You are on page 1of 18

Chapter 12

Tables and Overviews


12.1 Supply Network Operators in Germany
and Ripple Control Frequencies 192
12.2 Cable Cross Sections and Lengths
Depending on the Applied Motor 192
12.3 Utilization Categories acc. to
DIN EN 60947-4-1, 3, 5-1
(VDE 0660 Parts 102, 107 and 200) 193
12.4 Rated Currents and Initial Symmetrical
Short-circuit Currents of Three-phase
Distribution Transformers
with 50 up to 3,150 kVA 194
12.5 Fire Loads and Heating Values
for Fire Protection Rating 195
12.6 Planning with Software Support 196
12.7 Terms and Definitions 198
12.8 Abbreviations 201
12.9 Contents: Application Manual –
Part 2: Draft Planning 2007 202
12 Tables and Overviews

12.1 Supply Network Operators 12.2 Cable Cross Sections and Lengths
in Germany and Ripple Control Depending on the Applied Motor
Frequencies A good overview of cable lengths and cable cross sections
depending on the motor applied is provided by the “selec-
An overview of the ripple control frequencies in Germany, tion slider” for load feeders on the web pages of the
Austria and Switzerland sorted by the locations of supply Siemens AG. At: https://mall.automation.siemens.com the
network operators can be found on the Internet at the site Siemens Mall is accessed. After a country has been chosen,
address www.rundsteuerung.de. the “configurators’ list” in the next window will take the
user to the available configurators. Under the Drive Tech-
The supply network operators determine the “Technical nology item, the Load Feeder configurator (selection
supply conditions for connection to the low-voltage grid” slider) is available. If this configurator is selected, motor
in their supply area and ripple control frequencies must be feeders can be configured with their known data in the
taken into account when designing a compensation Configuration window (Photo 122/1). When the configura-
system. tion has been completed, the Circuit Diagram tab shows
the relevant configuration results.

The cable cross section is shown at item “12)”, permissible


cable lengths at items “14)”, “15)”, “16)”. More information
on the individual items can be found in the footnote
descriptions for the individual items. These explanatory
footnotes are displayed when the respective item numbers
at the column margin next to the circuit diagram are
clicked.

12
Photo 122/1: Configuration of a motor feeder

192 Totally Integrated Power – Tables and Overviews


12.3 Utilization Categories acc. to
DIN EN 60947-4-1, 3, 5-1 (VDE 0660
Parts 102, 107 and 200)

Alternating current Direct current DIN VDE IEC


Utilization Typical application Utilization Typical application 0660 Part 60947 Part
category category
AC 1 Non-inductive or low-inductive load, DC-1 Non-inductive or low-inductive load, 102 4
resistance furnaces resistance furnaces
AC-12 1) Control of ohmic load and DC-12 Control of ohmic load and 200 5
semiconductor load in input circuits of semiconductor load in input circuits of
optocouplers optocouplers

AC -13 Control of ohmic load and DC-13 1) Control of electromagnets 200 5


semiconductor load with transformer
isolation
AC -14 Control of small electromagnetic load DC-14 Control of electromagnetic load with 200 5
(max. 72 VA) economy resistances in the circuit
AC -15 Control of electromagnetic load (greater – – 200 5
than 72 VA)
AC -2 Slip-ring motors: starting, switching off – – 102 4
AC -20 Closing and opening at no load DC-20 Closing and opening at no load 107 3
AC -21 Switching of ohmic load including DC-21 Switching of ohmic load including 107 3
moderate overload moderate overload
AC -22 Switching of mixed ohmic and inductive DC-22 Switching of mixed ohmic and inductive 107 3
load including moderate overload load including moderate overload (e.g.
shunt motors)
AC -23 Switching of motor loads or other high- DC-23 Switching of heavily inductive loads 107 3
inductive loads (e.g. series-wound motors)
AC -3 Squirrel-cage motors: starting, DC-3 Shunt motors: starting, reversal braking 102 4
switching off during motor running 4) 2),reversing 2), jogging 3), dynamic
braking
AC -4 Squirrel-cage motors: starting, reversal DC-5 Series-wound motors: starting, reversal 102 4
braking 2), reversing 2), jogging 3) braking 2), reversing, jogging 2),
dynamic braking
AC-5a Switching of gas-discharge lamps 102 4
AC-5b Switching of incandescent lamps DC-6 Switching of incandescent lamps 102 4
AC-6a Switching of transformers
AC-6b Switching of capacitor banks
AC-7a Low-inductive load in household 1) DIN EN 60 947 (VDE 0660) transforms AC-11 into AC-15 and DC-11 into DC-13.
appliances and similar applications 2) Reversal braking or motor reversing is the fast braking or reversing of the rotational direction
AC-7b Motor load for household appliances by swapping two feeder lines when the motor is running.
3) Jogging means the one-time or repeated short-time on-switching of a motor in order to effect
AC-8a Switching of hermetically sealed cooling small movements of machines.
compressor motors with manual reset 4) The equipment may be used for occasional jogging or reversal braking during a limited period
of the overload release 5) of time, the number of actuations must not exceed 5/min and 10/10 min.
AC-8b Switching of hermetically sealed cooling 5) With hermetically sealed cooling compressor motors, the compressor and motor are sealed in
compressor motors with automatic reset the same casing without an outer shaft or shaft sealing, and the motor is operated in the
of the overload release 5) cooling agent.

