MMX 110-DIN<PLC>

Rail-Mount Split-PLC Prepayment Meter

User Manual
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

Contents
1 Overview ................................................................................................... 3
2 Reference Standard ................................................................................... 3
3 Installation connection and dimensions ................................................... 4
3.1 Front view, side view and dimensions ............................................... 4
3.2 Connection ......................................................................................... 4
4 Meter Operation User Guide .................................................................... 5
4.1 Mechanical Specification ................................................................... 5
4.2 Working environment specifications ................................................. 5
4.3 Electrical specifications ...................................................................... 5
4.4 LCD display ......................................................................................... 9
4.5 Meter Function User Guide ............................................................... 7
4.5.1 Energy Measurement.................................................................. 7
4.5.2 Communication ........................................................................... 7
4.5.3 RTC .............................................................................................. 7
4.5.4 Billing ........................................................................................... 7
4.5.5 LOAD CONTROL ........................................................................... 8
4.5.6 Tamper & Alarm .......................................................................... 8
4.5.7 Display contents .......................................................................... 9
4.6 Prepayment Operation Guide .......................................................... 10
4.6.1 Token Notification ..................................................................... 10
4.6.2 Short Code Operation Guide ..................................................... 11
4.6.3 Recharge.................................................................................... 11
4.6.4 Emergency Credit ...................................................................... 11
4.6.5 Friendly time and friendly holidays .......................................... 12
4.6.6 Balance Alarm ........................................................................... 12
4.7 PLC Communication Pairing ............................................................. 13
5 Appendix ................................................................................................. 14
5.1 Tamping Status Code........................................................................ 14
5.2 Relay Status Code ............................................................................. 14

2
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

1 Overview
The user manual document is for guidance in the prepayment energy meter
installation, use, maintenance technical reference.
Split prepayment keypad energy meter can widely apply for residential field
in different national and regional, and can combined with different STS
prepayment vending system for prepayment management. The mainly function
is for energy measurement, STS-based prepayment TOKEN recharge,
anti-tamper management, balance alarm etc.

2 Reference Standard
Standard Contents
Electricity metering equipment (a.c.) – General requirements, tests
IEC 62052-11
and test conditions – Part 11: Metering equipment
Electricity metering equipment (a.c.) – Particular requirements –Part
IEC 62053-21
21: Static meters for active energy (classes 1and 2)
Electricity Metering-Data exchange for meter reading, Tariff and Load
IEC 62056-21
Control-Part 21: direct local data exchange.
IEC 62055-41 Part 41: Standard Transfer Specification

3
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

3 Installation connection and dimensions


3.1 Front view, side view and dimensions

3.2 Connection

4
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

4 Meter Operation User Guide


4.1 Mechanical Specification
Paramenter Specifiacation
Terminal Box Din-rail Mounted
Enclosure protection IP54 indoor
1 meter terminal cover seals
Seal
4 meter cover seals
Meter material PC
EN/IEC62052-11
Against mechanical stroke and shake
parts 5.2.2.1, 5.2.2.2 & 5.2.2.3
Dimensions(LxWxH) 144mm×42.5mm×109.5mm
Weight Approx 1kg

4.2 Working environment specifications


Paramenter Specifiacation
Operating Relative Humidity <= 95%
Operating temperature range -25°C ~ +70°C
Limit temperature range -35°C ~ +80°C
Storage temperature -40°C ~ +85°C

4.3 Electrical specifications


Paramenter Specifiacation
Active accuracy Class 1
Rated voltage Un(V) 240V
Working voltage range 0.8~1.2Un
Rated frequency(Hz) 50Hz
Basic current Ib(A) 5A
Max. current Imax(A) 80A
Power consumption in current circuit ≦ 4VA
Power consumption in voltage circuit ≦ 2W/10VA
Measurement element One element

5
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

Optical communication IEC62056-21


Relay Latching contactor, 100A
1 implse output LED(red)
LED 1 credit balance LED(red and green)
1 alarm LED(yellow)
Buzzer Built-in
Battery Built-in

6
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

4.4 Meter Function User Guide


4.4.1 Energy Measurement
Parameters Specification
(1.8.0)Import Active Energy = |+A|
Energy measurement (2.8.0)Export Active Energy = |-A|
(15.8.0)Total Active Energy = |+A| + |-A|
Voltage(V)
Instantaneous measurement Current(A)
Active power(kW)

