfafus does not entitie me to use the NETA .ogo. t understand
claim Neri iimbership in the performance
$r testing. of erectrical
Signature
* Rates
cunent lgg9; suUjecit,o change.
Date
7. INSPECTION AND TEST PROCEDURES
1. Compare
-equipment nameplate data with drawings
and specifications.
4. Verifyremovat9fan.vshippingbracingandventplugs
after final placement.
qr--"'Y rv Yerr. Pru
methodJ
1. Use of tow-resistance ohmmeter
in accordance
vqr r\
with Secti on 7.12.1 z.z
terl"tri;"i i;[j'
2' Verify tightness of accessibre borted
erectricat
connections by calibrated torque-wrench
method in accordance with manufacturer,s
i
't"
2. ElectricalTests
i
3. Calculate polarization index.
t
ii
B
6. Verify that regulation corresponds to nameplate
I
I
I utilizing the voltage comparison method'
t
7. verify that the indicator correctly identifies neutral
i
i
position.
fr
i
i
i
f,
l"
;i
E
t
I
s
3
*Optional
Ii::..:...:.:_.r._
.. , .
-
f:i:t:.ri.
r:.
..r..
lr':r.if i.:,' .....:
7- INSPECTION AND TEST PROCEDURES
3. Test Values
&
*ili;?+. :-++-#:-i-zji1:--- .
+.
d
R
i.:
B
7.12 Regulating Apparatus (cont') 6
r-i
r. 1. Voltage (cont')
-lnduction Regulators (cont')
2.
$
4
.
4 lL?l'"i:ifr:l3ii:i""; ::$''3:":''"Jfi
as
il:i:a't11/s
o"t"l, not available, ihis information will serve
:j
baseline data'
?
5.Maximumpowerfactorofliquid-filledregulators.shall.
beinaccordance*itn*"n,facturer'sspecifications.ln
theabsenceofmanufacturer'sdatacomparetotest
manufacturer's published'data'
"q'iptunt
F6[;i"iG are indicated in Table 10.3
""rues
6'Bushingpowerfactorsandcapacitancesshouldnot
d; ;y";ore than ten pe rce nl of. .n 1t"p late val ues
the test
n"v n6t.ollar watts-loss results that exceedn s sh o u ld" b e
. i'J i Jilt"r]',nl r,rt" re r' s recom men d atio
" "tu
investigated'
T.Theregulationshouldbealinearratiothroughoutthe
and the maximum
tne maximum raise
f.l,5ff$'ffi:
a --^r,l+^
^L.all ha
B.lnsulatingliquidtestresultsshallbeinaccordancewith
Table 10'4'
g.lfwinding-resistancemeasurementsvarybymorethan
;; p;;#t from adjacent windings' consult
manufacturer'
?
I
i: 2. Gurrent - Reserved
a
*i.i
'k
v
*
'n
a
$
{
E
:;.1
n
a
*Optional
2. lnspectphysicarandmechanicarcondition.
PROCEDURES
7. INSPECTION AND TEST
7.12 -'
Regulating APPaftus (cont') $
3. lo"1 raP-cn"ngers (cont')
2. ElectricalTests
throuch all bolted
1. Perform resistance measurements
onmt"tlr, if applicable, in
connections with ro*-r"ririan"u nical
u."ololr,ir;;ith s".ti"r 7.-tz3j (visu al and Mecha
lnsPection)'
in ac cordance with
2. Perform insulation-resistance tests
Section 7'2'
issipation-factor tests in
3. Perform insulation Potwer-factor/d
accordance with Section 7'2'
*4.Performwinding-resistancetestsinaccordancewithSection
7.2.
as recommended by
5. Perform specialtests and adjustments
the manufacturer'
a^^t'.^^1n
6.Performturns-ratiotestinaccordancewithSectionT.2'
T.Removeasampleofinsulatingliquidinaccordancewith
tested for the following:
ASTM D923. rne sampi; ;h"iibe
A STM D877.
1. Dielectric breakdown voltage:
"Optional
118 ATS-1999
B
B.
Ei: ,* l
7. INSPECTION AND TEST PROCEDURES
3. Test Values
:i
PROCEDURES
i
7. INSPECTION AND TEST
::i
7.13 Grounding SYstems
i
1. Visual and Mechanical lnspection
::
ji
iil
i9 l.Verifygroundsystemisincompliancewithdrawingsand
speciflcations.
FE
i
+
2. ElectricalTests
''$
.i rl
il 1 3iilT$Jii"i-f,T:Hili?1"'Lx fJ:T:iJH:?"Ji3:tr
with r EEE
2.Performpoint-to-pointtests.to.determinetheresistancebetweenthe
frames'
;;in giolnoing Jvrte*.und ,l major eleclrical equipment
sy;ffi n"uio[ derived neutral points'
N
"nd/ot
t
3. Test Values
3 and ground
.:&
il
1. The resistance between the main Oro.yn{i19:'::ll"O"
R
i:
:F.t1*3ffi S*:i'gn':r;:ip:i:ffi!r.Lii'J'lJi1"1;"'
.{ groundsunr"''.otr'"*.rsespecifieouytheowner.(Reference:
Xr'rsutEeE standard 1 42')
i4
i:
t
2.lnvestigatepoint-to-pointresistancevalueswhichexceed0.5ohm.
!.
i
''
j
:i
$
-J
)l
!l
R
bl
!n
E
E
Ei
a
n
d
E
3
ii *Optional
s
5
!'
t. INSPECTION AND TEST PROCEDURES
I
2. ElectricalTests
,
I:
tll
1 [T:i'':':HilSiiT;?:'!ii'ii:;flili:fl S:i1'f;:fi::T:ffiJnn'n"
ili' disconnect link after testing.
