Technical Manual of CSI-200E Digital Measuring & Controlling Device
Table of Contents
1 INTRODUCTION...................................................................................................................1
1
Technical Manual of CSI-200E Digital Measuring & Controlling Device
3 HARDWARE COMPONENT..............................................................................................10
5 APPLICATION .....................................................................................................................28
6 MISCELLANEOUS..............................................................................................................29
2
Technical Manual of CSI-200E Digital Measuring & Controlling Device
7 APPENDIX ............................................................................................................................32
3
Technical Manual of CSI-200E Digital Measuring & Controlling Device
1 Introduction
CSI-200E digital measuring and controlling device is usually used
in the substation automation system, but it also may be used as
simple measuring and controlling device.
The device is Bay-oriented designed and mainly used in the
system of 110KV and above. This kind of Bay consists of main
transformer (high, medium, and low voltage), 110KV outgoing line,
220KV outgoing line, 500KV outgoing line, bus connector, transfer
bus, local chamber, the whole substation (the common part in one
substation) and so on.
1
Technical Manual of CSI-200E Digital Measuring & Controlling Device
1.1.8 Synchronization:
Based on different needs, the user can choose
check-synchronization or manual penesynchronization to implement
synchronization.
1.1.10 Auto-backup:
The function of auto-backup of the device may be used optionally
in some small substation.
2
Technical Manual of CSI-200E Digital Measuring & Controlling Device
3
Technical Manual of CSI-200E Digital Measuring & Controlling Device
1.2.7 Self-diagnose:
The device provides full self-diagnose function. Once some piece of
plug-in unit runs abnormally when being used, it can inform the
operator at once and point out where the fault is.
4
Technical Manual of CSI-200E Digital Measuring & Controlling Device
5
Technical Manual of CSI-200E Digital Measuring & Controlling Device
AC MASTER DI DO POWER
6
Technical Manual of CSI-200E Digital Measuring & Controlling Device
2 Technical Parameters
2.1 Rated Data
9 Rated DC voltage input: 220V or 110V (labeled on order list)
Rated DC voltage output:+5V, ±12V, +24V1( applied for output),
+24V2( applied for input)
9 Rated AC data:
AC voltage: 100V
AC current: 5A or 1A(labeled on order list)
Rated frequency: 50HZ
9 Power consumption:
DC loop: 19/2 inches bin: <25W; 19 inches bin: <40W
AC voltage loop: ≤ 0.2VA/ phase
AC current loop: < 0.8VA/ phase(In=5A), ≤0.2VA/phase (In=1A)
9 status variable and impulse variable:
Level: +24V
Width of impulse: ≥10ms
7
Technical Manual of CSI-200E Digital Measuring & Controlling Device
2.5.1 Oscillation
Device may bear oscillating response test and oscillating
enduring test of grade 1, which is defined in section 5.12.4 of
JB/T9568_2000 .
8
Technical Manual of CSI-200E Digital Measuring & Controlling Device
2.5.2 Impact
The device would stand up in the vibration response and
endurance tests of grade 1, which is stated in section 5.12.4 of
JB/T9568-2000.
9
Technical Manual of CSI-200E Digital Measuring & Controlling Device
3 Hardware Component
Hardware and software design of the device is flexible and
tolerance for the purpose of reliability in practical use. Each link is
designed delicately; to make sure it operates stably, reliably and with
strong anti-jamming capability.
Internal structure of the device is shown as Figure3-1.
supervisory
master PC CSI200E
Ethernet
relay of LonWork
Sifang UART1 UART2
Master Pluggalbe
MMI PC
RS485 unit of CSI200E
relay of other
producer
Internal Bus
Power
AI AI DT DT DI DI DO DO
Unit
10
Technical Manual of CSI-200E Digital Measuring & Controlling Device
11
Technical Manual of CSI-200E Digital Measuring & Controlling Device
- band-pass fairing
+ MCU
PT + filter
- loop
12
Technical Manual of CSI-200E Digital Measuring & Controlling Device
- lowpass
+
AC A/D
con- con- MCU
verter verter
module
- lowpass
+
U1a 2 I1 2 1 I1’
U1b 4 I2 4 3 I2’
U1c 6 I3 6 5 I3’
U1n 8 I4 8 7 I4’
U2a 10 10 9
U2b 12 12 11
U2c 14 14 13
U2n 16
U3 18
U3n 20
U4 22
U4n 24
26
28
30
32
Fig3-5: 8U/4I, external connectors
13
Technical Manual of CSI-200E Digital Measuring & Controlling Device
U2c 14 14 13
U2n 16
18
20
22
24
26
28
30
32
Fig3-6: 6U/6I external connector
For synchronization, the remote synchronization voltage should be
connected in two ways:
1. In case of 8U/4I: the opposite corresponding period voltage
should be connected with U2, U3 and U4
2. In case of 6U/6I: the opposite corresponding period voltage
should be connected with U2.
Synchronization LC (logical contactor) and PLC (Program logic
controller) can inform device which connector is connected. It is the
setting table’s duty to decide if the synchronization voltage is a
line-voltage or a phase-voltage.
