Airfield Lighting Cables Airfield Lighting Cables

XLPE Insulated, Shielded or XLPE Insulated, Shielded or


Non-shielded 5 kV Primary Airfield
Lighting Cables according to the FAA
Non-shielded 5 kV Primary Airfield
Lighting Cables according to the FAA
Specification
AC 150/5345-7E (L-824) Specification AC 150/5345-7E (L-824) Specification

APPLICATION:
For runway, taxiway and approach in underground SCOPE CONDUCTOR SHIELD OVERALL JACKET
primary series airfield lighting circuits. At 5 kV This specification describes XLPE insulated Optional for non-shielded cables, it is - Where applicable, an extruded PVC or black
rated voltage and maximum conductor shielded or non-shielded single core 5 kV cables mandatory for shielded cables. Accordingly, PE jacket shall be applied on the assembly.
temperatures of 90 °C for continuous normal for runway, taxiway and approach in the conductors are covered with a layer of - Properties of the jacket shall be in
operation and 250 °C for short circuit. Suitable Wunderground primary series airfield lighting extruded conducting cross-linked polyolefin accordance with NEMA WC71 /
for use in wet or dry conditions in metallic and circuits. For a maximum conductor compound, firmly bonded to the insulation ICEA S-96-659-1999 Standard, Table 5-1
non-metallic conduits, ducts, aerial and direct temperatures of 90 °C for continuous normal and which shall meet the requirements of or NEMA WC74-2000 / ICEA S-93-639-
burial installations. operation and 250 °C for short circuit, in wet NEMA WC74-2000 / ICEA S-93-639-1999 1999 Standard, Table 7-1 depending upon
or dry conditions. Suitable for use in metallic Standard, Section 3. the cable type.
STANDARDS: and non-metallic conduits, ducts, aerial and
Conforms to: direct burial installations. INSULATION TESTS
1. FAA Advisory Circular (AC) 150/5345-7E, copper seven wires stranded circular conductor extruded conductor shield and a XLPE Directly over the conductor, separator or screen The cable shall be tested in accordance with
Specification for L-824, Type C; has an extruded tracking resistant XLPE (cross- (cross-linked polyethylene) insulation. A STANDARDS (as applicable) shall be applied a homogeneous NEMA WC71 / ICEA S-96-659-1999 Standard,
2. NEMA WC71 / ICEA S-96-659-1999 for linked polyethylene) insulation. Optionally, a non-metallic insulation shield supplemented The following standards shall form a part of wall of XLPE insulation. For non-shielded cables Table 5-1 or NEMA WC74-2000 /
non-shielded cables; separator or conductor shield may be applied this specification to the extent specified herein: it shall meet the requirements of NEMA WC71 ICEA S-93-639-1999 Standard, Table 7-1
with a metallic shield (brass or copper tape;
3. NEMA WC74-2000 / ICEA S-93-639-1999 between both. - Conforms to FAA Advisory Circular (AC) / ICEA S-96-659-1999, Table 4-2. For shielded depending upon the cable type.
bare or tinned copper wires; or bare or
for shielded cables. 2. Non-shielded jacketed type: a bare copper 150/5345-7E, Specification for L-824, cables it shall meet the requirements of NEMA
tinned copper braiding) is applied Type C, Underground Electrical Cable for
seven wires stranded circular conductor has WC74-2000 / ICEA S-93-639-1999 Standard,
underneath the PVC or PE outer jacket. Airfield Lighting Circuits Section 4.
CERTIFICATION: an extruded XLPE (cross-linked polyethylene)
1. ETL Certified Optionally, a separator may be applied - NEMA WC71 / ICEA S-96-659-1999:
insulation. Optionally, a separator or conductor under the jacket. “Standard for Non-shielded Power Cables
2. FAA Listed as an Approved Supplier INSULATION SHIELD (for shielded cables)
shield may be applied between both. Rated 2,001 – 5,000 Volts for the - The insulation shield shall consist of a
A PVC or PE outer jacket is applied overall on PACKAGING Distribution of Electrical Energy” as graphite coating in combination with semi-
CONSTRUCTION:
an optional separating tape; Standard supply lengths are 3000 ft. Other referenced by FAA AC 150/5345-7E. conducting tape and a metallic layer applied
Three types of cable are provided:
1. Non-shielded and non-jacketed type: a bare 3. Shielded jacketed type: a bare copper seven bobbin lengths are available upon request. - NEMA WC74-2000 / ICEA S-93-639-1999: directly over the insulation.
wires stranded circular conductor has an “Standard for Shielded Power Cables Rated - The metallic layer shall consist of one of
5,000 – 46,000 Volts for the Transmission the following:
& Distribution of Electrical Energy” as - an overlapping copper tape
5000 V Non-shielded and Non- jacketed Cables referenced by FAA AC 150/5345-7E. - an overlapping brass tape
- helically applied bare copper wires
Nominal insulation thickness