*Optional
i'i
I'
s
, t. INSPECTION AND TEST PROCEDURES
N
T.Priortoinitialstart,applyvoltagetotheexcitersupp|y
anJ adjust exciter-fieid current to nameplate value.
F
;l
#
"Optional
126 ATS _
7. INSPECTIOhI AND TEST PROCEDURES
4. Locked-rotor current.
'
7 Accereration time to near synchronous
speed.
B. RpM just prior to synchronization.
"Optional
'ffi ATS- 1999 127
B
t
*
R
1. Compare bolted connection resistance to values of
u
similar connections.
i\
e
2. Bolt-torque levels should be in accordance with Table
)l 10.12 unless otherwise specified by manufacturer.
A
.t
i 4. lnsulation-resistance test results shall be in
accordance with Table 10.1 . lnvestigate dielectric
$
absorption ratios less than 1.4 and polarization index
ratios less than 2.0 for Class B insulation and Class F
f.
$
insulation.
R
f.i
NOTE: Overpotential, and surge comparison tests
t".
#
shall not be made on motors having values
]E
& lower than those indicated above.
;f
'a,;
'i
5. Stator winding dc overpotential test voltage shall be in
.) accordance with NEMA publication MG 1, paragraph
-! 3.01. Test results are dependent on ambient
conditions, and evaluation is on a withstand basis. lf
ti
-_.
phase windings can be separately teste!,.values of
J ieakage current may be compared for similar windings.
\i)
l
6. Vibration amplitudes shall not exceed values shown in
E
Table 10.10.
S,
v[t
3
E\
F]
F
rl
E
*Optional
B
ti*
128 ATS - 1999
'tffii
E
7. INSPECTION AND TEST PROCEDURES
t'
1. Motors (cont')
2. DG Motors
?
s
ti
t!
1. Visual and Mechanical Inspection
drawings
e 1. Compare equipment nameplate data with
;":
!: and specifications.
.g
:
3. Perform thermographic survey in accordance
with Section 9.
I
lt
s
E
)
h
$
s
E
E
l!
I *Optional
t
I
130 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
f eform
"5. ins ulation power-fa ctor or d issipation_factor
tests.
*Optional
lr
{ E-'
E:i
g?
! i'l
1. compare bolted connection resistance to values of
l!. similar connections.
It
i:
ia
2. Bolttorque levels should be in accordance with Table
t'i
1.9
lo.l2unlessotherwisespecifiedbymanufacturer.
r:g
i.
3. Microhm or millivolt drop values shall not exceed the
i:
t highlevelsofthenormalrangeasindicatedinthe
manufacturer's published data. lf manufacturer's data
'::l
i
is not available, investigate any values which deviate
fromsimilarconnectionsbymorethan50percentof
the lowest value.
te
i
6. Vibration amplitudes shall not exceed values shown in
t-
.fr
Table 10.10.
€
*Optional
il
ATS-1999 133
iti
$
T tRocEDURES
F z. tNsPEcTloN AND TEsT F
1. AC Generators (cont')
a.T
{t
2. ElectricalTests - lnduction Generators
T
l.Performresistancemeasurementsthroughallbolted
i;:
,E connectionswithlow-resistanceohmmeter'if
applicable, in accordan.c.e with Section 7 '15'2'1 '1
B
(Visual and Mechanical lnspection)'
i.l
:,il
with
2. Perform insulation-resistance tests in accordance
F ANSI/IEEE Standard 43'
i
I
1. All generators:
T
tt Record insulation-resistance value at one
minute, test voltage, and winding temperature'
tfl
Ii!
2. Generators rated above 600 volts:
Testdurationshallbeforl0minutes.Calculate
polarization index.
s
*.i
*
3. Generators rated 600 volts and less:
Testdurationshallbeforoneminute.Calculate
the d ielectric-absorption ratio'
.E
il
i
!
*3. Perform dc overpotential tests on generators in
accordance witlr ANSI/IEEE Standard 95'
l
t:
*4. Ferforminsulationpower-factorordissipation-factor
I tests.
(RTD)
7. Verify that resista n ce tempe ratu re d etecto r
: metering.gr
t circuits conform to drawings. Verify that
b
i"f"V O"ui.es using the RiD's have the correct rating.
€
*Optional
134 ATS-1999
7. INSPECTION AND TEST PROCEDURES
*2' perform an ac
vortage-drop test on at sarient
pores.
3' perform insuration-resistance
tests
winding, the exc*,er-neilwinoing, on the main fierd
and the exciter_
wjndins in accordan"J*iurJi'iiureee
P 3t}#ffi
"4' perform a high-potentiartest.on
the
ccordance with N EMn p unhati:o; excitation system in
3
rvG ;,';aragraph
Reconnection of generator
with load.
'e ("91r)
7.15 Rotating Machinery(cont')
i €'
ii
,t; 2. Generators
1. AC Generators (cont')
R
back to
3. Transfer load to utility power system and
F
fl
tij
,$
generator.
,T
Ii
f: 4.Generatoroutputvoltagedeviationfromnoload
t.'5fercentioadandleturn,and60percentto
100 Percent and return'
T
lt
4. Test Values
,\.
i
values of
1. Compare bolted connection resistance to
similar connections'
I
j with Table
2. Bolt-torque levels should be in accordance
ro.riuiiess otherwise specified by the manufacturer.
i tl -- -
1:,
*
3.Microhmormillivoltdropvaluesshall.notexceedthe
in the
tighl"u"tt of the notrnil range as indicated
t
g
1i
,"";;;;i;rer'i published da{a. lf manufacturer's data
s f#iil?,i?15,[::*r|i #;1ffi Hl5:'3#l;1i @
I the lowest value'
E
&
shall be'in
5. Stator winding 9t gLqPotential test v,oltage
'il
t'iitn ruruA publication MG 1' paragraph
E ".lotO"nt"
3.0i. Test results are dependent on ambientbasis. lf
and evaluatioh is on a withstand
"onJitionr, values of
phase windings can be separately.tested'
reakage may be compared for similar windings.