12
Totally Integrated Power – Tables and Overviews 193
12.4 Rated Currents and Initial
Symmetrical Short-circuit Currents
of Three-phase Distribution
Transformers with 50 up to 3,150 kVA

Rated voltage UrT 400/230 V, 50 Hz 525 V, 50 Hz 690/400 V, 50 Hz


Rated value of short-
4 % 1) 6 % 2) 4 % 1) 6 % 2) 4 % 1) 6 % 2)
circuit voltage ukr
Rated power SrT Rated current Initial symmetrical Rated current Initial symmetrical Rated current Initial symmetrical
Ir short-circuit current Ir short-circuit current Ir short-circuit current
Ik" 3) Ik" 3) Ik" 3)
[kVA] [A] [A] [A] [A] [A] [A] [A] [A] [A]
50 72 1,936 1,307 55 1,475 996 42 1,122 758
100 144 3,879 2,618 110 2,956 1,995 84 2,249 1,518
125 180 4,850 3,274 137 3,695 2,494 105 2,812 1,898
160 231 6,211 4,191 176 4,732 3,193 134 3,600 2,430
200 289 7,767 5,241 220 5,917 3,993 167 4,502 3,038
250 361 9,712 6,553 275 7,399 4,993 209 5,630 3,799
315 455 12,241 8,258 346 9,326 6,292 264 7,096 4,787
400 577 15,544 10,486 440 11,843 7,989 335 9,011 6,079
500 722 19,427 13,106 550 14,801 9,985 418 11,262 7,598
630 909 24,481 16,517 693 18,652 12,584 527 14,192 9,575
800 1,155 31,093 20,976 880 23,690 15,982 669 18,025 12,160
1,000 1,443 38,872 26,222 1,100 29,617 19,979 837 22,534 15,201
1,250 1,804 – 32,780 1,375 – 24,975 1,046 – 19,003
1,600 2,309 – 41,962 1,760 – 31,971 1,339 – 24,326
2,000 2887 – 52,451 2,199 – 39,963 1,673 – 30,407
2,500 3,608 – 65,567 2,749 – 49,956 2092 – 38,010
3,150 4,547 – 82,612 3,464 – 62,942 2,636 – 47,891
1) ukr = 4 %, standardized acc. to DIN 42503 for SrT = 50 ... 630 kVA
2) ukr = 6 %, standardized acc. to DIN 42511 for SrT = 100 ... 1,600 kVA
3) Ik Unaffected initial symmetrical transformer short-circuit AC current without system source impedance taking the voltage factor (C = 1.1)
and the correction factor of the transformer impedance acc. to DIN EN 60909/DIN VDE 0102 (July 2002) into account

Table 124/1: Initial symmetrical short-circuit current Ik (3-pole) acc. to DIN EN 60909 or VDE 0102:2002 without taking the system source
impedance into account

Approximation formula
Rated transformer current Transformer short-circuit AC current
In [A] = k × SrT [kVA] Ik" = In / ukr × 100 [A] × 1.1 400 V / k = 1.45
525 V / k = 1.1
690 V / k = 0.84

Table 124/2: Approximation formulae for rated and short-circuit AC current

12
194 Totally Integrated Power – Tables and Overviews
12.5 Fire Loads and Heating Values for
Fire Protection Rating
Correction factor for advance determination of
Ik (3-pole) acc. to DIN EN 60909 taking the system source In Germany, like in other countries, there are guidelines
impedance into account and building regulations to ensure fire safety. The basis of
all these regulations is an implicit risk evaluation, which
means that the building's fire risk is socially acceptable if
regulations have been observed. Social goals of protection
Sk" [MVA]
Sk"
Factor = ――――――――――― are as follows:
SrT [MVA]
Sk" [MVA] + 1.1 × ――――
ukr [%] . Safety of people (including the fire brigade)
. Protection of the adjacent buildings and the
Example: Transformer 1,000 kVA/4 % environment
at Sk" = 250 MVA
SrT Transformer
. Preventing component failure during a defined period
250 MVA of time (sufficient time for evacuation and fire-fighting).
ukr Transformer Factor = ―――――――――
1 MVA The basis for risk evaluation is the DIN 18230 “Structural
250 MVA + 1.1 × ―――
4% fire protection in industrial buildings.” This standard lists,
250 MVA among other things, the storage density, burnup factor,
Factor = ―――――
277.5 MVA heating value and the area-related fire load.

Ik" (3-pole) Factor = 0.9 More tables on the issue of fire loads and heating values
can be found on the Internet at www.bauen-mit-stahl.de.
Ik" (3-pole) without system source impedance = 41,272 A
41,272 A × 0.9 = 37,145 A

Fig. 124/1: Model calculation for correction factors

With 250 MVA short-circuit power of the upstream


medium-voltage network, the initial symmetrical short-
circuit AC current of the above transformer (Fig. 124/1) is
reduced by the factor 0.9.