Conductor Separator tape or conductor CONDUCTORS - helically applied tinned copper wires
Ampacity in underground

shield
Nominal diameter

Bare soft annealed, high conductivity copper - bare copper wires braid
per ASTM B-3, concentric stranded, class B - tinned copper wires braid
Number of strands

Nominal Diameter

DC resistance at

Catalog (seven strands) per ASTM B 8. Class C (19 - Other tape thickness or wire diameter than
Thickness

strands) is available upon request. the ones indicated in the tables can be
25 oC

Number Size Option


supplied upon request.
duct (1)

SEPARATOR (for non-shielded cables) - An optional separator tape may be applied


An optional separator is applied to facilitate over all.
AWG - inches Ω/1000 ft - mils mils inches A the insulation stripping.
1LC01108 8 7 0.143 0.652 None - 110 0.363 64

1LC01106 6 7 0.180 0.411 None - 110 0.400 85

1LC01104 4 7 0.226 0.258 None - 110 0.446 110

1LC11108 8 7 0.143 0.652 Separator 0.5 110 0.364 64

1LC11106 6 7 0.180 0.411 Separator 0.5 110 0.401 85

1LC11104 4 7 0.226 0.258 Separator 0.5 110 0.447 110

1LC21108 8 7 0.143 0.652 Cond. Shield 20 110 0.403 64

1LC21106 6 7 0.180 0.411 Cond. Shield 20 110 0.440 85

PCD 45-18, October 2007


1LC21104 4 7 0.226 0.258 Cond. Shield 20 110 0.486 110
Tel: (972) 4-8466222
Fax: (972) 4-8466286
e-mail: export@synergy-cables.com
http://www.synergy-cables.com
Airfield Lighting Cables Airfield Lighting Cables
5000 V Non-shielded and Jacketed Cables

