Wall-Mounted Panel Board

Featuring The SafePanel™

The Series 70 ePanel-1


Safe & Reliable Power
Distribution
The Series 70 ePanel-1 is a 42-circuit wall-mounted panel board with an

emphasis on safety and reliability, designed for critical facilities with a

need for high-reliability electrical power. LayerZero ePanels panel boards

protect power at the circuit breaker level, preventing individual branches

from impacting the critical power load with selective trip coordination.

The space saving design of Series 70 ePanels mounts against the wall,

appropriate for computer rooms, electrical rooms, or raised data center

floors.

The NFPA-70 inspired design protects operators from exposure to live

bus, and units feature non-conducting branch breaker bolt-on screws.

Series 70 ePanels provide selective tripping coordination up to 25kAIC for

branch circuits, with branch breakers that trip open in less than ¼ cycle.
High-Speed Fast-Acting Breakers
Remote monitoring is accessible utilizing open protocols such as TCP/IP, - Clears A Downstream Fault In 2 ms
SNMP, http://, and Bluetooth. - Overcurrent Protection

Innovative Safety Features

- IP-20 “Finger-Safe” Panel Board

- Fully Encapsulated Copper Bus


> 1”
- Isolated Breaker Mounting Bolt-On Screws

- Breaker Plug-in Well Is Over 1 Inch Deep

Selective Trip Coordinated

- Assures that the branch circuit breaker will clear the

Breaker Installation fault and not let the main circuit breaker open
Is Safe, Fast, & Easy
- Assures that the power to the remaining circuits is

unaffected
Electrical Configurations Mechanical Configurations

SafePanel 242: 225A, 42-circuit • Wall-Mounted


• Door-in-door construction
225A, 100% rated fixed mount main CB
» Hinged inner doors for safety
225A, 100% rated plug-in main CB option » Two separate inner doors
a. Branch circuit panel inner door for normal panel board
loading and wiring
SafePanel 442: 400A, 42-circuit
b. Main Circuit breaker inner door for installation and
400A, 100% rated fixed mount main CB maintenance access
400A, 100% rated plug-in main CB option » Hinged outer door
• Viewing window on outer door for branch circuit breakers and
main circuit breaker position view
Voltage configurations:
• Viewing windows on doors
480V, 3-wire: 14kAIC • Top main cable access
480Y/277V, 415Y/240V, 400Y/230V, 380Y/220V: 14kAIC • Top/Bottom branch cable access
• Circuit identification tags on panel board
208Y/120V: 25kAIC
• Plug-in main circuit breaker is optional
• Input feeder connection options:
Enclosures sized to accommodate 75 °C feeders » Single mechanical lug
» Dual mechanical lug (accepts two conductors per phase)
» NEMA 2-hole studs for long-barrel, 2-hole compression lugs
NRTL Listing To UL 67, UL 50

Panel Board Main CB Enclosure Enclosure Height Enclosure


& Main CB Mounting Width Input Feeder Termination Depth
Rating
Single, Dual, Two-Hole,
Mechanical Mechanical Compression
225A Fixed 20"W 60"H 60"H 70"H 6.75"D
400A Fixed 20"W 60"H 60"H 70"H 6.75"D
225A Plug-in 20"W 60"H 60"H 70"H 8.25"D Main Bus Voltage Waveform Capture
of an short-duration (3-cycle) under-
400A Plug-in 20"W 70"H 70"H 70"H 8.25"D voltage event.

Power Monitoring Option Connectivity Option


To support the total needs of an increasingly information centric Each panel board is equipped with the ability to communicate
critical power distribution environment, the Series 70 ePanel may measured information remotely to the Building Management
be optionally equipped with a branch circuit level and panel board
System using open protocols. The connectivity is Ethernet based
main circuit power monitoring. The Panel Board Branch Power
Monitor allows site management to monitor power consumption. and the design is plug-and-play. Each panel board is assigned a
This provides information that is increasingly vital to the revenue fixed IP address. Information is accessed via:
model of many data processing units.

• Web-browser (http://) service


In addition to measuring the main bus voltage of the panel board
and delivering Waveform Capture upon anomaly of main bus • MODBUS TCP/IP service
voltage, the power monitor measures the following parameters for • SNMP service
each of the 42 branch circuits in a given panel board:
• Bluetooth
• Current (A)
• Frequency (Hz)
• Power (kW)
• Apparent Power (kVA) Copyright © 2010
• Power Factor LayerZero Power Systems, Inc.
All rights reserved.
• Power Consumption (kW-H) Subject to change without notice.
• Waveform Capture Upon Overcurrent At Any Branch
• Waveforms Capture records 12-cycles of when a Power
Quality anomaly is detected on the Main Bus. 440-399-9000 • www.LayerZero.com