12
Totally Integrated Power – Tables and Overviews 195
12.6 Planning with Software Support SIMARIS project
The free SIMARIS project software, which is tailored to the
needs of planners, enables a quick overview of the budget
12.6.1 SIMARIS® Software Tools
and the space requirements inside the building for power
The SIMARIS software family can be used to calculate distribution systems from the medium voltage level to the
electrical power distribution reliably and the necessary distribution board for installations. After the project tree
devices and distribution boards can be determined. The has been created, it is sufficient to select the required
SIMARIS tool family is specially suited for electrical plan- devices per installation – without detailed knowledge of
ning ranging from the determination of basic data to devices or order numbers. The optimal distribution board
tendering: systems are automatically determined and equipped with
devices. The software factors in wiring, control, measure-
. SIMARIS design for network calculations and ment etc. automatically. If a network diagram is imported
dimensioning
from SIMARIS design, device selection can be omitted.
. SIMARIS project for calculating the space requirements Moreover, the software provides options for a subsequent
of the distribution boards and the budget optimization or change of systems.

. SIMARIS curves for comparing characteristic time- For cost finding and further project support, e.g. for pre-
current curves and displaying cut-off current and
paring alternative installations, the project file shall be
let-through energy curves
passed on to the responsible contact partner. There are
Tool use does not require any special knowledge of various output options for documentation purposes.
Siemens products and systems, as they are automatically
determined by the software based on user specifications. More detailed information on SIMARIS design can be
Each software tool can be used individually. Project data obtained from your local Siemens contact and on the
can be exchanged for the purpose of efficiency increase. Internet at www.siemens.com/simarisproject

SIMARIS design SIMARIS curves

Based on the requirements of the specific power distribu- The free SIMARIS curves software enables the comparison
tion system, the SIMARIS design dimensioning software between characteristic tripping curves of low-voltage
safely and reliably dimensions a system solution from a protective devices and fuses (IEC) made by Siemens. Possi-
broad product portfolio, in compliance with all relevant ble parameter settings at protective devices can be simu-
standards (VDE, IEC) and reflecting the present state of lated to determine the optimal selective behavior of two
technology – ranging from medium-voltage feed-in to the series-connected devices. Let-through current and let-
power consumers. The planner needn't perform time-con- through energy curves are offered in addition. A printout
suming data research in catalogs or check standards. documents the selected settings.
Besides an automatic selection of suitable components and
distribution board systems, the software also performs, SIMARIS curves can be obtained free of charge at
among other things, calculations of short-circuit current, www.siemens.com/simaris/download
load flow and voltage drop. And the settings regarding
personal, short-circuit and overload protection will be
performed automatically in line with the calculations
made. Users are provided with convenient options for
documenting results and for project export so that they are
able to re-use project data in SIMARIS project.

More detailed information on SIMARIS design can be


obtained from your local Siemens contact and on the
Internet at www.siemens.com/simarisdesign.

12 Fig. 126/1: Intuitive software operating interfaces facilitate


electrical planning

196 Totally Integrated Power – Tables and Overviews


12.6.2 More Tools for Planning a Power Pressure calculation is provided as a customer service by
Distribution System Siemens If you would like further information in this
matter, please get in touch with your contact, whom you
Complex network calculations with PSS™ SINCAL will find on the Internet at www.siemens.com/tip –>
Benefits –> Consultant –> Contact Partner.
The PSS™ SINCAL software tool is used for network
planning and designing complex meshed networks in high, Configurators for SIVACON 8PS busbar trunking systems
medium and low voltage environments (power utility and
industrial networks). It enables calculations of load flows Busbar trunking systems in low-voltage environments
and short circuits to be prepared together with a ensure safe and reliable transmission and distribution of
documentation of current-time curves for selected grading electric energy from the transformer to the main and
paths. PSS™ SINCAL is also suitable for analyzing existing subdistribution system and the power consumer. These
networks, makes suggestions on network expansion, busbar trunking systems by Siemens are “type-tested
rating details and the preparation of proofs that bear low-voltage switchgear and controlgear assemblies” in
building authorities’ scrutiny, e.g. selectivity proofs. This accordance with IEC/EN 60439-1.
tool is offered at your expense as a service for engineering
consultants by Siemens. The configurators for our busbar trunking systems can be
found on the Internet at www.siemens.com/tip –> Benefits
More detailed information on PSS™ SINCAL can be –> Consultant –> Tools. Right below you will also find a
obtained from your Siemens contacts in the area on link to further configurators for low-voltage control and
page 205 or on the Internet at www.siemens.com/tip –> distribution products.
Benefits –> Consultant –> Contact Partner.
Configuration software for low-voltage distribution
Siblitz calculation tool for lightning protection systems and ALPHA SELECT meter cabinets

Protection measures are required to reduce damage caused Distribution boards and meter cabinets can be easily and
by the impact of lightning. Siblitz© is a software tool for intuitively configured using this software. Configuration
the fast and comprehensive calculation of damage risks. errors are almost eliminated by collision tests and configu-
ration rules. The preparation of tender documents is sup-
You can find Siblitz on the Internet at ported with parts lists, the layout diagram, set-up and
www.siemens.com/tip –> Benefits–> Consultant –> Tools. electrical structure given as data on screen or as printout.

PROFIX configuration tool for medium-voltage You can find the software package on the Internet at
switchgear www.siemens.com/tip –> Benefits–> Consultant –> Tools.

The PROFIX 8DJ/8DH and PROFIX NXPLUS C configuration


Planning tools for GAMMA building management
tools create a block diagram, a front view and appropriate
systems
construction details for our medium-voltage switchgear.
With its “Export” function, the graphics generator provides This software tool for building management technology is
the option to save plans in a neutral data format, in EMF available online on the DIN building platform free of
(Enhanced Windows Metafile) and DXF (AutoCad). charge. It enables the easy preparation and completion of
an “STLB-Bau”-conforming master specification for building
You can download PROFIX quite conveniently from the management systems based on the GAMMA product range
Internet at www.siemens.com/profix that bears building authorities' scrutiny.