AC can calculate and decide if the condition of synchronization is
satisfied after receiving the synchronization command. If satisfied, it
would send synchronization close command. If not, it would report the
reason why the condition is not satisfied. For example, remote voltage
is lower or higher, remote frequency is lower or higher, remote
phase-angle is smaller or larger, etc.
14
Technical Manual of CSI-200E Digital Measuring & Controlling Device
FLASH
EEPROM
ethernet MCU
isolated RS485
LonWorks
GPS hard clock
15
Technical Manual of CSI-200E Digital Measuring & Controlling Device
Local functional
operation keys
16
Technical Manual of CSI-200E Digital Measuring & Controlling Device
→Trip
It can be chosen only in the state of outline diagram operation.
→Close
It can be chosen only in the state of outline diagram operation.
√ →Confirm
After trip/close operation, users need to press this key to send
command.
Each trip/close operation needs to be confirmed.
Sifang special keys, which serve as routine interface between the
user and the device, are at the right side of the screen. Their tasks are
as follows:
1. Setting some system information: clock modifying, password
modifying, and LC switching.
2. Checking current value of the device, including current state
of switch, r.m.s. of analog, harmonic, zero-drift, temperature,
etc.
3. Checking stored report, including running report and
operation report. It provides three convenient searching
methods for the user: newest report presenting, time sorting,
date sorting, etc.
4. Checking setting, or to modify.
5. Testing device, such as DO driving, etc. When testing,
messages will not be kept in store.
6. Calling for help, such as version code of a plug-in unit and
operation guide.
7. Configuring system information of the device, such as IP
address and the amount units.
8. Adjusting Contrast of LCD. It will prevent LCD from being
damaged by terrible environment.
9. Measuring and showing the interior temperature, for the
user can easily realize the running state of device.
17
Technical Manual of CSI-200E Digital Measuring & Controlling Device
information of all kind of relays, other common signal, etc. BCD input
includes collecting information of water level, state of tap, etc. Impulse
input includes collecting positive direction active power, reversed
active power, positive direction reactive power and reversed reactive
power, etc.
DI unit can be divided into two types: one with CPU is named
basic unit, the other one without CPU is named extended unit. Both
can be inputted with 24 digital signals, which are divided into four
groups (8+4+8+4). Each group has one common terminal, which can
be connected with each other if needed. Function of each group can be
configured flexibly in order to reduce hardware cost.
Tap position information can only be inputted into the first group
of the first basic DI unit.
Configuration table is defined group by group. The information
character within one group is completely identical. Debounce
time-delay (time of bounce eliminating and time of debounce) of the
device can be divided into two types: long time delay and short time
delay. Unit of the former is 100ms, and unit of the later is 1ms.
Concrete noun is setting by preset value. The time scope of debounce
is from 1ms to 25s
Each DI can be defined as long time delayed class or short time
delayed class. It also can be defined as normal mode (do not generate
SOE record) or SOE (synchronously generate normal state information)
typed mode. Each DI change can drive electrical bell or electrical
alarm, according to the configuration. All above is completed during
the setting process.
DI connection is shown as Figure 3-7.
DI1 2 DI13
DI2 4 DI14
DI3 6 DI15
DI4 8 DI16
1
DI5 DI17
0
1
DI6 DI18
2
18
Technical Manual of CSI-200E Digital Measuring & Controlling Device
1
DI7 DI19
4
1
DI8 DI20
6
1
COM1 COM3
8
2
DI9 DI21
0
2
DI10 DI22
2
2
DI11 DI23
4
2
DI12 DI24
6
2
COM2 COM4
8
3
GPS1
0
3
GPS2
2
Fig3-7: DI connection diagram
19
Technical Manual of CSI-200E Digital Measuring & Controlling Device
c a
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
Fig.3-8 DO terminal connection diagram
isolated op
amplifier
terminal
DC
multi-switch
low-pass
simulated
converter
filter
A/D
MCU
division network
risistor voltage
transmitter
thermo-
isolated op
resistor
amplifier
terminal
Internal
20
Technical Manual of CSI-200E Digital Measuring & Controlling Device
21
Technical Manual of CSI-200E Digital Measuring & Controlling Device
22
Technical Manual of CSI-200E Digital Measuring & Controlling Device
23
Technical Manual of CSI-200E Digital Measuring & Controlling Device
4.4.1 LC Setting
Totally 10 LCs were set for synchronization checking function. See
them as follows:
Synchronization check LC
Non-voltage check LC
Quasi-synchronization check LC
Fixed mode for synchronization node
Synchronization node 12 mode
Synchronization node 13 mode
24
Technical Manual of CSI-200E Digital Measuring & Controlling Device
25
Technical Manual of CSI-200E Digital Measuring & Controlling Device
26
Technical Manual of CSI-200E Digital Measuring & Controlling Device
27
Technical Manual of CSI-200E Digital Measuring & Controlling Device
5 Application
5.1 Typical Configuration
Because of the remarkable flexibility of CSI-200E, a typical line
configuration scheme is bay-oriented. According to practical
requirement, 25 optional typical configuration schemes are present as
shown in appendix table 1.
