Professional Documents
Culture Documents
Integrated Assignment
Aim: to apply load flow and fault calculation knowledge to analyse and control a real power system.
Objective: 1. to model a power system for load flow and fault calculations using a commercial
software
2. perform load flow calculations and fault analysis under different system configurations
Data: Figure 1 shows single line diagram of a simplified version of a real power system. Table 1 gives
basic information about busses. This power system is a 220 kV ring network with 7 busses. Three
radial lines are connected to the ring at Bus 1,6 and 7. This network is fed by: (a) two hydro power
plants connected at bus 1 and Bus 1_1, (b) two thermal power plants connected at bus 7 and Bus
6_1, (c) three coal plants connected at bus 3. In addition to that ring is supplied by another hydro
complex (via 132 kV) at bus 2 and 7_1. As shown in Fig. 1 this infeed is modelled as two generators.
Detail about loads at a particular time instant is given in Table 1.
Table 2, 3 and 4 gives line, generator and transformer data respectively. In case of line data, given
values are for an only one circuit. All the pu values are based on 100 MVA. P_Gen values given in
generator data is corresponds to loading condition specified in Table 1. Hydro 1 is taken as slack
bus. You may assume reasonable values for any missing parameters.
Bus 3
Bus 4 Coal_1
Coal_2
Coal_3
Bus 5
Infeed from 132
Bus 6 kVBus 2
Bus 6_1
Thermal_2
Bus 1
Bus 7
Bus 1_1
Bus 7_1
Hydro_1
Hydro_2
Infeed from 132
kV
Thermal_1
Sarath Kumara/2016
Table 1: Bus information.
Load
Bus Name Voltage( kV) P(MW) Q(MVAr) Generation
Bus 1 220
Bus 1_1 220 100 70
Bus 7_1 220 240 80 Hydro 4
Bus 6_1 220
Bus 7 220 600 200
Bus 6 220 200 10
Bus 2 220 500 175 Hydro 3
Bus 3 220
Bus 4 220 140 40
Bus 5 220 25 11
Hydro 2 13.8 Hydro 2
Hydro 1 12.5 Hydro 1
Thermal 1 10.5 Thermal 1
Thermal 2 14.5 Thermal 2
Coal 1 20 Coal 1
Coal 2 20 Coal 2
Coal 3 20 Coal 3
Task:
Final Presentation:
Each student should present the outcome of the assignment by means of a 10 minute power point
presentation. This presentation is the evaluation method of the assignment.
Sarath Kumara/2016
Table 2: Line data.
Sarath Kumara/2016
Table 4: Transformer data.
Specified X Vector
From Bus To Bus (pu) Group Connection
Bus 1 Hydro 2 0.03 YNd11 No series path, ground winding 1, earth winding 2
Bus 1_1 Hydro 1 0.08 YNd11 No series path, ground winding 1
Bus 7_1 Thermal 1 0.1325 Dd No series or ground paths
Bus 6_1 Thermal 2 0.107143 Dd No series or ground paths
Bus 3 Coal 1 0.038611 YNd1 No series path, ground winding 1, earth winding 2
Bus 4 Coal 2 0.038833 YNd1 No series path, ground winding 1, earth winding 2
Bus 5 Coal 3 0.038639 YNd1 No series path, ground winding 1, earth winding 2
Sarath Kumara/2016