Non-metallic insulation
Separator tape or Conductor

Minimum conductor
Jacket

Nominal insulation
Conductor conductor shield Jacket

Nominal diameter
Nominal insulation

Nominal diameter

shield thickness

shield thickness

Separator tape
DC resistance
Separator tape

Material type

underground
DC resistance
Catalog

Material type

underground

Ampacity in
Thickness

Number of
Size

Ampacity in
Catalog

Number of

thickness

Thickness
Diameter

thickness
at 25 oC
Number

Nominal
Thickness
Diameter

thickness

thickness

duct (1)
at 25 oC
Nominal

strands
duct (1)
Number

strands
Size Option

AWG - inches Ω/1000 ft mils mils mils mils mils - inches A


AWG - inches Ω/1000 ft - mils mils mils mils inches A
BARE COPPER BRAIDED SHIELD. 6 MILS WIRE DIAMETER
1LC09081 8 7 0.143 0.652 None - 90 6 30 PVC 0.395 64
7
1LC290851 8 7 0.143 0.652 90 6 6 6 55 PVC 0.53 64
1LC09082 8 7 0.143 0.652 None - 90 6 30 PE 0.395 64
7
1LC290852 8 7 0.143 0.652 90 6 6 6 55 PE 0.53 64
1LC09061 6 7 0.180 0.411 None - 90 6 30 PVC 0.432 85
7
1LC290651 6 7 0.180 0.411 90 6 6 6 55 PVC 0.57 85
1LC09062 6 7 0.180 0.411 None - 90 6 30 PE 0.432 85
7
1LC290652 6 7 0.180 0.411 90 6 6 6 55 PE 0.57 85
1LC09041 4 7 0.226 0.258 None - 90 6 45 PVC 0.508 110
7
1LC290451 4 7 0.226 0.258 90 6 6 6 55 PVC 0.61 110
1LC09042 4 7 0.226 0.258 None - 90 6 45 PE 0.508 110
7
1LC290452 4 7 0.226 0.258 90 6 6 6 55 PE 0.61 110
1LC19081 8 7 0.143 0.652 Separator 0.5 90 6 30 PVC 0.396 64
1LC19082 8 7 0.143 0.652 Separator 0.5 90 6 30 PE 0.396 64 TINNED COPPER BRAIDED SHIELD. 6 MILS WIRE DIAMETER
1LC19061 6 7 0.180 0.411 Separator 0.5 90 6 30 PVC 0.433 85 1LC290861 8 7 0.143 0.652 6 90 6 6 55 PVC 0.53 64
1LC19062 6 7 0.180 0.411 Separator 0.5 90 6 30 PE 0.433 85 1LC290862 8 7 0.143 0.652 6 90 6 6 55 PE 0.53 64
1LC19041 4 7 0.226 0.258 Separator 0.5 90 6 45 PVC 0.509 110 1LC290661 6 7 0.180 0.411 6 90 6 6 55 PVC 0.57 85
1LC19042 4 7 0.226 0.258 Separator 0.5 90 6 45 PE 0.509 110 1LC290662 6 7 0.180 0.411 6 90 6 6 55 PE 0.57 85
1LC29081 8 7 0.143 0.652 Cond. Shield 20 90 6 30 PVC 0.435 64 1LC290461 4 7 0.226 0.258 6 90 6 6 55 PVC 0.61 110
1LC29082 8 7 0.143 0.652 Cond. Shield 20 90 6 30 PE 0.435 64 1LC290462 4 7 0.226 0.258 6 90 6 6 55 PE 0.61 110
1LC29061 6 7 0.180 0.411 Cond. Shield 20 90 6 30 PVC 0.472 85
1LC29062 6 7 0.180 0.411 Cond. Shield 20 90 6 30 PE 0.472 85
1LC29041 4 7 0.226 0.258 Cond. Shield 20 90 6 45 PVC 0.548 110
1LC29042 4 7 0.226 0.258 Cond. Shield 20 90 6 45 PE 0.548 110
(1) Ampacity according to NEC Table 310.77: Three Single-Insulated Copper Conductors in Underground Electrical Ducts (Three Conductors
per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), 100 Percent Load Factor, Thermal Resistance (RHO) of 90,
5000 V Shielded and Jacketed Cables Non-metallic insulation Conductor Temperatures of 90°C (194°F)

Conductor
Minimum conductor

Jacket
Nominal insulation

The information given in this page is subject to change without notice.