"u,,"it
*Optional
136 ATS-1999
7. INSPECTION AND TEST PROCEDURES
ATS - 1999
.t
I
rs
-
i t. INSPECTIOhi AND TEST PROCEDURES
4
i, 1. Visual and Mechanical lnspection
ts l.Compareequipmentnameplatedatawithdrawings
;i and sPecifications.
id
-.s
i
2. lnspect physical and mechanical condition'
il
3.Confirmcorrectapplicationofmanufacturer's
't
lubricants'
i.
i!
J
i
1 ffi 3::.H?;i1n:,"i#?i:;t::tj:'ance
electrical €
$
lj
2. Verify ti.ghtness of accessible bolted
x conn-ections by calibrated torq ue-wrench
!;i
dl
method in accordance with manufacturer's
b
Published data or Table 10'12'
R
Li
H
#
3. survev in accordance
iiilT[li"Jmosraphic
*
t-
Er 6.Whenapplicable,performspecialtestssuchasairgap
sPacing and Pedestal alignment'
:?
I
a
F
ii
f
g
E
:l
i
E
"Optional
t
a 138 ATS-1999
s
7. INSPECTION AND TEST PROCEDURES
L perform. resistance
measurements through a, borted
connections with low_resistance
ofrmmEer, if
applicable, in accordance with Secti
on ' .
(Visual and Mechanical tnspectffiv" 7.15.2.2.1
2. perform insuration-resistance
tests on a[ windings in
accordance with ANSI/IEEf StanOarO
+i.
1. Allgenerators:
Record insutation-resistance value
of armatur_
and fields at 1 minute, test uoli"gl,
and windr,,g
temperature.
-1
2. DC Generators (cont')
3
.t
I 3. Test Values
j-f
F
tl
$
A
{
g
I
,
*Optional
140 ATS-1999
7. INSPECTION AND TEST PROCEDURES
ATS - 1999
rl.
t,
-1
t:
I
7. INSPECTION AND TEST PROCEDURES
1. lnsulation Tests
T
t !;,
1 ff'fjJTffiL1fiff: #'i'ffi:[:':Bl:3'sh
arr
T
l.:
:r
ohmmeter, if applicable, in accordance with
Section 7 .16.L 1.1 (Visual and Mechanical
t lnspection).
I
,L
2. Measure insulation resistance of each
i
combination starter, phase-to-phase and phase-
b
il
to-ground, with the starter contacts closed and
the protective device open. Test voltage shall
; be in accordance with Table 10.1. Referto
t:
{4
manufacturer's instructions for devices with
solid-state comPonents.
I
h
*, "3. Measure insulation resistance of each control
circuit-to-ground. €
a
{
i
s "4. Perform an insulation resistance test at 1000
volts dc on all control wiring. For units with solid-
t' state components, follow manufacturer's
i
recommendations.
I
L
2.Testthemotoroverloadrelayelementsbyinjecting
primary current through the overload circuit and
monitoring trip time of the overload element'
'i
j..
NOTE: Test times for thermal trip units will, in
s
general, be longer than manufacturer's Gurve
B
cl if single-pole testing is performed. Optionally
test with all poles in series for time test and
w
*
i 3. Test circuit breakers, including motor circuit protectors,
4
E
in accordance with Section 7 .6.1.1'
*Optional
t tr
controlwiring insuration test resistance shourd be a
minimum of two megohms.
ii
j' 2. Medium-Voltage
T
i)
1. Visual and Mechanical lnspection
)'
a,
s
1. Compare equipment nameplate information with
i drawings and specifications.
't
t
9fi
2. lnspect physical and mechanical condition.
L
t
h
3. Confirm correct application of manufacturer's
$
recommended lubricants.
li
i
]
4. lnspect all bolted electrical connections for high
-:
resistance using one of the following methods:
I
@
"Optional
144 ATS*1999
7. INSPECTION AND TEST PROCEDURES
9. lnspect contactors
4. perform^controlwiring
performance test. Use the
erementary.d iag rams-to identify
and protective device. verir/
;;;ilr;te control
of each control feature.
siti.i,;"i"rv i"rfo rma n ce
i 7.
5 7.16 Motor Gontrol (cont') $
Motor Starters (cont')
i
t 1.
2. Medium-Voltage (cont')
e
l.
*7. Perform an overpotential test' in accordance
with
has no
*.
*;;;i;;trrer's pubtished data. lf manufacturer
,";;;;oatioir for this test, it shall be in accordance
:,
{; with Table 10'11'
&
?
g.
v' perform vacuum bottle integrity test (overpotential), if
i ,ppiir"or", across each vacuum bottle with the
contactsintheopenpositioninstrictaccordancewith
t
exceed maxi m u m
i:
t
l:
ffiHx":T;n"'l*'*?il: B:iot
ii
9' Perform contact resistance tests'
I
l0.Measureblowoutcoilcircuitresistance.
';
)
t
.8
11' Measure resistance of power fuses'
l2.Energizecontactorusingan.auxiliarySource.Adjust
where
to minimize operating vibration
"it"iui" @
aPPlicable'
N orE: j'Hili!,1{l'ili.:
;fi:l[xx:"JiE;11fl "^Y"
itsingre-fot"t"-'tingisperformed.optionally
i.J ilinllr potes ii seiies for time test and
each pole separately for comparison'
primary.
