victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
C1*
G G1*
*B1
A B
A1*
K
F L
E H J
E1*
Approx.
Weight
Dimensions Each
Actual
Nominal Outside Without With
Size Diameter A A11 B B11 C11 D E E11 F G G11 H J K L Trim Trim
inches inches inches inches inches inches inches inches inches inches inches inches inches inches inches inches inches lbs. lbs.
mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm kg kg
1 1/2 1.900 9.00 16.35 27.50 34.50 16.50 9.75 12.50 15.00 15.75 9.25 11.25 10.20 8.50 3.04 6.98 16.7 43.0
40 48.3 228.60 415.29 698 876 419 247 317 381 400 234 285 259.08 215.90 77.21 177.29 7.6 19.5
2 2.375 9.00 13.37 27.50 34.50 16.50 9.75 12.50 15.00 15.75 9.25 11.25 10.20 8.53 3.04 6.98 17.0 43.0
50 60.3 228.60 339.60 698 876 419 247 317 381 400 234 285 259.08 216.66 77.21 177.29 7.7 19.5
3.000 12.61 16.44 31.75 44.25 21.25 11.25 14.50 18.25 16.75 10.00 9.75 10.65 9.04 3.76 6.69 41.0 65.0
76.1 mm
76.1 320.29 417.57 806 1123 539 285 368 463 425 254 247 270.51 229.61 95.50 169.92 18.7 29.5
3 3.500 12.61 16.50 31.75 44.25 21.25 11.25 14.50 18.75 16.75 10.00 9.75 10.65 9.04 3.76 6.69 41.0 65.0
80 88.9 320.29 419.10 806 1123 539 285 368 476 425 254 247 270.51 229.61 95.50 169.92 18.7 29.5
4 4.500 15.03 19.83 32.75 45.50 21.00 10.25 16.00 20.75 15.50 11.25 10.75 13.54 9.56 6.06 8.46 59.0 95.0
100 114.3 381.76 503.68 831 1155 533 260 406 527 393 285 273 343.91 242.82 153.92 214.88 26.7 43.0
6.500 16.00 22.00 33.00 45.75 20.00 10.25 17.25 22.25 15.75 11.50 11.00 13.46 9.94 6.06 8.38 80.0 116.0
165.1 mm
165.1 406.40 558.80 838 1162 508 260 438 565 400 292 279 341.88 252.47 153.92 212.85 36.2 52.6
8 8.625 17.50 23.00 33.00 45.75 18.75 10.00 19.00 24.25 16.00 11.75 11.00 14.80 11.00 6.06 9.72 122.0 158.0
200 219.1 444.50 584.20 838 1162 476 254 482 615 406 298 279 375.92 279.40 153.92 246.88 55.3 71.6
NOTES:
The “A” dimension coupling is not shown in order to clarify dimensional callouts.
Optional drain connection kit is shown for reference and takeout dimensions.
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 3
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
Performance:
6.0
5.0
4.0
3.0
mm
mm
5.1
.1m
50
16
76
2"/
0mm
2.0
and
d
PRESSURE DROP – PSI
an
8"/20
m
m
mm
m
0m
mm
0m
0m
5
"/4
"/6
15
80
10
1½
2½
6"/
3"/
4 "/
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
10 20 30 40 60 80 100 200 300 400 600 1,000 2,000 4,000 6,000 10,000 20,000
800 3,000 8,000
FLOW RATE – GPM
Frictional Resistance
The chart below expresses the frictional resistance of
Victaulic Series 764 FireLock NXT.
Alternate Valve in equivalent feet of straight pipe.
Actual Equivalent
Nominal Outside Length of
Size Diameter Pipe
inches inches feet
mm mm meters
1 1/2 1.900 3.00
40 48.3 0.914
2 2.375 9.00
50 60.3 2.743
3.000 8.00
76.1 mm
76.1 2.438
3 3.500 17.00
80 88.9 5.182
4 4.500 21.00
100 114.3 6.401
6.500 22.00
165.1 mm
165.1 6.711
8 8.625 50.00
200 219.1 15.240
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 4
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
CV Values: Operation:
CV values for flow of water at +60°F/+16°C through a fully The Series 764 Alternate Wet/Dry Valve contains a
open valve are shown in the table below. clapper, which has a replaceable rubber seal. The
clapper makes contact with the valve’s seat ring, which
Formulas for CV values Where: has access holes leading into an intermediate chamber
ΔP = Q /CV
2 2 Flow Coefficient Cv in the valve. When the valve opens and the clapper
Q (Flow) GPM
lifts, water enters the intermediate chamber of the valve
Q = CV × √ΔP
through the holes in the seat ring. The water flows
ΔP (Pressure Drop) psi
from the intermediate chamber to the alarm line, which
activates the system’s alarms. The alarms continue to
sound until the flow of water stops. When the flow of
water stops, the spring-assisted valve clapper returns to
the closed position. The Series 764 can be configured
Valve Size Full Open
for use with wet or dry systems by simply adjusting four
Actual
Nominal Outside valves.