Nominal diameter
shield thickness

shield thickness

Separator tape
DC resistance

Material type

underground
Catalog

Ampacity in
Number of

Size
thickness

Thickness
Diameter

thickness
at 25 oC

Number
Nominal

duct (1)
strands

AWG - inches Ω/1000 ft mils mils mils mils mils - inches A


B R A S S TA P E S H I E L D 4 M I L S T H I C K
1LC290811 8 7 0.143 0.652 6 90 6 6 55 PVC 0.51 64
1LC290812 8 7 0.143 0.652 6 90 6 6 55 PE 0.51 64
1LC290611 6 7 0.180 0.411 6 90 6 6 55 PVC 0.55 85
1LC290612 6 7 0.180 0.411 6 90 6 6 55 PE 0.55 85
1LC290411 4 7 0.226 0.258 6 90 6 6 55 PVC 0.60 110
1LC290412 4 7 0.226 0.258 6 90 6 6 55 PE 0.60 110
BARE COPPER TAPE SHIELD 4 MILS THICK
1LC290821 8 7 0.143 0.652 6 90 6 6 55 PVC 0.51 64
1LC290822 8 7 0.143 0.652 6 90 6 6 55 PE 0.51 64
1LC290621 6 7 0.180 0.411 6 90 6 6 55 PVC 0.55 85
1LC290622 6 7 0.180 0.411 6 90 6 6 55 PE 0.55 85
1LC290421 4 7 0.226 0.258 6 90 6 6 55 PVC 0.60 110
1LC290422 4 7 0.226 0.258 6 90 6 6 55 PE 0.60 110
BA R E C O P P E R W I R E S S H I E L D. 2 0 M I L S W I R E D I A M E T E R
1LC290831 8 7 0.143 0.652 6 90 6 6 55 PVC 0.54 64
1LC290832 8 7 0.143 0.652 6 90 6 6 55 PE 0.54 64
1LC290631 6 7 0.180 0.411 6 90 6 6 55 PVC 0.57 85
1LC290632 6 7 0.180 0.411 6 90 6 6 55 PE 0.57 85

PCD 33-24/3.02 March 6, 2002


1LC290431 4 7 0.226 0.258 6 90 6 6 55 PVC 0.62 110
1LC290432 4 7 0.226 0.258 6 90 6 6 55 PE 0.62 110
TINNED COPPER WIRES SHIELD. 20 MILS WIRE DIAMETER
1LC290841 8 7 0.143 0.652 6 90 6 6 55 PVC 0.54 64

PCD 45-18, October 2007


1LC290842 8 7 0.143 0.652 6 90 6 6 55 PE 0.54 64
1LC290641 6 7 0.180 0.411 6 90 6 6 55 PVC 0.57 85
1LC290642 6 7 0.180 0.411 6 90 6 6 55 PE 0.57 85
1LC290441 4 7 0.226 0.258 6 90 6 6 55 PVC 0.62 110
1LC290442 4 7 0.226 0.258 6 90 6 6 55 PE 0.62 110
Airfield Lighting Cables Airfield Lighting Cables
5000 V Non-shielded and Jacketed Cables