14. Test ground-fault protection by injecting
"""itthrough'"ntot'Confiimpickupleveland
timing.
rer avi n s
ll x1 ttES lJ *i;ffi?::Ti[E::,i#gctive
"Optional
146 ATS-1999
7. INSPECTION AND TEST PROCEDURES
2.
9glllqrqye varues shourd be in accordance with rabre
1AJ2 unless otherwise specified by manufacturer.
i:
p
appropriate inspections and tests of the motor control center
r starters.
b
s 2. Medium-Voltage
l.,l
"t
"e
I
switches.
:'j
"E
R
ii
E
F
r1 €
I
*Optional
*
4
s
! 148 ATS-1999
7. INSPECTION AND TEST PROCEDURES
2. lnspectphysicalandmechanicalcondition.
)
1
i7. INSPECTION AND TEST PROCEDURES
!)
l
i: 1. Perform resistance measurements through all bolted connections
, *ih io*-r"ri"t"n"r ohmmeter, if applicable, in.accordance with
section7.17.1(VisualandMechanicallnspection).
primary current
2. Test the motor overload relay elements by injecting
time of the overload
tfuorgf, the overload circuit ind monitoring trip
element.
i NOTE:Testtimesforthermaltripunitswill,ingeneral,belonger
than the manufacturer's curve if single-pole testing is
poles in series for time
ferformed. Optionally test with all
-i
I iest and eactr pole separately for comparison (Refer to
'r
'i,
"!
ANSI/NEMA ICS 2, Part 4.)
published
*li
3.
v' Perform startup of drive in accordance with manufacturer's
;;i;. c;librate drive to the system's minimum and maximum speed
iil
rj
control signals.
*
li
D
g
4. Perform operationaltests by initiating control devices.
t:
I
!:
il
1. check motor rotation operating on the drive and on the
l bypass.
I
2. Slowly vary drive speed between minimum and maximum'
Observe motor and bad for unusual vibration. lf excessive
L
'
I
*Optional
)
F.
N
s
v
:q
B
1. Visual and Mechanical lnspection
i
f 1. All CellTYPes
F
il
I
1. Compare equipment nameplate with drawings and
sPecifications'
T
i
t
2. lnspect physical and mechanicalcondition'
E
tj
ll
2.Verifytightnessofaccessibleboltedelectrical
'i connections by calibrated.torque-wrench
method in accordance with manufacture/s
s
h published data or Table 10-12.
IJ
'4
€
*Optional
*5.
Perform cell impedance test.
'I
.1
!
i t. INSPEGTION AND TEST PROCEDURES
t
7.18 Direct-Gurrent Systems (cont')
1. Batteries (cont') $'
1
!
Storage Batteies foi Generating Stations and Subsfafions.
)
i
ANSI/IEEE Std 1106-1995. Recommended Practice for
Maintenance, Testing and Replacement of Nickel-cadmium
'$
i Sforage Batteries foi Generating Stations and Subsfafions.
!
3
154 ATS-1999
7. INSPECTION AND TEST PROCEDURES
ATS - 1999
il
ii
I
"$
il
1. Visual and Mechanical lnspection
I
1. Compare equipment nameplate with drawings and
]i specifications.
I
2. lnspect physical and mechanical condition'
t
3.
I
lnspect all bolted electrical connections for high resistance
lf
r
2 yffl::i?l,l:ff :i'ilffi;'if'?:ij;1"?ffi1,o0,"
:!
I
F
!t
fr 5. Measure ac input current with charger at full rated load'
&
*Optional
3. Test Values
3. Rectifiers - Reserved
D
i
:9
!
*
I
1. Compare equipment nameplate data with drawings and
sPecifications.
3
il
il
2. lnspect physical and mechanical condition'
3
t
I
i1
3. lnspect for correct mounting and adequate clearances.
I
il
2. Verify tightness of accessible bolted electrical
t
h
:::i:rifs,lnf illlf i"1,1,",'J,v,";iffi ffi:ffi :?:il"
i( Table 10.12.
{.
$
I
2. ElectricalTests
:
i
1. Perform resistance measurements through all bolted .
l connections with low-resistance ohmmeter, if applicable, in
I
J
accordance with section 7.19.1.1 (Visual and Mechanical
lnsPection).
F
2.
i1
t Performinsulation-resistancetests.usemanufacturer's
{
recommended values or Table 10.1.
$
t.
,g
3. Test grounding connection in accordance with Section 7.13-
3. Test Values
*:i
1. Visual and Mechanical lnspection
n
* 1. Compare equipment nameplate data with drawings and
sPecifications'
?
::1
';
t 5. tnspect all bolted electrical connections for high resistance
using one of the following methods:
T'I
t:
,4, 1. use of low-resistance ohmmeter in accordance with
Section 7 .20.1.2 (Electrical Tests).
s
$:
I
2. ElectricalTests
:!
l
1. Perform resistance measurements through all bolted
g
ii connections with low-resistance ohmmeter, if applicable, in
accordance with section 7.20.1.1 (Visual and Mechanical
tj
lnspection).
tr
i)
u
2. Perform insulation-resistance tests from terminal(s) to case
a
,;!
for one minute on capacitors with more than one bushing.
g Test voltage and minimum resistance shall be in accordance
with manufacturer's published data or Table 10.1-
R
T
z
a 3. Measure the capacitance of all terrninal combinations.
ti
$
4. Measure resistance of internal discharge resistors-
I
*Optional
n
ii
H
162 ATS-1999
"c
ilj
$
2. Verify tightness of accessible bolted electrical
connections by calibrated torque-wrench
i3 method in accordance with manufacturer's
published data or Table 10.12- s
:i
'i
_!
