Professional Documents
Culture Documents
The IEC 61000-4-3 has been used for many years as the basic test standard for testing to
Radiated, electromagnetic field immunity testing in order to satisfy one of many European Union
requirements for the CE mark. This standard is usually used in conjunction with a product
standard that will specify this and other test standards detailing the requirements the product
must meet. The product standard may give additional guidance on how this test standard is used,
including test level severity and changes to procedure.
The object of this standard is to establish a common reference to radiated RF immunity caused by
any source. Electronic products need to be designed and tested to have immunity to these
sources. Radiated RF sources can radiate from many sources such as other electronic devices,
electric motors and intentional transmitters such as walkie-talkies and cell phones. The
introduction of more wireless devices in the past couple of years has increased the need for this
testing not only to satisfy governmental requirements but also increase product reliability which
increases customer satisfaction.
Note: This document should not be used in conjunction with or instead of the official released
publication. It is only intended to give you guidance and information on the possible changes.
Always refer to the latest standards.
IEC 61000-4-3: Electromagnetic compatibility (EMC) – Part 4-3: Testing and measurement
techniques – Radiated, radio-frequency, electromagnetic field immunity test.
Edition 3 has been approved and released ahead of schedule. Below is the current and
estimated status:
The above changes could have a big effect on some facilities and test equipment.
1 of 8
060906
Harmonic Distortion
Harmonic distortion is the difference in dB between the fundamental and harmonic of the
fundamental. The new standard calls for a harmonic distortion of better than -6 dBc for the test
setup. This means all harmonics need to be 6 dB below the fundamental out of the transmitting
antenna which could become a problem when using RF amplifiers in compression or when using
Traveling Wave Tube (TWT) amplifiers. TWT amplifiers have been used historically for testing
above 1 GHz when high power is required and can offer significant cost/performance benefits at
very high power levels. Since the introduction of solid-state amplifiers in this frequency range
many of the limitations of TWT amplifiers have been overcome, and at lower power levels solid-
state amps are readily available. TWT amplifiers can still be used for high field testing but care
must be taken in order to satisfy the standard. Some TWT amplifiers include methods for
harmonic reduction by combining tubes or switching in filters. For most other TWT amplifiers, RF
filters can be attached externally to block out these unwanted harmonics. Below is an example of
the harmonic content of a solid-state and a TWT amplifier (20 watt rated). The solid-state
amplifier has an excellent level of -24 dBc while the TWT amplifier’s level is only -0.8 dBc.
Figure 1: AR 25S1G4A Solid-State module AR 20T4G18A TWT Module both are in the AR 20ST1G18A amplifier
The harmonic of the TWT will contribute to the calibration level since a broad band RF field probe
is used and it can not distinguish between a wanted and unwanted signal. In addition, antenna
gain usually increases over its operating band. The antenna gain can be as much as 5 dB higher
at the harmonic. In the above case, the -0.8 dBc harmonic distortion of the TWT will result in a
much higher field level at the harmonic then at the fundamental. These harmonics will result in a
significant error in field level. RF filters will be needed. The consequence of using filters will be
some loss in power and productivity to switch these filters in and out. The amplifier used will
dictate what frequency range/s the filter will need to cover, or if multiple filters are will be needed.
The Solid-state amplifier will not need filtering for this reason.
High harmonic content can also have an unwanted adverse effect on the Equipment Under Test
(EUT). The harmonic could be at a frequency that causes the EUT to fail. Since the test personnel
are testing at the fundamental frequency, they will mark this frequency as the failure which is not
the case. It is quite possible that this harmonic may be outside the intended test frequency range,
so therefore should not even be part of the test. From the EUT manufacturer’s point of view
harmonics are very much unwanted since this signal can cause failures and is not part of the test.
2 of 8
060906
If we work backwards we can estimate an acceptable amplifier harmonic content rating:
Therefore a harmonic content for the amplifiers better than -14 dBc will be more then acceptable.
This would be a more than a safe harmonic content requirement for the amplifier guaranteeing
an acceptable harmonic level during testing. Keep in mind not to run the amplifier into
compression and filters can be used to reach this requirement.
Linearity Check
The linear region of an amplifier is the power range in which there is a 1:1 ratio in dB input
change to dB output change. As the amplifier starts to saturate, this will no longer be true. AR’s
solid-state amplifiers are specified at both a 1 dB and a 3 dB compression point. Below the 1 dB
compression point the amplifiers response is referred to as linear. Above the 3 dB compression
point the amplifier is in full compression.
There are two main reasons why this is important. First, if amplifiers are being run while in
compression the output signal will be distorted. This means a sine wave will start to resemble a
square wave. In the case of the IEC 61000-4-3, amplitude modulation (AM) will also be distorted
possibly causing different unrepeatable test results. Secondly, when an amplifier is being run
closer to saturation the harmonic content will increase.
dB Gain for 25S1G4A @ 1500MHz
The chart to the right shows 47
its 1 dB and 3 dB 44
AR 1dB comprestion
increased by 10 dB results in 40
dBm Input
triangle). Figure 2: Linearity curve of a production unit 25S1G4A amplifier at 1 frequency
The new specification calls for a check for a 2 dB compression point (aqua triangle) while
connected to the antenna. If the load (antenna) on the amplifier is a pure 50!, then amplifier
manufacturers could easily specify this new 2 dB compression point to be used as a reference
when calculating your needs. But since any antenna which is used during testing is not a pure
3 of 8
060906
50! load but an unknown complex load the compression point may vary slightly. For this reason
it is best to size amplifiers based on the manufacturer’s supplied 1 dB compression point to allow
for some margin of error. This will be a concern when using a TWT amplifier since they are
normally not as linear as solid-state amplifiers. The 1dB compression point is usually around 50%
of its rated power, therefore a 20 Watt TWT amplifier will have a 1 dB rating of about 10 Watts.