Non-metallic insulation
Separator tape or Conductor

Minimum conductor
Jacket

Nominal insulation
Conductor conductor shield Jacket

Nominal diameter
Nominal insulation

Nominal diameter

shield thickness

shield thickness

Separator tape
DC resistance
Separator tape

Material type

underground
DC resistance
Catalog

Material type

underground

Ampacity in
Thickness

Number of
Size

Ampacity in
Catalog

Number of

thickness

Thickness
Diameter

thickness
at 25 oC
Number

Nominal
Thickness
Diameter

thickness

thickness

duct (1)
at 25 oC
Nominal

strands
duct (1)
Number

strands
Size Option

AWG - inches Ω/1000 ft mils mils mils mils mils - inches A


AWG - inches Ω/1000 ft - mils mils mils mils inches A
BARE COPPER BRAIDED SHIELD. 6 MILS WIRE DIAMETER
1LC09081 8 7 0.143 0.652 None - 90 6 30 PVC 0.395 64
7
1LC290851 8 7 0.143 0.652 90 6 6 6 55 PVC 0.53 64
1LC09082 8 7 0.143 0.652 None - 90 6 30 PE 0.395 64
7
1LC290852 8 7 0.143 0.652 90 6 6 6 55 PE 0.53 64
1LC09061 6 7 0.180 0.411 None - 90 6 30 PVC 0.432 85
7
1LC290651 6 7 0.180 0.411 90 6 6 6 55 PVC 0.57 85
1LC09062 6 7 0.180 0.411 None - 90 6 30 PE 0.432 85
7
1LC290652 6 7 0.180 0.411 90 6 6 6 55 PE 0.57 85
1LC09041 4 7 0.226 0.258 None - 90 6 45 PVC 0.508 110
7
1LC290451 4 7 0.226 0.258 90 6 6 6 55 PVC 0.61 110
1LC09042 4 7 0.226 0.258 None - 90 6 45 PE 0.508 110
7
1LC290452 4 7 0.226 0.258 90 6 6 6 55 PE 0.61 110
1LC19081 8 7 0.143 0.652 Separator 0.5 90 6 30 PVC 0.396 64
1LC19082 8 7 0.143 0.652 Separator 0.5 90 6 30 PE 0.396 64 TINNED COPPER BRAIDED SHIELD. 6 MILS WIRE DIAMETER
1LC19061 6 7 0.180 0.411 Separator 0.5 90 6 30 PVC 0.433 85 1LC290861 8 7 0.143 0.652 6 90 6 6 55 PVC 0.53 64
1LC19062 6 7 0.180 0.411 Separator 0.5 90 6 30 PE 0.433 85 1LC290862 8 7 0.143 0.652 6 90 6 6 55 PE 0.53 64
1LC19041 4 7 0.226 0.258 Separator 0.5 90 6 45 PVC 0.509 110 1LC290661 6 7 0.180 0.411 6 90 6 6 55 PVC 0.57 85
1LC19042 4 7 0.226 0.258 Separator 0.5 90 6 45 PE 0.509 110 1LC290662 6 7 0.180 0.411 6 90 6 6 55 PE 0.57 85
1LC29081 8 7 0.143 0.652 Cond. Shield 20 90 6 30 PVC 0.435 64 1LC290461 4 7 0.226 0.258 6 90 6 6 55 PVC 0.61 110
1LC29082 8 7 0.143 0.652 Cond. Shield 20 90 6 30 PE 0.435 64 1LC290462 4 7 0.226 0.258 6 90 6 6 55 PE 0.61 110
1LC29061 6 7 0.180 0.411 Cond. Shield 20 90 6 30 PVC 0.472 85
1LC29062 6 7 0.180 0.411 Cond. Shield 20 90 6 30 PE 0.472 85
1LC29041 4 7 0.226 0.258 Cond. Shield 20 90 6 45 PVC 0.548 110
1LC29042 4 7 0.226 0.258 Cond. Shield 20 90 6 45 PE 0.548 110
(1) Ampacity according to NEC Table 310.77: Three Single-Insulated Copper Conductors in Underground Electrical Ducts (Three Conductors
per Electrical Duct) Based on Ambient Earth Temperature of 20°C (68°F), 100 Percent Load Factor, Thermal Resistance (RHO) of 90,
5000 V Shielded and Jacketed Cables Non-metallic insulation Conductor Temperatures of 90°C (194°F)

Conductor
Minimum conductor

Jacket
Nominal insulation

The information given in this page is subject to change without notice.

Nominal diameter
shield thickness

shield thickness

Separator tape
DC resistance

Material type

underground
Catalog

Ampacity in
Number of

Size
thickness

Thickness
Diameter

thickness
at 25 oC

Number
Nominal

duct (1)
strands

AWG - inches Ω/1000 ft mils mils mils mils mils - inches A


B R A S S TA P E S H I E L D 4 M I L S T H I C K
1LC290811 8 7 0.143 0.652 6 90 6 6 55 PVC 0.51 64
1LC290812 8 7 0.143 0.652 6 90 6 6 55 PE 0.51 64
1LC290611 6 7 0.180 0.411 6 90 6 6 55 PVC 0.55 85
1LC290612 6 7 0.180 0.411 6 90 6 6 55 PE 0.55 85
1LC290411 4 7 0.226 0.258 6 90 6 6 55 PVC 0.60 110
1LC290412 4 7 0.226 0.258 6 90 6 6 55 PE 0.60 110
BARE COPPER TAPE SHIELD 4 MILS THICK
1LC290821 8 7 0.143 0.652 6 90 6 6 55 PVC 0.51 64
1LC290822 8 7 0.143 0.652 6 90 6 6 55 PE 0.51 64
1LC290621 6 7 0.180 0.411 6 90 6 6 55 PVC 0.55 85
1LC290622 6 7 0.180 0.411 6 90 6 6 55 PE 0.55 85
1LC290421 4 7 0.226 0.258 6 90 6 6 55 PVC 0.60 110
1LC290422 4 7 0.226 0.258 6 90 6 6 55 PE 0.60 110
BA R E C O P P E R W I R E S S H I E L D. 2 0 M I L S W I R E D I A M E T E R
1LC290831 8 7 0.143 0.652 6 90 6 6 55 PVC 0.54 64
1LC290832 8 7 0.143 0.652 6 90 6 6 55 PE 0.54 64
1LC290631 6 7 0.180 0.411 6 90 6 6 55 PVC 0.57 85
1LC290632 6 7 0.180 0.411 6 90 6 6 55 PE 0.57 85