3. Perform thermographic survey in accordance
'I
with Section 9.
5.
i 6.
l
applicable.
'!
I
I
s
ll
I
I
3
€
*Optional
2. Performwinding-to-ground insulation-resistancetests
in accordance with Table 10.1.
3. Test Values
S.lnspectallboltedelectricalconnectionsforhigh
resistance using one of the following methods:
u
3. Perform thermographic survey in accordance
with Section 9'
s.
L
g
g.Verifycorrectliquidlevelinalltanksandbushings.
e
:l
(
J
s
$
I
"Optional
166 ATS-.1999 'ffi
7. INSPECTION AND TEST PROCEDURES
2. ElectricalTests
4. Pe rfo rm i n s u atio n powe r-fa cto r/d iss p ati o n-facto r tests
I i
-\\>\\\\\\\\\\h\\is-r\\:'sH.
\c-----.----\ G
--!.s---- '
:--:-::-:+!..-:=--_.___-: ji j1i++-,:'---i--_--
_<-5-:<:-:
, ; )rtEsEJtr:B B BgpDE t )R rBZ /rtbzz;;;;
o. -yJ]_:jg-batE
rnsufaung ftqufct tesf resurfs shail be
in accordance with
Table 10.4.
3. lnspect all bolted electricat connections for high resistance using one
of the following methods:
2. Electrical Tests
q
I.
t!
R
x
t
R
&
FJ
w
F (
E
"Optional
I
170 ATS- 1999
7- INSPECTION AND TEST PROCEDURES
T'
'i:
7. INSPECTION AND TEST PROCEDURES
4
*Optional
172 ATS-1999
7. INSPECTION AND TEST PROCEDURES
1- porarization
index varues shat be in accordance
ANS!/|EEE Standard 43. with
3. performance_tests
shail conform to manufacturer,s pubrished
data and ANSI/NFPA Standard -
1ib.
-
173
i
!
;i
! 2. lnspect physical, and mechanical condition.
iF.
T
it
3. Check for correct anchorage, required area clearances, and
t alignment.
l
4. Verify that fuse sizes and types correspond to drawings.
t
t-. 5. Test all electrical and mechanical interlock systems for correct
I
,i operation and sequencing.
?
!
6. lnspect all bolted electrical connections for high resistance
{:
I using one of the following methods:
fl
it
1. Use of tow-resistance ohmmeter in accordance with
$ Section 7 .22.2.2 (Electrical Tests).
$
I
I 2. Verify tightness of accessible bolted electrical
E connections by calibrated torque-wrench method in
accordance with manufacturer's published data or
Table 10.12.
4
*Optional
1- perform resistance
measurements through ail borted
connections with row-resistance ohmme6r,
if appricabre, in
accordance with section 7 .22.2.1 (visuar
ano trrtecn;;i.;i'
lnspection).
l.Compareboltedconnectionresistancetovaluesofsimilar
connections'
accordan ce with Table 10'12
2. Bolt-torque levels should be in
unrutt dGrwise specified by manufacturer'
3.Microhmormillivoltdropvaluesshallnotexceedthehigh
tevets of the normat r*[;;; in the manufacturer's
inoicateo
punGn"odata.rtmanuiacturer'Sdataisnotavailable' ns
i nvestig ate any
deviate f rom si mi lar conneclio
ue;;i;h
-val
UV moi" than 60 percent
of the lowest value'
{76 ATS-1999
7. INSPECTION AND TEST PROCEDURES
2. ElectricalTests
ATS - 1 999
$
!
*Optional
3. Test Values
4
5
n
is
t
7.24 Automatic Gircuit Reclosers and Line Sectionalizers
*:!: 1. Automatic Gircuit Reclosers, Oil/Vacuum €)
i
N
"t
1. Visual and Mechanical lnspection
ii
f
lt 1. Compare equipment nameplate data with drawings and
specifications.
s
ii
:l
I
2. lnspect physical and mechanical condition'
3
?
t
3. lnspect anchorage, alignment, and grounding'
I
4. perform all mechanical operation and contact alignment tests
ir onboththerecloseranditsoperatingmechanismin
accordance with manufacturer's published data'
.t
'i,
ti
i 5. lnspect all bolted electrical connections for high resistance
using one of the following methods:
-}.
a
i 1. Use of low-resistance ohmmeter in accordance with
Section 7 .24 -1.2 (Electrical Tests)'
q,
11
*;
& 2.Verifytightnessof.accessibleboltedelectrical6ii),
wa'
by calibrated torque-wrench method in
& "onn-ect'rns
accordalgewithmanufacturer'spublisheddataor
i Table 10.12.
3.Performthermographicsurveyinaccordancewith
Section 9.
ElectricalTests
@
*Optional
-1
i1 7.
T.24AutomaticcircuitReclosersandLinesectionalizers(cont.)
(cont') Q)
1. eutom"irc Circuit Reclosers' Oil/Vacuum
t
ll
j:
3
3. Test Values
i,
f.
l.Compareboltedconnectionresistancetovaluesofsimilar
n\ connections'
b
2.Bolt-torquelevelsshouldbeinaccordancewithTablelo.l2
unt"si othenruise specified by manufacturer'
3.Microhmormillivoltdropvaluesshallnotexceedthehigh
in the manufacturer's
levels of the normal r*b" ". indicated
not available'
punfitneO data' lf manuiacture.r's.data ]1
from similar connections
investigate any valuer *t'ri"r'r deviate
nV tot"" than 5O percent of the
lowest value'
be a minimum of
#
@
6. :t":;r",wiring insuration resistance shourd
F
l'
two megohms.