Pressure calculation tool for 8 DJ and 8DH10 medium- You can find this planning tool on the Internet at
voltage switchgear www.siemens.com/tip –> Benefits–> Consultant –> Tools.

This software tool provides a simplified pressure calcula- Tender texts for technical building equipment
tion for 8DJ and 8DH10 medium-voltage switchgear based
on Pigler. The tool computes a good approximation for With these tender text modules for technical building
enclosed areas if the room fills evenly with pressure. For equipment in commercial, institutional and industrial
any other medium-voltage switchgear, for highly complex buildings, Siemens provides for you free of charge, quali-
geometries or higher short-circuit loads, it is necessary to fied online support for the compilation of specifications of
perform a more detailed pressure calculation with 3D finite works and services.
elements which also takes dynamic pressure development
into account. You can find the tender texts on the Internet at
www.siemens.com/ausschreibungstexte
12
Totally Integrated Power – Tables and Overviews 197
12.7 Terms and Definitions Rated short-time withstand current (Icw)
IEC/EN 61439-1
Verification by type test
The effective short-circuit current value given by the
Verification performed on patterns of a switchgear switchgear assembly manufacturer, given as current and
assembly or parts thereof to demonstrate that the type time, which can be carried under defined conditions
meets the requirements of the applicable switchgear without damage.
assembly standard. Note: The verification may include one
or several equivalent and alternative approaches such as Rated peak withstand current (Ipk)
tests, calculations, physical measurements or the
IEC/EN 61439-1
application of construction rules.
Being the peak value of the surge current, the rated peak
. Verification by testing withstand current characterizes the dynamic strength of a
circuit in a switchgear assembly. Data on the rated peak
Verification performed on patterns of a switchgear withstand current is usually given for the power
assembly or parts thereof to demonstrate that the type distribution bars and/or main busbars of a switchgear
meets the requirements of the applicable switchgear assembly.
assembly standard. Note: Verifications by testing
correspond to type tests. Rated conditional short-circuit current (Icc)
. Verification by inspection IEC/EN 61439-1
Type verification of fixed construction rules or calculations The rated conditional short-circuit current corresponds to
performed on patterns of a switchgear assembly or parts the prospective short-circuit current which a circuit in a
thereof to demonstrate that the type meets the switchgear assembly can carry (for a certain time), being
requirements of the applicable switchgear assembly protected by a short-circuit protective device, without
standard. being damaged. For this reason, the rated conditional
short-circuit current is specified for outgoing and/or
. Construction rule incoming feeders, e.g. using circuit-breakers.
Defined rules for the construction of a switchgear
assembly which may be applied as an alternative to Rated current of the switchgear assembly (InA)
verification by testing.
IEC/EN 61439-1

Verification by routine test The rated current of the switchgear assembly is the
smaller of:
Verification to which every switchgear assembly is subject
during and/or after its manufacture to ensure that it meets . the rated currents total of the incoming feeders
operated in parallel within the switchgear assembly
the requirements of the applicable standard.
. the total current which the main busbar can distribute
in the respective configuration of the switchgear
Rated values
assembly.
Note: Depending on the applied standard, different
formulaic symbols may have been defined for individual It must be possible that the current is carried without that
terms. heating the individual parts will exceed limit values.

In accordance with IEC/EN 61439-1, manufacturers of Rated circuit current (InC)


low-voltage switchgear and controlgear assemblies specify
IEC/EN 61439-1
rated values. These rated values are to be applied in
defined operating conditions, they characterize the field of The circuit must be able to carry this current when
application of a switchgear assembly. Rated values shall be operated alone without that overtemperatures in
the basis for a coordination of equipment or the individual components will exceed limit values.
configuration of the switchgear assembly.

12
198 Totally Integrated Power – Tables and Overviews
Rated impulse withstand voltage (Uimp) Rated operating voltage (Ue)
IEC/EN 60947-1 IEC/EN 60947-1

Measure for the endurance of clearances in air inside a Voltage to which the characteristic data of a switching
switching device to withstand transient overvoltages. By device refers. The maximum rated operating voltage must
using suitable switching devices, it can be ensured that under no circumstances be higher than the rated
disconnected parts cannot transmit overvoltages from the insulation voltage.
network they are in.
➜ Rated insulation voltage
Rated current (In) (of a circuit-breaker)
IEC/EN 60947-2 Rated operating current (Ie)
IEC/EN 60947-1
For circuit-breakers, this current is identical with the rated
continuous current and the conventional thermal current. Current that a switching device can carry allowing for rated
operating voltage, operating hours, utilization category
➜ Rated continuous current and ambient air temperature.

Rated control voltage (Uc) ➜ Rated operating voltage


IEC/EN 60947-1
Rated continuous current (Iu)
Voltage which is applied at the NO contact in a control
IEC/EN 60947-1
circuit. It can deviate from the rated control supply voltage
owing to transformers or resistors being connected in the Current that a switching device can carry in a continuous
switched circuit. operating mode (over weeks, months or years).

