400kV GIS SUBSTATION AT BHACHHUNDA GE T&D INDIA LTD

Type of GIS (Internal Name) T155-3 Information in Yellow boxes


POWER DISSIPATION OF GIS
SUBSTATION : GETCO 400 KV GIS
ORDER GD156 Evaluation of power dissipation for each typical bay or section of GIS
COUNTRY INDIA calculated for a rating of 1000A at 20°C inside the GIS Building.
PRODUCT T155 Refer to sketch for more detail
LAYOUT N° GD53A000357
Bays
BAY10 BAY11
Reference BAY01 BAY02 BAY03 BAY04 BAY05 BAY06 BAY07 BAY08 BAY09 BAY12 BAY13 BAY14 BAY15 BAY16 BAY17 BAY18 BAY19 BAY20 BUSBAR
(BUS PT) (BC)
Type
Type of Components Quantity per bay
Circuit Breaker (3 phases) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Busbar Disconnector (3 phases) 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1
Line disconnector (3 phases) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Elbow (1 phase) 3 3 6 3 3 6 3 3 6 9 3 3 6 3 3 6 3 3 6
Current transformer assembly (3 phases) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Cable box end or transfo. connection (3 phases)
Linear meter of the busduct (1 phase) 15.0 15.0 30.9 15.0 15.0 30.9 15.0 15.0 30.9 15.0 15.0 30.9 15.0 15.0 30.9 15.0 15.0 30.9
Busbar (3 phases) 60.0
Heat Dissiapation of Equipments 546 546 785 546 546 785 546 546 785 67 411 546 546 785 546 546 785 546 546 785 3204
LCC 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
DS/ES Mechanism 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90 90
CB Mechanism 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150 150
Total Power dissipation (kW) @ 20 Deg C 886 886 1125 886 886 1125 886 886 1125 157 751 886 886 1125 886 886 1125 886 886 1125 3204
Power dissipation for 1000A (W) @50 degree celcius, convertion
1000 1000 1271 1000 1000 1271 1000 1000 1271 177 848 1000 1000 1271 1000 1000 1271 1000 1000 1271 3617
factor ( 1+0.0043*(t2-t1)=1.129

CALCULATION FOR COMPLETE SUBSTATION


Assumptions (if any)
Quantity of bays 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Rating (A) 200 0 3000 900 0 0 900 0 0 4000 4000 900 0 0 900 0 0 200 0 1000 4000
0.0 0.0 11.4 0.8 0.0 0.0 0.8 0.0 0.0 2.8 13.6 0.8 0.0 0.0 0.8 0.0 0.0 0.0 0.0 1.3 57.9
TOTAL POWER DISSIPATION OF THE GIS (kW) 90

TOTAL HEAT DISSIPATION OF THE 400 KV GIS IS 90 KW AT 50 DEG AMBIENT FOR 3000 A CONTINOUS CURRENT RATING

HEAT LOAD CALCULATIONS GD53A000369 REV00