Dissi pation-factor/power-facto
test results and tank loss
r
l 7. published data'
index should not exceed the manufacture/s the
iffi; ot-manutacturer's published data'
;;;#"n"niun""
shall be made to similar reclosers'
il
!1
I
3
$
ri
I
tI
A
*Optional
I
g
182 ATS - 1999
7. INSPECTION AND TEST PROCEDURES
3. perform thermographic
survey in accordance with
Section 9.
:!ii''
'
{:
7. INSPECTION AND TEST PROCEDURES
3.Removeasampleinsulatingliquid.inaccordancewithASTM
Dg23.Sampleshallbetestedforthefollowing:
4.Performanoverpotentialtestoneachpole-to-groundand
Pole-to-Pole. @
6.Testsectionalizercountingfunctionblapplicationof
simulatedfaultcurrent(greaterthanl60percentof
continuous current rating)'
positions'
7. Test sectionalizer lockout function for all counting
184 ATS-1999
7. INSPECTION AND TEST PROCEDURES
3. Test Values
ATS - 1999
I
i
1]
7. INSPECTION AND TEST PROCEDURES
damage'
Z. lnspect cable and connections for physical and mechanical
2. ElectricalTests
3. Test Values
for
1. The opticaltime domain reflectometer signal should be analyzed
by viewing the
excessive connection, splice, or cable backscatter
reflected Power/distance graPh'
Losses
Z. Attenuation loss measurement shall be expressed in dB/km.
no local
shall be within the manufacturer's recommendations when
site specifications are available.
*Optional
8.1 General
2. lmplementation
2' )/erify the correct operation of all interlock safety devices for
rv'q',-o,
fail-safr
functions in addition to design function.
3- Y".rirv the correct operation of ail sensing devices, ararms, and
indicating devices.
it
!
I
i
4
9. THERMOGRAPHIC SURVEY
'i.
$i
L
9.1 Visual and Mechanical lnsPection
F
i
t
l.lnspectphysical,electrical,andmechanicalcondition.
utilize
2. Remove all necessary covers prior to thermographicinspectigl'
h
:"
'" liililbii"ie caution, safety devices, and personal protective
equiPment.
*
current-carrying devices'
Equipment to be inspected shall include all
+
l:.
I 9.2
:
1. Description of equipment to be tested'
i
I
2. DiscrePanctes.
and the reference
3. Temperature difference between the area of concern
i
area.
I
a 4. Probable cause of temperature difference'
t
@
areas and/or
ii 5. Areas inspected. ldentify inaccessible and/or unobservable
equipment.
u
s
FI
6. ldentify load conditions at time of inspection'
E
l+
i!
i-
i.
i
;l
&
ii
;
s
F
lr
&
i
i
E
F
"Optional
N
F
188 ATS- 1999
9. THERMOGRAPHIC SURVEY
1999 189
TABLE 1O'1
Recommended Minimum
Minimum Test Voltage, dc lnsulation Resistance
Maximum Rating of in Megohrns
F-..!-*anl in Vnlfc in Volts
YurH.
500 25
250
1,000 100
600
2,500 1,000
5,000
2,500 2,000
8,000
2,500 5,000
15,000
5,000 20,000
?5 000
15,000 100,000
35,000
15.000 100,000
46,000
@
15,000 100,000
69,000
R
i1
F
tii
s
s
H
F
B.
E
G
lxl
g ATS - 1999
TABLE 10.2
4.76 14
Metal-Clad Switchgear 8.25 27
150 27 27
270 45
38.0 60
Station-Type Cubicle 37
Switchgear 38.0 60
72.5 120
4.76 14
20
8.25 1S
Metal Enclosed lnterrupter 27
15.0 27
Switchgear 37
15.5 37 52
25.8 45
38.0 60
L.
t:
l'i
I]
TABLE 10.3
0.5o/o
New Power Transformers and Reactors
1.OYo
New Distribution Transformers and Regulators
1.0%
Remanufactured Power Transformers and Reactors
1.5%
hemanufactured Distribution Transformers and Regulators
B
*jj
&
$
t;
..&
B
fi
il
a
R
s
L
ti
6
s
!':
j'i
B
v
#
g
F1
u
gi 6
I
g
H
E
TABLE 10.4
Test Limits for New rnsurating oir
Received in New Equipment
kV minimum
Test
Dielectric breakdowh,
uletectric breakdown,
kV minimum @ 0.04" gap
I nsrna Method
D877
D1816
m
Mineral Oill
30
Above 69 kV
through 230 kV
30
345 kV Class
and Above
3n
utetectric breakdown, 20 30 30
kV minimum @ 0.08" gap D1816
tllreffactat tension 40 48 60
MN/rn minimum D971
Neutralization numb6r, 35 35 40
mg KOH/g ryaximum D974
Water content, ppm 0.03 0.03 0.03
maximum D'1533 25 2A
Power factor al2S"C, o/o
10
D924 0.15 0.10 0.05
Powerfactorat 100"C, % D924 1.50 1.00
Color 0.30
D1500 10 1.0 0.5
Visualcondition D1524
ffi
Bright & Ctear Bright & Clear Bright & Clear
Test
ASTM Methorl
Dielectric breakdown, kV minimum ___,Acqeptable, Values
D877
Visual 30
D2129 clear, free of
Water content, ppm maximum
D1533
Dissipation factor, % max. 50
25.C @ D924
Viscosity, cSt @ 25.C 0.1
D445
Fire point, "C, minimum 47.5 - 52 5
D92
Neutrarization nur*a 340
mg KOH/g max.