28
Technical Manual of CSI-200E Digital Measuring & Controlling Device
6 Miscellaneous
6.1 Device Inner Module Structure and Dimension
Double DI
Single DI
19/2 inch
AC unit
AC unit
19 inch
DT DC
Master
Master
Master
Power
8U4I
6U6I
case
case
DO
-A
-B
-C
Width
84 40 12 12 8 8 8 8 4 4 4 6
(TE)
Width 60.9 60.9 40.6 40.6 40.6 20.3 30.6
426 203 40.64 20.32 20.32
(mm) 6 6 4 4 4 2 4
1TE=5.08mm
NOTE:If there are more than 1 Master unit in 19/2 inches case, the
width of Master A should be 8TE, and the others should be 6TE.
order
(from left to Unit
right)
1 AC
2 MASTER-A
3 MASTER-B
4 MASTER-C
5 Double DI
6 Single DI
7 DO
8 DT
9 Power
29
Technical Manual of CSI-200E Digital Measuring & Controlling Device
30
Technical Manual of CSI-200E Digital Measuring & Controlling Device
6.5 Contact Us
Address:9#, 4th Avenue, Shangdi, Haidian District,
Beijing, 100085
P. R. China
Tel:Marketing Dept: +86-10-62985012 FAX: +86-10-62978952
Tech Support Dept:+86-10-62986668 FAX: +86-10-62981900
31
Technical Manual of CSI-200E Digital Measuring & Controlling Device
7 Appendix
Table 1: CSI-200E representative model and ordering code
AI Doub Singl
MASTER -A DO Ordering code
le DI e DI TM
MAST MAST Cas
Index Model Description MPower
ER -B ER -C e
I
8U4I 6U6I 48 24 14 5
A B M N L I J O T P X Module Code
Line bay of 3/2
connection; 500kv side of
main transformer of 3/2
connection; 110kv(66kv)
side of main transformer
in dual network station,
fewer I/O required; 35kv 5A,220V:
CSI-200E/1 side of main transformer 19/ A15M10N10J10O10P12X12
1 1 1 1 1 1 1
in dual network 2” 1A,110V:
sub-station; bay of 110kV A11M10N10J10O10P11X12
(66kV) line/transfer
bus/bus connector, in a
dual network bus
connection; bay of 220kv
bus connector/segment
on dual network; other
32
Technical Manual of CSI-200E Digital Measuring & Controlling Device
33
Technical Manual of CSI-200E Digital Measuring & Controlling Device
X11
34
Technical Manual of CSI-200E Digital Measuring & Controlling Device
35
Technical Manual of CSI-200E Digital Measuring & Controlling Device
5A,220V:
Common bay on single
B25M10I10O10T10P12X11
14 CSI-200E/14 network for whole 2 1 1 1 1 19”
1A,110V:
sub-station
B21M10I10O10T10P11X11
5A,220V:
Common bay on dual A25M10N10I10O10T10P12
network for whole X11
15 CSI-200E/15 2 1 1 1 1 1 19”
sub-station, more AIs are 1A,110V:
required. A21M10N10I10O10T10P11
X11
Bay of breaker for 3/2
connection
(500kV/330kV); 220kv 5A,220V:
CSI-200E/16 side of main transformer A15M10N10I10O20P12X11
16 1 1 1 1 2 1 19”
*** (dual bus connection); 1A,110V:
bay of line/ transfer bus A11M10N10I10O20P11X11
on 220KV dual bus
connection.
Bay of breaker for 3/2
5A,220V:
connection
A15M10N10I10J10O20P12
(500kV/330kV); bay of
CSI-200E/17 X11
17 line/ transfer bus on 1 1 1 1 1 2 1 19”
*** 1A,110V:
220KV dual bus
A11M10N10I10J10O20P11
connection, more DIs are
X11
required.
36
Technical Manual of CSI-200E Digital Measuring & Controlling Device
37
Technical Manual of CSI-200E Digital Measuring & Controlling Device
5A,220V:
Common used for main
A15M10N10J10O10T30P12
transformer of 220KV
22 CSI-200E/22 1 1 1 1 1 3 1 19” X11 1A,110V:
and above, analogs are
A11M10N10J10O10T30P11
required.
X11
5A,220V:
Common used for local
A25M10N10J10T10P12X11
23 CSI-200E/23 chamber, less plug-in 2 1 1 1 1 19”
1A,110V:
unit than CSI-200E/7.
A21M10N10J10T10P11X11
Common used; both 5A,220V:
sides of main A25M10N10I10O10P12X11
24 CSI-200E/24 2 1 1 1 1 1 19”
transformer; less DTs 1A,110V:
than CSI-200E/15 A21M10N10I10O10P11X11
5A,220V:
A35M10N10I10O20T10P12
Common used; more X11
25 CSI-200E/25 3 1 1 1 2 1 19”
analog inputs. 1A,110V:
A31M10N10I10O20T10P11
X11
38
Technical Manual of CSI-200E Digital Measuring & Controlling Device