TDS® Series
Dehydrate wet transformers without
taking them out of service!
DESCRIPTION
Top of enclosure is hinged
The TDS® transformer dry-out
to allow access for filter changes
system incorporates all the
necessary features to allow a
transformer to remain in-service
while moisture from its insulation
is effectively removed. The
system is safe with several alarm A window
features that shut the system off, is installed
isolating it from the transformer, for visual
in the event of any abnormal checks of
signal. The TDS5-1 unit provides system
a non-intrusive, cost effective and
convenient method of maintaining
transformers in a dry condition.
In addition, once the transformer
is dried, the system can be
Enclosure is
retrofitted with Activated Alumina
sand blasted
cartridges to reduce acidity in the to bare metal
transformer oil. This flexibility and powder
allows increased oil processing coat painted
application compared to heat and
vacuum systems.
APPLICATIONS BENEFITS
Contact Info:
Dry wet transformers and Transformer remains in-
Parker Hannifin Corporation
insulation service during process
Hydraulic & Fuel Filtration Division
1210 Garden of the Gods Road Dry transformers not braced Reduce transformer dry-out
Colorado Springs, CO 80907 for vacuum costs
Dry transformers that cannot Improve oil dielectric values
phone 719 531 5855 be taken out of service Improve transformer power
fax 719 531 5690
factor
vfsales@parker.com
Operates continuously
www.velcon.com | www.parker.com unattended
Extend oil service life
Extend transformer service life
SYSTEM OVERVIEW returned from the TDS® to a top oil temperature should be kept
The TDS® oil processing system is connection valve. The number of at least 40 - 60 degree C for
designed to allow a transformer cartridge changeouts required to moisture equilibration between
under load to dry itself out. A dry the transformer insulation to insulation and oil to continue in
quantity of four part number an acceptable level and cartridge a timely fashion. A single set of
SD-1107 Superdri® cartridges change-out intervals will vary Superdri cartridges will remove
are installed in the filter vessel, according to moisture content approximately 1.4 gallons of water.
through which oil is processed at a and moisture transfer rate from Cartridge performance can be
rate of 5 gpm. The filtering system the insulation to the oil. One monitored by observing the Doble
removes dissolved water from oil set of Superdri® cartridges will DOMINO® moisture sensor (see
to less than 10 ppm, and includes remove a minimum of 1.4 gallons options below). The process will
1 micron nominal particle removal of dissolved water from the oil. not release moisture back into
capabilities. The process does Periodic moisture readings, the oil even if cartridges are fully
not affect dissolved gas in oil, and from both the inlet to and outlet saturated.
does not remove oil oxidation from the system can be taken to
inhibitors. The system is complete determine the amount of moisture
with all components necessary being removed and are also used
to monitor the mechanical and to determine when cartridges
electrical operating conditions should be changed.
of the unit. The system includes
components to purge air during GENERAL CONDITIONS AND
start up and after filter changes. GUIDELINES
The TDS5-1 relies on load from
PROCESS OVERVIEW the energized transformer to push
The on-line dryout process is moisture from the insulation out
designed for safe, unattended, to the surrounding oil. As the
24-hour operation. The system moisture is released into the oil,
suction line is connected to it is removed by the Superdri®
the transformer bottom fill cartridges which continually
connection. The oil is then dry the oil to less than 10 ppm
total water. Transformer top
For guidelines to estimate process cost and duration, contact Parker HFFD
TDS® SPECIFICATIONS and the system will shutoff OPTIONS
automatically. Extra contacts Doble DOMINO® on-line
Power Requirements: 120 vac, are provided for remote alarm
1-ph, 60 Hz, 12 amps, comes direct reading moisture sensor
detection. continuously displays oil
with 25-ft power cord.
Self Draining: Oil in the vessel temperature and ppm of total
Control Box: NEMA 4 is safely pumped back into the water in the oil (or percent
enclosure with motor starter, transformer during cartridge saturation of the oil). The piping
motor overload protection, changeouts. layout of the TDS system allows
programmable logic controller, easy checking of both the influent
start/stop/reset switch, run Dry Contact Relay: A dry
contact relay is provided and effluent moisture contents
light indicator, high pressure with a single sensor. A “Change
cutoff switch and indicating that can be wired to the
transformer’s low oil level Filter” alarm light is also mounted
light, and elapsed hour meter. to the control panel door.
alarm to shut the system off if
Electric Motor: 1/2 hp, TEFC, a low oil level is sensed.
1750 RPM. Please see data sheet #1995 for
Detachable Hoses: Have remote monitor and control
Fan: 6” for enclosure disconnect fittings at the options
ventilation, with thermostat enclosure end. When
and filtered louver. disconnected, the hoses can
Electronic Flow Meter: 0 - 30 be stored more conveniently in
gpm, indicates flow rate, a separate hose storage area.
resettable batch totalizer, and
cumulative gallons pumped,
battery powered.
Oil Pump: 5 gpm positive
displacement gear pump with
mechanical seal and internal
pressure bypass.
Vacuum Pump: 3 CFM
displacement, close coupled
motor and wired to main
electrical control box for power
source.
Coaxial Hoses with Oil Level
Alarm: (2) 25-ft coaxial lengths
of suction and discharge
3/4” hose are provided
with N.C. solenoids wired
to main control panel. If a
leak should develop on the
hose connections to the
transformer, oil will collect in
the bottom of the enclosure
DIMENSIONS
Depth: 36”
Width: 38”
Height: 49” (85” with lid open)
Shipping Weight: 1,125 lbs
ORDERING INFORMATION