D974
0.01
(Gurde rorAcceptance orsiticone
-
tl"n'"?o?11;j,t;:t?"ti:1ees) tnsutating Fruid and ,,
?o
D1816
34.5 kV Class ano setow
D1816 25
Above 34.5 kV Glass
Dielectric breakdown' 30
D1816
kV minimum 0.04" gaP Desirable
D1816 40
34.5 kV Class and Below
n{R{6 50
Ahove 34.5 kV Class
Dielectric breakdown' 60
D1816
kV minimum 0'08" gap Desirable
DB77 30
Dielectric breaKoown' Kv Clear
D1524
Visual 25
D15338
y'ater content' 0.1
np?4
Dissipation factor, ?o maxlmull @ f9i- D924 1.0
D92 300
Fire Point, ("C) minimum D92 270-294
Flash Point ("C) I Yplcar 0.03
D974 or D664
D971 38
€
ffia tension, mNtry rninimt
in
Less Ftammabte Hydrocarbon Fluid
(R19g5) (Guide for Acceptance and Maintenanceof
1EEEC57.121_1gBB
Transformerg,Table 2'
TABLE 10.5
GE
lR:r/kVA
=
lR Minimum recommended one minute insuration
rrrvsrerrvrr resistance
rsorotcrrluE'
Q = COnStant
f= Phase-to-phase voltage for delta connected windings;
connected windings. 'v-' phase{o-neutral
t'r'sev-rv-l voltage for star
kVA = Rated kVA of traniformer
Oil-filled C = 1.5
Dry-type C = 30
0
:
)
TABLE 10.6
Medium-Voltage Cables €
5KV 1 00% 25
5kv 133% 25
Elastomeric:
IOOYo 55
Butyl and Oil Base
-----15kV
ffinv f33% 65
lOgYo BO
25 KV
CKV 1 00% 25
5kv 133% 25
Elastomeric: EPR
BAV f00% 35
BKV 133% 45
t 55
i 15 kV 1OO"/o
J
15 kV 133% 65
..] -------z5kv 1 00% 80
25kV T33% 100
zgkv 1 00% 85
35 kV 1 00% 100
5kv 1 00% 25
5kv 133% 25
8kv 1 00% 3b
Polyethylene
akv 1 33% 45
T'KV TO0% 55
T5 KV 733% 65
25 kV 1 00% 80
25 kV 133% 100
t
e
t1 35 KV 1 00% fo0
H
196
'"-ffi
ATS - 1999
TABLE 10.7
t 226400
401-600
300 350
450
601-800
500
801-1000
600
1001 - 1200 70a
1201-1600
775
1601-2000
800
2001-2500
850
2501-5000
900
6000
1000
Derived from Table 5-3, NEMA Standard
AB 4_1996.
t
Trip times mav be substantially longer
for integrally-fused circuit breakers if tested
links (shorting bars). with the fuses replaced by solid
i' l
i,
TABLE 10.8
ffi ofManufacturers
Published TriP Range
Tolerance of Settin
+4A%
Adjustable
-30o/o
€
TABLE 10.9
tl
ll
1l
TABLE 10.10
€'
€
Tabte 10.11
overpotential rest voltages for
Electrical Apparatus other
than tnductive Equipment
Nominal -
System (Line) lnsulation Maximum
AC Factory Maximum
Vottage{ (kW Class Field Apptied
Test (kV) Field Apptier
A(} Taef lLrn
1.2 1.2
uv r est IKV
10
6.0 8.5
2.4 2.5 15
9.0 12.7
4.8 5.0 19
11.4 16.1
8.3 8.7 26 15.6
22.1
14.4 15.0 34
20.4 2B.B
18.0 18.0 40 24.0 -33.9
25.O 25.0 50
30.0 4)t
34.5 35.0 70 42.0 59.4
46.0 46.0 95 57.O -
80.6
69.0 69.0 140 84.O 118.8
.l
rj i-.,
'.',.,'.-ii
5L-------
e
B
- TABLE 10.12
$
US Standard
Bolt Torques for Bus Gonnections
Plated
Heat-Treated Steel 'Cadmium or Zinc
Head Marking
C O s s
133K 150K
hlinimum Tenstte (r.D.1., 64K
Torque (F, rot Pounds)
Bolt Diameter
in lnches
8.0 8.4
4.0 5.6
114
15.2 17.6
7.2 11.2
Stto
27.2 29.6
n.a 20.0
3/8
44.O 48.0
19.2 32.0
7116
68.0 73.6
29.6 48.0
112
96.0 105.6 @
42.4 70.4
9/16
133.6 144.0
59.2 96.0
5/B
224.O 236.8
96.0 160.0
314
352.0 378.4
152.0 241.6
7lB
528.0 571.2
225.6 372.8
1.0
TABLE 10.12 (CONT.)
1
Bronze alloy bolts shall have a minimum tensile strength of 70,000 pounds per
square inch.
