Power factor
Load level phase PF Criteria Pass/fail
20% / 0.9969 >0.85 Pass
50% / 0.9965 >0.95 Pass
100% / 0.9973 >0.95 Pass
Output voltage
The true value(V) Rated Difference Tolerance Pass /
voltage(V) fail
Ab 417.6 400 4.4% +7%, -7% pass
Bc 416 400 4.0% +7%, -7% pass
Ca 416.2 400 4.05% +7%, -7% pass
SAMIL POWER CO., LTD.
Hi-pot test
Grounding test
Insulation test
Others
Conclusion PASS
SAMIL POWER CO., LTD.