PCD 33-24/3.02 March 6, 2002


1LC290431 4 7 0.226 0.258 6 90 6 6 55 PVC 0.62 110
1LC290432 4 7 0.226 0.258 6 90 6 6 55 PE 0.62 110
TINNED COPPER WIRES SHIELD. 20 MILS WIRE DIAMETER
1LC290841 8 7 0.143 0.652 6 90 6 6 55 PVC 0.54 64

PCD 45-18, October 2007


1LC290842 8 7 0.143 0.652 6 90 6 6 55 PE 0.54 64
1LC290641 6 7 0.180 0.411 6 90 6 6 55 PVC 0.57 85
1LC290642 6 7 0.180 0.411 6 90 6 6 55 PE 0.57 85
1LC290441 4 7 0.226 0.258 6 90 6 6 55 PVC 0.62 110
1LC290442 4 7 0.226 0.258 6 90 6 6 55 PE 0.62 110
Airfield Lighting Cables Airfield Lighting Cables
XLPE Insulated, Shielded or XLPE Insulated, Shielded or
Non-shielded 5 kV Primary Airfield
Lighting Cables according to the FAA
Non-shielded 5 kV Primary Airfield
Lighting Cables according to the FAA
Specification
AC 150/5345-7E (L-824) Specification AC 150/5345-7E (L-824) Specification