Size Diameter Flow Coefficient Operation when used in the dry valve configuration:
inches inches Cv
mm mm Kv When the valve is set up, a direct acting diaphragm
1 1/2 1.900 60 contacts the latch, and the latch holds the clapper in
40 48.3 52.0
the closed position. The valve diaphragm is maintained
2 2.375 110
50 60.3 95.0
in the extended position by the water supply pressure
2 1/2 2.875 180
from upstream of the water supply control valve. The
65 73.0 156.0 Series 776 Low Pressure Actuator (LPA) maintains the
76.1 mm
3.000 180 water pressure in the diaphragm chamber. The actuator
76.1 156.0 is held closed by the system air pressure. The minimum
3 3.500 200 required system air pressure is 90 kPa/13 psi. Excess air
80 88.9 173.0
4 4.500 350
pressure above 90 kPa/13 psi will cause a delay in valve
100 114.3 302.8 operation. Once the system’s air pressure reduces to the
165.1 mm
6.500 1000 trip point of 48 kPa/7 psi (i.e. an open sprinkler), the
165.1 865.0 LPA opens and allows the water supply pressure in the
8 8.625 1500 diaphragm to release. This release allows the latch to
200 219.1 1499.1
retract and permits the clapper to pivot freely, thus
allowing water into the system and the intermediate
chamber through the holes in the seat ring. The water
flows from the intermediate chamber to the alarm line
and activates the system’s alarms. These alarms continue
to sound until the flow of water stops. The valve acts as
an alarm check valve until the system is back in service
as a dry system, according to the proper procedure.
Operation when used in the wet valve configuration:
When the valve is placed in service, the valve traps water
pressure above the clapper and prevents the reverse
flow of water. Minor pressure surges pass through the
bypass loop without lifting the clapper from its seat. The
swing check valve in the bypass line traps the pressure
above the clapper; this can be observed in the pressure
gauges. The system-side water pressure will always be
equal to or greater than the supply-side water pressure
in the absence of an open sprinkler. When a sustained
flow of water occurs, such as an activated sprinkler or
an open inspector’s test connection, the clapper lifts
from its closed position; this allows water to flow into the
system and the intermediate chamber through the holes
in the seat ring. The water flows from the intermediate
chamber to the alarm line and activates the system’s
alarms. These alarms continue to sound until the flow of
water stops.
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 5
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
Material Specifications:
Bill of Materials
1 Valve Body 12 Cover Plate
2 Clapper 13 Cover Plate Gasket
3 Clapper Seal 14 Cover Plate Bolts*
4 Seal Ring 15 Latch
5 Seal Washer 16 Latch Spring
6 Seal Retaining Ring 17 Latch Spring Bushing and O-ring (Qty. 2)
7 Seal Assembly Bolt 18 Diaphragm
8 Bolt Seal 19 Diaphragm Cover
9 Clapper Spring 20 Diaphragm Cover Cap Screws (Qty. 8)
10 Clapper Shaft 21 Latch Shaft
11 Clapper Shaft Bushing and O-ring (Qty. 2) 20
19
18
17
11
1 21
17
15
16
2
10
11
3
4
9
13
12
5
14
6
8
7
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 6
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 7
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
Compressor Sizing:
COMPRESSOR REQUIREMENTS
12
20 psi/138 kPa
13 psi/90 kPa
10
REQUIRED FLOW RATE (CFM)
0
1050
1300
1550
1800
300
550
800
50
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 8
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
Bill of Materials
1 1⁄8"/3.2 mm Restrictor
2 Slow Fill Ball Valve (Normally Open)
3 Air Regulator
4 Strainer (100 Mesh)
5 Spring-Loaded, Soft-Seated
Ball Check Valve 1
6
6 Fast Fill Ball Valve (Normally Closed)
2
4
5
Bill of Materials
1 1⁄8-inch/3.2-mm Restrictor
2 Pressure Switch
3 Slow Fill Ball Valve (Normally Open)
4 Fast Fill Ball Valve (Normally Closed)
5 Strainer (100 Mesh)
6 Spring-Loaded, Soft-Seated
Ball Check Valve 2
6
3
1
4
5
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 9
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 10
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
Bill of Materials
1 Series 764 FireLock NXT Alternate
Wet/Dry Valve
2 FireLock Rigid Coupling (Optional/Sold
Separately – Comes Standard when VQR 14a
Assembly is Ordered) Remove trim from this point up when 18
3 Water Supply Main Control Valve installing the optional dry accelerator.
14
The air gauge (Item 18) must remain in place.
(Optional/Sold Separately – Comes Add a tee to the accelerator to
14b
Standard when VQR Assembly is Ordered) re-position the air gauge
30.83 4630 Rev B Updated 01/2015 © 2015 Victaulic Company. All rights reserved.
victaulic.com 11
victaulic.com | NXT Alternate Wet/Dry Valve | Series 764 | Publication 30.83
WARNING
Failure to follow these instructions may result in serious personal injury, property
damage, or valve leakage.
If you need additional copies of this product literature or the valve installation
instructions, or if you have any questions about the safe installation and use of this
device, contact Victaulic Company, P.O. Box 31, Easton, PA 18044-0031 USA,
Telephone: 001-610-559-3300.
Installation Note
Reference should always be made to the appropriate Installation, Maintenance, and This product shall be manufactured by Victaulic or to Victaulic specifications. All products
Testing Manual included with each shipment of Victaulic products. These manuals are also to be installed in accordance with current Victaulic installation/assembly instructions.
available in PDF format on our website at victaulic.com Victaulic reserves the right to change product specifications, designs and standard
equipment without notice and without incurring obligations.
Warranty
Refer to the Warranty section of the current Price List or contact Victaulic for details. Trademarks
Victaulic ® and FireLock® are registered trademarks of Victaulic Company.