Professional Documents
Culture Documents
DESCRIPTION:
LOCATION:
OUTDOOR CONDITION:
INDOOR CONDITION:
32-24
td = 8°C
td = 7°C
MONTH:
JUNE
LOCATION:
PLASTER: 25 mm
1 𝑊2
𝑈= = 0.1282 𝐾
1 0.15 1 𝑚
+ +
0.22 0.38 0.35
B. SOLAR HEAT LOAD FROM WALLS, ROOFS AND WINDOW
𝑄 = 𝑈 ∗ 𝐴𝑊 ∗ 𝐶𝐿𝑇𝐷
GROUND FLOOR WALLS
NORTH WALL
SOUTH WALL
EAST WALL
WEST WALL
NORTH WALL
SOUTH WALL
EAST WALL
WEST WALL
𝑄 = 𝑈 ∗ 𝐴 ∗ 𝐶𝐿𝑇𝐷
𝑄 = 𝑆𝐻𝐺𝐹𝑚𝑎𝑥 ∗ 𝑆𝐶 ∗ 𝐶𝐿𝐹 ∗ 𝐴
GROUND FLOOR GLASS
NORTH GLASS
SOUTH GLASS
EAST GLASS
NORTH GLASS
SOUTH GLASS
EAST GLASS
WEST GLASS
𝑄𝑂𝑆 = 150 ∗ 40 ∗ 1
𝑄𝑂𝑆 = 6000 𝑊
𝑄𝐼𝑆 = 0.0984 𝑊
𝑄𝐼𝐿 = 3000 ∗ 𝑄 ∗ (𝑊𝑜 − 𝑊𝑖 )
𝑄𝐼𝐿 = 3000 ∗ 0.01 ∗ (0.0155 − 0.0093)
𝑄𝐼𝐿 = 0.186 𝑊
E. PUMP DESIGN
𝑛(𝑊2 − 𝑊1 )
𝑄𝑊 =
100
75(0.0082 − 0.0158)
=
100
𝑚3
= 0.0057 ≈ 0.095 𝐿/𝑠𝑒𝑐
𝑚𝑖𝑛
𝐻
𝑃 = 𝑄𝑊 ∗
75 ∗ 𝑛
1
= 0.095 ∗
75 ∗ 0.75
= 0.001689 ℎ𝑝 ≈ 1.2595 𝑊
F. DUCT DESIGN
GIVEN VELOCITIES:
OUTLETS – 5 m/s
OTHER – 7 m/s
DUCT DIMENSIONS:
W = 4H
DUCT LENGTH:
A = 2.5 m A=2m
B=4m B = 2.5 m
C = 3.5 m C=2m
D = 4.5 m D = 4.5 m
E=1m E=2m
F=6m F = 2.5 m
G = 2.5 m G=3m
H = 4.5 m H = 2.5 m
I=1m I=4m
J = 2.5 m
QB = 1 m3/s QD = 1 m3/s
QA = QB + QC = 4.4 m3/s QC = QD + QE = 4.5 m3/s
QB = 0.8 m3/s
QA = QB + QC = 5.3 m3/s
CONSIDER DUCT/SECTION A
𝐴
𝑄 =
𝑉
4.4 𝑚3 /𝑠
𝐴 =
7𝑚/𝑠
𝐴 = 0.6286 𝑚2
𝐴 = 𝑊𝐻 = 4𝐻 2
2 𝐴
𝐻=√
4
𝐻 = 0.3964 𝑚
𝑊 = 1.5856 𝑚
(𝐻𝑊)0.625
𝐷𝑒𝑞 = (1.3) ( )
(𝐻 + 𝑊)0.25
(0.3964 ∗ 1.5856)0.625
𝐷𝑒𝑞 = (1.3) ( )
(0.3964 + 1.5856)0.25
𝐷𝑒𝑞 = 0.8196
∆𝑃 = 0.85 𝑃𝑎/𝑚
∆𝑃𝐴 = 0.85 ∗ 2.5 = 2.125 𝑃𝑎
CONSIDER DUCT/SECTION B
𝐴
𝑄 =
𝑉
0.8 𝑚3 /𝑠
𝐴 =
5 𝑚/𝑠
𝐴 = 0.16 𝑚2
𝐴 = 𝑊𝐻 = 4𝐻 2
2 𝐴
𝐻=√
4
𝐻 = 0.2 𝑚
𝑊 = 0.8 𝑚
(𝐻𝑊)0.625
𝐷𝑒𝑞 = (1.3) ( )
(𝐻 + 𝑊)0.25
(0.2 ∗ 0.8)0.625
𝐷𝑒𝑞 = (1.3) ( )
(0.2 + 0.8)0.25
𝐷𝑒𝑞 = 0.4135
∆𝑃 = 0.9 𝑃𝑎/𝑚
∆𝑃𝐵 = 0.9 ∗ 4 = 3.6 𝑃𝑎
CONSIDER DUCT/SECTION C
𝐴
𝑄 =
𝑉
3.4𝑚3 /𝑠
𝐴 =
7 𝑚/𝑠
𝐴 = 0.4857 𝑚2
𝐴 = 𝑊𝐻 = 4𝐻 2
2 𝐴
𝐻=√
4
𝐻 = 0.3485 𝑚
𝑊 = 1.394 𝑚
(𝐻𝑊)0.625
𝐷𝑒𝑞 = (1.3) ( )
(𝐻 + 𝑊)0.25
(0.3485 ∗ 1.394)0.625
𝐷𝑒𝑞 = (1.3) ( )
(0.3485 + 1.394)0.25
𝐷𝑒𝑞 = 0.72
∆𝑃 = 0.9 𝑃𝑎/𝑚
∆𝑃𝐵 = 0.9 ∗ 4 = 3.6 𝑃𝑎