4.4.2 Communication
Parameters Specification
Communication port: optical port
Local communication
Protocol: IEC62056-21
Communication port: PLC
UIU communication
Protocol: STS

4.4.3 RTC
Parameters Specification
Auto-switch of leap year
Accuracy
Accuracy ≤ ±0.5s/d(23℃)

4.4.4 Billing
Parameters Specification
Billing Reset Automatically reset at predefined date.
Billing date Any day between 1st to 28th
Storage(times) Recently 12 times
Billing date and time
(15.8.0) Total active energy
Energy Billing Data (1.8.0) Import active energy T0
(1.8.1) Import active energy T1
(1.8.2) Import active energy T2

7
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

(1.8.3) Import active energy T3


(1.8.4) Import active energy T4
(2.8.0) Export active energy T0
(C.51.0) Balance energy

4.4.5 LOAD CONTROL


When the load exceeds the set power threshold, the alarm LED lights, the
alarm sound (press any key to cancel the alarm), the meter shows "loadover",
continuous 45s load exceeds the set power threshold relay off, 150s relay
automatically Close up. If the power-down display is cleared at this time, it will
be closed immediately after power-on.
If there is no load overload event within 30 minutes, the cumulative
number of overloads is automatically cleared.
If there are five overload events within 30 minutes, the meter will wait 45
minutes before closing the relay again after the fifth time the relay is
disconnected (recalculating five times after power-down), and the meter will
display "loadover" . Overload threshold can be set by the host computer. It can
also be set by managing the TOKEN code.

4.4.6 Tamper & Alarm


Tamper Status(XXXXX) Specification
00001 Energy reverse
00020 Meter cover open
00300 Meter terminal cover open
04000 Over voltage
50000 Under voltage
Storage Recently 10 times records for each event

8
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

5 UIU-PLC User Guide


5.1 LCD display
The LCD full-screen display as below:

LCD Symbol Description


Display: energy, voltage, current, power
etc.

Display OBIS code


Communication symbol
Meter is communicating if displayed
No communication if not displayed
kWh, kvarh, VA, V, A, kW unit

Low-battery alarm

Tariff1 to tariff4 running indicator

L1: current direction indicator

Relay open status: contactor disconnected

Energy balance

Vending success or fail

5.2 Display contents


Power on display contents are configurable.
OBIS Description Display format Unit
1.8.0 Import active energy of T0 xxxxxx.xx kWh

9
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

1.8.1 Import active energy of T1 xxxxxx.xx kWh


1.8.2 Import active energy of T2 xxxxxx.xx kWh
1.8.3 Import active energy of T3 xxxxxx.xx kWh
1.8.4 Import active energy of T4 xxxxxx.xx kWh
2.8.0 Export active energy of T0 xxxxxx.xx kWh
15.8.0 Total active energy xxxxxx.xx kWh
C.2.1 Balance energy xxxxxx.xx kWh
31.7.0 Instantaneous current phase A xx.xxx A
51.7.0 Instantaneous current phase B xx.xxx A
71.7.0 Instantaneous current phase C xx.xxx A
32.7.0 Instantaneous voltage phase A xxx.x V
52.7.0 Instantaneous voltage phase A xxx.x V
72.7.0 Instantaneous voltage phase A xxx.x V
84.0.0 Total Instantaneous power xx.xxx kW
84.0.1 Instantaneous power phase A xx.xxx kW
84.0.2 Instantaneous power phase B xx.xxx kW
84.0.3 Instantaneous power phase C xx.xxx kW
C.51.0 Balance energy(Credit) xxxxxx.xx kWh
0.9.1 Time hhmmss
0.9.2 Date DD-MM-YY
C.1.0 Electronic Meter number NNNNNNNN

Power off display contents:


OBIS Description Display format Unit
C.51.0 Balance energy(Credit) xxxxxx.xx kWh

5.3 Prepayment Operation Guide


5.3.1 Token Notification
TOKEN: Customer purchase energy though vending system, and input 20
digital codes to meter.
Notification about input TOKEN: time out is 20 seconds for each digital
code input.