Rated ultimate short-circuit breaking capacity (Icu) Rated making capacity


IEC/EN 60947-2 IEC/EN 60947-1
Maximum short-circuit current which a circuit-breaker can Current that a switching device can make corresponding to
break (test O – CO). After short-circuit interruption, the its utilization category, when the rated operating voltage is
circuit-breaker is capable of tripping in the event of over- applied.
load, increased tolerances must, however, be allowed for.
➜ Rated operating voltage
Rated service short-circuit breaking capacity (Ics)
IEC/EN 60947-2 Rated frequency
IEC/EN 60947-1
The short-circuit current depending on the rated operating
voltage which a circuit-breaker can repeatedly break (test Frequency for which a switching device is rated and to
O – CO – CO). After short-circuit interruption, the circuit- which its other characteristic data refer.
breaker continues to be capable of carrying the rated
current at an increased amount of self-heating, and ➜ Rated operating voltage; Rated continuous current
continues to be capable of tripping in case of overload.
Rated insulation voltage (Ui)
➜ Rated continuous current; Rated operating voltage
IEC/EN 60947-1

Rated operating capacity Voltage to which the dielectric tests and creepage
distances refer. The maximum rated operating voltage
IEC/EN 60947-1
must under no circumstances be higher than the rated
Power which a switching device can switch at a dedicated insulation voltage.
rated operating voltage according to its utilization
category, e.g. power contactor utilization category AC-3: ➜ Rated operating voltage
37 kW at 400 V.

12
Totally Integrated Power – Tables and Overviews 199
Rated short-circuit breaking capacity (Icn)
IEC/EN 60947-1

Highest current that a switching device can break at the


rated operating voltage and frequency without being
damaged, given as the r.m.s value.

➜ Rated operating voltage

Rated short-circuit making capacity (Icm)


IEC/EN 60947-1
Highest current that a switching device can break at a
certain rated operating voltage and frequency without
being damaged. Unlike other characteristic data, it is given
as the peak value.

➜ Rated operating voltage

Rated short-circuit current, conditional


IEC/EN 60947-1
➜ Rated conditional short-circuit current (Iq)

The explanations for the following terms are used with


reference to VDE 0660, Part 500 and IEC 61439-1.

Rated diversity factor (RDF)

Rated current value given as a percentage by the switch-


gear assembly manufacturer with which the outgoing
feeders of a switchgear assembly can continuously and
simultaneously be loaded taking the mutual thermal
influences into account. The rated diversity factor may be
specified:

. for groups of circuits


. for the entire switchgear assembly.
Number of main circuits Rated diversity factor
2 and 3 0.9
4 and 5 0.8
6 to including 9 0.7
10 and more 0.6

12
200 Totally Integrated Power – Tables and Overviews
12.8 Abbreviations L
LAN Local area network
A
LVMD Low-voltage main distribution
AGI Arbeitsgemeinschaft Industriebau [Working
Group on Industrial Building]
M
AS-i Actuator-sensor interface
MRT Magnetic resonance tomograph
B MVS Medium-voltage supply
BA Building automation
N
BACS Building Automation and Control Systems.
NPS Normal power supply
EN 15232 defines four so-called performance
classes for BACS
O
BDEW Bundesverband der Energie und Wasserwirtschaft
OPC OLE for process control (OLE = object linking and
e.V. [German Federal Association of Energy and embedding)
Water Management]
BIMSchV German Federal Ordinance on the Protection P
against Immissions, includes ca. 40 ordinances on PTC Positive temperature coefficient; PTC resistor
the implementation of the Federal Act on the
Protection against Immissions (BImSchG)
R
C RDF Rated diversity factor
CT Computer tomograph RPS Redundant/standby power supply

D S
DIN Deutsches Institut für Normung e. V.; German SCADA Supervisory control and data acquisition, concept
industrial standard for monitoring and control of technical processes
SF Simultaneity factor
E
SHV Smoke and heat vents
EEG German Act on Renewable Energies
SPS Safety power supply
EIB European installation bus
ELA Electro-acoustic system T
TA Technische Anleitung (technical instruction)
EMC Electromagnetic compatibility
TAB Technische Anschlussbedingungen; technical
EMS Energy management system
supply conditions (of the supply network operator)
EN European standard TBM Technical building management
EnEV Ordinance on energy saving THD Total harmonic distortion
ERP Enterprise resource planning THDI Total harmonic distortion index; input current
distortion factor
F
TÜH Staatliche Technische Überwachung Hessen
FMS Facility management system (see EMS) (Governmental Technical Control Board of Hesse/
Germany)
H
TÜV Technischer Überwachungsverein (German
HOAI Honorarordnung für Architekten und Ingenieure Technical Control Board)
(German regulation of architects’ and engineers’
fees) U
HVAC Heating, ventilation, air conditioning UGR Unified glare rating

I UPS Uninterruptible power supply

IEC International Electrotechnical Commission; V


IP International Protection (acc. to DIN); also: VDE Verband der Elektrotechnik, Elektronik und
ingress protection Informationstechnik e.V.
VDEW Verband der Elektrizitätswirtschaft e. V.
K
KNX Konnex; building management system in
VDN Association of Network Operators in the VDEW/VDN 12
compliance with EN 50090 VNB Supply network operator

Totally Integrated Power – Tables and Overviews 201


12.9 Contents: Application Manual – Part 2: Draft Planning 2007

1 Planning with Totally Integrated Power 6 Low Voltage

1.1 Introduction 1/2 6.1 Low-Voltage Switchgear 6/2

1.2 Draft Planning 6.2 Protective and Switching Devices


(System and Integration Planning) 1/3 in the Low-Voltage Power Distribution 6/9

6.3 Requirements of the Switchgear


in the Three Circuit Types 6/11
2 Power System
6.4 Container Solutions 6/14
2.1 Overview 2/2