)
Torque (Foot Pounds)
ATS - 1999
Table 10.11
overpotentiat rest voltages for
ElectricalApparatus other than
tnductive Equipment
Nominal-
System (Line) lnsulation AC Factory
Mailmum--- Maxtmum
Voltage{ (kvl Glass Field Apptied Field Apptied
_Igst (kv) AG Test (kV) DG Test (kVt
1.2 1.2 10
6.0 8.5
2.4 2.5 15
9.0 12.7
4.8 5.0 19
11.4 16.1
8.3 8.7 26
14.4
15.6 ,*
15.0 34 20.4 28.8
18.0 18.0 40 24.0 33.9
25.0 25.0 50 30.0 42.4
34.s 35.0
46.0 46.0
70 42.0 r*
95 57.0 80.6 I
lnsulation Resistance e
Gonversion Factors
Temperature Multiplier
Apparatus Containing Apparatus Containing
oG oF lmmersed Oil lnsulations Solid lnsulations
32 o.25 0.40
0
41 0.36 0.45
5
50 0.50 0.50
10
59 0.75 0.75
15
1.00 1.00
20 6B
77 1.40 1.30
25
1.98 1.60
30 B6
2.80 2.O5
35 95
3.95 2.50
40 104
5.60 3.25
45 113
7.85 4.00
F 50 122
*ji 11-20 5.20
55 131
E
140 15.85 6.40
60
149 22.40 8.70
n
! 65
,
31.75 10.00
70 158
167 44.70 13.00
75
!
I 176 63.50 16.00
J
80
TABLE 10.15
ffi
70 103
Derived from
vault, and submersibte Automaticlrri
s""t , alizers of AC systems).
I
:l
t
ii
li
j
:
x
t.
i
I
TABLE 10.17
@
MetalEnclosedBusDielectricWithstandTestVoltages
37 52,0
ffiratorLeads 24.5
29.5 45
34.5 60
*$
15.5 37 52.0
$ lsolated Phase 45
25.8
for Other than Generator Leads 60
* 35.0
ij
0.635 1.6 2.3
!
4.76 14 20.0
Nonsegregated Phase
I
15.0 27 37.0
i
25.8 45 63.0
i
38.0 60
i
15.5 37 52.O
I
i, 25,8 45 63.0
t
Segregated Phase
38.0 60
I
(
I'i
lij
d 0.3 1.6 2.3
0.8 2.7 3.9
DC Bus Duct
i;
'& 1.2 3.4 4.8
1.6 4.0 5.7
F
i
3.2 6.6 9.3
Thermographic Survey
Suggested Actions Based on Temperature Rise
TESTTNG ASSOCratro^r
To
The lnterNational Electrical resting Asso..ciation
(NETA) is an accredited standards developer
for the American National standards lnstitute
:: IANSI)and defin." tru ,t"ndards by which
electrical equipment is deemed safe and reliabte. ruErn certifieJ iectnicians conduct the
a
that ensure this equipment meets the association's tests
stringent *p*in.riions. NETA 6id
.? source of specifications, procedure.s., testing, and requirJmentl,-noi leading
onlv ro, commisr-ioiing n"*
equipment but for testing the reliability and -performance
;.
':.
of existing equipment.
'5
,, Certification
certification of competency is particularly important in
the determination of the equipment's service'abiliiyis
t"
electrical testing industry. lnherent in
'i the prereqrLite t,at individuals performing
the tests be capable of conducting the tests in a
sar" manner and with complete knowledge
the hazards involved' They must also evaluate the of
test data ano ma[e a judgmental opinion
the continued serviceability, deterioration, or nonr"rio"**t on
a nationally-recognized certification agency, provides
in! ri""inc equipment. NETA,
"t of four levels of competency
recognition
' ,:s
within the electrical testing industry.
s$t
&
w
r,ffi
The NETA Affitiate
"Technical Affiliate to the Electrical Testig-and
Maintenance Industry,,
It is the intention of NETA, in establishing the Affiliate
crassification, to provide interaction
between NETA and those people who re'quire
electrical testing. This classification
applies to those individuals who have an interest"r 9p""iV
i'iin"iL.trical testinglndustry.
This classification willtypically be chosen by engineers,
electrical contracting personnel,
project manasers, erectricians, prant ensinJers,il;;h;Li;ffi;;il;;;,h;r,
rv s'vr rae' qr ru \Jtr r.' who wish to
participate and learn about the electricaitesting
;il;.try.
Benefits of being a NETA Affitiate:
. Access ernerge ncy consultation
.' Attend NEVLqraining seminars
Attend Annuarrechnicar conference at reduced
rate
at reau"eiioii
-*'
. Receive
. PurchaseNlllWor[d technicartjourr"t---
NETA publication" ui ruirred rate
. Serye on TechnicatWorking Comniiees-''
. Be an active pafticipant in developind,TrvSr standards
First Time Affiliates onlv:
NETA Electricat Accepta'nce or Maintenance
Testing specifications included in Affiliate fee.
ri
'* _^3{:fftoa|{'.,Ei:,#x"3ii,.jJf l;xS"t#,q",
Po PpI6sZ:J!q^SJop.e Sireet, ii,ro"#ii"on, Co 8046s
i phone: 303.692.8441 .
F;iiao,.osiz.shi'-"
{e
:!
{.
E-mail : neta@ netaworld.org . W"U,-***. neiaworld.org
n
rt'tllfllt'llillrlllrtlll'llltlllrt'rfartrrirrtirllrrrrtlrtrrlrrlrlrrlrrrlrttatrtriirrrrrr
t
i
I N ETA Affiliate Appt ication
Nameffitle
Firm
Address
City/State/Zip
t-
,r Phone
J
I
L
I
li
1 year$75
"j"
&
I
i Affiliate fee enclosed: Check # or Visa
i
m
Mastercard Amex
$r
tI Credit Card Number
i
Expiration Date
I
First time Affiliates:
*
F Please send Acceptance Specifications OR
H
E
Maintenance Specifications
I hereby agree to abide by the ByLaws of theAssociafib n and not to
my Affiliate sfafus does not entitie me to use the NETA .ogo. t understand
claim Neri iimbership in the performance
$r testing. of erectrical
Signature
* Rates
cunent lgg9; suUjecit,o change.
Date