In the case of the 25S1G4A solid-state amplifier, it has a minimum output rating of 25 watts and
a minimum 1 dB compression rating at about 20 watts (at 1.5 GHz on this unit shown in the
actual production testing shown below the 25S1G4A amplifier is actually rated at 38 watts with
about a 1 dB compression rating of 30 watts). It is always best to check the amplifier’s
specification or to contact the manufacturer directly for this information and assistance with the
selection of the product that will meet your needs.
The frequency range increase from 2 GHz up to 6 GHz is directly in response to the use of more
of the RF spectrum by the communication industries. In different countries and locations the RF
spectrum is being divided up depending on each country’s laws. So based on where the
Equipment Under Test (EUT) is being used, not all frequency bands may need to be tested. In
addition, not all communication standards use the same signal strengths. This is why this new test
standard is leaving this further definition up to forthcoming product standards. Product standards
will specify what additional frequencies to cover in the communications bands: 800 to 960 MHz
and 1.4 to 6 GHz. Product standards will also specify test levels which may not be consistent
throughout the bands. The current 80 MHz to 1 GHz should remain the same.
Chamber setups may have to change because of this higher frequency requirement. Many labs
only have a ferrite lined chamber. This works well when testing less than 1 GHz, but as frequency
rises it will become increasingly difficult to meet the field uniformity requirements. This is because
the ferrite is not very absorbent above 1 GHz and will reflect the RF field. Annex C of IEC 61000-
4-3 Ed. 3 does explain this situation and gives good advice and options on correcting this
problem. A fully lined anechoic chamber with ferrite and absorber material will work fine.
Test Table
The test table is now specified to be made of low permeable material. Rigid polystyrene is one
material that is suggested. In the past many labs have always used wood, which is fine when
testing at lower frequencies. Now that testing can be as high as 6 GHz, wood will start to have
4 of 8
060906
some unwanted properties. High frequencies will reflect making it difficult to meet the uniform
field requirement. The reflections will also make test results less repeatable.
If working in saturation.
! Reduce all RF losses in the system
o Use good low loss RF Cabling and connectors
o Make sure all connections are tight
o Make sure all connectors are clean
o Shorten RF Cabling (may require amplifier to be moved closer to the antenna)
! Use a different RF antenna
o Higher gain antennas will require less power
o Keep in mind narrow beam width may not cover the full window of 1.5 m x1.5 m
uniform field calibration requirement (See Appendix A for antenna coverage
calculations)
" Calibration to smaller window is allowed above 1 GHz.
o Horn antenna will direct the energy forward better then Log antennas
" Resulting in better field performance
! Move antenna in closer, no less the 1 meter
If the above considerations are taken into consideration and the requirements can still not be met
a new amplifier may be needed.
Conclusion
The increased frequency range of this standard has brought some common test problems to light
as to their contribution to test error. Continuing efforts must be taken to maintain a consistently
repeatable test. Both Harmonic distortion and amplifier linearity are issues that until now have
been overlooked by this standard. All RF amplifiers can run in compression and produce
harmonics. If the amplifier is running in compression and if the antenna and cabling can not be
improved upon, a new higher power amplifier will be needed. If harmonic content becomes an
issue, RF filters will be needed to block out these harmonics. With AR’s solid-state amplifiers
filters will not be needed. It is also a good idea to ask manufacturers for examples of test data
taken form production units. This data can aid in product selection and give a better level of
confidence of the manufacturer’s ability to meet their published specs. Quality of testing and
repeatability should be the goal of every EMC test lab. If repeatability was not important then
these international test standards would be useless.
Once this IEC standard is published, there will be an overlap period before the previous standard
is removed from use. The main procedural changes will be harmonic distortion, linearity check,
5 of 8
060906
and test table. Depending on your setup, you may need to change the test setup and/or possibly
purchase new equipment.
Top View
Anechoic Cones
& Tiles
Antenna
Polystyrene
Test
Table 3 meters
Field probe
ar
worldwide Directional
Coupler
RF Amplifier
Power Head
Computer ar
854.000000 MHz
80% 1.000 kHz AM
Control w o rl d w i d e
ar
worldwide
ar
worldwide
ar
worldwide
6 of 8
060906
AR Worldwide’s Solution
Additional equipment
FP7018/Kit & FM7004 RF field probe and Monitor– for 16 point field calibration
PM2002 & PH2000 Power head and meter – for monitoring forward RF power from amplifier
SW1006 RF Test Software – test software to further automate the test
SC1000 RF System Controller – switch matrix to fully automate testing
Complete systems can be designed per your needs. Please contact the an applications engineer
at 1-800-933-8181
7 of 8
060906
Annex A
Using basic Geometry we can calculate window size (spot size) from the 3 dB beam width of the
antenna.
1.5 m
&W #
( ' 2 tan )1 $
% 2 D !" 1m
74°
&(#
W ' 2D tan $ !
%2"
2m
W
D'
2 tan ( * 2+ 41°
Antenna
8 of 8
060906