Features General
Dual Power Supply (CT power / Auxiliary voltage)
> The ADR 241S is member of ADITYA series designed to meet demand of Ring Main Unit
Low energy pulse output tripping for RMU.
> (RMU) type switchgear where Auxiliary supply is not available. The relay takes power from
CT's and continuously monitors all 3 phases and earth current, through CT connections. The
User friendly setting procedure with wide setting range.
> high-speed micro controller samples this current through a A/D converter. The micro
Wide Setting Range 20- 200% for phase and 10 - 80% for EF.
> controller performs powerful Digital Algorithms to find out RMS current signal and use for
4 Element (3 Phase + 1 Earth Fault) over current IDMT / Definite time and
> protection and metering function. All measurement is tuned to fundamental frequency. Input
Instant Trip. current is displayed on 16x2 Backl it LCD displayfor metering.
The relay is buffered by a battery for feeding the Backlit LCD display and SCADA
RS 232 and RS 485 Communication Port for remote SCADA.
> communication. After tripping operation relay maintains fault indication on Backlit LCD
Communication Protocol ASCADAOr IEC870-5-103 or any other as per
> display. During this time, the relay uses power through internal rechargeable battery. The
requirement relay can maintain fault indication for more than Eight Hours. During normal condition battery
Programmable (Non Volatile) setting by local keyboard as well as remote
> is continuously charged on CT current. Failure of the battery has no effect on the protection
function of the relay. The battery has a service life of more then 10 years. Relay is provided
setting by communication port.
with optional Auxiliary supply input having range of 77V- 250V AC/DC. PT supply can be
Back - Lit LCD Display for settings / parameters.
> connected at this input Relay can use power for communication when there is no current in
Display of Fault current as well as Load current.
> CT circuit for SCADAapplication.
Latching of last 5 faults with relay time.
> Relay is provided with 2 latching type potential free contact which can be used for remote
indication. The relay is available with different version 1) RMU application 2) Numerical
Selectable Inverse Time Characteristics (Five selectable curves): Normal
> series tripping arrangement for normal SF6 CB. Etc. They are distinguishing by different
Inverse! (C1), Normal Inverse2 (C2), Very Inverse (C3), Extremely Inverse model numbers. The technical details are out of scope of this document. Please contact
(C4), Long Time Inverse (C5), Define time (C6) factory for further details.
Separate curve setting for phase and EF.
>
Internal Battery for maintaining LCD display and communication during fault
>
condition. Battery is re- chargeable and remains charged on input current
/Aux. Supply.
Designed using DSP technology.
>
Latching of Fault Current and storing in a non-volatile memory with time
>
stamping.
Remote trip (230Vac).
>
External latching type potential free contact for remote trip indication.
>