10
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

5.3.2 Short Code Operation Guide


Short Code Function
800 15.8.0 Total active energy(kWh)
801 Balance energy(kWh)
802 Date
803 Time
804 Meter No
805 SGC
806 Relay open/close reason
807 Meter Status
808 Power
809 TI
810 Overload limit value(kW)
811 Start emergency credit function
812 Close buzzer alarm
813 Last day energy consumption(kWh)
814 Last month energy consumption(kWh)
815 recently the 1st recharge date

5.3.3 Recharge
TOKEN descript Result
TOKEN success LCD display “SUCCEED”, then display charge energy.
TOKEN refuse LCD display “rEJEct”
TOKEN used LCD display “USED”
TOKEN expired
(unused after 50 times TOKEN LCD display “OLD”
input)

5.3.4 Emergency Credit


After balance credit is finished, relay will be disconnected automatically. But
if customer is in an emergency need of electricity at this time, he can activate
the emergency overdraft function via key in short code "811" to reconnect the

11
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

relay. With emergency overdraft function, meter will still register in a negative
way, when it reaches the overdraft value, the meter will be disconnected again.
Emergency overdraft function can only be used once, and recovered after the
meter is recharged next time. The overdraft value will be deducted from the
balance credit automatically
LCD display Meter status
10.00RM(Assume the amount of The emergency overdraft is enabled and the
overdraft is 10.00RM) current meter balance is shown
The emergency overdraft function has been
01rEJECt
used, cannot be used again
There is still a balance on the meter and there is
02rEJECt
no need to activate the emergency overdraft
The emergency overdraft is enabled, the meter
03rEJECt
is still arrears

5.3.5 Friendly time and friendly holidays


In some public holidays or some special predefined time, such as midnight,
it is not convenient for customers to purchase credit. In this situation, utility can
offer the friendly overdraft function to customers. With these predefined
holidays or time period, the meter will not disconnected even the balance credit
is zero. The holiday and time period is configurable
The friendly mode function can be turned on or off by the host computer.
Friendly credit mode to open, in the set time period will not meter balance due
to lack of arrears, the balance will not be enough during the friendly opening,
you can continue to electricity to the remaining amount is negative until the end
of the friendly period table Meter will pull.
Friendly time has the following time can be set: (through the PC S/W)
1) Night Time:For example, 20:00 to 8:00, for the evening 20:00 to 8:00
the next day
2) Weekends:Up to two days at the same time
3) Holidays
4) Festivals

5.3.6 Balance Alarm

12
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

Visible and audible low credit alarm is available to facilitate user to manage
the balance and credit the meter in time.
There are three thresholds which are programmable in the meter.
The remaining amount of less than the alarm meter set a three threshold:
1) When the meter is less than the amount of the remaining threshold
alarm threshold, the red light. (50 kWh)
2) When the meter is less than the amount of the remaining two alarm
threshold, the red light flashes. (25 kWh)
3) When the meter is less than the amount of the remaining three
threshold alarm, the red light flashes, the buzzer alarm. (5 kWh)

5.4 PLC Communication Pairing


The PLC communication pairing configuration step as follow:
1) Input 5609-7869-4675 by keypad of UIU after power on the first time;
2) Waiting for UIU display “succeed” and “ALT”(upper right corner);
3) Input 11 digit meter number, and ok button;
4) Waiting for UIU display “connect” and display “succeed”;
5) Pairing finish;

13
MMX 110-DIN<PLC> Rail-Mount Split-PLC Prepayment Meter User Manual

6 Appendix

6.1 Tamping Status Code


Meter Status Code Description

00001 Energy reverse


00020 Meter cover open
00300 Terminal cover open
04000 Over voltage
50000 Lowe voltage
Note: Simultaneous occurrence of the event, the code also shows, such as:
simultaneous energy reverse and terminal cover open display 00301.

6.2 Relay Status Code


Relay Status Code Description

00 Relay closing status


01 Insufficient balance and overdraft function
closed
02 Insufficient balance and the overdraft exhausted
03 Overload, relay open
04 Short code test, relay open
05 Tamper: Meter cover open, relay open
06 Tamper: Terminal cover open, relay open
07 Tamper: Magnetic influence, relay open
08 Relay open by PC software

14