You are on page 1of 2

Protection and Control IED Manager 1MRS756450

PCM600 Issued: 11.12.2007


Version: L/20.11.2013

INSTALLATION GUIDE
Related items
PCM600 Ver. 2.6 Installation CD

PCM600 Ver. 2.6 Setup can be downloaded from https://www143.abb.com/SoftwareLibrary

Content on CD
 PCM600 Setup
 PCM600 Ver. 2.6 Readme file
 PCM600 Ver. 2.6 Installation Guide
 PCM600 Ver. 2.6 Product Guide

PCM600 Setup includes the following software:


 Protection and Control IED Manager PCM600 Ver. 2.6
 Generic IEC 61850 IED Connectivity Package Ver. 2.4
 Adobe® Reader® XI
 Wavewin Tool for Disturbance Analysis

System requirements Framework 3.5 SP1, which will also be installed


(on Windows XP/Server 2003/ Vista). Windows
Operating system (32-bit versions): Windows XP
Installer 4.5 requires a reboot.
SP3, Server 2003 SP2, Windows Vista SP2,
Windows 7 (32-bit/64-bit), Windows 8/8.1 (32-
When installing PCM600 on Windows 8 or 8.1, a
bit/64-bit)
network connection is mandatory. The reason for
Hardware requirements, this is that .NET Framework 3.5 SP1 is only
minimum/recommended: available from Windows Update in Windows 8 and
8.1.
Physical RAM memory: 2 GB / 3 GB
Free hard disk space: 2 GB / 4 GB Installing a Windows language pack in Windows 8
Processor: 1.0 GHz / 2.2 GHz or 8.1 before installing the .NET Framework 3.5
will cause the .NET Framework 3.5 installation to
Windows compatible pointer (e.g. mouse) fail. Install the .NET Framework 3.5 before
installing any Windows language packs.
How to install PCM600 Ver. 2.6
a) CD Installation: Installation requires administrator rights. In all
Insert the installation CD into the CD-drive. If the versions of Windows it might be necessary to
setup doesn’t start automatically, execute switch off or configure antivirus software to not
setup.exe in the root folder of the installation CD. block the installation and operation of PCM600
(e.g. McAfee Host Intrusion Prevention).
b) Downloaded from ABB Software Library:
After free registration, you will get an email with a Prerequisites for using PCM600 Ver. 2.6
link to download the executable installation. Start To operate with PCM600, there must be at least
the installation and follow the instructions. one IED Connectivity Package installed and
selected to be used with PCM600 Ver. 2.6.
After the installation starts, select the needed soft-
ware components and follow the instructions to License
complete the installation.
There is no license required for PCM600 Ver. 2.6.
PCM600 requires Microsoft SQL Server 2008
Express edition. The correct SQL Server instance IEC 61850 communication configuration
will be installed automatically. If the correct SQL
Server instance is already installed, the PCM600 Separate IEC 61850 communication configuration
installation will skip this step. The SQL Server software can be purchased through ABB sales
requires Windows Installer 4.5 and .NET representatives.

1
Protection and Control IED Manager 1MRS756450
PCM600 Issued: 11.12.2007
Version: L/20.11.2013

Previous versions of PCM600 SQL Server Express 2008 R2 and later versions
PCM600 2.6 can be installed in parallel with a
PCM600 is not compatible with SQL Server
previous version. If you only want to use PCM600
Express 2008 R2 or later versions of the SQL
2.6, you should uninstall the previous version of
Server such as SQL Server 2012. The PCM600
PCM600 before installing PCM600 2.6. PCM600
SQL Server instance should not be upgraded to
2.6 must be installed after installing the previous
SQL Express 2008 R2 or later. The previously
version. E.g. PCM600 2.5 cannot be installed on
mentioned SQLInstaller utility can be used to
top of PCM600 2.6.
uninstall SQL Express 2008 R2 and reinstall the
correct SQL Server instance.
If PCM600 2.5 or an older version is uninstalled
after PCM600 2.6 has been installed, PCM600 2.6
will be broken and must be repaired. This can be
done through Control Panel and Add and Remove Disclaimer
Programs (Uninstall a Program in Windows 7).
The information in this document is subject to change without
notice and should not be construed as a commitment by ABB
Note that the Lifecycle Service Tool will only work Oy. ABB Oy assumes no responsibility for any errors that may
with one version of PCM600. If you want to appear in this document.
operate the Lifecycle Service Tool with a previous © Copyright 2013 ABB Oy
version of PCM600 (e.g. PCM600 2.5), please
uncheck the Lifecycle Service Tool in the PCM600 All rights reserved.
2.6 installation dialog.
Trademarks

When opening projects in PCM600 2.6 that have ABB is a registered trademark of ABB Group. All other brand or
product names mentioned in this document may be trademarks
been created with previous versions of PCM600, or registered trademarks of their respective holders.
the projects will be converted automatically. After
project conversion, the projects can't be opened
with older PCM600 versions anymore.

In order to migrate IED 670 configuration from


PCM600 Ver. 1.5 to 2.6 (the whole PCM600
project including all IEDs in the project), please
refer to the document “1MRG002586 -
Configuration Migration for 670 series in PCM600
User Manual", that can be found on the 670 series
ConnPack DVD.

Changing SQL Server


It is possible to change the SQL Server from SQL
Server 2000 (from a previous installation of
PCM600) to SQL Server Express 2008, or vice
versa, using a setup utility that is included on the
CD. To launch the utility, insert the CD into the PC
where you want to change the SQL Server,
browse to the directory UTILITIES on the CD,
double-click the file SQLInstaller.exe and follow
the instructions. Before doing this, make an export
or backup of projects.

The utility can also be downloaded from ABB


Substation Automation Software Library,
https://www143.abb.com/SoftwareLibrary.

NOTE: As of April 8, 2008, Microsoft has retired


mainstream support of SQL Server 2000. It is not
compatible with Windows Vista, Windows 7 or later
operating systems.