Professional Documents
Culture Documents
Ranger(NJZ-FEL-E Series)
Hazardous Location LED Luminaire
Ranger
Hazardous Loca�on LED Luminaire
NJZ-FEL-E Series
Product description
The Ranger NJZ-FEL-E Series LED Luminaire is designed for installations where moisture, dirt, corrosion and
vibration may be present. They can be used in locations made hazardous by the presence of flammable vapors or
gases as defined by the NEC.
NJZ-FEL-E Series is ideal for retrofit of existing HPS/MH and offers higher efficacy for increased energy savings,
lower maintenance costs and shorter paybacks.
Features
Best-in-class system efficacy - Up to 137 Lm / W
Universal Voltage: AC120-277V, AC347-480V (50/60Hz)
Wide ambient temp. range from - 40°C to + 50 °C ( -40°F ~ + 122°F)
Safe and reliable heat transfer - Offering a T-rating of T3C ( CID2 )
Instant on/off operation
Shock-and vibration-resistant - Durable LEDs with solder-less board connection
Copper-free aluminum body and corrosion resistant
All exposed fasteners with quality stainless steel
Thermal shock and impact resistant PC lens
Slim and compact design
Compliance Application
NEC/CEC Standard Power Plants / Heavy Industrials
UL844 & CSA C22.2 No. 137-M1981 Storage Facility / Paper mills
Class I Division 2, Group A, B, C, D Wastewater Treatment Plants
UL 1598A Marine(Salt Water) Loading Docks / Platforms / Shipyards
UL 1598 Wet Locations Chemical Processing Facility
UL 8750 LED Safety Petrochemical Processing Facility
DLC 4.2
FCC
Warranty
5-Year Standard Warranty
Product Dimensions
190mm (7.5in)
8-Φ8.5 (0.3in)
2-Φ6.5 (1.1in)
Φ36mm(1.4in)
70mm (2.8in)
58mm (2.3in)
50mm (0.4in)
10mm (0.4in)
Φ5mm(0.2in)
192mm (7.6in)
80mm (3.1in)
80mm (3.1in)
600mm(23.6in)
200mm (7.9in)
1200mm (47.2in)
127mm (5in)
600×127×192 mm 675×180×230 mm
NJZ-FEL-E-40 5.5kg/12.1lbs 6.2kg/13.6lbs
23.6×5.0×7.6in 26.6×7.1×9.1in
Mounting
Stanchion Pendant
Technical Parameter
Electrical
Specification NJZ-FEL-E-40 NJZ-FEL-E-80
Optical
Specification NJZ-FEL-E-40 NJZ-FEL-E-80
Environmental
Specification NJZ-FEL-E-40 NJZ-FEL-E-80
Mechanical
Specification NJZ-FEL-E-40 NJZ-FEL-E-80
Photometric
110 Degree
0 24 Illumina�on-110 Degree
16 6m 20m 16Lux
900
8 8m 26m 9Lux
1800
0 10m 33.6m 6Lux
2700 32 24 16 8 8 16 24 32
12m 40m 4Lux
3600 16
15m 50m 2.5Lux
Series Wattage Hazloc Voltage Color Temp Beam Angle Lens Option
AC120-277V
P/N Watt CID2 Lumen Output LPW Beam Angle CCT(K) CRI
FEL-E-402BNBT 40W 6000Lm 150 110° 3000K(Warm White) 70
FEL-E-402BLBT 40W 6000Lm 150 110° 4000K(Neutral White) 70
FEL-E-402BZBT 40W 6000Lm 150 110° 5000K(Neutral White) 70
FEL-E-802BNBT 80W 12000Lm 150 110° 3000K(Warm White) 70
FEL-E-802BLBT 80W 12000Lm 150 110° 4000K(Neutral White) 70
FEL-E-802BZBT 80W 12000Lm 150 110° 5000K(Neutral White) 70
AC347-480V
P/N Watt CID2 Lumen Output LPW Beam Angle CCT(K) CRI
FEL-E-402NNBT 40W 6000Lm 150 110° 3000K(Warm White) 70
FEL-E-402NLBT 40W 6000Lm 150 110° 4000K(Neutral White) 70
FEL-E-402NZBT 40W 6000Lm 150 110° 5000K(Neutral White) 70
FEL-E-802NNBT 80W 12000Lm 150 110° 3000K(Warm White) 70
FEL-E-802NLBT 80W 12000Lm 150 110° 4000K(Neutral White) 70
FEL-E-802NZBT 80W 12000Lm 150 110° 5000K(Neutral White) 70
*Parts number listed in the table above are transparent PC lens.
For diffuse PC lens, replace the final character with F. EX. FEL-E-402BNBT becomes FEL-E-402BNBF.
Class I Locations
Class I locations are those in which inflammable gases or vapors are or may be present in sufficient quantities to
produce explosive or flammable mixtures.
CLASS I, DIVISION 1
Class I, Division 1 locations are where hazardous atmosphere may be present during normal operations. It may be
present continuously, intermittently, periodically or during normal repair or maintenance operations, or those areas
where a breakdown in processing equipment releases hazardous vapors with the simultaneous failure of electrical
equipment.
CLASS I, DIVISION 2
Class I, Division 2 locations are those in which volatile flammable liquids or gases are handled, processed or used.
Normally they will be confined within closed containers or in closed systems from which they can escape only in the
case of rupture or deterioration of the containers or systems.
Class II Locations
Class II locations are those that are hazardous because of the presence of combustible dust.