APPLICATION:
For runway, taxiway and approach in underground SCOPE CONDUCTOR SHIELD OVERALL JACKET
primary series airfield lighting circuits. At 5 kV This specification describes XLPE insulated Optional for non-shielded cables, it is - Where applicable, an extruded PVC or black
rated voltage and maximum conductor shielded or non-shielded single core 5 kV cables mandatory for shielded cables. Accordingly, PE jacket shall be applied on the assembly.
temperatures of 90 °C for continuous normal for runway, taxiway and approach in the conductors are covered with a layer of - Properties of the jacket shall be in
operation and 250 °C for short circuit. Suitable Wunderground primary series airfield lighting extruded conducting cross-linked polyolefin accordance with NEMA WC71 /
for use in wet or dry conditions in metallic and circuits. For a maximum conductor compound, firmly bonded to the insulation ICEA S-96-659-1999 Standard, Table 5-1
non-metallic conduits, ducts, aerial and direct temperatures of 90 °C for continuous normal and which shall meet the requirements of or NEMA WC74-2000 / ICEA S-93-639-
burial installations. operation and 250 °C for short circuit, in wet NEMA WC74-2000 / ICEA S-93-639-1999 1999 Standard, Table 7-1 depending upon
or dry conditions. Suitable for use in metallic Standard, Section 3. the cable type.
STANDARDS: and non-metallic conduits, ducts, aerial and
Conforms to: direct burial installations. INSULATION TESTS
1. FAA Advisory Circular (AC) 150/5345-7E, copper seven wires stranded circular conductor extruded conductor shield and a XLPE Directly over the conductor, separator or screen The cable shall be tested in accordance with
Specification for L-824, Type C; has an extruded tracking resistant XLPE (cross- (cross-linked polyethylene) insulation. A STANDARDS (as applicable) shall be applied a homogeneous NEMA WC71 / ICEA S-96-659-1999 Standard,
2. NEMA WC71 / ICEA S-96-659-1999 for linked polyethylene) insulation. Optionally, a non-metallic insulation shield supplemented The following standards shall form a part of wall of XLPE insulation. For non-shielded cables Table 5-1 or NEMA WC74-2000 /
non-shielded cables; separator or conductor shield may be applied this specification to the extent specified herein: it shall meet the requirements of NEMA WC71 ICEA S-93-639-1999 Standard, Table 7-1
with a metallic shield (brass or copper tape;
3. NEMA WC74-2000 / ICEA S-93-639-1999 between both. - Conforms to FAA Advisory Circular (AC) / ICEA S-96-659-1999, Table 4-2. For shielded depending upon the cable type.
bare or tinned copper wires; or bare or
for shielded cables. 2. Non-shielded jacketed type: a bare copper 150/5345-7E, Specification for L-824, cables it shall meet the requirements of NEMA
tinned copper braiding) is applied Type C, Underground Electrical Cable for
seven wires stranded circular conductor has WC74-2000 / ICEA S-93-639-1999 Standard,
underneath the PVC or PE outer jacket. Airfield Lighting Circuits Section 4.
CERTIFICATION: an extruded XLPE (cross-linked polyethylene)
1. ETL Certified Optionally, a separator may be applied - NEMA WC71 / ICEA S-96-659-1999:
insulation. Optionally, a separator or conductor under the jacket. “Standard for Non-shielded Power Cables
2. FAA Listed as an Approved Supplier INSULATION SHIELD (for shielded cables)
shield may be applied between both. Rated 2,001 – 5,000 Volts for the - The insulation shield shall consist of a
A PVC or PE outer jacket is applied overall on PACKAGING Distribution of Electrical Energy” as graphite coating in combination with semi-
CONSTRUCTION:
an optional separating tape; Standard supply lengths are 3000 ft. Other referenced by FAA AC 150/5345-7E. conducting tape and a metallic layer applied
Three types of cable are provided:
1. Non-shielded and non-jacketed type: a bare 3. Shielded jacketed type: a bare copper seven bobbin lengths are available upon request. - NEMA WC74-2000 / ICEA S-93-639-1999: directly over the insulation.
wires stranded circular conductor has an “Standard for Shielded Power Cables Rated - The metallic layer shall consist of one of
5,000 – 46,000 Volts for the Transmission the following:
& Distribution of Electrical Energy” as - an overlapping copper tape
5000 V Non-shielded and Non- jacketed Cables referenced by FAA AC 150/5345-7E. - an overlapping brass tape
- helically applied bare copper wires
Nominal insulation thickness

Conductor Separator tape or conductor CONDUCTORS - helically applied tinned copper wires
Ampacity in underground

shield
Nominal diameter

Bare soft annealed, high conductivity copper - bare copper wires braid
per ASTM B-3, concentric stranded, class B - tinned copper wires braid
Number of strands

Nominal Diameter

DC resistance at

Catalog (seven strands) per ASTM B 8. Class C (19 - Other tape thickness or wire diameter than
Thickness

strands) is available upon request. the ones indicated in the tables can be
25 oC

Number Size Option


supplied upon request.
duct (1)

SEPARATOR (for non-shielded cables) - An optional separator tape may be applied


An optional separator is applied to facilitate over all.
AWG - inches Ω/1000 ft - mils mils inches A the insulation stripping.
1LC01108 8 7 0.143 0.652 None - 110 0.363 64

1LC01106 6 7 0.180 0.411 None - 110 0.400 85

1LC01104 4 7 0.226 0.258 None - 110 0.446 110

1LC11108 8 7 0.143 0.652 Separator 0.5 110 0.364 64

1LC11106 6 7 0.180 0.411 Separator 0.5 110 0.401 85

1LC11104 4 7 0.226 0.258 Separator 0.5 110 0.447 110

1LC21108 8 7 0.143 0.652 Cond. Shield 20 110 0.403 64

1LC21106 6 7 0.180 0.411 Cond. Shield 20 110 0.440 85

PCD 45-18, October 2007


1LC21104 4 7 0.226 0.258 Cond. Shield 20 110 0.486 110