2.2 Dimensioning of Power Distribution Systems 2/10


7 Busbar Trunking Systems, Cables and Wires
2.3 System Protection and Safety Coordination 2/14
7.1 Busbar Trunking Systems 7/2
2.4 Protection Equipment
7.2 Cables and Wires 7/10
for Low-Voltage Power Systems 2/20

2.5 Selectivity in Low-Voltage Systems 2/41


8 Subdistribution Systems
2.6 Protection of Capacitors 2/52
8.1 General 8/2
2.7 Protection of Distribution Transformers 2/53
8.2 Configuration 8/2
2.8 Protection of Technical Building Installations –
Lightning Current and Overvoltage Protection 2/62 8.3 Selectivity and Back-up Protection 8/3

8.4 Small Distribution Boards and Wall-


or Floor-Mounted Distribution Boards 8/6
3 Medium Voltage
8.5 Circuit Protection Devices 8/9
3.1 Introduction 3/2

3.2 Basics of Switchgear 3/3


9 Power Consumers
3.3 Requirements on Medium-Voltage Switchgear 3/7
9.1 Starting, Switching and Protecting Motors 9/2
3.4 Siemens Medium-Voltage Switchgear 3/9
9.2 Lighting 9/8
3.5 From Medium-Voltage Switchgear
9.3 Elevator Systems 9/19
to Turnkey Solutions 3/25

3.6 Protection of Power Distribution Systems


and Switchgear 3/28 10 Ease of Operation, Safety and Control
Engineering

4 Transformers 10.1 Power Management with SIMATIC powercontrol 10/2

10.2 Building Management System 10/7


4.1 Distribution Transformers 4/2
10.3 Energy Automation for the Industry 10/14
4.2 Control and Isolating Transformers 4/6
10.4 Safety Lighting Systems 10/20

10.5 Robust Remote Terminal Unit for Extreme


5 Power Generation
Environmental Conditions (SIPLUS RIC) 10/27

12 5.1 Grid-Connected Photovoltaic (PV) Systems 5/2

5.2 Basis for the Use of UPS 5/5 11 Appendix

202 Totally Integrated Power – Tables and Overviews


Your Siemens Contact Partners
Consultant Support Portugal United Kingdom
Jose Alves Calado Howard John
Tel.: +3 51 21 4 17 84 69 Tel.: +44 1 61 4 46 64 00
Austria E-mail: alves.calado@siemens.com
E-mail: howard.john@siemens.com
Erich Thauer Anabela Correao
Tel.: +43 5 17 07 2 29 86 Tel.: +3 51 21 4 17 84 69
E-mail: erich.thauer@siemens.com E-mail: anabela.m.correia@siemens.com
Leopold Holzhacker Russia
Tel.: +43 5 17 07 2 33 30 Alexander Bourlaka
E-mail: leopold.holzhacker@siemens.com Tel.: +7 4 95 7 37 23 39
E-mail: alexander.bourlaka@siemens.com
Greece China
Ilias Antoniou Schwitzerland
Roger Weigold Mr. He You Lin
Tel.: +30 2 10 68 64-3 79
Tel.: +41 58 5 58 65 18 Tel.: +86 21 38 89-30 82
E-mail: ilias.antoniou@siemens.com
E-mail: roger.weigold@siemens.com E-mail: youlin.he@siemens.com
Italy
Spain Mr. Ge Da Lin
Paolo Parma
Ramon Rodriguez Belda Tel.: +86 21 38 89-26 65
Tel.: +39 02 24 36 29 52 Tel.: +34 91 5 14-70 55
E-mail: paolo.parma@siemens.com E-mail: dalin.ge@siemens.com
E-mail: ramon.rodriguez@siemens.com
Netherlands USA
Turkey
Merijn Dijkema Ali Kaan Eryasar Bill Reid
Tel.: +31 70 3 33 21 52 Tel.: +90 2 16 4 59 32 28 Tel.: +1 913 8 88 26 46
E-mail: merijn.dijkema@siemens.com E-mail: kaan.eryasar@siemens.com E-mail: bill.reid@siemens.com

Contact Partners for Special Subjects

Lighting technology Standby power supply systems

Siteco Beleuchtungstechnik GmbH Evers & Co.


Technical Support Standard Aggregatebau KG
Georg-Simon-Ohm-Straße 50 Grünauer Straße 24
12557 Berlin, Germany
83301 Traunreut / Upper Bavaria, Germany
Tel.: +49 30 / 65 47 27 23
Tel.: +49 86 69 / 3 38 44
Fax: +49 30 / 65 47 27 26
Fax: +49 86 69 / 3 35 40
www.sab-hamburg.de
E-mail: technicalsupport@siteco.de
www.siteco.de or www.siteco.com Lutz Schulz
E-mail: l.schulz@sab-berlin.de
Reactive power compensation
Uninterruptible power supply systems
MODL GmbH
MASTERGUARD GmbH
Sales Management
PO Box 2620
Langenaltheimer Straße 5–9
91014 Erlangen, Germany
91788 Pappenheim, Germany
Fax: 0 91 31 / 6 30 03 00

12
Gerd Sonnek www.masterguard.info
Tel.: +49 91 43 / 6 03-56 Infoline (weekdays 9.00 am – 5.00 pm)
Fax: +49 91 43 / 6 03-12 Tel.: +49 1 80 / 5 32 37 51
E-mail: gerd.sonnek@modl.de E-mail: info@masterguard.de

Totally Integrated Power – Tables and Overviews 203


We would like to thank the companies MASTERGUARD
(UPS), Modl (reactive power compensation), Siteco
(lighting technology) and Evers & Co. Standard Aggre-
gatebau KG (standby power supply systems) for their
technical support in the preparation of this manual.

Imprint
Totally Integrated Power Application Manual – Part 1:
Basic Data and Preliminary Planning 2nd edition 2009

Published by

Siemens Aktiengesellschaft

Sector Industry
Division Automation and Drives
Division Building Technologies

Sector Energy
Division Power Transmission and Distribution

Editor and Author

Ralf Willeke, Siemens AG, I IA CD TIP

Layout

Publicis KommunikationsAgentur GmbH, GWA


Nägelsbachstr. 33
91052 Erlangen, Germany

Image rights
Page 25 © Roland Halbe/Messe Stuttgart; Page 31, 59
Wolfgang Geyer/Forum Wetzlar; Page 5, 139, 147, 153
Dominik Obertreis/Flughafen Stuttgart. Any other non-
identified photographs and graphics © Siemens AG.

Print

Hofmann Infocom AG
Emmericher Straße 10
90411 Nuremberg, Germany

Bindery

Thalhofer, 71101 Schönaich, Germany


ethabind jacket protected by patent

© 2009 Siemens Aktiengesellschaft Berlin and Munich


All rights reserved. Token fee 24.00 euros
All data and circuit examples without engagement.
Subject to changes.

Order No. E20001-A110-M104-X-7600

12 Dispo 27612
The omission of any specific reference with regard to trademarks, brand names,
technical solutions, etc., does not imply that they are not protected by patent.

204 Totally Integrated Power – Tables and Overviews


Conversion Factors and Tables

Volume Volume flow rate Pressure

SI unit Non-metric unit SI unit Non-metric unit SI unit Non-metric unit

1 cm3 0.061 in3 = 0.034 fl. oz 1 l/s 0.264 Gallone/s 1 bar 29.53 in Hg =


1 dm3 61.024 in3 = 1 l/h 0.0044 Gallone/min = 105 pa 14.504 psi =
= 102 kpa 2088.54 lbf/ft2 =
=1l 0.035 ft3 = 1.057 Quart = 1 m3/h 4.405 Gallone/min =
14.504 lbf/in2 =
2.114 Pint = 0.264 Gallone 0.589 ft3/min = 0.0098 ft3/s
0.932 tonf/ft2
1 m3 6.29 Barrel Non-metric unit SI unit 6.457 × 10–3 tonf/in2
(= 1.02 kgf/cm2)
Non-metric unit SI unit 1 Gallone/s 3.785 l/s
1 Gallone/min 0.227 m3/h = 227 l/h Non-metric unit SI unit
1 in3 16.387 cm3
1 ft3 28.317 dm3 = 0.028 m3 1 ft3/s 101.941 m3/h 1 in HG 0.034 bar
1 yd3 0.765 m3 1 ft3/min 1.699 m3/h 1 psi 0.069 bar
1 fl. oz. 29.574 cm3 1 lbf/ft2 4.788 × 10–4 bar =
1 lbf/in2 4.882 × 10–4 kgf/cm2
1 Quart 0.946 dm3 = 0.946 l Force
1 tonf/ft2 0.069 bar = 0.070 kgf/cm2
1 Pint 0.473 dm3 = 0.473 l
SI unit Non-metric unit 1 tonf/in2 1.072 bar = 1.093 kgf/cm2
1 Gallone 3.785 dm3 = 3.785 l
1 Barrel 159 dm3 = 0.159 m3 = 159 l 1N 0.225 lbf = 0.102 kgf 154.443 bar =
157.488 kgf/cm2
1 kN 0.100 tonf

Non-metric unit SI unit


Velocity 1 lbf 4.448 N Energy, work, heat content

1 kgf 9.807 N
SI unit Non-metric unit SI unit Non-metric unit
1 tonf 9.964 kN
1 m/s 3.281 ft/s = 2.237 mile/h 1 kWh 1.341 hp h = 2.655 kgf m
1 km/h 0.911 ft/s = 0.621 mile/h 1J = 3.6 × 105 J
Torque, moment of force
3.725 × 10–7 hp h =
Non-metric unit SI unit 0.738 ft lbf =
SI unit Non-metric unit
1 kgf m 9.478 × 10–4 Btu
1 ft/s 0.305 m/s = 1.097 km/h
(= 2.388 × 10–4 kcal
1 Nm 8.851 lbf in = 0.738 lbf ft
1 mile/h 0.447 m/s = 1.609 km/h 3.653 × 10–6 hp h =
(= 0.102 kgf m)
7.233 ft lbf
Non-metric unit SI unit
Non-metric unit SI unit
1 lbf in 0.113 Nm = 0.012 kgf m
Mass, weight
1 lbf ft 1.356 Nm = 0.138 kgf m 1 hp h 0.746 kWh = 2.684 × 106 J
1 ft lbf = 2.737 × 105 kgf m
SI unit Non-metric unit
Moment of inertia 1 Btu 0.138 kgf m
1g 0.035 oz 1.055 kJ = 1,055.06 J
1 kg 2.205 lb = 35.27 oz Numerical value equation GD2 = Wr2
J = –––– (= 0.252 kcal)
4
1t 1.102 sh ton = 2205 lb
SI unit Non-metric unit
Non-metric unit SI unit
1 kg m2 23.73 lb ft2
1 oz 28.35 g
Non-metric unit SI unit
1 lb 0.454 kg = 453.6 g
1 sh ton 0.907 t = 907.2 kg 1 lbf ft2 0.04214 kg m2
Conversion Factors and Tables

Electrical power Linear measure

SI unit Non-metric unit SI unit Non-metric unit

1 kW 1.341 hp = 1 mm 39.37 mil


101.972 kgf m/s 1 cm 0.394 in
(= 1.36 PS)
1m 3.281 ft = 39.370 in
1W 0.738 ft lbf/s = 0.86 kcal/h = = 1.094 yd
3.412 Btu
1 km 0.621 mile = 1.094 yd
(= 0.102 kgf m/s)
Non-metric unit SI unit
Non-metric unit SI unit
1 mil 0.0254 mm
1 hp 0.746 kW = 745.70 W =
76.040 kgf m/s 1 in 2.54 cm = 25.4 mm
1 ft lbf/s (= 1.014 PS) 1 ft 30.48 cm = 0.305 m
1 kcal/h 1.356 W (= 0.138 kgf in/s) 1 yd 0.914 m
1 Btu/h 1.163 W 1 mile 1.609 km = 1,609 m
0.293 W

Square measure
Specific steam consumption

SI unit Non-metric unit


SI unit Non-metric unit
1 mm2 0.00155 in2
1 kg/kWh 1.644 lb/hp h 1 cm2 0.155 in2
Non-metric unit SI unit 1 m2 10.76 ft2 = 1550 in2
= 1.196 yd2
1 lb/hp h 0.608 kg/kWh
1 km2 0.366 mile2

Non-metric unit SI unit


Temperature
1 in2 6.452 cm2 = 645.16 mm2
SI unit Non-metric unit 1 ft2 0.093 m2 = 929 cm2
1 yd2 0.836 m2
°C °F 9
– (∂C + 32) = ∂F
5 1 acre 4046.9 m2
K °F 5
– (∂T – 459.67) = ∂F 1 mile2 2.59 km2
9

Non-metric unit SI unit


Examples of decimal multiples
°F °C 9
– (∂F – 32) = ∂C and fractions of metric units
5
5 1 km = 1,000 m;
°F K – (∂F + 459.67) = T
9 1 m = 100 cm = 1,000 mm
Note: 1 km2 = 1,000,000 m2;
Quantity Symbol Unit 1 m2 = 10,000 cm2;
Temperature 1 cm2 = 100 mm2
∂F °F
in degrees Fahrenheit
1 m3 = 1,000,000 cm3;
Temperature Btu = British thermal unit
∂C °C 1 cm3 = 1,000 mm3
in degrees Celsius Btu/h = British thermal unit/hour
1 t = 1,000 kg; 1 kg = 1,000 g
Thermodynamic lbf = pound force
T K 1 kW = 1,000 W
temperature in Kelvin tonf = ton force
Conversion Factors and Tables

Conductor cross sections in the Metric and US System Temperature

Metric cross American Wire Gauge °C °F


sections acc. (AWG)
to IEC

8m
Conductor Equivalent AWG or 160 320
cross metric CSA MCM

15 m
3m
section 305
150
[mm2] [mm2] 290

7m
140
275

13 m
130
0.653 19 AWG 260
0.75
0.832 18
120
245

6m
1.040 17
1.310 16
1.50 110 230

11 m
1.650 15
2.080 14 100 212
2.50 2.620 13 200

2m

5m
3.310 12 90
4.00 185
4.170 11

9m
80
5.260 10 170
6.00
6.630 9 70 155

4m
8.370 8
10.00 10.550 7 60 140

7m
13.300 6
125
16.00 16.770 5 50
3m

21.150 4 110
25.00 40
26.670 3
95
33.630 2
5m
1m

35.00 30
42.410 1 80
50.00 53.480 1/0 20
2m

65
70.00 67.430 2/0
85.030 3/0 10 50
95.00
3m

107.200 4/0
120.00 0 32
126.640 250 MCM
150.00 152.000 300
1m

20
185.00 –10
202.710 400
5
240.00 253.350 500
1m
M 1 : 100

–20
M 1 : 20

M 1 : 50

300.00 304.000 600 –10


354.710 700
400.00 405.350 800 –30 –25
500.00 506.710 1000
625.00 –40 –40
The information provided in this manual contains merely
general descriptions or characteristics of performance which
Siemens AG Siemens AG in case of actual use do not always apply as de-scribed or
Industry Sector Energy Sector which may change as a result of further development of the
Industry Automation and Drive Technologies Building Technologies Group Power Distribution
products. An obligation to provide the respective
Gleiwitzer Straße 555 Gubelstraße 22 Freyeslebenstr. 1
characteristics shall only exist if expressly agreed in the
90475 NUREMBERG 6301 ZUG 91058 ERLANGEN
terms of contract.
GERMANY SWITZERLAND GERMANY
All product designations may be trademarks or product
names of Siemens AG or supplier companies whose use by
www.siemens.com/tip third parties for their own purposes could violate the rights
of the owners.

You might also like